Unical EVE 05 RTN 24, EVE 05 CTN 24 F, EVE 05 CTFS 24 F, EVE 05 CTN 24, EVE 05 CTFS 24 Installation, Use And Maintenance Manual

...
EVE
05
RTN 24 - RTFS 24 CTN 24 F - CTFS 24 F CTN 24 - CTFS 24
00332243 - 3rd edition - 10/2010
INSTALLATION USE
AND MAINTENANCE
English
2
General info
IMPORTANT
This INSTRUCTION MANUAL, which is an integral and indispensable part of the product, must be handed over to the user by the plumbers and must be kept in a safe place for future reference. The manual must be handed over with the boiler should it be sold or transferred.
This boiler must be used for the purposes for which it has been designed. Any other use shall be considered incorrect and therefore dangerous.
The boiler must be installed in compliance with applicable laws and standards and according to the manufacturer’s instructions given in this manual. Incorrect installation may cause injury to persons and/or animals and damage to property. The manufacturer shall not be held liable for any such injury and/or damage.
Damage and/or injury caused by incorrect installation or use and/or damage and/or injury due to non-observance of the manufacturer’s instructions shall relieve UNICAL from any and all contractual and extracontractual liability.
Before installing the boiler, check that the technical data correspond to requirements for its correct use in the system.
Check that the boiler is intact and that it has not been damaged during transport and handling. Do not install equipment which is patently damaged and/or faulty.
Do not obstruct the air suction and/or heat dissipation grates.
Only original accessories must be used for all boilers supplied with optionals or kits (including electrical ones).
Dispose of the packaging with care as all the materials can be recycled. The packaging must therefore be sent to specific waste management sites.
Keep the packaging out of the reach of children as it may represent a choking and suffocation hazard.
In the event of failure and/or faulty functioning, switch off the boiler. Do not attempt to make repairs: contact qualified technicians.
Original parts must be used for all repairs to the boiler.
Non-observance of the above requirement may jeopardize the safety of the boilers and expose people, animals and property to danger.
To guarantee efficiency and correct functioning of the equipment it is legally binding to service the boilers once a year according to the schedule indicated in the relative section of this manual.
In the event of long periods of inactivity of the boiler, disconnect it from the power mains and close the gas tap (Warning! In this case the boiler’s electronic anti-freeze function will not be operative).
Should there be a risk of freezing, add anti-freeze: it is not advisable to empty the system as this may result in damage; use specific anti-freeze products suitable for multi-metal heating systems.
N.B. IF YOU SMELL GAS:
- do not turn on or off electrical switches and do not turn on electrical appliances;
- do not ignite flames and do not smoke;
- close the main gas tap;
- open doors and windows;
- contact a Service Centre, qualified installer or the gas supply company.
Never use flames to detect gas leaks.
WARNING
This boiler has been built for installation in the country indicated on the technical data plate: installation in any other country may be a source of danger for people, animals and property.
Read the warranty conditions and clauses on the warranty certificate attached to the boiler with care.
‘’WATER TREA TMENT IN C.H. SYSTEM FOR CIVIL USE’ ’
NOTE FOR INSTALLER AND USER
1) The frequency of the cleaning of the D.H.W. heat exchanger is related to the hardness of the feeding water .
2) With a water hardness higher than 14°f the use of antiscaling devices, whose choice will be made on the base of water characteristics, is suggested.
3) To increase the resistance to the scaling, a D.H.W. temperature adjustment very close to that one of the actual use, is suggested.
4) The adoption of a modulating room thermostat reduces the scaling danger.
5) We advise you to verify the state of cleaness of the D.H.W. heat exchanger at the end of the first year and subsequently every two years.
3
Users easy guide
REMEMBER:
Periodically check the water pressure into the boiler .
Ascertain to be able to turn OFF the appliance in case of emergency (power, gas and water
supply).
Make sure to be familiar with the switching ON and OFF and with the temperature adjusting
knobs.
The user is not allowed to remove the casing and get access to the internal parts of the boiler .
Don’t hang dresses, …..etc. to the boiler.
Don’t forget to plan the annual maintenance
INFORMA TION FOR YOUR SAFETY
GAS LEAK
Don’t switch on the appliance if there is a suspicion of gas leak. Contact IMMEDIA TELY the technical personnel.
DON’T SEEK GAS LEAKS WITH NAKED FLAMES!!
LACK OF W A TER
If the pressure decreases repeatedly below the minimum operational pressure it means that there is a lack of water in the heating circuit. Contact the technical personnel for an inspection to the system.
°C
T o put again the boiler in operation, it will be neces­sary to press the button.
In case the boiler goes frequently into lockout po­sition, contact the service technician.
Reset push button
Display
LOCKOUT
The function of this symbol is to indicate that the burner is in lockout position, due to a lack of gas (check if the gas cock is open) or to a non detected ignition.
GAS VALVE LABEL
003319 80
4
Users easy guide
Reset
push button
Central heating
temperature adjusting
knob
Domestic Hot Water
temperature adjusting
knob
Manometer
CONTROLS
HOW TO START THE BOILER
- Swicth ON the boiler through the external switch.
- Check if a room thermostat or a chronothermostat is fitted and set it on heat request.
MAX
M
I
N
MAXMIN
Set the Central Heating tempera­ture knob into the range shown in the figure
Set the Domestic Hot Water tempera­ture knob into the range shown in the figure
By adjusting the Domestic Hot Water temperature to the real required tem­perature, you will avoid to mix hot wa­ter with cold water, in this way reduc­ing both the boiler operation costs and the scaling formation.
Winter operation
(Central Heating + Domestic Hot Water) for C models (Central Heating only) for R models
Summer operation (Domestic Hot Water only) for models C
MAX
M
I
N
Set the Central Heating tempera­ture knob to the symbol
MAXMIN
Set the Domestic Hot Water tempera­ture knob into the range shown in the figure
°C
°C
The display indicates that the boiler is in Central Heating mode and the flow temperature is 63°C.
The display indicates that the boiler is in Domestic Hot Water mode and the water temperature is 38°C.
HOW TO ADJUST THE BOILER
MAX
M
I
N
MAXMIN
°C
®
MAX
MAXMIN
M
I
N
EVE
05
Display
5
Users easy guide
HOW TO SET THE WATER PRESSURE INTO THE SYSTEM
The water pressure into the system has to be checked periodically , in order to be sure of the boiler correct operation. The manometer arrow has to be above 0.8/1 bar when the boiler is switched off or in stand-by position. The boiler lock-out due to lack of water is displayed with the failure code (low Pressure). In order to see this code, once the boiler is in lock-out and the symbol appears, push the reset push-button. In order to increase the water pressure into the system, open the filling valve (black) under the boiler; when the pressure indicated on the manometer is between 0.8 and 1 bar, close the filling valve.
CLEANING
For the simple cleaning use a dry cloth. To remove hard blots, clean with a wet cloth and wipe with a dry cloth. DO NOT USE abrasive products.
ANTIFROST PROTECTION
The boiler is equipped with an antifrost system that operates au­tomatically when the boiler water temperature decreases under 6°C: the burner and the pump are automatically put into operation until the Central Heating system water temperature reaches 16°C.This protection is active only if the boiler is electrically
feeded.
B
C
MAX
M
I
N
MAXMIN
HOW TO SWITCH-OFF THE BOILER For short periods: Rotate the knob “B” in position
For long periods: Cut off the electrical and gas supply.
°C
Position during water pressure setting
Standard posi­tion during operation
Set the Central Heating and Domestic Hot Water temperature knobs to the symbol shown in the figure. For R version boilers only knob B is there.
6
General info
DATA PLATE
LEGEND:
1 = CE Surveillance notify body 2=
Boiler type
3=Boiler model 4=Number of stars (Directive 92/42/CEE) 5=(S.N°) Serial number 6=P.I.N. code 7=Approved fluing configurations 8=(N0x) N0x class
A = Central Heating circuit features
9=
(Pn) Nominal output
10 = (Pcond) Condensing nominal output 11 = (Qmax) Nominal heat input
12 = (Adjusted Qn) Adjusted for nominal Heat input 13 =
(PMS) Max. pressure C.H. system
14 = (T max) Max. C.H. temperature
B = Domestic Hot Water circuit features
15 = (Qnw) Nominal heat input in D.H.W. mode (if different from Qn) 16 = (D) Specific D.H.W. flow rate according to EN 625 - EN 13203-1
17 = (R factor) N° taps based on the quantity of water declared EN
13203-1
18 = (F factor) N°stars based on the quality of water declared
EN 13203-1 19 = (PMW) Max. pressure D.H.W. system 20 = (T max) Max. temperature D.H.W system
C = Electrical features
21 = Electrical power supply 22 = Consumption 23 = Protection grade
D = Countries of destination
24 = Direct and indirect country of destination 25 = Gas family 26 = Supply pressure
E = Factory setting
27 = Adjusted for gas type X 28 = Space for national brands
CE Marking
- The CE marking documents that the boilers satisfy:
- The essential requirements of the Directive regarding gas appliances (Directive 90/396/CEE)
- The essential requirements of the Directive regarding electromagnetic compatibility (Directive 89/336/CEE)
- The essential requirements of the Efficiency Directive (Directive 92/42/CEE)
- The essential requirements of the low voltage Directive (Directive 73/23/CEE)
®
1
2
3
5
7 8
6
4
9
11
13
10
12
14
15
17
19
16
18
20
28
A
B
21 22
23
24
25
26
27
C D
E
7
General info
1
2
3
For your own safety, observe these safety instructions.:
PLEASE NOTE:
User tip for the optimum utilisation and setting of the control(s) plus useful information.
WARNING
from risk of electric shock.
WARNING
Identifies potentially dangerous situations.
