Unical INOXIA GJ Series, INOXIA GJ 200, INOXIA GJ 150, INOXIA GJ 350, INOXIA GJ 600 Installation And Servicing Manual

...
INOXIA GJ
00335290 - 1st edition - 04/11
INSTALLATION AND SERVICING MANUAL
General Information
1 GENERAL INFORMATION .................................................................................................................................................................................... 3
1.1 Symbols used in this manual ............................................................................................................................................................................... 3
1.2 Correct use of the appliance ................................................................................................................................................................................3
1.3 Water treatment ................................................................................................................................................................................................... 3
1.4 Information to be handed over to the user ..........................................................................................................................................................3
1.5 Safety warnings .................................................................................................................................................................................................. 4
1.6 Data badge ......................................................................................................................................................................................................... 5
1.7 General warnings ...............................................................................................................................................................................................6
2 TECHNICAL FEATURES AND DIMENSIONS .....................................................................................................................................................7
2.1 Technical features ............................................................................................................................................................................................... 7
2.2 Main components ................................................................................................................................................................................................ 7
2.3 Dimensions .......................................................................................................................................................................................................... 8
2.4 Performance data according to the Standard UNI 10348 ...................................................................................................................................9
3 INSTRUCTIONS FOR THE INSTALLER ............................................................................................................................................................10
3.1 General warnings .............................................................................................................................................................................................10
3.2 Standard codes for installation .........................................................................................................................................................................11
3.3 Handling ...........................................................................................................................................................................................................12
3.4 Heating plant location ....................................................................................................................................................................................... 12
3.5 Burner ............................................................................................................................................................................................................... 12
3.5.1Burner’s choice ............................................................................................................................................................................................... 12
3.5.2 Burner’s installation .......................................................................................................................................................................................13
3.6 Connection flame spy control to the burner ..................................................................................................................................................... 13
3.7 Flue connection ................................................................................................................................................................................................ 14
3.8 Condensate drain ............................................................................................................................................................................................. 14
3.9 Furnace door : regulation, opening, closing .....................................................................................................................................................15
3.9.1 Boilers INOXIA GJ 150÷ INOXIA GJ 350 ....................................................................................................................................................15
3.9.2 Boilers INOXIA GJ 450÷ INOXIA GJ 1000 ..................................................................................................................................................15
3.9.3 Important note ............................................................................................................................................................................................... 16
3.10 Connection boiler to the plant ......................................................................................................................................................................... 16
3.11 Filling the system ............................................................................................................................................................................................. 17
3.12 Gas connection ................................................................................................................................................................................................17
3.13 Packaging ........................................................................................................................................................................................................19
3.14 Shell assembly ................................................................................................................................................................................................20
3.15 Electric connections.........................................................................................................................................................................................22
3.16 Tools panel MASTER MODULANTE cod. 37892 ............................................................................................................................................23
3.17 Thermoregulator programming with single boiler ............................................................................................................................................23
3.18 Electric and hydraulic connection to the plant with tools panel cod. 37892 ..................................................................................................... 27
3.19 thermoregulator programming with boiler cascade .........................................................................................................................................29
3.20 Tools panel modulating cascade cod. 37900 ................................................................................................................................................... 33
3.21 Electric and hydraulic connection to the plant with boilers cascade tools panels cod. 37892 and 37900 ....................................................... 35
3.22 Tools panel MASTER BISTADIO cod. 38778 ................................................................................................................................................... 37
3.22 Thermoregualtors programming with single boiler ...........................................................................................................................................37
3.24 Electric and hydraulic connection to the plant with tools panel cod.38778 ...................................................................................................... 41
3.25 thermoregulator programming with boiler cascade .........................................................................................................................................43
3.26 Tools panel CASCATA BISTADIO cod. 37901 .................................................................................................................................................47
3.27 Electric and hydraulic connection to the plant with boilers cascade tools panels cod 38778 and 37901 ........................................................ 49
3.28 Initial lighting .................................................................................................................................................................................................... 51
3.29 Burner regulation ............................................................................................................................................................................................. 52
4 SERVICING SCHEDULE .....................................................................................................................................................................................52
Instructions for inspecting and servicing the appliance .......................................................................................................................................... 52
Shell servicing ......................................................................................................................................................................................................... 53
Burner servicing ...................................................................................................................................................................................................... 53
Checking the electrode lighting ...............................................................................................................................................................................53
Components to verify during the annual inspection .................................................................................................................................................53
2
General Information
Warning: this manual contains instructions to be used exclusively by the installer and/or a competent person in accor­dance with the current laws. The end user is not qualified to carry out any service work on the boiler. Failure to follow the instructions indicated in this manual, which is supplied with the boiler, could cause injury to persons, animals or damage to property. UNICAL shall not be held liable for any injury and/or damage.
1
GENERAL INFORMATION
1.1 - SYMBOLS USED IN THIS MANUAL
When reading this manual particular care has to be given to the parts marked with the followings symbols:
DANGER! Indicates serious danger for your personal safety and for your life
WARNING! Indicates a potentially dangerous situation for the pro­duct and the environment
NOTE! Suggestions for the user
1.2 - A CORRECT USE OF THE APPLIANCE
The INOXIA GJ appliance has been designed utilizing today’s heating technology and in compliance with the current safety regulations. However, following an improper use, dangers could arise for the safety and life of the user or of other people, or damage could be caused to the appliance or other objects. The appliance is designed to be used in pumped hot water central heating systems. Any other use of this appliance will be considered improper. UNICAL declines any responsibility for any damages or injuries caused by an improper use; in this case the risk is completely at the user’s responsibility. In order to use the appliance according to the foreseen scopes it is necessary to carefully follow the in­structions indicated in this manual.
1.3 - WATER TREATMENT (refer to specific guide)
• The hardness of the mains water supply conditions the frequency with which the heat exchanger is cleaned.
• In hard water areas where the main water can exceed 15°f total hardness, a scale reducing device is recommen­ded. The choice of this device has to be made taking into consideration the characteristics of the water.
• We recommend you to check the state of cleanliness of the domestic hot water heat exchanger at the end of the first year and subsequently every two years; in this occasion check the state of wear of the anode.
1.4 - INFORMATION TO BE HANDED OVER TO THE USER OR PERSON IN CHARGE OF THE APPLIANCE
The user or the person in charge has to instructed on the use and operation of his heating system, in particular:
- Hand over these instructions to the end user or person in charge of the appliance, together with any other literature regarding this appliance placed inside the envelope contained in the packaging. The user has to keep these do-
cuments in a safe place in order to always have them at hand for future reference.
- Inform the user on the importance of air vents and of the flue outlet system, stressing the fact that it is absolutely forbidden to make any alterations to the boiler.
- Inform the user how to check the system’s water pressure as well as informing him how to restore the correct pres­sure.
- Explain the function of time and temperature controls, thermostats, heating controls and radiators, to ensure the greatest possible fuel economy.
- Remind the user that it is obligatory to service the appliance at least annually and to carry out a combustion analysis in compliance with the schedule indicated in the national Codes of Practice.
- If the appliance is sold or transferred to another owner or if the present user moves home and leaves the appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by the new owner and/or installer.
3
General Information
1.5 - SAFETY WARNINGS
WARNING! The installation, adjustment, and servicing of this appliance must be carried out by a competent, qualified person and installed in accordance with the current standards and regulations. Failure to correctly install this appliance could cause injury to persons, animals or damage to property. The manufacturer shall not
be held liable for any injury and/or damage.
DANGER!
NEVER try to carry out any repairs or service work on the boiler on your own initiative. Servicing or repairs of the appliance must be carried out by qualified service engineers; UNICAL recommends drawing up a service contract. Bad or irregular servicing could compromise the safe operation of the appliance, and could cause injury to persons, animals or damage to property for which UNICAL shall not be held liable.
Modifications to parts connected to the appliance
Do not carry out any modifications to the following parts:
- the boiler
- to the gas, air, water supply pipes and electrical current
- to the flue pipe, safety relief valve and to the central heating’s drainage pipe
- to the constructive components which influence the appliance’s safe operation
WARNING!
When tightening or loosening the screw pipe connections, use only adequate fork spanners. The improper use and/or the use of inadequate equipment can cause damages (for example water or gas leakages).
WARNING!
Indications for appliances operating with propane gas Ensure yourself that before installing the appliance the gas tank has been purged. For a correct purging of the tank contact the liquid gas supplier or a competent person who has been legally authorized. If the tank has not been correctly purged problems could occur during ignition. If this occurs contact the liquid gas tank’s supplier.
Smell of gas
If you smell gas follow these safety indications:
• Do not turn on or off electrical switches
• Do not smoke
• Do not use the telephone
• Close the mains gas tap
• Open all windows and doors where the gas leakage has occurred
• Contact the gas society or a company specialized in installing and servicing heating systems
Explosive and easily inflammable substances
Do not use or leave explosive or easily inflammable material (as for example: petrol, paint, paper) in the room where the appliance has been installed.
4
General Information
1.6 - DATA BADGE
The data badge is adhesive and placed inside the documentation envelope; it must be glued on to one side of the casing, on the external part, by the installer.
The boiler’s serial number is indicated on the plate screwed on the boiler’s front plate (front side, upper left hand side).
CE Marking
- The CE marking documents that the boilers satisfy:
- The essential requirements of the Directive regarding gas appliances (Directive 90/396/CEE)
- The essential requirements of the Directive regarding electromagnetic compatibility (Directive 89/336/CEE)
- The essential requirements of the Efficiency Directive (Directive 92/42/CEE)
Boiler type Serial number Year of manufacture
Mains: 230V~ 50Hz W:
Fuels (only those with X)
OUTPUTS Useful Furnace P.I.N. code
Approval See serial no. on boiler body
Gas
Storage tank:
Category
kW
min. max.
AG S.P.A.
Boiler water capacity Max. operating pressure Max. operating temp. °C
Capacity Max. press. Max. temp.
l °Cbar
Wood
Sup. m²
46033 CASTELDARIO (MN) - Via Roma tel. 0376 57001 - fax 0376 660556 www.unical.ag info@unical-ag.com
Charcoal
kW
Diesel oil
min.
l
bar
kW
Naphtha
max.
5
General Information
1.7 - GENERAL WARNINGS
This instruction manual is an integral and indispensable part of the product and must be retained by the person in charge of the appliance.
Please read carefully the instructions contained in this manual as they provide important indications regarding the safe installation, use and servicing of this appliance.
Keep this manual in a safe place for future reference.
The installation and servicing must be carried out in accordance with the regulations in force according to the manufacturer’s instructions and by legally competent authorized persons.
By a competent person, we imply a person who has a specific technical qualification in the field of components for central hea­ting systems for domestic use, domestic hot water production and servicing. The person must have the qualifications foreseen by the current laws in force.
Bad or irregular servicing could compromise the safe operation of the appliance, and could cause injury to persons, animals or damage to property. The manufacturer shall not be held liable for any such injury and/or damage.
Before carrying out any cleaning or servicing turn off the electrical supply to the boiler by means of the ON/OFF switch and/or by means of the appropriate shutdown devices.
In the event of failure and/or faulty functioning of the appliance, switch off the boiler. Do not attempt to make any repairs: contact qualified technicians.
Any repairs must be carried out by Unical authorized technicians and using only original spare parts. Non-observance of the above requirement may jeopardize the safety of the appliance.
To guarantee the efficiency and correct functioning of the ap­pliance it is indispensable to have the boiler serviced annually by a qualified person.
