Unical GHISS 48R AP, GHISS 24R AP PV, GHISS 32R AP PV, GHISS 40R AP, GHISS 56 R AP User Manual

...
1. VERSION GB
GHISS 16, 24, 32, 40, 48, 56 R AP
GHISS 16, 24, 32, 40, 48, 56 R AE
GHISS 16, 24, 32, R AP PV
GHISS 16, 24, 32, R AE PV
GHISS 16, 24, 32, 40, B AP
GHISS 16, 24, 32, 40, B AE
GHISS 16, 24, 32, B AP PV
GHISS 16, 24, 32, B AE PV
®
STANDARD GAS DEVICE WITH CAST-IRON SEGMENTED HEAT­EXCHANGER, WITH DIRECT SPARK IGNITION (AE), AND PIEZO IGNITION (AP)
2 GENERAL 1. VERSION GB
SUITABILITY
GHISS R ..., and GHISS B... boilers have been certified according to the following European standards:
o 90/396/CEE gas directive o 92/42/CEE degree of efficiency directive o 89/336/CEE electromagnetic suitability directive o 73/23/CEE low voltage directive
DEVICES
Type Ignition Heating
pump
Start-up
container GHISS ... R AP piezo - ­GHISS ... R AE ionisation - ­GHISS ... R AP PV piezo in place ­GHISS ... R AE PV ionisation in place ­GHISS ... B AP piezo - in place GHISS ... B AE ionisation - in place GHISS ... B AP PV piezo in place in place GHISS ... B AE PV ionisation in place in place
Dear Customer,
Thank you for purchasing the gas boiler of Unical. Thus you have become the owner of a high technical quality device operating economically and safely. Congratulations!
Please check the completeness and intactness of the product!
Do not remove and do not damage the labels found on the device!
This document is the operating and maintenance instructions. The guarantee slip found in the attachment must be stamped upon purchase and commissioning and must be filled in legibly!
Please, in your own interest, read the information we presented on the following pages carefully, and keep it because you will need it later too.
If you take our advice, our product will serve you reliably for long years to come.
TABLE OF CONTENTS
GENERAL
Suitability .......................................................................2
Devices ..........................................................................2
Important details to know................................................3
Basic safety rules ...........................................................3
General introduction .......................................................4
Identification...................................................................4
Construction...................................................................4
Technical data................................................................6
Hydraulic operation ........................................................8
Pump .............................................................................9
Electric connection diagrams ........................................10
Operating surface.........................................................12
THE OPERATION OF THE DEVICE
Switching on.................................................................13
Setting the boiler thermostat .........................................17
Temporary shut-down...................................................17
Shutting down for a longer period of time......................17
Cleaning.......................................................................17
Maintenance ................................................................17
THE INSTALLATION OF THE DEVICE
The documentation of the device ..................................18
Sizes and weight ..........................................................18
The boiler room ............................................................20
The connection of the boiler to the existing old heating
system .........................................................................20
Hydraulic connection .................................................... 20
Electric connections .....................................................22
Gas connection ............................................................23
Conducting combustion products.................................. 23
Filling up and draining the system.................................24
SEVICE INSTRUCTIONS
Preparations for start-up ...............................................25
First start-up.................................................................25
Checking during operation............................................27
Shutting down for a longer period of time......................28
Maintenance ................................................................28
Calibration....................................................................29
Switching over to another gas type ...............................30
Cleaning the boiler .......................................................31
The operating instructions contain the following symbols:
Warning = this operation requires greater attention! Prohibition = this operation must not be carried out!
3 GENERAL 1. VERSION GB
IMPORTANT DETAILS TO KNOW
After you have unwrapped the device, check the
intact and complete status of the product.
Upon planning and execution, the requirements of the
valid gas service provider, the construction, environmental and related electric standards as well as the other related standards must be taken into account and followed to the fullest.
The producer cannot take responsibility for
unprofessional operation and other external mechanical damage that does not originate from unprofessional operation.
In the event of an error, if you cannot eliminate the
error on the basis of the instructions of the operating manual, call the designated brand service.
Check the pressure of the heating system at regular
intervals to prevent its decrease below 1 bar.
If the device switches off interlocking on several
occasions, repeatedly, call the brand service; until then the following is to be executed:
o Turn off the main switch of the device o (cutting off electricity). o Close the connecting gas and water
connection.
o In the case of frost danger, drain the
heating and cold-and-hot-water circles (draining).