User easy guide
................................................................ pag. 4-6
TECHNICAL FEATURES
AND DIMENSIONS ........................................................... pag. 8
1.1 Technical features ................................................................... pag. 8
1.2 Dimensions .............................................................................. pag. 8
1.3 Hydraulic circuits ..................................................................... pag. 9
1.4 Technical data ......................................................................... pag. 12
1.5 Main characteristics ................................................................ pag. 12
DIRECTIONS FOR
INSTALLERS......................................................................... pag. 13
2.1 Installations rules .................................................................... pag. 13
2.2 Installation ............................................................................... pag. 13
2.2.1 Packing ....................................................................... pag. 13
2.2.2 Positioning the boiler .................................................. pag. 14
2.2.3 Assembling the boiler ................................................. pag. 15
2.2.4 Ventilation ................................................................... pag. 15
2.2.5 Flue gas discharge system ........................................ pag. 15
2.2.6 Discharge and suction pipe configuration .................. pag. 17
2.2.7 Positioning of terminals for type C boilers .................. pag. 18
2.2.8 Smoke evacuation Ø80 air suction flange .................. pag. 19
2.2.9 Discharge of flue gas into coaxial ducts with a
diameter of 100/60 mm (Type A accessories) ........... pag. 20
2.2.10 Flue gas discharge and air suction with separate
pipes with 80 mm diameter ........................................ pag. 21
2.2.11 Measurements of combustion efficiency ................... pag. 23
2.2.12 Connection to the gas mains...................................... pag. 24
2.2.13 Hydraulic connection .................................................. pag. 24
2.2.14 Electrical connection ................................................. pag. 26
2.2.15 Jumper location ......................................................... pag. 26
2.3 Wiring diagram ........................................................................ pag. 27
2.3.1 Pratical connection diagram ..................................... pag. 27
2.4 Filling the system ................................................................... pag. 28
2.5 Starting the boiler ................................................................... pag. 28
2.6 Adjusting the burner ............................................................... pag. 29
2.7 Modification of other gases ................................................... pag. 30
2.8 Failure code ............................................................................ pag. 31
USERS' INSTRUCTION ............................................... pag. 33
3.1 Control panel ........................................................................... pag. 33
3.2 Switching on/off ....................................................................... pag. 34
3.3 Antifrost protection .................................................................. pag. 35
3.4 Important suggestion and notes ............................................. pag. 35
8
Installation info
1
TECHNICAL FEATURES AND DIMENSIONS
Pump anti-jamming function;
Pump over run function;
High limit thermostat (95°C);
Three-speed circulating pump;
Expansion vessel;
Automatic air vent;
C.H. system water filling valve;
Safety pressure switch for low water level;
Priority flow switch for D.H.W.;
Tap water flow rate restrictor set at 12
litres/min.
Control panel with IP X4D insulation pro-
tection
Manometer;
Warning light for: presence of power, re-
quest for heating, burner in operation, lock out, by the display
D.H.W. temperature selector (35/57°C) for
EVE 05 CTN 24 F - CTFS 24 F - CTFS 24 CTN 24 ;
C.H. temperature selector (45/78°C) + sum-
mer/winter position.
Reset push button / Chimney sweeper but-
ton / Error codes visualization / Thermo­meter
Paper mounting jig for connections predi-
sposition
Mounting jig opt.
Flue gas antispillage thermostat (EVE 05
TN)
1.1 - TECHNICAL FEATURES
EVE 05 is a wall hung gas boiler with built-in
atmospheric gas burner; it is available in the following versions:
24 with 24 kW output;
C with instantaneous D.H.W.
production;
R for heating only;
TN with natural draught open chamber; TFS with forced draught room sealed
combustion chamber;
All versions have electronic ignition. Models in the EVE 05 series are the following:
EVE 05 CTN 24 F open boiler, with electronic ignition and instantaneous D.H.W. produc­tion;
EVE 05 RTN 24 open boiler, with electronic ignition, for heating only;
EVE 05 CTFS 24 F forced draught room se­aled boiler, with electronic ignition and in­stantaneous D.H.W. production;
EVE 05 RTFS 24 forced draught room sea­led boiler, with electronic ignition for heating only;
EVE 05 CTN 24 open boiler, with electronic ignition and instantaneous D.H.W. produc­tion with DHW plates heat exchanger
EVE 05 CTFS 24 forced draught room sea­led boiler with electronic ignition and instan­taneous D.H.W production with DHW plates heat exchanger
EVE 05 is supplied with all control and safety devices according to the latest laws in for­ce. The main technical features of the EVE 05 boilers are summarised below.
Bithermal, copper, high performance heat
exchanger (CTN 24F - CTFS24F);
• Plates heat exchanger for the DHW pro­duction (CTN 24 – CTFS 24)
Electronic ignition;
Electronic flame modulation;
Minimum output control;
Electronic control of ignition ramp;
Anti-freeze function;
fig. 1
1.2 - DIMENSIONS
420
700
123
87
120 90
152
85
107
43 56
60 70
61131
CFG
R
M
Rc
V
s
Si
M
C.H. system flow
C
D.H.W. outlet
G
Gas inlet
F
D.C.W. inlet
R
C.H. system return
Rc
Filling valve
VS
Heating circuit safety valve
Si
Boiler drain cock
view from above
view from below
310
9
Installation info
fig. 3
EVE 05 CTN 24 F
EVE 05 CTFS 24 F
fig. 2
CF G R1M
3
4
2
5
6
7
9
10
11
8
12
13
14 15
16
17 18
19
20
21
1
3
4
2
5
6
7
8
9
10
11
12 13
CF G
14
15
16 17
18
19 20
21
22
23
RM
1.3 - HYDRAULIC CIRCUIT
1 Flow switch - Cold water filter 2 D.H.W. flow restrictor 3 Gas valve 4 D.H.W. temperature sensor 5 Burner nozzles 6 Ionisation/Ignition electrode 7 Burner 8 Bithermal heat exchanger 9 H.L. thermostat 10 Flue gas manifold/down-draught
diverter 11 Flue gas anti-spillage thermostat 12 Expansion vessel inflating valve 13 Expansion vessel 14 Automatic air vent 15 Circulating pump 16 C.H. temperature sensor 17 Minimum water pressure switch 18 By-pass (unadjustable) 19 Boiler drain cock 20 Heating circuit safety valve 21 Filling valve
C D.H.W. outlet F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
1 Flow switch - Cold water filter 2 D.H.W. flow restrictor 3 Gas valve 4 D.H.W. temperature sensor 5 Burner nozzles 6 Ionisation/Ignition electrode 7 Burner 8 Bithermal heat exchanger 9 H.L. thermostat 10 Flue gas extractor fan 11 Air/flue coaxial duct 12 Micro-switch on flue gas pressure
switch 13 Flue gas pressure switch 14 Expansion vessel inflating valve 15 Expansion vessel 16 Automatic air vent 17 Circulating pump 18 C.H. temperature sensor 19 Minimum water pressure switch 20 By-pass (unadjustable) 21 Boiler drain cock 22 Heating circuit safety valve 23 Filling valve
C D.H.W. outlet F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
10
General info
fig. 5
EVE 05 RTFS 24
fig. 4
EVE 05 RTN 24
FG RM
1
2
3
4
6
7
5
9
10
11
12 13
14 15
16
17
18
8
1
Gas valve
2
Burner nozzles
3
Ionisation/Ignition electrode
4
Burner
5
Monotermal heat exchanger
6
Flue gas manifold/down-draught
diverter
7
Flue gas anti-spillage thermostat
8
H.L. thermostat
9
Expansion vessel inflating valve
10
Expansion vessel
11
Automatic air vent
12
Circulating pump
13
C.H. temperature sensor
14
Minimum water pressure switch
15
By-pass
16
Boiler drain cock
17
Heating circuit safety valve
18
Filling valve
F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
1
Gas valve
2
Burner nozzles
3
Ionisation/Ignition electrode
4
Burner
5
Monotermal heat exchanger
6
Air/flue coaxial duct
7
Flue gas extractor fan
8
Micro-switch on flue gas pressure
switch
9
Flue gas pressure switch
10
H.L. thermostat
11
Expansion vessel inflating valve
12
Expansion vessel
13
Automatic air vent
14
Circulating pump
15
C.H. temperature sensor
16
Minimum water pressure switch
17
By-pass
18
Boiler drain cock
19
Heating circuit safety valve
20
Filling valve
F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
1
2
3
4
5
6
7
8 9
11
12
13 14
15
16 17 18
19
20
10
FG RM
11
General info
fig. 7
EVE 05 CTN 24
EVE 05 CTFS 24
fig. 6
1
3
2
4
5
6
7
8
9
10
11
12
13 14
15 16
17
18
19
20
21
22
23
2425
C
F
GR
M
C
F
GR
M
1
3
2
4
5
6
7
8
9
10
2526
17
18
19
20
21
22
23
24
11
12
13 14
16
15
1 Flow switch - Cold water filter 2 D.H.W. flow restrictor 3 Gas valve 4 D.H.W. temperature sensor 5 Plates heat exchanger for DHW
production 6 Circulating pump 7 Burner nozzles 8 Ionisation/Ignition electrode 9 Burner 10 Monothermal heat exchanger 11 Combustion chamber 12 Flue gas manifold/down-draught
diverter 13 Flue gas anti-spillage thermostat 14 H.L. thermostat 16 Expansion vessel inflating valve 17 Expansion vessel 18 Automatic air vent 19 By-pass 20 C.H. temperature sensor 21 Diverting valve motor 22 Boiler drain cock 23 Diverting valve 24 Heating circuit safety valve 25 Filling valve
C D.H.W. outlet F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
1 Flow switch - Cold water filter 2 D.H.W. flow restrictor 3 Gas valve 4 D.H.W. temperature sensor 5 Plates heat exchanger for DHW
production 6 Circulating pump 7 Burner nozzles 8 Ionisation/Ignition electrode 9 Burner 10 Monothermal heat exchanger 11 Flue gas extractor fan 12 Air/flue coaxial duct 13 Micro-switch on flue gas pressure
switch 14 Flue gas pressure switch 15 H.L. thermostat 16 Minimum water pressure switch 17 Expansion vessel inflating valve 18 Expansion vessel 19 Automatic air vent 20 By-pass 21 C.H. temperature sensor 22 Diverting valve motor 23 Boiler drain cock 24 Diverting valve 25 Heating circuit safety valve 26 Filling valve
C D.H.W. outlet F D.C.W. inlet G Gas inlet R C.H. system return M C.H. system flow
12
General info
l/min
bar
bar
l
°C
°C
l
bar
l
l
bar
bar
l/min.
l/min.
l/min.
l/min.
l/min.
l/min.
l/min.