If the boiler remains unused for long periods, ensure that any dangerous parts are rendered innocuous.
If the appliance is sold or transferred to another owner or if the present user moves home and leaves the appliance installed, ensure yourself that the manual always follows the appliance so that it can be consulted by the new owner and/or installer.
Only original accessories must be used for all appliances sup­plied with optional accessories or kits (including electrical ones).
This appliance must be used only for the purposes for which it has been expressively designed. Any other use shall be considered incorrect and therefore dangerous
Do not obstruct the intake/outlet terminal ducts.
6
Technical features and dimensions
2
1
4
5
3
M
Rmt
Rbt
Ve
2
TECHNICAL FEATURES AND DIMENSIONS
2.1 - TECHNICAL FEATURES
The boilers of the INOX series consist of a firebox GJ horizontal direct-fired and a bundle consisting 316L stainless steel tubes and aluminum fins immersed in a vertical plating. The building meets all the requirements set in EN 303 part 1 ª. The components of the part under pressure, such as sheets and tubes, are constructed in 316L stainless steel, under the tables EURONORM and EURONORM 25 and 28. The welders and welding procedures are approved by TÜV (D) - UDT (PL) - SA (S) and ISPESL (I). For all models, the fireplace is bound to the tube plate back. The boilers are equipped with a door opening to the right with the possibility of changing the rotation. The outer shell is covered with a wool mattress 100 mm thick glass in turn protected by a fabric mineral fiber.
The upper shell is fitted with holes (mod. 150/ 300) and hooks for the lifting of the boiler.
Note: The stainless steel tank are designed to operate with GJ Burner ON / OFF; two stage or modulating, provided that thermal power reached minimum is lower specified on the rating plate.
The boilers are equipped with 2 ½ “sheathing with internal diameter of 15 mm (suitable for housing 3 bulbs each). The sides of the mantle are fitted with holes for cable glands power cables, pump, burner and every other auxiliary device.
2.2 - MAIN COMPONENTS
The INOXIA GJ are equipped with a cylindrical furnace blind, in which the central flame burner goes to the fund and then distributed in the flue, the ends of the tubes combustion gases are collected in the smoke chamber and here sent to the fireplace. During the burner operation, within the field power of the boiler, the combustion chamber is always under pressure. For the value of this pressure see table page. 8, the column “Pressure drop gas side.” The furnace must be calculated so that its base not detected any positive pressure
1 Furnace 2 Smoke pipe with smoke deflectors 3 Door with Flame inspection 4 Smokebox 5 Insulation body
- Tool panel (not visible) M System delivery Rbt system return low Temperature Rmt System return medium temperature Ve Expansion tank
fig. 1
7
Technical features and dimensions
G
T7
A
S
Q
H
U
I
J
K
BE F
O
C
D
T3
T2
T6
T4
R
P
T
T8
T7
T5
L N
V
T1-T4
M
T1
T1-T4
1
2
3
Lana di roccia
Fibra ceramica
Piastra porta-bruciatore cieca 250x250
Guarnizione piastra porta-bruciatore 250x250
ø 180
ø 150
120
Lana di roccia
Fibra ceramica
Piastra porta-bruciatore cieca 330x330
Guarnizione piastra porta-bruciatore 330x330
ø 270
ø 270
130
Lana di roccia
Fibra ceramica
Piastra porta-bruciatore cieca 280x280
Guarnizione piastra porta-bruciatore 280x280
ø 210
ø 210
130
2.3 - DIMENSIONS
1 Control panel 2 burner flange 3 Flame inspection
A
mm 766
766 866 866 896
896 1076 1076
Useful output
(50°-30°C)
kW
150 200 270 350 450 600 800
1000
B
mm
1295 1295 1530 1530 1952 1952 2250 2250
INOXIA GJ
Models
150
200
270
350
450
600
800
1000
INOXIA GJ
Models
150
200
270
350
450
600
800
1000
(80°-60°C)
C
mm
1558 1558 1649 1649 1790 1790 2075 2075
Useful output
kW
135 180 244 316 406 541 720 902
mm 190
190 190 190 190 190 190 190
T1 Heating flow T2 Low-temperature heating return T3 Return heating medium temperature T4 Expansion tank connection
Furnace
output
kW
140 186 253 327 420 560 746 934
capacity
Boiler
l
248 248 380 380 533 533 907 907
Water side
pressure
drop(**)
m c.a.
0,27 0,45 0,35 0,55 0,30 0,50 0,37 0,60
Flue gas pressure
mm c.a.
drop
10 15 14 23 18 32 30 45
M
aximum
operating
pressure
boiler
bar
5 5 5 5 5 5 5 5
W
1090 1090 1650 1650
eight
kg
480 480 675 675
T1 , T2, T3
UNI 2278 PN16
65 65 80
80 100 100 125 125
T5 Boiler drain T6 Chimney connection T7 Burner connection T8 Drain condense
CONNECTIONS
T4
ISO 7/1
UNI 2278 PN16T5ISO 7/1
1½ 1½
2
2 65 65 80 80
T6
Øi
mm
¾
180
¾
180
¾
200
¾
200
1
250
1
250
1
300
1
300
T7
Øi
mm 180
180 180 180 210 210 270 270
T8
Øe
mm
40 40 40 40 40 40 40 40
DIMENSIONS
fig. 2
D
E
F
G
H
I
mm 112
112 112 112 125 125 140 140
mm
75 75 91 91 66 66 78 78
mm
1243 1243 1309 1309 1415 1415 1629 1629
mm 283
283 300 300 328 328 345 345
mm 489
489 536 536 590 590 655 655
mm 719
719 809 809 845 845 940 940
J
K
mm
1545 1545 1635 1635 1893 1893 2178 2178
mm 278
278 287 287 312 312 341 341
L
M
N
O
P
Q
R
S*
T
U
mm 200
200 220 220 320 320 340 340
mm
1004 1004 1226 1226 1511 1511 1787 1787
mm
1482 1482 1733 1733 2143 2143 2468 2468
mm 299
299 353 353 288 288 364 364
mm 1005
1005 1205 1205 1666 1666 1866 1866
mm 178
178 175 175 189 189 238 238
mm 665
665 765 765 795 795 975 975
mm
85 85 85 85 85 85 85 85
mm 328
328 355 355 400 400 490 490
V*
mm
1645 1645 1745 1745 1893 1893 2178 2178
(*) Dimensione minima di passaggio attraverso la porta della centrale termica. (**) Perdite di carico corrispondenti ad un salto termico di 15K.
DETAIL FOR DOOR DRILLING
INOXIA GJ 150 / 350
Blind burner plate 250x250
Burner plate insulation gasket 250x250
Mineral wool
Ceramic fibre
fig. 3
DETAIL FOR DOOR DRILLING
Blind burner plate 280x280
8
INOXIA GJ 450 / 600
Burner plate insulation gasket 280x280
Mineral wool
Ceramic fibre
fig. 4
DETAIL FOR DOOR DRILLING
INOXIA GJ 800 / 1000
Burner plate insulation gasket 200x200
Blind burner plate 330x330
Mineral wool
Ceramic fibre
fig. 5
1000
917,5
INOXIA GJ 1000
800
732,8
INOXIA GJ 800
550
600
INOXIA GJ 600
450
412,5
INOXIA GJ 450
350
320,5
INOXIA GJ 350
934
107
98,2
746
98,2
107,2
560
98,2
107,1
420
98,2
107,1
32798107
109
109
109
109
109
98,3
98,3
98,3
98,3
98,1
99,1
99,1
99,1
99,1
99,1
0,10
0,11
0,12
0,12
0,14
0,07
0,07
0,09
0,09
0,10
1,66
1,66
1,66
1,66
1,85
0,92
0,92
0,92
0,92
0,92
0,10
0,10
0,10
0,10
0,10
Technical features and dimensions
36
20
10,5
139,4
1322,7
36
20
10,5
111,3
1056,5
36
20
10,5
83,6
793,1
36
20
10,5
62,7
594,8
40
20
10,5
48,8
463,1
271
253
247,5
INOXIA GJ 270
200
186
181,5
INOXIA GJ 200
150
140
136,5
INOXIA GJ 150
kWkWkW%%%%%%%%%%°C°C%kg/h
97,8
97,5
97,5
109
107,1
107,5
109
107,1
109
97,9
97,8
97,7
99,1
99,1
99,1
0,14
0,25
0,23
0,10
0,17
0,16
2,03
2,17
2,27
0,92
0,95
0,95
0,10
0,11
0,10
44
48
46
20
20
20
10,5
10,2
10,2
37,7
353,8
270,1
20,9
203,3
l/h
27,7
Heat output nominal (80°-60°C)
Heat output nominal (50°-30°C)
GAS OPERATION
2.4 - PERFORMANCE DATA ACCORDING TO STANDARD UNI 10348
Thermal power of the hearth
Efficiency at nominal load (80°-60°C)
Efficiency at nominal load (50°-30°C)
Heat efficiency at 30% load
Combustion efficiency (80°-60°C)
Combustion efficiency (50°-30°C)
Losses to the mantle (80°-60°C)
Losses to the mantle (50°-30°C)
Losses with burner on (80°C)
Losses with burner on (30°C)
Losses with burner off
Flue gas temperature tf-ta (80°-60°C)
Flue gas temperature tf-ta (50°-30°C)
CO2 content
Flue gas mass flow
Condensate production max, (natural gas)
9
Instructions for the installer
INSTALLATION
3
INSTRUCTIONS
3.1 - GENERAL WARNINGS
WARNING! This boiler is to be destined only to the use for which it has expressly been designed for. Every other use is to be considered improper and therefore dangerous. This boiler is designed to heat water at a temperature inferior to boiling point at an atmospheric pressure.
WARNING! These appliances are exclusively designed for indoor installations or installed in ade­quate sitings. Therefore these appliances must not be installed and operated out­doors. An outdoor installation could cause malfunctioning and could be dangerous. For outdoor installations, it is recommended to use appliances which have been specifically
designed for this purpose.
Before installing the boiler the following points have to be carried out by a professionally qualified person:
WARNING! In rooms where aggressive vapours or dust is present the appliance must operate independently from the air present in the boiler’s location room!
WARNING! The appliance must be installed by a qualified, registered engineer, whom, under his own responsibility, guarantees the compliance of the standards according to the latest re­gulations.
NOTE: The boiler must be connected to a heating system which is compatible to its performance and output.
a) The whole system should be thoroughly flushed in order to remove any residual dirt or grime which could compromise correct boiler operation.
b) Check that the boiler has been preset for operating with the gas type available. This is verifiable via the indication on the packaging and on the data badge;
c) Check that the chimney/flue pipe has an adequate draught, does not have any constrictions, and that no other appliance’s flue outlets have been fitted, unless the chimney is serving more than one heating appliance, according to the specific standards and regulations in force. The connection between the boiler and chimney/flue outlet can be made only after this verification has been carried out.
10
3.2 - INSTALLATION CODES OF PRACTICE
The INOXIA GJ is a boiler foreseen for operation with firewood. The appliance must be installed in compliance with all applicable laws and regulations.
Instructions for the installer
11
Instructions for the installer
1000
X
XX
XX
600
600
3.3 - HANDLING
The boiler can be easily handled by lifting hooks through holes or higher. If for reasons of space was necessary, is possible to remove the door to facilitate the introduction in the central heating.