In the interest of the safe and economical operation
of the device, it is practical to have the inspection recommended by the manufacturer and the necessary maintenance work executed by the designated brand service at least once a year.
The present operating instructions contains all the
important information in connection with the use of the device for the user, therefore, it is practical to keep it close to the boiler. If the device is sold or relocated, it should always be accompanied by the operating instructions so that the new owner and/or repairman could get sufficient information.
BASIC RULES OF SAFETY
The user is to pay attention to the fact that this device uses gas, electric energy and water during its operation, which poses some basic rules of safety:
The boiler must not be used by children or individuals
not trained for its operation.
Do not use electric devices, machines, equipment, and do not switch on the lights if you can smell gas. In this case, close the gas tap, air the room and call the brand service.
Do not touch the boiler with wet hands if you are in your bare feet.
Do not clean the boiler while it is turned on and is going.
Safety and other parts can be replaced in the device only by the authorised brand service, only with original parts identical with that of the manufacturer.
Do not pull or twist the connecting cable of the boiler as long as it is live.
The operation of the device requires air supply, therefore, do not cover or close off or narrow down the ventilation openings or windows that provide the replacement of the air required for burning.
For the fear of frost danger, do not install the boiler in an open room.
Do not store packaging materials in the vicinity of the boiler (cardboard paper, plastic or wood), or inflammable or explosive materials.
4 GENERAL 1. VERSION GB
GENERAL INTRODUCTION
GHISS R is the basic type atmospheric furnace-chamber
hot water boiler with cast iron, segmented heat­exchanger. It is suitable for the execution of the pump- system central heating system of residential and public buildings and, together with the indirectly heated hot water containers installed next to them, the execution of the provision of hot water for use. The “PV” types of the boiler have built-in circulation pumps, closed expansion tank, and safety blow-off valves. GHISS B device is an atmospheric furnace-chamber hot water gas boiler with a cast-iron, segmented heat­exchanger, built together with a combined-execution, 100-litre, indirectly heated hot water container. It is suitable for the execution of the pump-system central heating system of residential and public buildings and the execution of the provision of hot water for use. This boiler, in the building and hot water container heating functions operates with two separate heating pumps, working in alternate phases. Its execution, upon demand, can be: PV built together with circulation pump on building-heating side, automatic de-airing valve, closed expansion tank, and safety blow­off valve, or the version without those, made for already existing heating systems. Its hot water container has an absolutely hygienic water­space provided with double enamel coating and high­output magnesium anode protection. For protection against over-pressure originating from the expansion of hot water for use, a safety valve is installed holding back 6 bars. For the circulation of hot water for use, the device is equipped with a separate circulation pipe connection. Both families of devices can be operated with piped natural gas (“H” or “S”) and tanked PROPANE-BUTANE gas (II2H,S3B/P). Type of combustion product conduction: B11BS
IDENTIFICATION
The data sheet serving the identification of the boiler can be found on the inside wall of the left side housing, after the removal of the door of the device.
No not remove the data plate and do not damage it!
This data plate contains the main parameters of the device and the individual identification features (type, serial number, date of production, etc.).