°C
V-Hz
A (F)
W
IP
kg
kW
kW
%
%
%
%
n.
%
%
%
°C
g/s
%
%
mg/kWh
%
%
RTN 24
24 10,17 90,57 89,76 92,60 87,14 2 92,85 90,83 2,38 - 2,28 86,7 14,11-20,03 117,89 2,9-5,1 152,4 2 9,17 - 7,15 0,831
RTFS 24
24,2 9,9 91,34 89,77 89,93 87,15 2 92,71 87,81 1,7-1,37 116,7 13,41-15,1 60,86 3,0-7,0 184,4 2 12,19-7,29 0,405
CTN 24 F
24 10,17 90,57 89,76 92,60 87,14 2 92,85 90,83 2,38 - 2,28 86,7 14,11-20,03 117,89 2,9-5,1 152,4 2 9,17 - 7,15 0,831
CTFS 24 F
24,2
9,9
91,34
89,77
89,93
87,15
2
92,71
87,81
1,7-1,37
116,7
13,41-15,1
60,86
3,0-7,0
184,4
2
12,19-7,29
0,405
CTN 24
24 10,17 90,57 89,76 92,60 87,14 2 92,85 90,83 2,38-2,28 86,7 14,11-20,03 117,89 2,9-5,1 152,4 2 9,17-7,15 0,831
RTN 24
II
2H3P
7,3 0,7 3 3,5 78 45 6 1 137,9
-
-
-
-
-
-
-
-
-
-
230/50 3,15 96 X4D 28 31
CTN 24 F
II
2H3P
7,3 0,7 3 3,5 78 45 6 1 137,9 2,5 0,5 6 11,5 12 7,6 8,6 9,8 11,4 13,7 35 - 57 230/50 3,15 96 X4D 30 33
CTFS 24 F
II
2H3P
7,10 0,7 3 3,5 78 45 6 1 137,9 2,5 0,5 6 11,5 12 7,6 8,6 9,8 11,4 13,7 35 - 57 230/50 3,15 130 X4D 36,5 39,5
RTFS 24
II
2H3P
7,10 0,7 3 3,5 78 45 6 1 137,9
-
-
-
-
-
-
-
-
-
-
230/50 3,15 130 X4D 34,5 37,5
CTN 24
II
2H3P
7,3 0,7 3 3,5 78 45 6 1 137,9 2,5 0,5 6 11,5 12 7,6 8,6 9,8 11,4 13,7 35 - 57 230/50 3,15 98 X4D 32 35
EVE 05
CTFS 24
II
2H3P
7,10 0,7 3 3,5 78 45 6 1 137,9 2,5 0,5 6 11,5 12 7,6 8,6 9,8 11,4 13,7 35 - 57 230/50 3,15 132 X4D 38,5 41,5
CTFS 24
24,2 9,9 91,34 89,77 89,93 87,15 2 92,71 87,81 1,7-1,37 116,7 13,41-15,1 60,86 3,0-7,0 184,4 2 12,19-7,29 0,405
Warning:If the boilers are used in low tem­perature heating system (ex. floor hea­ting) it is necessary to use a mixing valve to avoid condensation phenomena.
1.4 - OPERATING DATA
Nominal output
Minimum output
Actual water efficiency at full load (100%)
Min. required water efficiency at full load (100%)
Actual water efficiency at part load (30%)
Min. required water efficiency at part load (30%)
Stars No. off (According EEC Directive 92/42)
Combustion efficiency at nominal load (100%)
Combustion efficiency at part load (30%)
Stand-by losses (min.-max.)
(*)Flue gas temperature (min. - max.)
Flue gas mass flow rate (min. - max)
Excess of air l
CO
2
NOX (value according EN 297/A3 + EN 483)
NOX class
Flue losses with burner in operation (min.-max)
Flue losses with burner off
For the following data: Nozzle - Burner pressure - Diaphragm (where applicable) - Inputs - Gas consumptions refer to pagraph SUIT ABILITY T O USE OTHER GASES.
Appliance category
Min. water flow rate in CH circuit (Dt 20 K)
Min. pressure in CH circuit
Max. pressure in CH circuit
Water content primary circuit
Max. oper. temperature in CH mode
Min. oper. temperature in CH mode
Total capacity of expansion vessel
C.H. expansion vessel pre-loading
Max. water content CH circuit (calc. x max. T°of 82°C)
Min. water flow rate in D.H.W. circuit
Min. DHW. pressure
Max. DHW. pressure
DHW specific flow rate (Δt 30 K)
Flow restrictor
DHW production in continuous operation with Δt 45 K
DHW production in continuous operation with Δt 40 K
DHW production in continuous operation with Δt 35 K
DHW production in continuous operation with Δt 30 K
DHW production in continuous operation with Δt 25 K*
DHW Temperature range
Electrical supply
Supply fuse
Maximun absorbed power
Insulation protection
Net weight
Gross weight
1.5 - GENERAL FEATURES
(*) mixed
13
Installation info
fig.8
2.2.1 - PACKING
EVE 05 is delivered completely assembled and
packed in a strong cardboard box. Once the boiler has been unpacked check that it is in­tact.
750
430
330
Keep the packaging material (cardboard box, plastic strips, plastic bag, etc.) out of the reach of children as it represen­ts a choking and suffocation hazard.
In addition to the boiler packaging contains:
- a bag with:
- installation, use and maintenance handbook,
- template for fixing the boiler to the wall,
A bag containing:
- 2 dowels with screws hook to fix the boiler to the wall,
- Only for models TFS, a diaphragm for flue gas outlet
UNICAL refuses all liability for injury to persons and ani­mals or damage to property resulting from non-observan­ce of the above.
2
DIRECTIONS FOR INSTALLER
2.1 - DIRECTIONS FOR
INSTALLER
EVE 05 is a gas boiler which must be instal­led in accordance with the latest regulations or rules in force. For the boiler category, which changes according to the destination country, see page 6.
NOTE:
Observe the corresponding technical rules and the building supervisory and statutory regulations of the country of final use when installing and operating the system.
Always ensure that an appropriately specialised company is entrusted with installation, gas supply and flue gas connection, commissioning and power supply connection, as well as all servicing and repair work. Work on gas conduits and fittings must only be carried out by a registered service provider. The system must be cleaned and serviced once a year. This includes an inspection of the entire system to see if it is in full working order. Defects and faults must be eliminated
immediately. Please note that we can accept no liability whatsoever for loss or injury resulting from unauthorised adjustment or manipulation of the system’s control or regulating devices.
2.2 - INSTALLATION
Only for the TFS (room sealed fan assisted) models a bag containing:
- 2 sealed room closing covers + 2 sealing gaskets and the fixing screws. “
14
Installation info
fig. 9
2.2.2 - POSITIONING THE BOILER
Every boiler is supplied with special “MOUNT­ING JIG” with which the pipes for connection to the system, D.H.W. and gas can be positioned when the hydraulic system is being laid out and before the boiler is installed. This MOUNTING JIG, comprising a sheet of strong paper which must be fixed to the wall chosen for the installation of the boiler, gives all the indications needed to make the holes in the wall using two screws with expanding dowels. Use the lower part of the MOUNTING JIG to mark the exact point of the connection of the gas supply, cold water supply pipe, D.H.W. outlet, C.H. flow and return.
When choosing the position of the boiler:
- refer to the indications given in the section “Flue gas evacuation system “.
- leave a clearance of 50 mm on each side of the boiler to facilitate maintenance ope­rations.
- Leave a 200 mm free space under the boi­ler in order to allow the possible verifica­tion or substitution of the DHW plates heat exchanger.
- check that the wall is suitable.
- avoid fixing the boiler to thin partitions.
- avoid installing the boiler above applian­ces which might affect operation when in use (cookers which produce greasy steam, washing machines, etc.)
- avoid installing natural draught boilers in corrosive or very dusty atmospheres such as hairdressers’, laundrettes, etc. as the life of the boiler components could be si­gnificantly shortened.
M = C.H. system
flow
C = D.H.W.
outlet
G = Gas F = Cold water
inlet
R = C.H. system
return
Vs = Safety valve
discharge
Si = Boiler drain cock
ØL mm
= 3/4'' 107
= 1/2'' 107 = 3/4'' 107
= 1/2'' 107
= 3/4'' 107
= 143 =60
For EVE 05 TFS
Since the temperature of the wall on which the boiler is installed
and the temperature on the sur­face of the coaxial duct do not increase, in normal operating conditions, more than 60 K, it is not necessary to keep a minimum distan­ce from inflammable walls.
For boilers with dual suction and exhaust ducts, place insulating material between the wall and the pipe in the case of inflammable walls and wall crossings.