3.4 - HEATING PLANT LOCATION
The boiler must be installed in accordance with the rules and regulations in force. The room must be well ventilated with openings having an area of not less than 1 / 30 of the floor area of the boiler room with a minimum of 0.5 m². The ventilation openings must be permanent, communicating directly with the outside and be positioned at a level high and low in accordance with the regulations in force. The location of the vents, the supply circuits Fuel, power distribution and lighting must comply with the applicable laws in force in relation to the type of fuel used You should install the boiler as close as possible to connection of the chimney. To facilitate the cleaning of the smoke circuit in front of the boiler, it must have a clear space not less than the length the boiler , and in any case, never less than 1300mm and it must verify that with the door open to 90 ° the distance between the door and the adjacent wall, is at least equal to the length burner. The boiler may be placed directly on the floor, because it has a basement. However, it is useful to provide a concrete platform, a plan to level and able to withstand the weight of the boiler when is filled with water. When placed on the hoof, this must be have at least a size of Q x S (see size tables). Once installed, the base must be perfectly horizontal and well stable (to reduce vibration and the noise level).
fig. 6
x = not less than the length of the boiler body (dimensions in mm); in any case, never less than 1300 mm. xx = see instructions to the side.
3.5 - BURNER
The burners in the service of boiler INOXIA GJ will be CE certified, and in particular comply with:
- Gas Appliance Directive (90/396/EEC);
- EMC Directive - Electromagnetic Compatibility (89/336 / EEC). They must also be approved in accordance with the specifications:
- UNI EN 676 - forced draft burners for fuel gas.
- Efficiency Directive (92/42 EEC)
3.5.1 - CHOICE OF THE BURNER
A proper selection and the adjustment of the burner are fundamental for an optimal operation of the boiler and therefore they should be accurate and not underestimated. The burner must be chose verifying its field work (fuel flow rate - pressure in the combustion chamber) that should
12
compatible with similar characteristics declared the boiler Please note that the pressure drop gas side of the boiler, or the back pressure in the combustion chamber, are reported at zero pressure at the base of the chimney. It is appropriate that the burner tube length is not less than the minimum stated in the table below, and the flame must be developed and adapted to the characteristics of our combustion chamber To exploit all the surface of the heat exchange dead-end, you must use burners that are able to provide a flame “long and narrow” in every operating condition, or even at minimum power in the case of setting up two or more stages or modulating. Flames too short causing localized overheating the front of the furnace and combustion products, not sufficiently cooled, take the flue to extreme heat can cause serious damage to the generator.
The construction companies of the burners are able to
L
Ø A
1
provide the size of the flames that develop their products, in particularly those approved under the rules indicated above. Further details are given in the “First lighting”.
Instructions for the installer
BOILER TYPE
INOXIA GJ 150 / 350 180 280
INOXIA GJ 450 / 600 210 320
INOXIA GJ 800 / 1000 270 350
øA
mm
L min.
mm
3.5.2 - BURNER INSTALLATION
The burner installation to the boiler door, must ensure a perfect seal to the combustion products.
The boiler is supplied with a piece of rope fiber ceramics to be placed on the mouthpiece of the burner so as to completely seal the space between the mouthpiece itself and the hole in the door.
Make sure that no gaps remain between the mouthpiece and the hole refractory inside the door. In the event that mounted a cone with a diameter bigger than the mouthpiece, this is must be removed before mounted the burner on the plate and reassembled it later.
fig. 7
DIMENSIONS OF BURNER BLAST TUBE
Burner installed, check that the wires have a sufficient length to allow the opening door to 90 degrees. For the gas burners is not allowed to use hoses connection so that will have the possibility of removal the final section of the outlet pipe gas, through the joint threaded or flanged.
3.6 - CONNECTION SPY CONTROL TO THE BURNER FLAME
The light flame control is equipped of a threaded 1/8 “ (Item
1) where mounted on a outlet pressure of 9 mm. to be used
with silicone pipe for measuring pressure in the combustion chamber. Instead of this outlet, which must be preserved, will be mounted a proper fitting so you can connect, through a copper tube (item 2), the light flame control directly to the plenum chamber downstream of the fan burner. The air blown by the fan will cool down properly the sight glass and prevent blackening. Failure to link the cooling to the light can cause breakage of the glass control.
CAUTION: The light flame monitoring can be very hot and then pay lot attention.
fig. 8
13
Instructions for the installer
PAVIMENTO DELLA C.T.
150
150
TAPPO DI RIEMPIMENTO INIZIALE DEL SIFONE
La di scarico non dovrà trovarsi ad un livello superiore al .
generatrice superiore del tubo
fondo della camera fumo
CAMERA FUMO
3.7 - FLUE CONNECTION
For the connection of the flue pipe must be respected the local and national regulations (see UNI-CIG 7129 4 point and 7131 point 5).
The INOXIA GJ boiler lends itself to different solutions for connecting the chimney, it is possible, by pipe line or straight curves, leaving the rear, left, right, or vertical to take in the flue in a higher level. It is recommended to isolate the connecting pipe to the chimney to reduce heat loss and noise
In the stretch between the boiler and the chimney, it must have suitable measuring points for the smokes temperature and the analysis of combustion products. WARNING: The temperature of the smoke produced from burning are lower than the other non-condensing boilers and have a content of high humidity
3.8 - CONDENSATE DRAIN
The discharge of condensate drain must be:
- designed to prevent the escape of the gas products or
combustion in the environment or sewer (siphon);
- Designed and realized in order to allow proper flow of the
liquid waste by preventing leaks;
- Installed in order to prevent freezing of the liquid that it
contains during the intended operating conditions;
- For example, mixed with domestic sewage (waste washing
machines, dishwasher, etc.). for the most basic pH in order to form a buffer solution so that it can then enter sewage system.
Should be avoid the stagnation of the condense in the system exhaust of combustion products (which is why the flue must have an inclination towards the discharge of at least 30 mm / m) with the exception of any swing of liquid in the siphon discharge system for the evacuation of the combustion
For this reason, the flue must be of a suitable material, waterproof and resistant to the acid condense. It must also be sized to ensure adequate draft.
We recommend using only conducted drain suitable for the type of fuel used. Does not accept any responsibility contractual and non- contractual of the supplier for damages caused by errors during the installation and the using and for the not observances of the instructions given by the manufacturer.
In the case of installation or replacement, replace ALWAYS also the accessory exhaust fumes. The chimney must comply with current standards.
products (which must be filled after installation and the minimum height with the boiler activated, it must be at least 25 mm-see Fig. 9).
You must not discharge the condensate through the rain gutters, because the risk of ice and degradation materials normally used in the creation of the rain gutter themselves (see the local health regulations). The connection to the discharge must be visible. The level of condensate acidity (pH 3 to 5) as materials for drain pipes must be used only plastics for (Special kits are available with optional salt neutralizers of acid condensate).
* Minimum Siphon of safety required by the standard **Minimum ledge with working boiler at the maximum power. In the event that you would or would not create a socket, the
14
BOILER ROOM FLOOR
SIPHON INITIAL FILLING CAP
SMOKE CHAMBER
PLINTH (H min 100 mm)
boiler can be fitted at the floor level and create a deep pit at least 100 mm to store the siphon.
The upper generator of the drain pipe must be higher at the bottom of the smoke chamber.
TO CONDENSATION DRAIN
fig. 9
3.9 - FURNACE DOOR, REGOLATION,
C
C
C
C
C
C
C
C
A
B
C
A
B
OPEINING, CLOSING.
IMPORTANT
- You must open the door when boiler is cold to prevent fiber
damage for the thermal shock.
- The fiber insulation door may have some cracks after a
short period of operation, this, however, does not reduce the insulating capacity and not impede the duration.
3.9.1 - BOILERS INOXIA GJ 150 ÷ INOXIA GJ 350
For all these models, the hinge and fixing the door made according to the scheme of fig. 10. In these cases, the door is fitted with two rotation hinges on the left side, and two locking pins on the right side, the two hinges on the left side allow the closure the door on this side, which is close by 4 screws (C). It will have exactly the opposite, however, where the door will open from left to right. To perform the inversion of the rotation, just reverse the hinges. On the door of these models is possible the following adjustment: A) adjustment in the axial direction: You can tighten more or less the screws “C”.
Instructions for the installer
- The fiber port is easily replaceable and is covered by 2 year warranty.
fig. 10
3.9.2 - BOILERS INOXIA GJ 450 ÷ INOXIA GJ 1000
For all these models, the hinge and fixing the door made according to the scheme of fig. 11. In these cases, the door is fitted with four equal hinges : the two on the left side, with pin added, are normally used as hinges rotation (from right to left), while the two on the right are used as hinges closing; the door is then locked with four screws. It will have exactly the opposite, however, where the door will open from left to right. To perform the inversion of the rotation, just move the pins on the opposite side. On the door of these models are possible the following adjustments: A) Vertical adjustment: it is possible only with the inserting of washers with suitable thickness under the hinge on which rotates the door. B) Transversal Adjustment: it is possible loose the hinges fixed on the plate to the front of the boiler and moving them to the side. C) Axial adjustment: you can tighten more or less the nuts.
fig. 11
15
Instructions for the installer
3.9.3 - IMPORTANT
Before opening the furnace door is necessary to take following security measures:
- Close the fuel supply to the burner.
- Cool the boiler circulating water system, and then remove the power supply.
- Put a sing on the boiler with the following Text: DO NOT
USE, BOILER MAINTENANCE OUT OF SERVICE
3.10 - CENTRAL HEATING CONNECTION
WARNING! Before installing the boiler we recommend that the system is flushed out with a suitable product in order to eliminate any metallic tooling or welding residues, oil and grime which could reach the boiler and affect the proper running of the boiler. Do not use any solvents for flushing out the system as they could damage the system and/or its components. Non-observance of these instructions could cause injury to persons, animals or damage to property. The manufacturer shall not be held liable for any such injury and/or damage.
WARNING! If this precaution is not taken it could lead to injury to persons, animals or damage to property. The manufacturer shall not be held liable for any such injury and/or damage.
Expansion vessel connection
The INOXIA GJ boilers are suitable for operation with water movement forced with open or closed expansion vessel An expansion vessel is always necessary to compensate the increase in water volume caused to the heating.
The piping connecting of the expansion vessel will start by the attack T3 (see Table Size) and should not have any interception valve
Connection the filling /discharge cock
For the filling and the discharge of the boiler an apposite cock can be connected to the attack T5, which is located in back.
Warning! Be sure to make a connection pipes without stress mechanics points to avoid the danger of loss!
The flow and return circuits have to be connected to the boiler via the respective connections as indicated on page 8. When determining the size of the CH circuit pipes it is essential to bear in mind the pressure losses induced by the radiators, any eventual thermostatic radiator valves, lockshield valves and by the system’s layout..
Ensure yourself that the system’s piping is not used as earth clamps for the electrical or telephonic system. They are absolutely unsuitable for this use. In a short time this could cause serious damage to the piping, boiler and radiators.
Pressure relief valve drain pipe
In correspondence to the heating pressure relief valve provision should be made to install a discharge pipe with a funnel and a siphon which lead to an adequate drainage. The drainage has to be controllable by sight.
16
Instructions for the installer
3.11 - FILLING THE SYSTEM
Warning! Do not mix the CH system’s water with unsuitable antifreeze products or use wrong concentrations of anti-corrosion solutions ! This could cause damage to the washers and could provoke noise during normal boiler operation. UNICAL refuses all liability for injury to persons, animals or damage to property deriving from not having respected the above mentioned recommendations.
After completing all the system’s service connections the circuits may be filled by carefully following out the following phases:
- open the radiator’s air vents and check that the automatic air vent in the boiler is working properly.
