Unical ENERPUMP DHW 72, ENERPUMP DHW 97, ENERPUMP DHW 110, ENERPUMP DHW 143, ENERPUMP DHW 173 Installation And Service Manual

Page 1
Luxury Air Source Heat Pump
Monobloc system
- Installation and Service Manual -
Heating/Cooling/Domestic Hot Water Heating/Cooling
ENERPUMP DHW 72 ENERPUMP RK 72
ENERPUMP DHW 97 ENERPUMP RK 97
ENERPUMP DHW 110 ENERPUMP RK 110
Page 2
TABLE OF CONTENT
INTRODUCTION ………………………………………………………………………………………………………………. 3
General information …………………………………………………………………………………………………………………….. 3 Model identification …………………………………………………………………………………………………………………….. 3 Items inside product box ……………………………………………………………………………………………………………… 4 Cycle diagram: ENERPUMP DHW 72 (97)(110)……………………….…………………………………………….………. 6 Cycle diagram: ENERPUMP DHW 143 (173)………………………………………………………………………….………. 7 Cycle diagram: ENERPUMP RK 72 (97)(110)………………………………………….………………………………………. 8 Cycle diagram: ENERPUMP RK 143 (173)………………………….………………………………..…………………………. 9
SAFETY PRECAUTIONS …………………………………………………………………………………………………………….. 10
Warning ………………………………………………………………………………………………………………………………………. 10 Caution ……………………………………………………………………………………………………………..………………………… 11
OVERVIEW OF THE UNIT ………………………………………………………………………………..………………….…….. 13
External view: ENERPUMP DHW 72 (97) and ENERPUMP RK 72 (97) ……………………………………………. 13 Internal view: ENERPUMP DHW 72 (97) and ENERPUMP RK 72 (97).……………………………………………. 14 External view: ENERPUMP DHW 110 and ENERPUMP RK 110……………………………………………………….. 15 Internal view: ENERPUMP DHW 110 and ENERPUMP RK 110……………………………………………………….. 16 External view: ENERPUMP DHW 143 (173) and ENERPUMP RK 143 (173) ……………………………………. 17 Internal view: ENERPUMP DHW 143 (173) and ENERPUMP RK 143 (173)……………………..……………... 18
CONTROL PARTS …………………………………………………………………………………………………………………….. 19
Control panel ………………………………………………………………………………………………………………………………. 19 Wiring diagram: ENERPUMP DHW 72 (97)……………………………………………………………………………………. 20 Wiring diagram: ENERPUMP DHW 110………..………………………………………………………………………………. 21 Wiring diagram: ENERPUMP DHW 143 (173)………………………………………………………………….……………. 22 Remarks for ENERPUMP DHW version ……………….………………………………………………………….……………. 23 Wiring diagram: ENERPUMP RK 72 (97)……………………………………………………………………..……..…………. 24 Wiring diagram: ENERPUMP RK 110………..……..…………………………………………………………..…….…………. 25 Wiring diagram: ENERPUMP RK 143 (173)………………………………………………..…………………………………. 26 Remarks for ENERPUMP RK version ……………….……………………………………………………………………………. 27
INSTALLATION OF THE UNIT ……………………………………………………………………………..…………… 28
Installation guidelines ………………………………………………………………………………………………………………… 28
Precautions for selecting the location …………………………………………………………………………………… 28 Selecting a location in cold climates ……………………………………………………………………………………… 28
Installation space ………………………………………………………………………………………………………………….. 29 Mounting the unit …………………………………………………………………………………………………………………………. 29 Water pipe work ……………………………………………………………………………………………………………………………. 30
Checking the water circuit ………………………………………………………………………………………………………. 30
Checking the water volume and expansion vessel pre-pressure ……………………………………………. 31
Calculating the pre-pressure of the expansion vessel ……………………………………………………………. 31
Checking the maximum allowed water volume ……………………………………………………………………… 31
Setting the pre-pressure of the expansion vessel …………………………………………………………………… 32
Connecting the water circuit …………………………………………………………………………………………………… 32 Charging water ………………………………………………………………………………………………………………………………. 33
Luxury Air Source Heat Pump-Monobloc System
1
Page 3
Piping insulation …………………………………………………………………………………………………………………………….. 33 Field wiring …………………………………………………………………………………………………………………………………….. 34
SYSTEM SET-UP ………………………………………………………………………………………………………………. 35
DIP Switch Setting …………………………………………………………………………………………………………………………. 35 Pre-operation Checks ……………………………………………………………………………………………………………………. 38
Checks before initial start-up …………………………………………………………………………………………………. 38