CONSTRUCTION
The construction and main parts of GHISS R AP and GHISS R AE type devices are the following:
The construction and main parts of GHISS R AP PV and GHISS R AE PV type devices are the following:
5 GENERAL 1. VERSION GB
Part list:
1. Boiler housing
2. Deflector
3. Return pipe
4. Circulation pump
5. Burner tray
6. Pressure switch
7. Safety valve
8. Electric control cabinet
9. Automatic de-aerator
10. Cast heat-exchanger
11. Forward pipe
12. Gas pipe
13. Gas valve
14. Ignition controller – only on AE type
15. Ignition electrode
16. Nozzle holding collector
17. Pressure meter
18. Draining tap
19. Expansion tank
20. Filling tap
21. 100-l tank
22. Hot water for use draining tap
The construction and main parts of GHISS B AP and GHISS B AE type devices are the following:
The construction and main parts of GHISS B AP PV és GHISS B AE PV type devices are the following:
6 GENERAL 1. VERSION GB
TECHNICAL DATA
UNICAL GHISS R
Unit of
measur
ement
16 AP, -AE
16 AP,-AE,-PV
24 AP, -AE
24 AP,-AE,-PV
32 AP, -AE
32 AP,-AE,-PV
40 AP, -AE 48 AP, -AE 56 AP, -AE
Technical data
Nominal heat load kW 16 24 32 40.5 48.9 57.4 Nominal heat output kW 14 22 29.3 36.8 44.4 52 Nominal degree of efficiency (water-side)
% 90.5 91 90.9 90.8 90.7 90.6
Distinction of degree of efficiency
**
Min. –max. operating water temperature
°C 45/85
Water cubic capacity of the boiler dm3 5.5 7 8.6 10.2 11.8 13.4
Number of burners / main nozzles
(v)
Db 2 3 4 5 6 7
Number of cast segments (v+1) Db 3 4 5 6 7 8
Heatable cubic capacity lgm
3
300-350 350-450 450-550 600-700 700-800 800-900 Maximum operating overpressure bar 3 (2nd pressure class) Boiler body test overpressure bar 6 Pressure loss (80/60 °C) mbar 0.6 0.5 0.4 0.3 0.2 0.1 Expansion tank cubic capacity (NB)
l 10 10 10 - - -
Expansion tank pre-tensioning pressure
bar 1 1 1 - - -
Connecting sizes
Forward and return heating water coll 1
Gas connection coll
¾
Gas-technical data Classification according to gas used: II
2H,S3B/P
Piped natural gas Connecting gas pressure mbar 25 Burner nozzle pressure “H” mbar 12.8 12.5 11.6 12 11.5 11.5 Burner nozzle pressure “S” mbar 14.5 13.5 12.5 13 12.5 13 Burner nozzle diameter “H” Ø/mm 2.35 2.35 2.35 2.35 2.45 2.45 Burner nozzle diameter “S” Ø/mm 2.6 2.6 2.6 2.6 2.6 2.7
Amount of fuel “H” M3/h 1.6 2.5 3.4 4.3 5.2 6.1
Amount of fuel “S” M3/h 2.0 2.9 3.9 5.0 6.0 7.1 Tanked PB-gas Connecting gas pressure mbar 28-30
Burner nozzle pressure mbar 25.9 25.9 22.0 24.1 24.5 24.0
Burner nozzle diameter Ø/mm 1.45 1.45 1.6 1.6 1.6 1.6 Amount of fuel m3/h 1.1 1.8 2.5 3.1 3.7 4.4
Combustion product data Classification according to the conduct of combustion products: B
11BS
Combustion product conduct Ø 130 130 130 150 180 180 Combustion product temperature °C 100 110 120 130 140 150
Chimney draft demand mbar 0.1 Combustion product mass flow m3/h 38.1 55.8 72.3 87.9 102.7 115 NOx –class
2. (NO
x
– concentration < 200 mg /kWh)
Electric data
Electric connection V/Hz 230/50 Electric output W 14-107 14-107 14-107 14 14 14 Electric protection IP 20 Shock-protection class I. Pilot light protection Ionisation Ignition Hz / kV 16/16 electric spark
Noise level
dB max.50
Quality certification
CE CE 1009
Enveloping sizes
Height mm 860 Width mm 410 485 560 635 710 785 Depth mm 610 Boiler volume (without water) kg 92 106 120 134 145 160
7 GENERAL 1. VERSION GB
UNICAL GHISS B
Unit of
measure
ment
16 AP, -AE
16 AP,-AE,-PV
24 AP, -AE
24 AP,-AE,-PV
32 AP, -AE
32 AP,-AE,-PV
40 AP, -AE
Technical data
Nominal heat load kW 16 24 32 40.5
Nominal heat output kW 14 22 29.3 36.8
Nominal degree of efficiency (water-
side)
% 90.5 91 90.9 90.8
Distinction of degree of efficiency
**
Min. –max. operating water temperature °C 45/85
Water cubic capacity of the boiler dm3 5.5 7 8.6 10.2
Number of burners / main nozzles (v) db 2 3 4 5
Number of cast segments (v+1) db 3 4 5 6
Heatable cubic capacity lgm3 300-350 350-450 450-550 600-700
Maximum operating overpressure bar 3 (2nd pressure class)
Boiler body test overpressure bar 6