- gradually open the appropriate filling cock and check that the automatic air vents fitted onto the system are working properly.
- close the radiator’s air vents as soon as water begins to flow out.
- using the pressure gauge check that the pressure reaches the value of 1 bar.
- close the filling cock and then bleed off the air once again through the radiator’s air vents.
- check all the connections for soundness.
- after having fired the boiler and the system has reached the correct temperature , stop the pump and repeat the air
bleeding operations.
- let the system cool down and, if necessary, re-establish the water pressure to1 bar.
3.12 - GAS CONNECTION
DANGER! The gas connection must be carried out only by a qualified engineer who will have to respect and comply to the regulations in force and to the requirements indicated by the local gas supplier. An incorrect installation could cause injury to persons, animals or damage to property. The manufacturer shall not be held liable for any injury and/or damage.
Before installing the boiler it is recommended to thoroughly clean all the fuel feed pipework in order to remove any eventual residual grime which could compromise the boilers correct functioning.
Warning! Be sure to make a connection pipes without stress mechanics points to avoid the danger of loss!
If you smell gas: a. Do not turn on or off electrical switches, use the telephone or any other object which can provoke sparks; b. Open all doors and windows in order to allow fresh air to enter and purify the room; c. Close all gas cocks; d. Contact a service engineer, qualified installer or the gas supply company.
NOTE: The minimum low water pressure switch will not give the electrical impulse to fire the burner if the pressure is lower then 1 bar. use the filling cock on the boiler to adjust the pressure. This operation must be carried out when the system is cold.
NOTE! If the boiler has not been fired for a long period the pump could be jammed. Before firing the boiler, it is important to carry out the following un­jamming operation:
- place a cloth underneath the pump
- remove the pump vent plug positioned in the centre of the pump
- using a screwdriver, rotate the shaft in a clockwise direction. Once this operation has been concluded, screw back the pump vent plug and check that there have been no water leaks.
WARNING! After removing the pump vent plug some slight water leakage could occur. Before replacing the front panel dry all the wet surfaces.
As a safety measure against gas leaks, Unical recommends installing a surveillance and protective system composed of a gas leakage detector combined with an on-off solenoid valve fitted on the gas supply line.
The gas supply pipe must have an appropriate section to the burner capacity.
The gas supply pipe must have a section which is identical or greater then the one used on the boiler and must assure a correct gas pressure.
It is however important to comply with the “General installation standards” indicated in the standards UNI 7129, UNI 7131 and UNI 1137-1.
Before commissioning an internal gas distribution system and therefore before connecting it to the gas meter, the complete installation must be tested for gas soundness.
If any part of the system is concealed from view the gas soundness test must be carried out before covering the pipes.
Before connecting the pipework the system must be tested with air or inert gas at a pressure of at least 100mbar.
17
Instructions for the installer
Before commissioning the boiler ensure that the following operations are carried out:
- Open the gas meter cock and vent the air contained in the
piping and subsequently proceed to vent device by device.
- Check, with the gas cock turned off, that there are no gas
leaks. During the 2nd quarter of the hour from the start of the test, no pressure reduction should be detected by the pressure gauge. Any gas leaks must be found by using only water soap solutions, or an equivalent product, and eliminated. Never look for gas leaks using a naked flame
18
3.13 - PAKAGING
Instructions for the installer
The INOXIA GJ boilers are supplied with door and smokebox fitted, while the casing with the isolation is contained in cardboard boxes separately.
The instrument panel and accessories are within the combustion chamber.
Before starting the installation, make sure that the length and the width of the boiler received, listed in Table pag. 8, correspond to the size of the boiler ordered and that the boxes containing the casing, or part of it are branded as the table below.
The coat of boilers from INOXIA GJ150 to INOXA GJ 350, complete with its insulating mats, is contained in 2 cartons.
The coat of boilers from INOXIA GJ 450 to INOXA GJ 1000 is contained in 3 boxes
In addition to the above panel, packed with its own board, as
accessories in the combustion chamber it will find also:
- 1 carton containing the flanges hydraulic connection with
related fittings and bolts.
- Ceramic fiber rope for insulation between the cylinder
burner and the door.
- 1 bag containing the kit drain.
After having unpacked the boiler check that it is intact and undamaged.
Keep the packaging material (cardboard box,plastic bags, polyester protection etc.)
out of the reach of children as they can be dangerous. UNICAL refuses all liability for injury to
persons, animals or damage to property deriving from not having respected the above mentioned recommendations.
In the packaging, in addition to the boiler, you can also find the following contents:
- Service logbook
- User’s instruction guide
- Installation and servicing manual
- Warranty
- Adhesive label local ventilation standards
N.B. For the INOXIA GJ 150 model to INOXIA GJ 350 (ref. fig.
12),
the casing and insulation are contained in 2 marked
boxes
:
34059 ( 34060 (lower casing INOXIA GJ 150/200) 34061 ( 34062 (lower casing INOXIA GJ 270/350)
N.B. For the INOXIA GJ 450 model to INOXIA GJ 1000 (ref.
34063 ( 34064 (lower casing INOXIA GJ 450/600) 34065 ( 34066 ( 34067 (lower casing INOXIA GJ 800/1000) 34068 (
top casing
top casing
fig. 12), boxes:
top casing
front casing top casing
front casing
INOXIA GJ 150/200)
INOXIA GJ 270/350)
the casing and insulation are contained in 3 marked
INOXIA GJ 450/600)
/rear INOXIA GJ 450/600)
INOXIA GJ 800/1000)
/rear INOXIA GJ 800/1000)
19
Instructions for the installer
3.14 - SHELL INSTALLATION
A) Fix the support brackets (item 1 and 2) of the below hip
shell to the boiler by 8 screws M 6x20 and the associated nuts and washers.
B) Install the bottom insulation of the boiler (Item 3) and fix
the two strips joints with elastic pegs (item 5) provided in the accessory box, hooked to the outer fabric insulation.
C) Install the upper insulation of the boiler (item 4) and fix
the two strips joints with elastic pegs (item 5) provided in the accessory box, hooked to the outer fabric of the bottom insulation
D) Install the front insulation (Item 6) on the hinges.
E) Install the insulation back pos. 7.
F) Put the lower side panels (item 8 and 9) with the lower
fold in the L profiles on the support basis of the boiler, and hooking the top part in the cuts on the brackets pos. 1 and
2.
G) Lift forward the cover of the control panel after unscrew the
two side screws with a screwdriver and drive in holes on the base the entering electrical cables and the capillaries of output the probe. Fasten the control panel to the right above side panel (item
11).
H) Place the side panels above (Item 10 and 11) by engaging
side panels below and fitting the upper part in the cuts expected on the plates of the boiler.
I) Insert the bulbs into the sheaths of the instruments as
shown in fig. 13, route the cables through the side fairlead on the side where you want to go out and make the electrical connection of the panel control to the power line, to the burner and any eventual pumps, etc.. Replace the box cover of the electric board. Fix the support plate of the fairlead (item 12) on two side
Fix the side cover plate (item 13) on the left side
J) Attach to the side panels the front panels pos. 16 and 17.
K) Put the upper front panel pos. 14 and attach it by pressing
the two side panels.
L) Fix the two crossbeams can. 19 to the rear panel pos. 18. Fasten the panel to the rear side panel lower left .
Secure the two panel pos. 20 at the rear side panel lower right corner. Combine the two rear panels with reinforcing profile pos.
21.
M) Fix the top rear panel to the two side upper panels
N) Place the top rear panel pos. 23 and attach it by pressing
to the two side panels.
O) Fix the boiler labels and installation data (Item 24) to the
side panel after degreasing it with a suitable solvent.
The plates are inserted into the envelope documents
20
Instructions for the installer
5
24
4
8
10
12
13
6
3
1
2
7
23
20
14
19
17
21
18
1
2
11
9
16
12
15
fig. 12
21
Instructions for the installer
2
1
4
3
5
3
4
1 Thermometer probe 2 Working thermostat probe 3 Capillaries fixing spring 4 Safety clip 5 Safety thermostat probe
fig. 13
3.15 - ELECTRICAL CONNECTIONS
GENERAL WARNINGS
The appliance’s electrical safety is guaranteed only when the same appliance has been correctly earthed in compliance with the regulations in force. The gas and water feeding pipes and the CH system pipes cannot be used as ground plates.
Ensure that the above safety electrical requirements subsist; in case of doubt, ask for a professionally qualified technician to check the appliance’s electrical system. UNICAL refuses responsibility for any damages arising from failure to earth the boiler correctly.
It is necessary that a qualified technician verifies that the electrical system is adequate to the appliance’s maximum absorbed power, indicated on the data plate, verifying in particular that the section of the system’s cables is suitable to the appliance’s maximum absorbed power.
For the appliance’s general electrical supply the use of adaptors, multiple sockets and/or extension cords is strictly forbidden.
The use of any power supplied equipment implies the observance of several fundamental rules, such as:
- Do not touch the appliance with any wet part of your body
and/or barefooted;
- Do not pull the supply cables;
- Do not expose the boiler to sunlight, rain, etc., unless it is
- Do not permit children or inexpert people to use the
explicitly foreseen;
appliance.
Connection to mains supply 230V
The electrical connections are shown at ch. 3.16, 3.17, 3.18,
3.19 and 3.21 for operation with modulating burners and the ch. 3.22, 3.23, 3.24, 3.25 and 3.27 for operation with burners two stages
A mains supply of 230 V – 50 Hz is required. The wiring to the boiler must be in accordance with the current CEI regulations.
DANGER! The electrical connections must be carried out only by a qualified engineer. Before carrying out the connections or any other operation on the electrical parts, always switch off and disconnect the electricity supply and ensure yourself that it cannot be accidentally turned on.
Note: It is necessary to fit a double pole switch on the electrical supply line, having a 3 mm contact separation in both poles, in an easy accessible position so as to ensure quick and safe servicing.
The replacement of the supply cable as to be carried out by a qualified authorized UNICAL engineer, using only original spare parts. The non-observance of the above could compromise the appliance’s safety.
22
3.16 - TOOLS PANEL MODULATING MASTER
14 15 16 17
35
33
34
18 19 20 21 22 23
21. 0
20
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
COD. 37892
Through the general switch 14, place under tension the framework and equipment connected to it. The switches 18 and 19 , controlling the burner and the pump P1 in the case of boiler cascade. The switches 20 and 21, controls the pump Z1 (direct) and pump Z2 (mixed). With the temperature controller, adjusts the temperature of the boiler, to achieve this, the thermostat will be located at the bottom scale up. 33 The possible modulation of the burner will be managed by thermoregulation. On the power line control panel of the boiler, must be provided with a switch with fuses protection
Instructions for the installer
14 switch with indicator light 16 main fuse 18 Burner switch 19 P1 Switch pump system (cascade)
20 switch system pump direct zone PZ1 21 switch system pump mixed zone Pz2 33 thermostat operation 35 Safety thermostat
To use the instrument panel, see instruction manual for the installer. As for the practical schemes of connection and operation, see documentation provided in the instrument panel code. 37892
The probes of the temperature controller (boiler, water heater, external delivery) are included in the supply, environmental probes 1 and 2 are optional, the mixing valve and its engine command are not supplied.
If you fit the room temperature sensors (optional), temperature environments will be determined only under the curve boiler set by the program.
If you plan the installation of two boilers in cascade see Section 3.19, 3.20, 3.21.