87 120
78.5
110
139
182
CF G R M
10
56 60
51
79
70
752
00332145
143
34
14.5
420
CONNECTION POSITION SEEN FROM BELOW
MOUNTING JIG FOR BOILER CONNECTIONS 00332145
EVE 05 TN
Maintain distance of at least 200
mm on the sides with wall which
have inflammable materials.
107
290
CF
G
R
M
Rc
Vs
Si
143
60
360 60
130
15
Installation info
2.2.3 - ASSEMBLING THE BOILER
Before connecting the boiler to the D.H.W. and heating system pipes, carefully clean the pi­pes to remove all traces of metal resulting from processing and welding operations as well as any oil and grease which could damage the boiler or jeopardize its operation.
To install the boiler:
- Fix with tape the paper template to the wall;
- make two Ø 12 holes in the wall and insert the dovels;
- position the junction points for the connect­ion of the gas supply pipe, cold water sup­ply pipe, D.H.W. outlet, CH flow and return in the positions shown by the template. ;
- fit the boiler onto the support hooks;
Do not use solvents which could damage the components.
Unical refuses all liability for injury to persons and animals or damage to property resulting from non-observance of the abo­ve.
- connect the boiler to the gas pipe, domestic cold and hot water pipes, CH flow and return pipes.
- connect to electrical supply
2.2.4 - VENTILATION
The boiler must be installed in a suitable room according to the rules in force and particular­ly:
NATURAL DRAUGHT OPEN FLUE BOILERS (TYPE B11bs and VMC INSTALLATIONS) The boilers EVE 05 CTN 24 F, EVE 05 RTN 24, EVE 05 CTN 24, are open flue boilers and are
foreseen for chimney connection: the air for combustion is taken directly from the room in which the boiler is installed. The room can have both a direct ventilation (i.e. with ventilation openings facing out­wards) or an indirect ventilation (i.e. with ven­tilation openings facing an adjacent room) pro­vided that the following requirements are com­plied with:
Direct ventilation:
- The room has to have a ventilation open­ing of, at least, 6 cm² /kW of installed input (see input ta­ble on par. 2.7) and, in no case, lower than 100 cm² and made directly onto an exter­nal wall.
- The opening has to be as close as possi­ble to the floor.
- It should not be possible to close it and it should be protected with a grate not redu­cing its usefull ventilation section.
- A correct ventilation can be optained also through the addition of more openings, pro­vided the addition of the different sections is not less than that really needed.
connection duct to the draught diverter.
- starting from the draught diverter, the duct must have a vertical section with a length more than twice the diameter, before get­ting into the chimney.
2.2.5 - FLUE GAS DISCHARGE SYSTEM
NATURAL DRAUGHT OPEN FLUE BOILERS
Connection to the chimney
A good chimney is very important for the cor­rect functioning of the boiler; it must therefore conform with the following requirements:
- it must be made from waterproof material
and be resistant at the temperature of the flue gas and relative condensate;
- it must have sufficient mechanical strength and low thermal conductivity;
- it must be perfectly sealed to prevent cool­ing due to parasite air inlets;
- it must be as vertical as possible and the end section must have a chimney cap which guarantees efficient and constant evacuation of the combustion products;
- the chimney must have a diameter not smaller than that of the boiler’s draught di­verter; for chimneys with a square or rectangular section, the internal section must be 10% larger than the section of the
- In case it is not possible to make a venti­lation opening close to the floor, it will be necessary to increase its usefull section of at least 50%.
- If an open fire is present in the same room it needs an indipendent air supply, other­wise the installation of a type B appliance is not permitted.
- If in the room there are other devices which need air for their operation (e.g. a wall exhauster) the section of the ventila­tion opening has to be the properly sized.
Indirect ventilation
In case it is not possible to make a room ven­tilation opening on an external wall, it is pos­sible to have an indirect ventilation, sucting the air from an adjacent room, making an opening in the lowest part of a door. This solution is possible only if:
- The adjacent room is not a bed room
- The adjacent room is not a common part of the building and is not a room with fire danger (e.g. a fuel deposit, a garage, etc..)
FORCED DRAUGHT ROOM SEALED BOI­LER (TYPE C12 - C32 - C42 - C52 - C62 - C82) The EVE 05 CTFS 24 F - EVE 05 RTFS 24 ­EVE 05 CTFS 24 are forced draught, room seal-
ed boilers; so they do not need particular ven­tilation openings for the combustion air, in the
room in which they are installed.
FORCED DRAUGHT, OPEN FLUE BOILER (TYPE B22) If the EVE 05 CTFS 24 F - EVE 05 RTFS 24 ­EVE 05 CTFS 24 are installed in a room ac-
cording to the chimney configuration on type B22, the same ventilation requirements esta­blished in paragraphs Direct ventilation and Indirect ventilation apply.
16
Installation info
fig. 10
2 Ø min.
Slope min. 3%
Ø
1,5 m min.
2 Ø
1 m max.
1,5 m min.
2 Ø
Ø
Slope min. 3%
1 m max.
2 Ø min.
> 3 Ø
> 3 Ø
fig. 11
210
Ø 130
180
Direct emission into the atmosphere
Natural draught boilers can discharge combustion products directly into the atmo­sphere using a duct, which goes through the outside walls of the building, connected to a flue exhaust terminal. The exhaust duct must also comply with the following requirements:
- the sub-horizontal part inside the building must be as short as possible (no more than 1 m);
- for boilers with vertical discharge, such as boilers EVE 05 TN 24, there must be no more than 2 direction changes;
- it must receive the discharge from a single boiler;
- the part going through the wall must be
protected by a sheath duct; the part of the sheath duct facing the inside of the build­ing must be sealed and the part facing outwards must be open;
- the final section, on which the draught ter­minal will be fixed, must protrude from the wall of the building for a length of at least twice the diameter of the duct;
- the draught terminal must overlap the con­nection to the boiler by at least 1.5 m (see fig. 8).
DIMENSIONS FOR CONNECTING FLUE GAS DUCT
WARNING:
The boiler is fitted with an automatic safety reset device as protection against spillage of combustion products inside the building. In case of the device operation, the boiler will remain in lock-out position indicating the ano­maly on the display with the symbol “M” (fig.
35) (failure code AF)
After the cooling down of the smoke thermostat it will be possible to restart the boiler by pressing the reset button L fig. 35.
It is absolutely forbidden to by-pass the smoke thermostat.
If the boiler cuts off regularly, it is necessary to ask a technician for a check of the flue gas exhaust duct. This duct may be obstructed or may be unsuitable for the discharge of flue gas into the atmosphere.
UNICAL refuses all liability for damage caused as a result of in­correct installation, use, modifica-
tion of the boilers or for non-observance of the instructions provided by the manufacturer or applicable installation regulations
17
Installation info
2.2.6 - SMOKE DISCARGE AND AIR SUCTION DUCT CONFIGURATION C12, C32, C42, C52, C62, C82 - B22
type C12
type C32
type C52
type C82
type C62
type C42
SEPARATE
type B22
C12 Boiler designed for connection to hori-
zontal exhaust and suction terminals directly into the atmosphere using coaxial or dual ducts. The distance between the air intake duct and the flue gas outlet duct must be at least 250 mm and both end sections must be located within a 500 mm square.
C32 Boiler designed for connection to verti-
cal discharge and suction outlets directly into the atmosphere using coaxial or dual ducts. The distance between the air intake duct and the flue gas outlet duct must be at least 250 mm and both end sections must be located within a 500 mm square.
C42 Boiler designed for connection to col-
lective chimneys including two ducts, one for the suction of combustion air and the other for the exhaust of the combustion products, through coaxial or dual ducts.
The chimney must comply with relevant applicable law provisions.
C52 Boiler with separate combustion air
suction and combustion product exhaust ducts.
These ducts can discharge into are­as with different pressure. The dual ducts must not be located on two opposite walls.
C62 Boiler that has to be connected to a
system of air supply and smoke of ap­proved type and sold apart.
C82 Boiler designed for connection to an air
supply terminal and fitted to an indivi­dual or shared chimney.
The chimney must comply with re­levant applicable law provisions.
B22 Boiler designed for connection to an
external flue gas evacuation duct, with the air for combustion taken from the room in which the boiler is installed. For this type of installation the boiler house follows the same installation re­quirements used for the open type boi­lers.
Note: type B22
is not approved by
Turkish market.
18
Installation info
fig. 12
Pursuant to the directives of regulations in force, discharge of forced draught boilers can
2.2.7 - POSITIONING OF
TERMINALS FOR TYPE ‘’C’’ BOILERS
either take place through the roof or directly outwards the room they are installed in. The following distances shall be considered for terminals proper positioning:
POSITIONING OF TERMINALS FOR "FORCED DRAUGHT" BOILERS
Min.
POSITIONING OF THE TERMINAL distances in mm.
Under a window A 600
Under a ventilation opening B 600
Under a gutter C 300
Under a balcony (1) D 300
From an adjancent window E 400
From an adjacent ventilation opening F 600
From vertical or horizontal air pipes or drains (2) G 300
From an external corner of the building H 300
From an internal corner of the building I 300
From the ground or from another floor L 2500
Between two vertical terminals M 1500
Between two horizontal terminals N 1000
From a facing front surface without opening or teminals within a radius
of 3 mt. from smoke outlet point O 2000
As above, but with openings or terminals within a radius of 3 mt. from
smoke outlet point P 3000
NOTES (1) Terminals below a practicable balcony shall be arranged in such a way as to assure that the total run of smokes, from their outlet from
terminal up to outlet from balcony external perimeter, including the height of protection baluster, if any, is not less than 2 m.
(2) Distances of not less than 500 mm shall be adopted in placing the terminals, due to the proximity to materials subject to the action of
products of combustion such as plastic gutters or waterspouts, wooden jetties, etc.) unless adequate screeening measures are taken for the said materials.