Setting the pump speed …………………………………………………………………………………………………………. 39
MAINTENANCE …………………………………………………………………………………………………..…………… 40 TROUBLESHOOTING …………………………………………………………………………………………………………………. 41
General guidelines ………………………………………………………………………………………………………………………… 41 General symptoms ………………………………………………………………………………………………………………………… 41
Error codes ………………………………………………………………………………………………………………………………….... 43
TECHNICAL SPECIFICATION ………………………………………………………………………………………………………. 46 TEMPERATURE SENSOR R-T CONVERSION TABLE………………………………………………………….. 48 Logbook for F gases…………………………………………..…………………………………………………………….49
READ THIS MANUAL CAREFULLY BEFORE STARTING UP THE UNIT. DO NOT THROW IT AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
BEFORE OPERATING THE UNIT, MAKE SURE THE INSTALLATION HAS BEEN CARRIED OUT CORRECTLY BY A PROFESSIONAL DEALER. IF YOU FEEL UNSURE ABOUT OPERATION, CONTACT
YOUR DEALER FOR ADVICE AND INFORMATION.
Luxury Air Source Heat Pump-Monobloc System
2
Page 4
INTRODUCTION
This manual
This manual includes the necessary information about the unit. Please read this manual carefully before you use and maintain the unit.
General information
The luxury air source heat pump monobloc system consists out of only the outdoor unit in which all hydraulic parts are located. In this system no refrigerant lines need to be connected which makes the installation easier for the domestic installer. These units are used for both heating and cooling applications. The unit can be combined with fan coil units, floor heating, low temperature radiators, and the domestic hot water tanks.
The unit range consists out of two main versions: a heating/cooling/domestic hot water version and a heating/cooling version.
Both versions can optionally be delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of the outdoor unit. The backup heaters are available in different capacities.
Domestic hot water tank option
An optional domestic hot water tank with integrated electrical booster heater can be connected to the indoor unit. The domestic hot water tank is available in different sizes.
Luxury Air Source Heat Pump-Monobloc System
3
Page 5
Items inside product box
Thank you for choosing the luxury air source heat pump- Monobloc system. Before starting installation, please make sure that all parts are found inside the product box.
The Unit Box
Item Image Quantity
ENERPUMP DHW 72
ENERPUMP RK 72
ENERPUMP DHW 97
ENERPUMP RK 97
1
ENERPUMP DHW 110
ENERPUMP RK 110
ENERPUMP DHW 143
ENERPUMP RK 143
ENERPUMP DHW 173
ENERPUMP RK 173
Installation and Service
Manual
1
1
1
Operation Manual
Luxury Air Source Heat Pump-Monobloc System
1
4
Page 6
Cycle diagram
As the luxury air source monobloc unit is an air to water heat pump, there are two different fluids cycling
inside the system, one is refrigerant and the other is water. The whole cycle diagram is shown below.
Heating/Cooling/Domestic Hot Water version:
Luxury Air Source Heat Pump-Monobloc System
5
Page 7
Model: ENERPUMP DHW 72 , ENERPUMP DHW 97 and ENERPUMP DHW 110
Luxury Air Source Heat Pump-Monobloc System
6
Page 8
Model: ENERPUMP DHW 143 and ENERPUMP DHW 173
Luxury Air Source Heat Pump-Monobloc System
7
Page 9
Heating/Cooling version:
Model: ENERPUMP RK 72 , ENERPUMP RK 97 and ENERPUMP RK 110
Luxury Air Source Heat Pump-Monobloc System
8
Page 10
Model: ENERPUMP RK 143 and ENERPUMP RK 173
Luxury Air Source Heat Pump-Monobloc System
9
Page 11
SAFETY PRECAUTIONS
To prevent injury to the user, other people, or property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage.
Install the unit only when it complies with local regulations, by-laws and standards. Check the main voltage and frequency. This unit is only suitable for earthed sockets.
The following safety precautions should always be taken into account:
- Be sure to read the following WARNING before installing the unit.