3.17 - PROGRAMMING THE TEMPERATURE
CONTROLLER WITH SINGLE BOILER
Regarding the adjustment or programming of the temperature controllers, see the booklet enclosed with the individual Temperature Controller Following the parameters programmed in the factory and therefore “can not be changed.”
Regarding the user-programmable parameters according to your needs, see the instruction manual for the responsible of the installation.
fig. 14
23
Instructions for the installer
PROGRAMMABLE PARAMETERS FOR THECNICIAN AND PROTECTED BY CODE NUMBER FOR THERMOREGULATOR type E8.5064
INSTALLATION
Default Personal valuesValue range Designation
CODE NUMBER Entry
CODE NUMBER (variation) 0000
ADDRESS BUS BOILER ----
ADDRESS BUS 1 01
ADDRESS BUS 2 02
VOLTAGE AF 01 (ON)
BUS CONNECTION 01
POWER BUS 01 (ON)
MASTER TEMPERATURE
MAX T-MAX CR1 COLLECTOR
MIN MIN-T CR1 COLLECTOR
MAX-T CR2 85 °C
MIN-T CR2 10 °C
VOLTAGE CURVE 11
CURVE 11-U2 0V
CURVE 11-U2 10V
CURVE 11-T1 0 °C
CURVE 11-T2 100 °C
CURVE 11-UA 0V
WASTE START 10
MINIMUM
HYSTERESIS
TIME HYSTERESIS
BOILER FOUND
POWER LEVEL * see notes
NEW CONFIGURATION
MINIMUM MODULATION 00
ACS LEVELS 00
DIFFERENCE REGULATOR Display
INDEX POWER RATED Display
SWITCHING VALUE Display
TIME BLOCK Display
MAXIMUM TEMPERATURE BOILERS 85
DYNAMIC BOILER RISING 30K
DYNAMIC BOILERS DESCENDANT 20K
TIME READJUSTMENT 50
INDEX MODULATION ON 80%
INDEX MODULATION OFF 50%
INDEX MODULATION MIN 0%
POWER INDEX MODULATION 80%
BOILER SERIES 1° 12345678
BOILER SERIES 2° 87654321
0000 - 9999
0000 - 9999
......, 01 - 08
(00), 01 - 015
(00), 01 - 016
00,01 (disins/ins)
0,01
00,01 (disins/ins)
00, 01 (OFF / ON)
30 °C - 110 °C
10 °C - 80 °C
30 °C - 110 °C
10 °C - 80 °C
0 - 11
0,00-10,00V
0,00-10,00V
00 - 120 °C
00 - 120 °C
0,00-10,00V
10 °C - 85 °C
00, 01, 02
2K - 20K
00 - 30 min
Only display
00 - 1000kW
00,01 (disins/ins)
00 - 100
00 - 08
(K)
0 - 100%
(-99) - 0 - (99)
RESTO (min)
50 - 110°C
20 - 500K
20 - 500K
5 - 500
0% - 100%
0% - 100%
0% - 100%
40% - 100%
----
----
01 (ON)
85 °C
10 °C
00
5
00 min
24
Instructions for the installer
Default Personal valuesValue rangeDesignation
MODE SERIES 01
CHANGE SEQUENCE
CYCLE BLOCK
HYSTERESIS 2 ° BURNER
BOILER COOLING
COOLING TEMPERATURE. BOILER
TYPE 1 CIRCUIT
CIRCUIT 1 BUS
TYPE 2 CIRCUIT
TANK CIRCUIT 2
PUFFER TYPE
SCREED
SCREED PROGRAM
* Set the value of the first stage of the first boiler to 1, in the second to leave the dashes. All other stages of the boilers should be disabled.
** See instruction manual controller E8.5064
DOMESTIC HOT WATER PRODUCTION
CHARGE PUMP 01 (ON)
PARALLEL PUMP OPERATION 01
TAC 20K
AC HYSTERESIS 5 gradi
DELAY AC 00 min
INLET THERMOSTAT 00 OFF
FUNC. THERMOSTAT 00 OFF
LOADING 00 OFF
01 - 06
10 - 800 hours
00 min - 30 min
2K - 20K
00 - 01
30°C - 120°C
00 - 06
00 - 04
00 - 05
01 - 03
01 - 01 - 02
00, 01 (OFF - ON)
** see note
00 - 01 (OFF / ON)
00 , 01, 02, 03
00K - 50K
5K - 30K
00 min - 30 min
00, 01 (OFF / ON)
00, 01 (OFF / ON)
00, 01 (OFF / ON)
200 hours
00 min
2K
00
95
06
04
00
00
00
00 OFF
Default Personal valuesValue rangeDesignation
BACK
HEATING CIRCUIT 1
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
MAX TEMPERATURE DISCHARGE 80 °C
MINIMUM DELIVERY TEMPERATURE 30 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
BACK
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
Exit level using
25
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
HEATING CIRCUIT 2
Default Personal valuesValue rangeDesignation
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
MAX TEMPERATURE DISCHARGE 45 °C
MINIMUM DELIVERY TEMPERATURE 10 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
BACK
Exit level using
SOLARE M/F
Default Personal valuesValue rangeDesignation
FUNCTION MF (1-4) 00,00,01,02
MF (1-4) T- NOM 30°C
HISTERESIS (1-4) MF 5°C
FUNCTION F 15 0
BACK
Exit level using
00 - 26
00 - 03
5 - 25
5 - 25
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR
type Lago Basic 0201 RV 1
1
2
3
fig. 15
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2)
2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2)
3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 1 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN.
26
Instructions for the installer
Ps
PRODUTTORE ACQUA CALDA SANITARIA
Pb
Pz1
IR/BT
Pz2
Vmix2
IR/AT
SPF
VF
KF1
VE
14 15 16 17
35
33
34
18 19 20 21 22 23
21.020
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
KF
CALDAIA INOXIA GJ
3.18 - WATER AND ELECTRICAL CONNECTION WITH THE PANEL INSTRUMENTS cod.
37892
The fig. 16 shows the typical pattern of connection of the boiler to the heating system made by a high direct area and a zone low temperature controlled by mixing valve engine + hot sanitary water
IMPORTANT NOTE: In case of a single area (high or low) always enter the system return lower back in the attack
Key:
Vmix2 = mixing valve area (motorized) PZ1 = pump heating zone HIGH TEMPERATURE Pz2 pump heating zone = LOW EV = vessel expansion IR / AT = distribution of the heating HIGH TEMPERATURE IR / BT = distribution of the heating LOW Ps = hot water recirculation pump Pb = charge pump hot water producer SPF = tank sensor KF = boiler temperature control probe E8.5064 KF1 = boiler temperature control probe Lake Basic 0201 RV 1 VF = outlet probe AF = external probe
For practical connections, and electrical probes, refer to the diagram supplied with the panel instruments cod. 37892
fig. 16
27
Instructions for the installer
The instrument panel of the boiler INOXIA GJ manages automatically the turn off the burner when the temperature in the boiler reaches the value set on the controller.
It also runs the pump for the load of a for the heater production of A.C.S.
The management of heating, it comes automatically on the basis of data collected by the sensors external boiler environment and delivery
The high temperature zone pump system will be in a position of working through the control switch pos.20, and will turn off only when reaches the temperature by the thermo regulator.
The pump system lower temperature zone, is put on operating status through the control switch pos. 21, and will turn off only when reaches the temperature delivery through the thermo regulator.
The charge pump of the boiler for the production of acs, will be put into operation automatically, and will be switched off when will reach the temperature of delivery through the controller.
For practical connections, electrical, and probes, refer to the diagram supplied with the panel instruments cod. 37892
The panel is designed for the management of burners in operation modulator.
With this plant configuration, the controller is able to control:
- Plant of a direct area, the controller controls the pump plant. The temperature will be controlled by programming curves set in the thermo regulator.
- Plant of an area with motorized mixing valve: install the flow sensor (downstream of the valve mixing), the controller controls the pump system and mixing valve. The temperature will be adjusted through curves programming set in the thermo regulator;
- Production of a.c.s. through boiler;
- Anti-Legionella function with increased water temperature storage in the boiler (function not enabled factory, but which can be activated by the customer).
28
3.19 - PROGRAMMING TEMPERATURE WITH
BOILERS CASCADE
Instructions for the installer
Regarding the adjustment or programming of the temperature controllers, see the booklet enclosed with the individual Temperature Controller Following the parameters set in the factory and therefore “can not be changed.”
PROGRAMMABLE PARAMETERS FOR TECHNICIANS, PROTECTED BY CODE NUMBER FOR THERMOREGULATOR type E8.5064
INSTALLAZIONE
CODE NUMBER Entry-
CODE NUMBER (variation) 0000
ADDRESS BUS BOILER ----
ADDRESS BUS 1 01
ADDRESS BUS 2 02
VOLTAGE AF 01 (ON)
BUS CONNECTION 01
POWER BUS 01 (ON)
MASTER TEMPERATURE
MAX T-MAX CR1 COLLECTOR
MIN MIN-T CR1 COLLECTOR
MAX-T CR2 85 °C
MIN-T CR2 10 °C
VOLTAGE CURVE 11
CURVE 11-U2 0V
CURVE 11-U2 10V
CURVE 11-T1 0 °C
CURVE 11-T2 100 °C
CURVE 11-UA 0V
WASTE START 10
MINIMUM
HYSTERESIS
TIME HYSTERESIS
BOILER FOUND
POWER LEVEL * see notes
NEW CONFIGURATION
MINIMUM MODULATION 00
ACS LEVELS 00
DIFFERENCE REGULATOR Display
INDEX POWER RATED Display
SWITCHING VALUE Display
TIME BLOCK Display
MAXIMUM TEMPERATURE BOILERS 85
DYNAMIC BOILER RISING 30K
Regarding the user-programmable, according to the needs , see the instruction manual for Responsible of the installation.