FLUE TERMINAL POSITIONING
19
Installation info
fig. 13
fig. 14
Diaphragm
Ø 42 mm
Fitting of the diaphragm Ø 42
2.2.8 - SMOKE EVACUATION Ø 80
WITH AIR SUCTION FLANGE - Type B22 (see par. 2.2.6)
Note: For evacuation system with 80 mm dia.
and a lenght between 0.5 m and 4 m, it is necessary to introduce a diaphragm of 42 mm dia. supplied with the boiler in the plastic bag, into the fan outlet adap­tor (see fig. 13).
The maximum allowed length for a smo­ke pipe of 80 mm dia. is 20 m, included a wide radium curve and one smoke ter­minal.
For this type of installation the chim­ney has to serve just one boiler, i.e. the boiler must have its indipendent smo­ke duct.
WARNING: For the installation where there is a freezing risk it is suggested to insulate the smoke duct 80 mm dia. on all its length, both in case it discharges from a verti­cal wall or in a chimney.
WARNING: For the smoke ou­tlet configuration (see fig. 13-
14) it is necessary to close the holes of air entry ''1-2'' with the provided for closing co­vers and the gaskets delive­red with the boiler.
Closing cover with
gasket in neoprene
Closing cover with
gasket in neoprene
Closing cover with
gasket in neoprene
Closing cover with
gasket in neoprene
20
Installation info
fig. 15
fig. 16
Ø 80/125
Ø 80/125
Ø 60/100
Ø 80/125
Rubber foam gasket
Up to 2 m
Up to 1 m
Up to 2,5 m
Rubber foam gasket
Diaphragm Ø 42
Diaphragm
Ø 42
2.2.9 - DISCHARGE OF FLUE
GAS INTO COAXIAL DUCTS Ø 100/60 mm
Type C12 Ø 100/60 mm
The minimum length of horizontal coaxial ducts is 0.5 metres. The maximum allowable length of horizontal co-axial ducts is 3 me- tres; for each additional bend the maximum allowable length must be reduced by 1 metre. Moreover, the duct must have a downward dip of 1% towards the outlet point to prevent rain water from getting into the duct.
Type C32 100/60 mm
The minimum length of vertical coaxial ducts is 0.5 metres. The maximum allowable length of vertical coaxial ducts is 4 metres exclu­ding the stack (Ø 80/125); for each additional bend the maximum allowable length must be reduced by 1 metre.
The diaphragm Ø 42 supplied with the boi­ler must be inserted in the flue gas exhaust pipe as shown in figure 15, for installa­tions with horizontal coaxial pipe up to 1 m and with vertical coaxial pipe up to 2 m.
VERTICAL FLUE DUCT WITH COAXIAL DUCT Ø 80/125
Tipo C32 Ø 80 / 125
The minimum length of vertical coaxial ducts is 1,2 metres. The maximum allowable length of vertical coaxial ducts is 6 metres exclu­ding the stack (Ø 80/125); for each additional bend the maximum allowable length must be reduced by 1 metre.
The diaphragm Ø 42 supplied with the boi­ler must be inserted in the flue gas exhaust pipe, as shown in figure 16, for installa­tions with a coaxial pipe up to 2,5 m.
Fitting of the diaphragm Ø 42
Closing cover with gasket in neoprene
Closing cover with gasket in neoprene
Closing cover with gasket in neoprene
Closing cover with gasket in neoprene
WARNING: For the smoke ou­tlet configuration (see fig. 15-
16) it is necessary to close the holes of air entry ''1-2'' with the provided for closing co­vers and the gaskets delive­red with the boiler.
21
Installation info
fig. 17
152
100
95
Up to
ΔΔ
ΔΔ
Δ P = 20 Pa
Rubber foam gasket
Diaphragm Ø 42
fig. 18
It is not allowed to position the 2 termi­nals in opposite walls, see configuration type C52.
DIMENSIONS FOR CONNECTION TO COAXIAL FLUE GAS DUCTS
2.2.10 - FLUE GAS DISCHARGE
AND AIR SUCTION WITH DUAL DUCTS WITH 80 mm DIAMETER
NB: The maximum allowable pressure loss, irrespective of the type of installation, must not exceed 50 Pa .
For all installations with a pressure loss of the ducts not exceeding 20 Pa, the diaphragm supplied with the boiler must be installed insi­de the flue gas outlet pipe (see fig. 18).
WARNING! In case the flue duct has to cross walls or floors, or if it is easily reachable, it is ne­cessary to foresee a convenient insulation of such a duct. The flue duct, during the operation of the boiler can reach tempera­tures higher than 120°C.
IMPORTANT Flue gas pressure switch operation
The boiler is fitted with a device control­ling flue gas pressure. This device shuts down the boiler in the event of a malfunction.
This situation is indicated by the failure led
lighting on the display; by pressing the reset push-button the failure code “AF” is di­splayed and the boiler will repeat it's ignition sequence. If the reset button is not pressed
the boiler will in any case repeat it's ignition sequence after 10 minutes.
WARNING: Per For the smo­ke outlet configuration (see fig. 18) it is necessary to clo­se the hole of air entry ''1'' with the provided for closing
Closing cover with gasket in neoprene
cover and the gasket delivered with the boiler. Note: in case the air aspiration will be effected by the hole ''1'', close the hole ''2''.
22
Installation info
fig. 19
fig. 20
DIMENSIONS FOR CONNECTION THE AIR INTAKE AND THE FLUE GAS DISCHARGE WITH DUAL DUCTS
_
>
500
Hmin. = 150 mm
CONFIGURATIONS FOR SEP ARA TE PIPES (SUCTION AND OUTLET) Ø 80
Example N.1
Primary air suction from perimeter wall and flue gas discharge on roof.
Maximum allowable pressure loss: 50 Pa
87
120 152
Ø 80
123
90
Example N.1
23
Installation info
fig. 22
fig. 21
135
45
C
2
1
250 min.
Example of check using wide radius bends:
- 17 mt duct Ø 80 x 2 = 34 Pa
- 2x90° Ø 80 long radius bends 2x4 = 8 Pa
- horizontal Ø 80 air inlet terminal = 3 Pa
- horizontal Ø 80 terminal = 5 Pa
Tot. pressure loss = 50 Pa
1
2
A
Air inlet
1
Smoke outlet
B
2
Example N.2
CALCULATION OF PRESSURE LOSSES FOR DISCHARGE AND SUCTION DUCTS
Bear in mind the following parameters when calculating pressure losses:
- for each metre of duct with Ø 80 (both
suction and discharge) the pressure loss is 2 Pa;
- for each 90° Ø 80 (R=D) bend with long
radius, the pressure loss is 4 Pa;
- for each 90° Ø 80 (R=½ D) bend with
short radius, the pressure loss is 14 Pa
- for the Ø 80 L = 0.5 m horizontal air inlet
terminal, the pressure loss is 3 Pa;
- for the Ø 80 L = 0.6 m horizontal
discharge end section, the pressure loss is 5 Pa;
NB: These values refer to dis­charges through original UNI­CAL non-flexible and smooth ducts.
Example N.2
Primary air suction from perimeter wall and flue gas discharge from the same outside pe­rimeter wall. It is not allowed to position the 2 termi-
nals in opposite walls,
Maximum allowable pressure loss:
50 Pa
2.2.11- MEASUREMENTS OF
COMBUSTION EFFICIENCY
Ducts Ø 80 type B22 (C)
Coaxial ducts (A)
Dual ducts Ø 80 (B)
To determine combustion efficiency the fol­lowing measurements must be made:
- the combustion air temperature measured
in hole 2 (see fig. 22).
- the flue gas temperature and CO2 % mea-
sured in hole 1 (see fig. 22).
Make these measurements with the boi­ler running in a steady state condition.
Air inlet
Smoke outlet
Analyser probe
Analyser probe
Analyser probe
Analyser probe
24
Installation info
2.2.13 - HYDRAULIC CONNECTION
Before installing the boiler we recommend that the system be cleaned to remove any impuri­ties which could originate from components and which could risk damaging the circulating pump and heat exchanger.
Note: The use of solvents could damage
the components of the heating cir­cuit.
Basing on the feeding water hardness, it has to be considered the opportunity to install appropriate devices for
POSITION By-Pass CLOSE
POSITION By-Pass OPEN
ADJUST By-Pass
By-Pass ADJUSTMENT SCREW CTN 24 - CTFS 24
fig. 24
INSTALLA TION WITH BENDED PIPES (00361193 kit pipes)
INSTALLA TION WITH V AL VES (00360682 + 00361193)
INSTALLA TION OF BEBDED PIPES AND PRESSURE FITTING 00361265
OPTIONAL CONNECTION KITS
water treatment (for domestic use). With feeding water hardness higher than 14°f it’s always recommended the water treat­ment.
2.2.12 - CONNECTION TO THE GAS
MAINS
The supply pipe must have a section which is the same as or greater than the one used in the boiler. Comply with the applicable local installation requirements which shall be considered as having been incorporated in full in this ma­nual. Before opening the internal gas supply system; i.e. before connecting the gas meter, all seals must be checked. If any part of the system is concealed the seals must be checked before the pipes are cove-
red. The seal test must be conducted using air or nitrogen at a pressure of at least 100 mbar. The commissioning of the boiler also inclu­des the following operations and checks:
- Opening of the gas gate valve and venting of the air contained in the piping and ap­pliances, proceding appliance by appliance.
- Check, with the gate valve of all the ap-
pliances Off, that there are no gas leaks. During the 2nd quarter of a hour from the beginning of the test no pressure reduc­tion is to be detected on the gas pressure gauge. If gas leaks have to be found, use only water soap solution or any other spe­cific gas leak detector which can be avai­lable on the market. Never look for gas leaks using a naked flame.