Pressure loss (80/60 °C) mbar 0.6 0.5 0.4 0.3
Expansion tank cubic capacity (NB) l 10 10 10
Expansion tank pre-tensioning pressure bar 1 1 1
Connecting sizes
Forward and return heating water coll 1
Gas connection coll ¾
Cold-hot water connection coll ½
Data of hot water for use
Nominal heat output kW 27 27 27 27
Container cubic capacity l 100 100 100 100
Maximum operating water temperature °C 60 60 60 60
Permanent water-transport at 45°C
(t=30°C)
l 7.5 11 11 12
Container max. operating water
pressure
bar 6 6 6 6
Container test overpressure bar 10 10 10 10
Gas-technical data Classification according to gas used: II2H,S3B/P
Piped natural gas
Connecting gas pressure mbar 25
Burner nozzle pressure “H” mbar 12.8 12.5 11.6 12
Burner nozzle pressure “S” mbar 14.5 13.5 12.5 13
Burner nozzle diameter “H” Ø/mm 2.35 2.35 2.35 2.35
Burner nozzle diameter “S” Ø/mm 2.6 2.6 2.6 2.6
Amount of fuel “H” m3/h 1.6 2.5 3.4 4.3
Amount of fuel “S” m3/h 2.0 2.9 3.9 5.0
Tanked PB-gas Connecting gas pressure mbar 28-30
Burner nozzle pressure mbar 25.9 25.9 22.0 24.1
Burner nozzle diameter Ø/mm 1.45 1.45 1.6 1.6
Amount of fuel m3/h 1.1 1.8 2.5 3.1
Combustion product data Classification according to the conduct of combustion products: B11BS
Combustion product conduct Ø 130 130 130 150
Combustion product temperature °C 100 110 120 130
Chimney draft demand mbar 0.1
Combustion product mass flow m3/h 38.1 55.8 72.3 87.9
NOx –class 2. (NOx – concentration < 200 mg /kWh)
Electric data
Electric connection V/Hz 230/50
Electric output W 107 / 200 107 / 200 107 / 200 107
Electric protection IP 20
Shock-protection class I.
Pilot light protection Ionisation
Ignition Hz/ kV 16/16 electric spark
Noise level
dB max.50
Quality certification
CE CE 1009
Enveloping sizes
Height mm 1473
Width mm 635 635 635 635
Depth mm 635 Boiler volume (without water) kg 147 160 173 190
8 GENERAL 1. VERSION GB
HYDRAULIC OPERATION
The hydraulic switching of GHISS R AP and GHISS R AE type devices
The hydraulic switching of GHISS R AP PV and GHISS R AE PV type devices
Legends:
1. Forward
2. Return
3. Gas
4. Network water
5. Draining
6. Filling up
7. Hot water for use
8. Circulation
9. Hot water for use drainage
10. Boiler thermostat
11. Restricting thermostat
12. Thermometer
The hydraulic switching of GHISS B AP and GHISS B AE type devices
The hydraulic switching of GHISS B AP PV and GHISS B AE PV type devices
9 GENERAL 1. VERSION GB
PUMP
The character curve of the heating circulation pump built
into the GHISS .. . .. PV type devices can be seen in the
following illustration. The pump has III levels; it is always practical to use the lower level that still provides for the heating system; this way you can save electric energy.
The pressure-loss of PV-type boilers:
Upon the first start-up of the boiler and after a longer
shut-down, it is practical to check the turnability of the axle of the pump with the help of a screwdriver.
It is forbidden to operate the pump without water!
The hydraulic loss of the boilers
With the exception of the GHISS .. . .. PV type devices,
there is no heating circulation pump in the device. This is to be provided for in the heating system. For sizing, use the following graph.
10 GENERAL 1. VERSION GB
ELECTRIC CONNECTION DIAGRAMS
GHISS .... AP
Legends:
T-NY.K. Winter-summer switch G.SZ. Gas valve F.K. Indicator lamp switch HMV SZ Pump of hot water for use K.SZ.T. Boiler regulating thermostat R Relay B.T. Limiting safety thermostat B.SZ.T Boiler regulating thermostat F.B.T. Smoke gas safety thermostat F.T. Fixed thermostat SZ.T. Room thermostat N Neutral conductor F.SZ. Heating circulation pump L Phase conductor L.J. Indicator lamp (flame indicator) PE Protective grounding 1L. Gas magnetic valve switched phase K.H.J Error indication of restrictors BVE. Boiler control unit
Supplementary unit necessary for the connection of the indirect container
In case of connection, the wire indicated with * is to be removed!
The units are contained by the PV types!