Default Personal valuesValue rangeDesignation
0000 - 9999
0000 - 9999
......, 01 - 08
(00), 01 - 015
(00), 01 - 016
00,01 (disins/ins)
0,01
00,01 (disins/ins)
00, 01 (OFF / ON)
30 °C - 110 °C
10 °C - 80 °C
30 °C - 110 °C
10 °C - 80 °C
0 - 11
0,00-10,00V
0,00-10,00V
00 - 120 °C
00 - 120 °C
0,00-10,00V
10 °C - 85 °C
00, 01, 02
2K - 20K
00 - 30 min
Only display
00 - 1000kW
00,01 (disins/ins)
00 - 100
00 - 08
(K)
0 - 100%
(-99) - 0 - (99)
RESTO (min)
50 - 110°C
20 - 500K
01 (ON)
85 °C
10 °C
00
5
00 min
29
Instructions for the installer
Default Personal valuesValue rangeDesignation
DYNAMIC BOILERS DESCENDANT 20K
TEMPO RIAGGIUSTAMENTO 50
INDEX MODULATION ON 80%
INDEX MODULATION OFF 50%
INDEX MODULATION MIN 0%
POWER INDEX MODULATION 80%
BOILER SERIES 1 ° 12345678
BOILER SERIES 2 ° 87654321
20 - 500K
5 - 500
0% - 100%
0% - 100%
0% - 100%
40% - 100%
----
----
SEQUENCE MODE 01
CHANGE SEQUENCE
CYCLE BLOCK
HYSTERESIS 2 ° BURNER
BOILER COOLING
COOLING TEMPERATURE. BOILER
TYPE 1 CIRCUIT
CIRCUIT 1 BUS
TYPE 2 CIRCUIT
TANK CIRCUIT 2
PUFFER TYPE
SCREED
SCREED PROGRAM
* Set the value of the first stage of the first boiler to 1, in the second to leave the dashes. Set the value of the first stage of the second boiler 1, the second to leave the dashes. In the case of more than 2 boilers in cascade to enable the early stages of the boilers in cascade ** See instruction manual controller E8.5064 **
DOMESTIC HOT WATER PRODUCTION
CHARGE PUMP 01 (ON)
PARALLEL PUMP OPERATION 01
T AC 20K
AC HYSTERESIS 5 degrees
DELAY AC 00 min
INLET THERMOSTAT 00 OFF
FUNC. THERMOSTAT 00 OFF
LOADING 00 OFF
01 - 06
10 - 800 hours
00 min - 30 min
2K - 20K
00 - 01
30°C - 120°C
00 - 06
00 - 04
00 - 05
01 - 03
01 - 01 - 02
00, 01 (OFF - ON)
** see notes
00 - 01 (OFF / ON)
00 , 01, 02, 03
00K - 50K
5K - 30K
00 min - 30 min
00, 01 (OFF / ON)
00, 01 (OFF / ON)
00, 01 (OFF / ON)
200 hours
00 min
2K
00
95
06
04
00
00
00
00 OFF
Default Personal valuesValue rangeDesignation
BACK
HEATING CIRCUIT 1
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
30
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
Instructions for the installer
Default Personal valuesValue rangeDesignation
MAX TEMPERATURE DISCHARGE 80 °C
MINIMUM DELIVERY TEMPERATURE 30 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
BACK
HEATING CIRCUIT 2
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN 18
MIXER CLOSED 12
MAX TEMPERATURE DISCHARGE 45 °C
MINIMUM DELIVERY TEMPERATURE 10 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
BACK
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
Exit level using
SOLAR M/F
Default Personal valuesValue rangeDesignation
FUNCTION MF (1-4) 00,00,01,02
MF (1-4) T- NOM 30°C
HISTERESIS (1-4) MF 5°C
FUNCTION F 15 0
BACK
Exit level using
00 - 26
00 - 03
5 - 25
5 - 25
31
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR Type Lago Basic 0201 RV 1 ON BOILER N°1
1
2
3
fig. 18
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2)
2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2)
3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 1 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN.
32
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
31
42
11
41
12
13
32
3.20 - PANEL INSTRUMENTS MODULATING
CASCADE cod. 37900
With the switch 11 , place under tension the framework and equipment connected to it. The switches 12 and 13 , control the burner and the pump P1 in the case of boiler cascade The temperature controller adjusts the temperature Boiler No. 2: To achieve this, the thermostat will be located in scale up pos. 32 . The possible modulation of the burner will be managed by the thermoregulatory
On the boiler power line control panel must be provided with a switch fuses protection
Instructions for the installer
11 switch with indicator light 12 Power Burner
32 thermostat operation 41 main fuse
fig. 17
13 Power plant pump P1 (waterfall) 31 Safety thermostat
To use the instrument panel, see instruction manual for the plant manager. As for the practical schemes of connection and operation, see documentation provided in the instrument panel code. 37900
The boiler sensor included in the supply.
33
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR Type Lago Basic 0201 RV 1 ON BOILER N°2
1
2
3
fig. 19
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2)
2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2)
3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 2 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN.
34
Instructions for the installer
P1
°C
OK
12
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
31
42
11 41
12
13
32
Ps
PRODUTTORE ACQUA
CALDA SANITARIA
Pb
Pz1
P1
IR/BT
Pz2
Vmix2
IR/AT
SPF
VF
14 15 16 17
35
33 34
18 19 20 21 22 23
21.020
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
12
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
EVENTUALE SEPARATORE IDRAULICO
PER IL PERFETTO BILANCIAMENTO
DELL’IMPIANTO
KF
KF1
VE
CALDAIA INOXIA GJ 1
KF1
VE
CALDAIA INOXIA GJ 2
fig. 20
P1= circulator pump
Pb = charge pump hot water producer
SPF = tank sensor
KF = boiler temperature control probe E8.5064
KF = 1 boiler temperature control probe Lake Basic 0201 RV 1
VF = outlet probe
AF = external probe
3.21 – WATER AND ELECTRICAL CONNECTION WITH CASCADE BOILER PANEL INSTRUMENTS cod. 37892 & 37900
The fig. 20 shows the typical pattern of connection of the boiler to the heating system, it consists of two boilers with cascade function at the service of an area high
temperature and a low temperature zone controlled by motorized mixing valve + production of hot water.
The boiler No. 1 is equipped with an instrument panel code. 37892, boiler No. 2 is equipped with an instrument panel code. 37900
Vmix2 = mixing valve area (motorized)
PZ1 = pump heating zone HIGH TEMPERATURE
Pz2 pump heating zone = LOW
EV = vessel expansion
IR / AT = distribution of the heating HIGH TEMPERATURE
IR / BT = distribution of the heating LOW
Ps = hot water recirculation pump
35
Instructions for the installer
The instruments panels of the boilers INOXIA GJ manage automatically the turn off the burner when the temperature in the boiler reaches the value set on the controller. It also runs the pump for the load of a for the heater production of A.C.S.
The management of heating, it comes automatically on the basis of data collected by the sensors external boiler environment and delivery
The high temperature zone pump system will be in a position of working through the control switch pos.20 of the Master table, and will turn off only when reaches the temperature by the thermo regulator.
The pump system lower temperature zone, is put on operating status through the control switch pos. 21 of the Master table, and will turn off only when reaches the temperature delivery through the thermo regulator.
The charge pump of the boiler for the production of acs, will be put into operation automatically, and will be switched off when will reach the temperature of delivery through the controller.
The panel is designed for the management of burners in operation modulator.
With this plant configuration, the controller is able to control:
- Plant of a direct area, the controller controls the pump plant. The temperature will be controlled by programming curves set in the thermo regulator.
- Plant of an area with motorized mixing valve: install the flow sensor (downstream of the valve mixing), the controller controls the pump system and mixing valve. The temperature will be adjusted through curves programming set in the thermo regulator;
- Production of a.c.s. through boiler;
- Anti-Legionella function with increased water temperature storage in the boiler (function not enabled factory, but which can be activated by the customer)
For practical connections, electrical, and probes, refer to the diagram supplied with the panel instruments cod. 37892 and 37900
36
3.22 - PANEL INSTRUMENTS MASTER
14 15 16 17
35
33
34
18 19 20 21 22 23
21. 0
20
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
BISTADIO cod. 38778
With the switch 14 , place under tension the framework and equipment connected to it. The switches 18 and 19 , control the burner and the pump P1 in the case of boiler cascade The switches 20 and 21 , control the PUMP Z1 (direct) and the PUMP Z2 (mixed) The temperature controller adjusts the temperature Boiler No. 2: To achieve this, the thermostat will be located in scale up pos. 33 . The possible modulation of the burner will be managed by the thermoregulatory On the boiler power line control panel must be provided with a switch fuses protection
Instructions for the installer
14 switch with indicator light 16 main fuse 18 Burner switch 19 P1 Switch pump system (cascade
20 switch system pump forward zone PZ1 21 switch system pump area mixed Pz2 33 thermostat operation 35 Safety thermostat
To use the instrument panel, see instruction manual for the plant manager. As for the practical schemes of connection and operation, see documentation provided in the instrument panel code. 38778
The probes of the temperature controller (boiler, water heater, external delivery) are included in the supply, environmental probes 1 and 2 are optional, the mixing valve and its engine command are not supplied.
If you fit the room temperature sensors (optional), temperature environments will be determined only under the curve boiler set by the program.
If you plan the installation of two boilers in cascade see Section 3.25, 3.26, 3.27
3.23 - PROGRAMMING THE TEMPERATURE
CONTROLLER WITH SINGLE BOILER
Regarding the adjustment or programming of the temperature controllers, see the booklet enclosed with the individual Temperature Controller Following the parameters programmed in the factory and therefore “can not be changed.”
Regarding the user-programmable parameters according to your needs, see the instruction manual for the responsible of the installation.
fig. 21
37
Instructions for the installer
PROGRAMMABLE PARAMETERS FOR THECNICIAN AND PROTECTED BY CODE NUMBER FOR THERMOREGULATOR type E8.5064
INSTALLATION
Default Personal valuesValue rangeDesignation
CODE NUMBER ENTRY
CODE NUMBER (variation) 0000
ADDRESS BUS BOILER ----
ADDRESS BUS 1 01
ADDRESS BUS 2 02
VOLTAGE AF 01 (ON)
BUS CONNECTION 01
POWER BUS 01 (ON)
MASTER TEMPERATURE
MAX T-MAX CR1 COLLECTOR
MIN MIN-T CR1 COLLECTOR
MAX-T CR2 85 °C
MIN-T CR2 10 °C
VOLTAGE CURVE 11
CURVE 11-U2 0V
CURVE 11-U2 10V
CURVE 11-T1 0 °C
CURVE 11-T2 100 °C
CURVE 11-UA 0V
WASTE START 10
MINIMUM
HYSTERESIS
TIME HYSTERESIS
BOILER FOUND
POWER LEVEL * see notes
NEW CONFIGURATION
MINIMUM MODULATION 00
ACS LEVELS 00
DIFFERENCE REGULATOR Display
INDEX POWER RATED Display
SWITCHING VALUE Display
TIME BLOCK Display
MAXIMUM TEMPERATURE BOILERS 85
DYNAMIC BOILER RISING 30K
DYNAMIC BOILERS DESCENDANT 20K
TIME READJUSTMENT 50
INDEX MODULATION ON 80%
INDEX MODULATION OFF 50%
INDEX MODULATION MIN 0%
POWER INDEX MODULATION 80%
BOILER SERIES 1 ° 12345678
BOILER SERIES 2 ° 87654321
0000 - 9999
0000 - 9999
......, 01 - 08
(00), 01 - 015
(00), 01 - 016
00,01 (disins/ins)
0,01
00,01 (disins/ins)
00, 01 (OFF / ON)
30 °C - 110 °C
10 °C - 80 °C
30 °C - 110 °C
10 °C - 80 °C
0 - 11
0,00-10,00V
0,00-10,00V
00 - 120 °C
00 - 120 °C
0,00-10,00V
10 °C - 85 °C
00, 01, 02
2K - 20K
00 - 30 min
Only display
00 - 1000kW
00,01 (disins/ins)
00 - 100
00 - 08
(K)
0 - 100%
(-99) - 0 - (99)
RESTO (min)
50 - 110°C
20 - 500K
20 - 500K
5 - 500
0% - 100%
0% - 100%
0% - 100%
40% - 100%
----
----
01 (ON)
85 °C
10 °C
00
5
00 min
38
Instructions for the installer
Default Personal valuesValue rangeDesignation
SEQUENCE MODE 01
CHANGE SEQUENCE
CYCLE BLOCK
HYSTERESIS 2 ° BURNER
BOILER COOLING
COOLING TEMPERATURE. BOILER
TYPE 1 CIRCUIT
CIRCUIT 1 BUS
TYPE 2 CIRCUIT
TANK CIRCUIT 2
PUFFER TYPE
SCREED
SCREED PROGRAM
* Set the value of the first stage of the first boiler to 1, in the second to leave the dashes. All other stages of the boilers should be disabled.