While connecting gas inlet pipe of the boiler to the pipe coming from gas network, it is MANDATORY to insert a TIGHT GASKET, whose dimensions and material must be adequate. Connection is NOT sui­table for hemp, teflon strip or similar materials
HEATING
The heating flow and return must be con­nected to the relevant ¾” connections of the boiler M and R (see fig. 9).
When determining the size of the heating circuit pipes it is essential to bear in mind the pressure losses induced by radiators, any thermostatic valves, radiator cut-off valves and the configuration of the system. In the boiler, onto a brass group, positioned between the flow and return, an automatic by-pass device is fitted (a differential valve with a flow rate of about 150 l/h) which gua­rantees always minimum flow rate through the heat exchanger, also in the case, for instance, that all the thermostatic valves fit­ted on the radiators, are closed.
On boilers model: RTN 24 – CTN 24 F – RTFS 24 – CTFS 24 F the by-pass is automatic and pre-adjusted. On boilers model CTN 24 – CTFS 24 is pos­sible to adjust the by-pass by acting onto
the adjusting screw
We recommend that the discharge of the safety valve mounted in the boiler be con­veyed into the sewer.
If this precaution is not taken, activation of the safety valve may result in flooding of the room where the boiler is installed.
UNICAL shall not be held responsible for damage caused by non-observance of this technical precaution.
D.H.W.
Inlet and outlet of D.H.W. must be connected to the relevant ½” connections of the boiler F and C (see fig. 9). The hardness of the supply water affects the frequency of the cleaning of the heat exchanger.
For the lower connections po­sitioning, see the mounting jig of figure 9
25
Installation info
fig. 23
EVE 05 RTN 24 - EVE 05 RTFS 24
EVE 05 CTN 24 F - EVE 05 CTFS 24 F
EVE 05 CTN 24 - EVE 05 CTFS 24
6,2 6,0 5,8 5,6 5,4 5,2 5,0 4,8 4,6 4,4 4,2 4,0 3,8 3,6 3,4 3,2 3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8 0,6 0,4 0,2
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
1250 1300 1350
1400
V1
V2
V
3
6,2 6,0 5,8 5,6 5,4 5,2 5,0 4,8 4,6 4,4 4,2 4,0 3,8 3,6 3,4 3,2 3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8 0,6 0,4 0,2
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
1250 1300 1350
1400
V1
V2
V
3
6,2 6,0 5,8 5,6 5,4 5,2 5,0 4,8 4,6 4,4 4,2 4,0 3,8 3,6 3,4 3,2 3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8 0,6 0,4 0,2
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
1250 1300 1350
1400
V1
V2
V
3
DIAGRAM FLOW RATE/MANOMETRIC HEAD AVAILABLE FOR THE CH SYSTEM
Manometric Head available in m W.G.
Flow rate Q (l/h)
Manometric Head available in m W.G.
Flow rate Q (l/h)
Manometric Head available in m W.G.
Flow rate Q (l/h)
Note: The boiler is delivered with the by-pass in OPEN position.
= By-Pass CLOSED
- - - - - - - - = By-Pass OPEN
26
Installation info
2.2.14 - ELECTICAL CONNECTIONS
The electrical connections of EVE 05 are shown in the clause ‘’WIRING DIAGRAMS’’ (par. 2.3 - pag. 29)
The boiler must be connected to the mains supply at 230 V - 50 Hz. This connection is to be perfectly done, as foreseen
by the IEC and local rules and must be earthed. This fundamental requirement for safety pur­poses must be checked; in case of doubt, ask for a professionally qualified technician to check the electrical system. UNICAL disclaims all liability for damage or injury caused by failure to earth the system properly.
Gas, domestic water and central heating pipes are not suitable for earthing purpo­ses.
The boiler is supplied with 1.5 m long 3 x 0.75 mm² cord. A double pole switch with a distance between the contacts higher than 3 mm, must be ins­talled upstream the boiler to enable all main­tenance operations to be carried out safely.
Access to the electrical terminal strip
- WARNING! Switch off the electrical sup­ply
- Remove the securing screws B in order to rotate the control panel
- Remove the casing.
- To get access directly to the connections, unscrew the 4 screws on the panel cover (CP) and remove the cover.
Replacement of the electrical supply cord
The replacement of the electrical supply cord has to be done by competent technical
personnel.
Should the electrical supply cord be repla­ced, you have to use the original cable code
95600259.
M1
CP
A
fig. 24
B
B
- Open the rear cover (CP) and replace
the cable A (connector A7)
The female faston of the hearting cable has to be connected on the male faston
GND 1
Connection of the ON/OFF room thermostat (RT)
- Approach the connector M1.
- Remove the existing jumper and connect, on its place the room thermostat cable.
Collegamento ad un bollitore esterno
It is necessary to make the electrical connection as indicated.
The diverting valve has to be fitted with the priority to the DHW circuit and the microwitch, whose its motor must to be equipped, has to be closed once the DHW has been satisfied and the valve is retourned in the normal position.
The microswitch contacts C. and N.C. have to be connected to the two pole terminal block (TA), fitted on the boiler panel board, after removal of the existing link (bridge - shunt).
The connection of a room thermostat will be done onto the same terminals, in parallel with the contacts of the diverting valve.
2.2.15 - JUMPER LOCATION
They are placed on the modulation card and their purpose is to settle basic operational functions. In order to get access to the jumper:
- WARNING! switch off electrical supply.
- Remove the casing.
JP1: For nat. gas boilers, the jumper is on
NAT. For LPG boilers, the jumper is on LPG.
The boilers operating with natural gas will at­tempt the ignition for 3 times before to be put in lock-out. The boilers operating with LPG will be put in
lock-out after a single ignition attempt.
LPG
JP1
NAT
LPG
NAT
230V / 30-65°C
Boiler
thermostat
3 Way motor 230V with
internal micr oswi tc h
Boiler panel board
TA terminal block
27
Installation info
2.3 WIRING DIAGRAM
2.3.1 ACTUAL WIRING DIAGRAM
fig. 25
LEGENDA
A1...A8 = Connectors
TA = Room thermostat (optional)
VG = Gas valve
RIV/AC = Ignition/Ionisation electrode
V = Fan (only for TFS)
PV = Fan pressure switch (only for TFS)
TL = H.L. Thermostat
TF = Flue-gas spillage thermostat
P = Circulating pump
DK = Minimum water pressure switch
SR = C.H. sensor
FL = Flow switch
SS = Rotary flow switch (only for CTN-CTFS)
MVD = Motor 3 way valve (optional for only heating boiler).
MD = Modulating coil
MD – MODULATING COIL
DK – MINIMUM WATER PRESSURE
SR – C.H. TEMPERATURE SENSOR
TA – ROOM THER MOSTAT
TF – FLUE GAS SPILLAGE THERMOSTAT
TL – HIGH LIMIT THERMOSTAT
PV – FAN PRESSURE SWITCH
TL – HIGH LIMIT THERMOSTAT
FL = Flow switch
SS = DHW sen sor
MDV – MOTOR 3 WAY VALVEGREEN
V – FAN
MAIN SUPPLY
230V-50HZ
P – PUMP
IONISATION IGNITION ELECTROD
GAS VALVE
- 1/4 W
28
Installation info
Example: At 25°C, the nominal resistance is 10067 Ohm
At 90°C, the nominal resistance is 920 Ohm
Relation between the temperature (°C) and nominal resistance (Ohm) of the heating sensor SR and D.H.W. sensor SS
TABLE OF RESISTANCE VALUES AS A FUNCTION OF THE TEMPERATURE OF THE HEATING SENSOR (SR) AND D.H.W. SENSOR (SS) with a nominal resistance of ten kOhm
T°C0123456789
0 32755 31137 29607 28161 26795 25502 24278 23121 22025 20987 10 20003 19072 18189 17351 16557 15803 15088 14410 13765 13153 20 12571 12019 11493 10994 10519 10067 9636 9227 8837 8466 30 8112 7775 7454 7147 6855 6577 6311 6057 5815 5584 40 5363 5152 4951 4758 4574 4398 4230 4069 3915 3768 50 3627 3491 3362 3238 3119 3006 2897 2792 2692 2596 60 2504 2415 2330 2249 2171 2096 2023 1954 1888 1824 70 1762 1703 1646 1592 1539 1488 1440 1393 1348 1304 80 1263 1222 1183 1146 1110 1075 1042 1010 979 949 90 920 892 865 839 814 790 766 744 722 701
2.5 - STARTING THE BOILER
PRELIMINARY CHECKS
Before starting the boiler check that:
- the boiler installation has been made in
accordance with all the applicable regu­lations concerning water and gas instal­lation, smoke evacuation and electrical installation
- the flue gas exhaust duct and its terminal
are installed correctly: when the boiler
FILLING TAP
is switched on there must be no le­akage of any combustion products from any seals;
- the supply voltage of the boiler is 230 V­50 Hz;
- the system is correctly filled with water (pressure at the gauge 0.8/1 bar);
- any gate valves taps of the system are open;
- the mains gas corresponds to that with which the boiler has been calibrated: otherwise, convert the boiler to use the gas available (see section: “MODIFICA­TION FOR OTHER GASES “): this ope-
ration must be performed by quali­fied technicians;
- the gas supply tap is open;
- there are no gas leaks;
- the external mains switch is on;
- the boiler’s safety valve is not locked;
- there are no water leaks.
SWITCHING ON AND OFF
To switch on and off the boiler follow the indications in the “Users’ Instructions”.