** See instruction manual controller E8.5064
DOMESTIC HOT WATER PRODUCTION
CHARGE PUMP 01 (ON)
PARALLEL PUMP OPERATION 01
T AC 20K
AC HYSTERESIS 5 degrees
DELAY AC 00 min
INLET THERMOSTAT 00 OFF
FUNC. THERMOSTAT 00 OFF
LOADING 00 OFF
01 - 06
10 - 800 hours
00 min - 30 min
2K - 20K
00 - 01
30°C - 120°C
00 - 06
00 - 04
00 - 05
01 - 03
01 - 01 - 02
00, 01 (OFF - ON)
** see notes
00 - 01 (OFF / ON)
00 , 01, 02, 03
00K - 50K
5K - 30K
00 min - 30 min
00, 01 (OFF / ON)
00, 01 (OFF / ON)
00, 01 (OFF / ON)
200 hours
00 min
2K
00
95
05
04
00
00
00
00 OFF
Default Personal valuesValue rangeDesignation
BACK
HEATING CIRCUIT 1
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
MAX TEMPERATURE DISCHARGE 80 °C
MINIMUM DELIVERY TEMPERATURE 30 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
BACK
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
Exit level using
39
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
HEATING CIRCUIT 2
Default Personal valuesValue rangeDesignation
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
MAX TEMPERATURE DISCHARGE 45 °C
MINIMUM DELIVERY TEMPERATURE 10 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
BACK
Exit level using
SOLAR M/F
Default Personal valuesValue rangeDesignation
FUNCTION MF (1-4) 00,00,01,02
MF (1-4) T- NOM 30°C
HISTERESIS (1-4) MF 5°C
FUNCTION F 15 0
BACK
Exit level using
00 - 26
00 - 03
5 - 25
5 - 25
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR
type Lago Basic 0201 RV 1
1
2
3
fig. 22
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2)
2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2)
3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 1 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN.
40
Instructions for the installer
Ps
PRODUTTORE ACQUA CALDA SANITARIA
Pb
Pz1
IR/BT
Pz2
Vmix2
IR/AT
SPF
VF
KF1
VE
14 15 16 17
35
33
34
18 19 20 21 22 23
21.020
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
KF
CALDAIA INOXIA GJ
3.24 - WATER AND ELECTRICAL CONNECTION PLANT WITH THE PANEL
INSTRUMENTS - cod. 38778
The fig. 23 shows the typical pattern of connection of the boiler to the heating system made by a high direct area and a zone low temperature controlled by mixing valve engine + hot sanitary water.
NB: In case of a single system return (low or medium temperature), the connection must ALWAYS be
Keys:
carried out on the inlet and the lower back of the boiler (stub “low-temperature system return”).
fig. 23
Vmix2 = mixing valve area (motorized) PZ1 = pump heating zone HIGH TEMPERATURE Pz2 pump heating zone = LOW EV = vessel expansion IR / AT = distribution of the heating HIGH TEMPERATURE IR / BT = distribution of the heating LOW Ps = hot water recirculation pump Pb = charge pump hot water producer SPF = tank sensor KF = boiler temperature control probe E8.5064 KF1 = boiler temperature control probe Lake Basic 0201 RV 1 VF = outlet probe AF = external probe
For practical connections, and electrical probes, refer to the diagram supplied with the panel instruments cod. 38778
41
Instructions for the installer
The instrument panel of the boiler INOXIA GJ manages automatically the turn off the burner when the temperature in the boiler reaches the value set on the controller. It also runs the pump for the load of a for the heater production of A.C.S.
The management of heating, it comes automatically on the basis of data collected by the sensors external boiler environment and delivery
The high temperature zone pump system will be in a position of working through the control switch pos.20, and will turn off only when reaches the temperature by the thermo regulator.
The pump system lower temperature zone, is put on operating status through the control switch pos. 21, and will turn off only when reaches the temperature delivery through the thermo regulator.
The charge pump of the boiler for the production of acs, will be put into operation automatically, and will be switched off when will reach the temperature of delivery through the controller.
The panel is designed for the management of burners in operation modulator.
With this plant configuration, the controller is able to control:
- Plant of a direct area, the controller controls the pump plant. The temperature will be controlled by programming curves set in the thermo regulator.
- Plant of an area with motorized mixing valve: install the flow sensor (downstream of the valve mixing), the controller controls the pump system and mixing valve. The temperature will be adjusted through curves programming set in the thermo regulator;
- Production of a.c.s. through boiler;
- Anti-Legionella function with increased water temperature storage in the boiler (function not enabled factory, but which can be activated by the customer)
For practical connections, electrical, and probes, refer to the diagram supplied with the panel instruments cod. 38778
42
3.25 - PROGRAMMING TEMPERATURE
WITH BOILERS CASCADE
Instructions for the installer
Regarding the adjustment or programming of the temperature controllers, see the booklet enclosed with the individual Temperature Controller. Following the parameters set in the factory and therefore “can not be changed.”
PROGRAMMABLE PARAMETERS FOR TECHNICIANS, PROTECTED BY CODE NUMBER FOR THERMOREGULATOR type E8.5064
INSTALLATION
CODE NUMBER Entry
CODE NUMBER (variation) 0000
ADDRESS BUS BOILER ----
ADDRESS BUS 1 01
ADDRESS BUS 2 02
VOLTAGE AF 01 (ON)
BUS CONNECTION 01
POWER BUS 01 (ON)
MASTER TEMPERATURE
MAX T-MAX CR1 COLLECTOR
MIN MIN-T CR1 COLLECTOR
MAX-T CR2 85 °C
MIN-T CR2 10 °C
VOLTAGE CURVE 11
CURVE 11-U2 0V
CURVE 11-U2 10V
CURVE 11-T1 0 °C
CURVE 11-T2 100 °C
CURVE 11-UA 0V
WASTE START 10
MINIMUM
HYSTERESIS
TIME HYSTERESIS
BOILER FOUND
POWER LEVEL * see notes
NEW CONFIGURATION
MINIMUM MODULATION 00
LEVEL ACS 00
DIFFERENCE REGULATOR Display
INDEX POWER RATED Display
SWITCHING VALUE Display
TIME BLOCK Display
MAXIMUM TEMPERATURE BOILERS 85
DYNAMIC BOILER RISING 30K
Regarding the user-programmable, according to the needs , see the instruction manual for Responsible of the installation.
Default Personal valuesValue rangeDesignation
0000 - 9999
0000 - 9999
......, 01 - 08
(00), 01 - 015
(00), 01 - 016
00,01 (disins/ins)
0,01
00,01 (disins/ins)
00, 01 (OFF / ON)
30 °C - 110 °C
10 °C - 80 °C
30 °C - 110 °C
10 °C - 80 °C
0 - 11
0,00-10,00V
0,00-10,00V
00 - 120 °C
00 - 120 °C
0,00-10,00V
10 °C - 85 °C
00, 01, 02
2K - 20K
00 - 30 min
Only display
00 - 1000kW
00,01 (disins/ins)
00 - 100
00 - 08
(K)
0 - 100%
(-99) - 0 - (99)
RESTO (min)
50 - 110°C
20 - 500K
01 (ON)
85 °C
10 °C
00
5
00 min
43
Instructions for the installer
Default Personal valuesValue rangeDesignation
DYNAMIC BOILERS DESCENDANT 20K
TIME READJUSTMENT 50
INDEX MODULATION ON 80%
INDEX MODULATION OFF 50%
INDEX MODULATION MIN 0%
POWER INDEX MODULATION 80%
BOILER SERIES 1 ° 12345678
BOILER SERIES 2 ° 87654321
20 - 500K
5 - 500
0% - 100%
0% - 100%
0% - 100%
40% - 100%
----
----
SEQUENCE MODE 01
CHANGE SEQUENCE
CYCLE BLOCK
HYSTERESIS 2 ° BURNER
BOILER COOLING
COOLING TEMPERATURE. BOILER
TYPE 1 CIRCUIT
CIRCUIT 1 BUS
TYPE 2 CIRCUIT
TANK CIRCUIT 2
PUFFER TYPE
SCREED
SCREED PROGRAM
* Set the value of the first stage and the second stage of the first boiler 1. Set the value of the first stage and the second stage of the second boiler 1. In the case of more than 2 boilers in cascade to enable the early stages and second stages of the boilers in cascade. ** See instruction manual controller E8.5064
DOMESTIC HOT WATER PRODUCTION
CHARGE PUMP 01 (ON)
PARALLEL PUMP OPERATION 01
T AC 20K
AC HYSTERESIS 5 degrees
DELAY AC 00 min
INLET THERMOSTAT 00 OFF
FUNC. THERMOSTAT 00 OFF
LOADING 00 OFF
01 - 06
10 - 800 hours
00 min - 30 min
2K - 20K
00 - 01
30°C - 120°C
00 - 06
00 - 04
00 - 05
01 - 03
01 - 01 - 02
00, 01 (OFF - ON)
** see notes
00 - 01 (OFF / ON)
00 , 01, 02, 03
00K - 50K
5K - 30K
00 min - 30 min
00, 01 (OFF / ON)
00, 01 (OFF / ON)
00, 01 (OFF / ON)
200 hours
00 min
2K
00
95
05
04
00
00
00
00 OFF
Default Personal valuesValue rangeDesignation
BACK
HEATING CIRCUIT 1
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN ----
MIXER CLOSED ----
44
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
Instructions for the installer
Default Personal valuesValue rangeDesignation
MAX TEMPERATURE DISCHARGE 80 °C
MINIMUM DELIVERY TEMPERATURE 30 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
BACK
HEATING CIRCUIT 2
CIRCUIT OPERATION 0
PUMP OPERATION 0
MIXER OPEN 18
MIXER CLOSED 12
MAX TEMPERATURE DISCHARGE 45 °C
MINIMUM DELIVERY TEMPERATURE 10 °C
ANTIFREEZE 0 °C
RIT-TEMP-EST 0.00
DIST-CUR-RIS 5 °C
OBLIDGE REDUCTION 01
BACK
Exit level using
Default Personal valuesValue rangeDesignation
00 - 04
00 - 03
5 - 25
5 - 25
20 °C - 110 °C
10 °C - 110 °C
(-15)°C - (5)°C
0:00 - 24:00
00K - 50K
00 - 01 (OFF / ON)
Exit level using
SOLAR M/F
Default Personal valuesValue rangeDesignation
FUNCTION MF (1-4) 00,00,01,02
MF (1-4) T- NOM 30°C
HISTERESIS (1-4) MF 5°C
FUNCTION F 15 0
BACK
Exit level using
00 - 26
00 - 03
5 - 25
5 - 25
45
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR
type Lago Basic 0201 RV 1 ON BOILER N°1
1
2
3
fig. 18
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2)
2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2)
3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 1 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN.
46
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
31
42
11
41
12
13
32
3.25 - PANEL INSTRUMENTS MODULATING
CASCADE BISTADIO cod. 37901
With the switch 11 , place under tension the framework and equipment connected to it. The switches 12 and 13 , control the burner and the pump P1 in the case of boiler cascade
The temperature controller adjusts the temperature Boiler No. 2: To achieve this, the thermostat will be located in scale up pos. 32 . The possible modulation of the burner will be managed by the thermoregulatory On the boiler power line control panel must be provided with a switch fuses protection
Instructions for the installer
11 switch with indicator light 12 Power Burner
32 thermostat operation
41 main fuse 13 Power plant pump P1 (waterfall) 31 Safety thermostat
To use the instrument panel, see instruction manual for the plant manager As for the practical schemes of connection and operation, see documentation provided in the instrument panel code. 37901.