Filling position
fig. 26
Normal posi­tion
FILLING TAP
2.4 -FILLING THE SYSTEM
After completing all the connections of the system the heating circuit can be filled. This filling operation must be performed with care as follows:
- open the air vents of the radiators and
check that the automatic air vent in the boiler is works properly;
- gradually open the water tap and check
operation of any automatic air vents in­stalled in the system;
- close the air vents on the radiators as
soon as water comes out;
- use the pressure gauge on the boiler to
check that the pressure has reached the value of 0.8/1bar;
- close the water inlet tap and then release
the air again through the radiator air ven­ts;
- after switching on the boiler and after the
system has reached the correct tempe­rature, stop the pump and repeat the air relief operations;
- let the system cool down and then adjust
the water pressure to 0.8/1 bar.
WARNING
NB: After a given period of inactivity and without electri­cal supply the pump could be
blocked. Before switching on the boiler it is important to restart the pump as follows: loosen the protection screw in the centre of the pump motor, insert a screwdriver in the hole and then manually rotate the pump shaft clockwise. Once the pump has been restarted tighten the protection screw and check that there are no water leaks.
WARNING
Once the protection screw has been remo­ved a little water may leak out. Before repla­cing the casing of the boiler dry any wet surfaces.
The minimum water pressure switch does not give electrical impulse to the burner to ignite when the pressure is lower than 0.4 bar. The pressure of the water in the C.H. system must not be lower than 0.8/1bar; if this value is lower use the water filling tap on the boiler to adjust the pressure. This must be performed when the system is cold. Use the pressure gauge on the boiler to read the pressure value of the circuit.
29
Adjustment info
°C
°C
Outlet pressure test nipple
fig. 27
2.6 - ADJUSTING THE
BURNER
All the instructions below are for the exclusive use of qualified technicians. All the boilers leave the factory calibrated and tested. If it is necessary to change the calibration fol­lowing changes in the type of gas or adapta­tion to the supply network conditions, it is necessary to recalibrate the gas valve. WARNING: During these steps do not draw Domestic Hot Water. For that reason it is necessary to know the boiler operation in chimney-sweeper mode. In order to activate this function, push and keep depresses the reset push button for 3 seconds, on the control panel, then push once again the same button: the display symbols “F” and “L” will be lighted (F: blink­ing – L: fixed) and the boiler will operate at the maximum capacity. By pushing again the reset push button: the display symbols “F” and “L” will be lighted (F: blinking – L: blinking) and the boiler will operate at the minimum capacity. The chimney sweeper function remains active for 15 minutes. For cleaning this function before this fixed
period, switch OFF and ON the boiler.
To correctly regulate the gas valve, follow the steps below:
1) Maximum output adjustment
- check the value of the supply pressure (see
table NOZZLES - PRESSURES);
- Remove the cover (A) protecting the pres-
sure regulator on the top of the modulat­ing coil.
Connect a manometer at the outlet gas pressure test nipple (fig. 28).
Activate the chimney sweeper function to the maximum capacity (“F” blinking; “L” fixed); when the burner is ignited, check that the “MAXIMUM” pressure value cor­responds to that indicated on the table
“NOZZLES - PRESSURES”:
- Correct eventually the value rotating the
nut “C” with a 10 mm wrench (fig. 28); by rotating clockwise, the gas pressure increases, anticlockwise the gas pressure is reduced.
2) Minimum output adjustment
- Push a second time the reset push button
and the boiler will operate at the minimum capacity (both leds F and L will blink).
- When the burner is ignited, check that the
MINIMUM pressure value corresponds to that indicated on the table “NOZZLES – PRESSURES, etc.
- Correct, eventually, the value rotating the
red screw “B” with a cross-screw driver or a 6 mm wrench (fig. 28): by rotating clockwise the gas pressure increases, by rotating counter clockwise the gas pres­sure decreases
GAS VALVE
A
CHIMNEYSWEEPER ACTIVATION
OPERATION AT THE MAXI­MUM CAPACITY
OPERATION A T THE MINI­MUM CAPACITY
Push the reset push button for 3 seconds
Push again the reset push button; the symbol “F” (Cen­tral Heating) blinks, the sym­bol “L” (burner in operation) is fixed.
Push again the reset push button; the symbol “F” (Cen­tral Heating) and the symbol “L” (burner in operation) are both blinking
fig. 28
F
L
F
L
Inlet pressure test nipple
B = Screw (red) for minimum pressure adjustment
C = Adjust­ment nut (10 mm) for maximum pressure
3) Ending of basic adjustings
- check the minimum and maximum pres­sure values of the gas valve;
- if necessary make any fine adjustments
- Clear the chimneysweeper function by cut-
ting off the voltage.
- Remove the plastic pipe from pressure test nipple and close the inner screw;
- Using a soapy solution check for gas
leaks.
PRESSURE TEST NIPPLE
fig. 29
30
Adjustment info
fig. 30
1
EVE 05 CTN 24 F - EVE 05 CTN 24 - EVE 05 RTN 24
Tipe of gas
Output
min. - max
(kW)
Input
min. - max
(kW)
Supply
pressure
(mbar)
No. of
Nozzles
Ø
Diaphragme
(mm)
Natural gas(G20)
Propan (G31)
10,17 - 24,0
10,17 - 24,0
11,5 - 26,5
11,5 - 26,5
20
37
12
12
Ø
Nozzles
(mm)
-
-
EVE 05 CTFS 24 F - EVE 05 CTFS 24 - EVE 05 RTFS 24
9,9 - 24,2
9,9 - 24,2
11,5 - 26,5
11,5 - 26,5
20
37
12
12
-
-
1,25
0,80
2,7
6,2
13,3
33,0
1,22 m³/h
0,89 kg/h
2,80 m³/h
2,06 kg/h
1,30
0,80
2,3
6,2
12,0
33,0
1,22 m³/h
0,89 kg/h
2,80 m³/h
2,06 kg/h
Gas nat. (G20)
Propano (G31)
fig. 31
JP1: For nat. gas boilers, the jumper is
on NAT. For LPG boilers, the jumper is on LPG.
LPG
JP1
NAT
LPG
NAT
The pressures at the burner indicated in the following table must be checked after the boiler has been operating for 3 minutes.
NOZZLES - PRESSION - DIAPHRAGME - CONSUMPTION TABLE
max.
min.
(mbar)
max
(mbar)
min.
Burner pressure
Tipe of gas
Supply
pressure
(mbar)
No. of
Nozzles
Ø
Diaphragme
(mm)
Ø
Nozzles
(mm)
min.
(mbar)
max
(mbar)
Burner pressure
2.7 - MODIFICATION FOR OTHER GASES
The boilers are manufactured for the type of gas specifically required upon order. Any subsequent conversion must be perfor­med by qualified technicians who will use the kits supplied by Unical and perform the con­version and required adjustments for correct preparation of the boiler for use. To convert the boiler from one type of gas to another proceed as follows:
for conversion from natural gas to LPG
- remove the main burner;
- disassemble injectors of the main burner
and replace them with those with a diame­ter corresponding to the new type of gas (see table “INJECTORS - PRESSURES”);
- reassemble the main burner;
- position the jumper on the modulation PCB
in the panel board as shown in fig. 31
- remove plug ‘’A’’ (fig.28) on the gas valve
and fully tighten max pressure adjustment screws ‘’B’’
- check the pressure value upstream the gas
valve (see table “INJECTORS - PRESSU­RES”) and adjust the pressure of the bur­ner as indicated in section “ADJUSTING THE BURNER”
- check that the burner is functioning pro-
perly;
- check that there are no gas leaks.
- tighten the plug ”A” (fig.28) of the max
pressure adjustment screw
- when the conversion is completed, fill in
the label supplied in the kit with the infor­mation required and stick it onto the boiler alongside the data plate.
for conversion from LPG to natural gas
- remove the main burner;
- disassemble injectors of the main burner and replace them with those with a diame­ter corresponding to the new type of gas (see table “INJECTORS - PRESSURES”);
- reassemble the main burner;
- position the jumper on the modulation PCB in the panel board as shown in figure 31;
- remove plug ‘’A’’ (fig.28) on the gas valve
- check the pressure value upstream the gas valve (see table “INJECTORS - PRESSU­RES”) and adjust the burner pressure as indicated in section “ADJUSTING THE BURNER”;
- check that the burner is functioning pro­perly;
- check that there are no gas leaks.
- tighten the plug “A” (fig.28) of the max pressure adjustment screw;
- when the conversion is completed, fill in the label supplied in the kit with the infor­mation required and stick it onto the boiler alongside the data plate.
Gas
consumption
max.
min.
Gas
consumption
Output
min. - max
(kW)
Input
min. - max
(kW)
31
Service info
2.8 FAILURE CODES
In case of failure the burner is automatically deactivated and the symbol on the display is shown. By pushing the reset button the failure blinking code is shown on the display. Each fault is characterised by a priority level : if different failures are detected at the same time,
the code with the highest priority level is shown. The following failure codes are recognised:
2.10.1 Lock-out (priority 1)
Description: Modureg coil interrupted
Possible solution: verify the wiring, replace the modureg
2.10.2 Lock-out (priority 2)
Description: Fault at the fan pressure switch
Possible solution: Verify the fan pressure switch (TFS version) and the electric connections or replace the main PCB.
2.10.3 High temperature (priority 3)
Description: Overheating of the boiler
Possible solution: verify the correct operation of the pump and, eventually, descale the heat exchanger .
2.10.4 Difficult smoke evacuation (priority 4)
Description: Difficult smoke evacuation
Possible solution: TN boilers: verify the chimney draught, or the smoke thermostat. TFS boilers: verify the fan and its own pressure switch operations.
2.10.5 Lack of water (priority 5)
Description: Insufficient water pressure: intervention of minimum water pressure switch.
Possible solution: Set the water pressure by the filling valve and look for possible leakages. If the code appears again, call the service technician.
2.10.6 FROST (priority 6)
Description: Freezing of the heat exchanger is detected if CH sensor < 2°C; ignition in inhibited until CH sensor reaches 5°C.
Possible solution: Cut off the voltage, close the gas feeding, call the service technician.
2.10.7 High Limit thermostat (priority 7)
Description: High limit thermostat intervention
Possible solution: Verify the water circulation into the heat exchanger; verify that the high limit thermostat and its
own connections are not interrupted
°C
°C
°C
°C
°C
°C
°C
32
Service info
°C
2.10.8 Sanitary sensor (priority 8)
Description: Sanitary temperature sensor intervention
Possible solution: verify the sensor operation and its own connections
2.10.9 Heating sensor (priority 9)
Description: Heating temperature sensor intervention Possible solution: verify the sensor operation and its own connections
2.10.10 Factory parameters (priority 10)
Description: Factory parameters alteration
Possible solution: with the access code, reset the 13 factory parameters
2.10.11 Flame control (priority 1 1)
Description: Burner control is damaged.
Possible solution: replace the main PCB.
2.10.12 Lock-out
Description: Lack of gas or burner ignition not detected
Possible solution: verify the gas feeding and the correct operation of the ignition electrode
°C
°C
°C
The tool blinks, by pushing the reset push button no failure codes are displayed.
33
Service info
fig. 34
EVE 05 CTN 24 F - EVE 05 CTN 24 F- EVE 05 CTFS 24 F - EVE 05 CTFS 24
EVE 05 RTN 24 - EVE 05 RTFS 24
A = Manometer B = Summer / Winter switch + C.H. tempe-
rature control
C = D.H.W. temperature control (only for
combi C version)
D = Reset button / chimney sweeper
/ diagnostics
F = CH mode active G = DHW mode active I = Lock out
L = Burner in operation M = Failure N = Temperature or failure code indication
Summer/Winter switch + C.H. temperature control (B)
You can select which mode to use by turning this knob.
If the knob is in the following po­sition – – it indicates that the boiler is working only for do­mestic hot water production and that the temperature can be adju­sted turning knob ''C''.
If the knob is set within the ran­ge indicated by the arrow on the illustration it means that the boi­ler always gives priority to the pro­duction of domestic hot water (if it is requested) and controls the temperature of the water of the
heating circuit from a minimum of 45°C to a maximum of 78°C.
D.H.W. temperature control (C) (Only for EVE 05 CTN 24 F - EVE CTFS 24/28 F)
If the knob is set within the ran­ge indicated by the arrow on the illustration it means is possible to adjust the domestic hot water temperature. The temperature can be controlled from a minimum of 35°C to a maximum of 57°C.
By adjusting the Domestic Hot Water temperature to the real required temperature, you will avoid to mix hot
BD ACE
BD AE
MAX
M
I
N
MAX
M
I
N
water with cold water, in this way reducing both the boiler operation costs and the scaling formation.
MAXMIN
fig. 35
°C
F G
L
I
M
°C
®
MAX
MAXMIN
M
I
N
EVE
05
°C
®
MAX
MAXMIN
M
I
N
EVE
05
N
USERS' INSTRUCTION
3.1 - CONTROL PANEL
3
34
Service info
Reset push button
In order to restart the boiler when the lockout symbol is displayed, it will be necessary to
push this button.
Chimney sweeper button
This push button, depressed for 3 seconds, activates the chimney sweeper function: the boiler will be forced to operate at the maximum (or minimum) capacity, in order to allow the gas valve adjustment and the smoke analysis.
When this function is activated, by pushing this button once, the boiler will operate at maximum capacity . The radiator symbol will be blinking, while the flame symbol will be permanently lighted.
By pushing again the button (when the boiler is set to the maximum capacity), the boiler will operate at minimum capacity. The radiator and the flame symbols, both, will be blinking.
In order to clear this function switch OFF and ON the boiler; if not, the boiler will revert to nor­mal operation after 15 minutes.
3.2 SWITCHING ON / OFF
For the operation of the boiler in WINTER mode, the knob “B” pointer must be positio­ned in the grey range indicated by the arrow on the figure shown above. The limit of the arrow corresponds to the minimum and maximum temperature values of 45°C and 78°C.
Note: If a room thermostat is fitted, set it to the desired temperature.
SWITCHING ON
D.H.W. temperature adjust­ment range for the models:
EVE 05 CTN/CTFS
C
B
B
SWITCHING OFF
Put the “B” knob on the SUN position and the “C” knob to the minimum. Switch OFF the boiler by acting on the external main switch, provided the antifrost protection is not required; otherwise go to 3.3.
For the operation of the boiler in SUMMER mode, only for domestic hot water production, the knob ''B'' reference has to be positioned on the SUN and the D.H.W. temperature value has to be adjusted using the knob ''C''.
Shut OFF the gas cock upstream the boiler in case a prolonged inac­tivity period of the boiler is ex­pected.
Burner in operation
This symbol indicates that the burner is in operation, in CH or DHW mode.
CH mode operation
This symbol is present if there is a CH demand. If a contemporary DHW drawing is done, this sym-
bol disappears.
DHW mode operation
This symbol is present if there is a DHW drawing.
Lockout symbol
The function of this symbol is to indicate the burner safety inter­vention, due to:
- lack of gas
- not detected ignition In the first case, no ignition oc­curs: verify that the gas feeding is present. In the second case, check the ignition electrode and the con­nections to the main PCB.
°C
°C
CHIMNEY SWEEPER AT THE MAXIMUM CAPACITY
CHIMNEY SWEEPER AT THE MINIMUM CAPACITY
Failure symbol
The symbol is displayed when the boiler detects an operation anomaly or when the boiler is in lock-out for a permanent failure. The code iden­tifying the cause is displayed instead of the boiler temperature by pushing the reset push-button.
MAX
M
I
N
MAX
M
I
N
MAXMIN
35
Maintenance info
The boiler is fitted with an anti-freeze system which is automatically activated when the tem­perature of the boiler water drops below 6°C: the burner is automatically switched on and the pump started until the temperature of the water in the boiler reaches 16°C.
3.3 ANTI FROST PROTECTION
B
C
WARNING!
This anti-freezing protection does not work when the boiler is disconnected from the electrical supply and/or the gas cock is closed.
This system protects the boiler and the even­tual DHW tank from freezing, but it does not protect the C.H. and sanitary circuits. Moreover special anti-freeze products suita­ble for the multimetal installations can effecti­vely protect the heating system from the free­ze.
Do not use the anti-freeze products for car's engines because they can damage the water sealing gaskets.
The anti-freeze protection system, which is above described, can not work when, for any reasons, there is no electricity or gas supply.
When the temperature detected by the heat­ing sensor is under 2 °C, the boiler's operation is automatically inhibited until the temperatu­re raises again to 5 °C.
In case the display shows the wrenck symbol and thr Fr info on the display , call the service
technician.
MAX
M
I
N
MAXMIN
°C
3.4 IMPORTANT SUGGESTIONS AND NOTES
The boiler must be serviced once a year by qualified personnel.
Correct maintenance allows the boiler to work optimally, respecting the environment and without endangering people, animals and pro­perty.
Only qualified and technical personnel can make adjustment onto the gas valve.
Nobody, included qualified personnel, is authorized to make modifications to the boiler.
Check regularly the pressure of the boiler wa­ter through the pressure gauge fitted onto the panel board, and restore it, if necessary.
If some fault appears during the operation, the boiler is automatically put in lockout position and the red warning lamp (G) lights. In this case proceed as follows:
- Ascertain that the gas cock is open and that
there is gas in the gas pipe (try to ignite a gas cooker)
- If so, wait one minute before resetting the
boiler by depressing the L push button. If the boiler does not start and goes into lockout position after three times, (just once if is ope­rated on LPG) ask for a service or for a qualified technician.
If the boiler goes into lockout position frequently, indication of a repeatetive fault in the operation, ask for a service or for a qualified technician
WARNING In case of an open flue boiler (TN) the burner lockout can be due to the intervention of the
smoke thermostat (antispillage thermostat). In this case to restart the boiler it is necessary to depress the reset push button L. This fault, if repeated in the time, means a bad chimney operation. Ask a qualified technician for a check.
If the boiler remains inactive and disconnected from the power supply for long periods it may be necessary to unlock the pump.
This operation, for which it is necessary to disassemble the outside casing and work on the inside of the boiler, must be performed by qualified personnel.
It is possible to prevent the pump from blocking by adding special filming products suitable for multi-metal systems to the water.
If the boiler is not disconnected from the mains power supply the pump will not block becau­se the boiler’s PCB has an anti-jamming pro­gramme. In this case the pump goes into ope­ration for a 5 seconds every 24 hour of inacti­vity.
The boiler is equipped with a pressure gauge which allows the control of the water pressure in the heating system.
The pressure of the water must be around
0.8-1 bar when the C.H. system is cold.
If this value drops then use the filling cock to adjust to the correct value.
WARNING
The anti-frost protection is ope­rational only if the boiler is con-
WARNING
After adjusting the pressure, clo-
se the tap without over-tightening it. If the tap is not closed properly the pressu­re could rise, resulting in the safety valve ope­ning and the water leaking.
nected to the mains supply and the gas cock is open
Information for the user The user can get access only to the parts of the boiler which can be reached without the need of tools. It is therefore forbidden to disassemble the outer casing of the boiler and tamper with the internal parts.
AG S.P.A.
46033 casteldario - mantova - italia - tel. 0376/57001 (r.a.) - telefax 0376/660556
The Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to bring those changes that it will hold necessary to it own products or profits, without jeopardizing its essential characteristics.
Loading...