The boiler sensor included in the supply.
fig. 24
47
Instructions for the installer
°C
OK
1
2
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
PROGRAMMABLE PARAMETERS FOR TECHNICIANS OF THERMOREGULATOR
type Lago Basic 0201 RV 1 ON BOILER N°2
1
2
3
fig. 26
1 1) Set the switch on the burner (1)
2) Press the OK key (2)
3) Turn the knob (3) until it appears on the display mm (modulating burner)
4) Press the OK key (2) 2 1) Move the selector (1) the symbol of the mixing valve
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 15 (the time of the servo-burner)
4) Press the OK key (2) 3 1) Move the selector (1) on the BUS ID
2) Press the OK key (2)
3) Turn the knob (3) until the display shows the number 2 (identification of the boiler)
4) Press the OK key (2). Turn the knob to position 1. RUN
48
Instructions for the installer
P1
°C
OK
12
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
31
42
11 41
12
13
32
Ps
PRODUTTORE ACQUA
CALDA SANITARIA
Pb
Pz1
P1
IR/BT
Pz2
Vmix2
IR/AT
SPF
VF
14 15 16 17
35
33 34
18 19 20 21 22 23
21.020
Servizio
Data/Ora/Vacanze
Visual Inf.
Utente
Progr.Tempo
Tecnico
Impianto
Acqua Calda
Circuito risc. I
Solare/MF
Circuito risc. II
°C
OK
12
1
2
>1s
+
°C
°C
°C
BUS ID 1/2/11/Mod
Run
2
1
EVENTUALE SEPARATORE IDRAULICO
PER IL PERFETTO BILANCIAMENTO
DELL’IMPIANTO
KF
KF1
VE
CALDAIA INOXIA GJ 1
KF1
VE
CALDAIA INOXIA GJ 2
fig. 27
P1= circulator pump
Pb = charge pump hot water producer
SPF = tank sensor
KF = boiler temperature control probe E8.5064
KF = 1 boiler temperature control probe Lake Basic 0201 RV 1
VF = outlet probe
AF = external probe
3.27 - WATER AND ELECTRICAL CONNECTION WITH CASCADE BOILER PANEL INSTRUMENTS cod. 37892
The fig. 27 shows the typical pattern of connection of the boiler to the heating system, it consists of two boilers with cascade function at the service of an area high
temperature and a low temperature zone controlled by motorized mixing valve + production of hot water.
The boiler No. 1 is equipped with an instrument panel code. 37892, boiler No. 2 is equipped with an instrument panel code. 37900
Keys:
Vmix2 = mixing valve area (motorized)
PZ1 = pump heating zone HIGH TEMPERATURE
Pz2 pump heating zone = LOW
EV = vessel expansion
IR / AT = distribution of the heating HIGH TEMPERATURE
IR / BT = distribution of the heating LOW
Ps = hot water recirculation pump
49
Instructions for the installer
The instruments panels of the boilers INOXIA GJ (cascade) manage automatically the turn off the burner when the temperature in the boiler reaches the value set on the controller.
It also runs the pump for the load of a for the heater production of A.C.S.
The management of heating, it comes automatically on the basis of data collected by the sensors external boiler environment and delivery
The high temperature zone pump system will be in a position of working through the control switch pos.20 of the Master table, and will turn off only when reaches the temperature by the thermo regulator.
The pump system lower temperature zone, is put on operating status through the control switch pos. 21 of the Master table, and will turn off only when reaches the temperature delivery through the thermo regulator.
The charge pump of the boiler for the production of acs, will be put into operation automatically, and will be switched off when will reach the temperature of delivery through the controller.
With this plant configuration, the controller is able to control:
- Plant of a direct area, the controller controls the pump plant. The temperature will be controlled by programming curves set in the thermo regulator.
- Plant of an area with motorized mixing valve: install the flow sensor (downstream of the valve mixing), the controller controls the pump system and mixing valve. The temperature will be adjusted through curves programming set in the thermo regulator;
- Production of a.c.s. through boiler;
- Anti-Legionella function with increased water temperature storage in the boiler (function not enabled factory, but which can be activated by the customer)
The panel is designed for the management of burners in operation modulator.
For practical connections, electrical, and probes, refer to the diagram supplied with the panel instruments cod. 38778 and 37901
50
Instructions for the installer
3.28 - INITIAL LIGHTING
PRELIMIARY CHECKS
The first ignition must be carried out by a qualified technician. Failure to do so could cause injury to persons, animals or damage to property. UNICAL shall not be held liable for any injury and/or damage.
Before lighting the boiler check that:
- the boiler installation has been carried out in accordance with the specific Standards UNI 7129 and 7131 for the gas part and the Standards CEI 64-8 and 64-9for the electrical part;
- the combustion air inlet and the discharge of the products of combustion occur in the correct way in accordance to the specific Standards in force (UNI 7129/7131);
- the gas supply system is correctly dimensioned for the boiler’s output
- the boiler’s electrical supply is 230 V - 50 Hz;
- the system has been filled with water (pressure registered on the gauge 1 bar with pump not running);
- any of the system’s on-off valves are open;
- the mains supply gas corresponds to the one which the boiler has been calibrated for: otherwise convert the boiler to use the available gas (refer to section: “GAS CONVERSION”); this operation must be carried out by a qualified technician in compliance to the regulations in force;
- the gas supply cock is open;
- there are no gas leaks;
- the external mains supply switch is on;
- the boiler system’s safety valve is not blocked and that it is connected to the sewage system;
- there are no water leaks;
- all the necessary ventilation conditions and minimum clearance distances are guaranteed for subsequent servicing in case the boiler is sited in a cupboard compartment.
Lighting and shutting down procedures
For lighting and shutting down the boiler refer to the “USER’S
INSTRUCTIONS GUIDE”.
Information to be passed on to the user
The user must be instructed on the use and operation of
his boiler and in particular detail:
- Hand over to the end user the booklet: “USER’S
INSTRUCTIONS GUIDE”, as well as all the other literature
relative to the appliance and placed in the envelope contained
in the packaging. The user must retain this literature for any
future reference.
- Inform the user of the importance of the air vents and of
the flue outlet system, stressing the fact that absolutely no
alteration can be made.
- Inform the user regarding the control of the system’s water
pressure and how to restore it to the correct value.
- Explain and demonstrate to the user the correct function and
adjustment of the temperature, thermostats and radiators for
the economic use of the system.
- Remind the user that in order to comply to the regulations in
force the boiler has to be inspected and serviced regularly as
indicated by the manufacturer.
- If the appliance is sold or transferred to another owner or if
the present user moves home and leaves the appliance
installed, ensure yourself that the manual always follows the
appliance so that it can be consulted by the new owner
and/or installer.
The Inoxia GJ are boiler with forced circulation: is
necessary to ensure the water circulation when the
burner is in operation
Ensure that the burner is moving without the pump in the
system has been activated, otherwise the safety thermostat
could intervene.
The temperature in the valve will be regulated by mixing
controlled by thermoregulation.
During the On and the off of the burner some sound can be
heard due of settling structure.
This should not worry because the expansion have been
foreseen at the design stage.
51
Instructions for the installer
3.29 - BURNER ADJUSTMENT
WARNING! All the instructions indicated below are for the exclusive use of qualified UNICAL service technicians or installers.
The calibration and the preparations of the burner to carried out, are in the owners manual for the burner itself. The gas burners are equipped with a gas valve which can determine the capacity: At the first start you should always
INSPECTION AND
4
SERVICING SCHEDULE
To ensure the continued safe and efficient operation of the boiler it is highly recommended that it is checked at regular intervals and serviced when necessary, and that only original spare parts are used.
Regular attention will prolong the life of the boiler.
If the boiler is not checked and serviced re­gularly it could cause material and personal damages.
For this reason UNICAL recommends that a servicing contract should be made with our authorized After Sales Service Assistance Centre.
monitoring the effective thermal capacity, through the counter on the main line, making sure it is not less than the minimum value of the boiler plate. With a proper adjustment of the burner should obtain values on average obtain, measured at the chimney with a special analyzer, corresponding to the table on page. 9.
INSTRUCTIONS FOR INSPECTION AND SERVICING
To ensure a long life to all your boiler components and in order not to alter the conditions of the approved product, only original UNICAL spare parts must be used.
Before servicing always carry out the following steps:
- Disconnect the mains electricity supply.
- Separate the appliance from the electrical supply by means of a separating device with an opening contact of at least 3 mm (for example safety devices or power switches) and ensure yourself that it cannot be accidentally reinserted.
- Close the on-off valve fitted upstream of the boiler.
- Close any on-off valves fitted on the CH flow and return pipes.
The boiler must have regular maintenance and cleaning in order to ensure reliable and efficient operation. Regular attention will prolong the life of the boiler.
The frequency of servicing will be determined by the service engineer and will depend on the appliance’s state of condition.
These adjustments can be performed only by Service Centres authorized by UNICAL.
52
After having carried out all the necessary maintenance work always follow these steps:
- Open the CH flow and return valves
-If necessary, proceed with restoring the heating system’s pressure until an equal value of the static pressure on the highest point of the plant is reached
- Open the on-off gas cock.
- Reconnect the appliance to the electrical supply and switch on the mains electrical supply.
- Test for gas soundness, on the gas side and on the water side.
- Vent the heating system and if necessary restore pressure.
If decide to temporarily deactivate the boiler is necessary to:
a) carry out the interception of powers: electricity, water and fuel; b) drain the water system, unless is provided the use of antifreeze.
Ispezioni e manutenzione
ROUTINE SERVICE
Warning! Before doing any work on the boiler, make sure that it and its components have cooled
Disconnect the boiler from the mains supply and turn the gas supply at the appliance.
Warning! Before cleaning the boiler, to protect the control panel against splashing water.
Once a year, at the end of each heating season, it is necessary make a general cleaning of the boiler. Before carrying out any maintenance work, check that all the precautions referred to in the previous paragraph have been taken. To do the maintenance, is necessary to:
- Remove tension using the main switch;
- Remove the burner, that in this case could be revised;
- Open the firebox door so is possible to accede to the room combustion;
- Remove the access door to the smoking room;
- Check the integrity of internal components.
Checking seals and insulating fibers
The fiber insulation of the door, after a short period of operation, may submit cracks; this, however, does not reduce the insulating and does not affect the duration. Check the status of the seal which must not show signs of deterioration; otherwise need to be replaced, using Only original spare parts.
Check the status of the inspection cover gasket smoke
chamber.
In case of deterioration should be replaced, using Only
original spare parts
Burner Maintenance
The burner maintenance of the must be carried out by
central assistance authorized by Unical (punishment void the
warranty).
Check electrode ignition
The maintenance of the burner must be carried out by Central
assistance authorized by Unical (punishment void the
warranty).
Components to be checked during the annual review
Component:
Safety Thermostat
Expansion vessel
Door seal
Smoke chamber seal
Checking:
Does the thermostat make the boiler safe in case of overheating?
Does the vessel contain the right amount of air?
Is there smoke from the door seal?
Is there smoke from the chamber seal?
Intervention/ control method:
Bring the temperature of the boiler with the pump stopped
Check the pressure of nitrogen.Replace the boiler pressure(open the venting pump). Open the closing taps of the heating circuit.
Further tighten the screws of the door. Replace the gasket seal and the seal inside the door.
Tighten the nuts further closing of the smoke chamber.Replace the seals
53
AG S.P.A.
46033 casteldario - mantova - italia - tel. 0376/57001 (r.a.) - fax 0376/660556
www.unical.eu - info@unical-ag.com
The Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to bring those changes that it will hold necessary to it own products or profits, without jeopardizing its essential characteristics.
Loading...