- Be sure to observe the cautions specified here as they include important items related to safety.
- After reading these instructions, be sure to keep it together with the manual in a handy place for
future reference.
Do not install the unit yourself.
Incorrect installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or a specialized installer.
Install the unit securely in a place.
When insufficiently installed, the unit could fall causing injury. The minimum support weight of 20g/mm² of the installation place is required. When installing the unit in a small room, please take measures (like sufficient ventilation) to prevent the asphyxia caused by the leakage of refrigerant.
Use the specified electrical wires and attach the wires firmly to the terminal board (connection in such a way that the stress of the wires is not applied to the sections).
Incorrect connection and fixing could cause a fire.
Be sure to use the provided or specified parts for the installation work.
The use of defective parts could cause an injury due to possible fire, electric shocks, the unit falling etc.
Perform the installation securely and please refer to the installation instructions.
Incorrect installation could cause an injury due to possible fire, electric shocks, the unit falling, leakage of water etc.
Perform electrical work according to the installation manual and be sure to use a dedicated section.
If the capacity of the power circuit is insufficient or there is an incomplete electrical circuit, it could result in a fire or an electric shock.
The unit must always have an earthed connection.
If the power supply is not earthed, you may not connect the unit.
Luxury Air Source Heat Pump-Monobloc System
10
Page 12
Never use an extension cable to connect the unit to the electric power supply.
If there is no suitable, earthed wall socket available, have one installed by a recognized electrician.
Do not move/repair the unit yourself.
Improper movement or repair on the unit could lead to water leakage, electrical shock, injury or fire. Have any repairs and/or maintenance only carried out by a recognized service engineer.
Do not plug or unplug the power supply during operation
There is a risk of fire or an electric shock
Do not touch/operate the unit with wet hands
There is a risk of fire or an electric shock
Do not place a heater or other appliances near the power cable
There is a risk of fire or an electric shock
Be cautious that water could not be poured to the product directly, do not allow water to run into electric parts
There is a risk of fire or an electric shock
IF THE PRODUCT IS NOT USED FOR A LONG TIME, WE STRONGLY RECOMMEND NOT TO SWITCH ‘OFF’ THE POWER SUPPLY OF THE UNIT. IF THE POWER IS NOT SUPPLIED, SOME SPECIAL PRODUCT-PROTECTING ACTIONS (SUCH AS WATER PUMP ANTI-LOCKING) WILL NOT BE PERFORMED.
Do not install the unit in a place where there is a chance of flammable gas leaks.
If there is a gas leak and gas accumulates in the area surrounding the unit, it could cause an explosion.
Perform the drainage/piping work according to the installation instruction.
If there is a defect in the drainage/piping work, water could leak from the unit and household goods could get wet and be damaged.
Do not clean the unit when the power is ‘on’.
Always shut ‘off’ the power when cleaning or servicing the unit. If not, it could cause an injury due to the high speed running fan or an electrical shock.
Luxury Air Source Heat Pump-Monobloc System
11
Page 13
Do not continue to run the unit when there is something wrong or there is a strange smell.
The power supply needs to be shut ‘off’ to stop the unit; otherwise this may cause an electrical shock or fire.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Especially watch the edges and the fins on the heat exchanger of the product.
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of the product.
Keep level even when installing the product.
This is to avoid vibration or water leakage.
Do not put your fingers or others into the fan, or evaporator.
The ventilator runs at high speed, this could cause serious injury.
Luxury Air Source Heat Pump-Monobloc System
12
Page 14
OVERVIEW OF THE UNIT
External view: ENERPUMP DHW 72, ENERPUMP RK 72
ENERPUMP DHW 97, ENERPUMP RK 97
Luxury Air Source Heat Pump-Monobloc System
13
Page 15
Internal view: ENERPUMP DHW 72, ENERPUMP RK 72
ENERPUMP DHW 97, ENERPUMP RK 97
No. Description No. Description
1 Left front plate 17 Switch box
2 Air outlet grill 18 Water pump (RS15/6)
3 Fan motor 19 Four-way valve assembly
4 Fan 20 Water flow switch
5 Plate heat exchanger 21 Three-way valve (only for DHW version)
6 Fan motor holder 22 H/C OUT
7 Condenser 23 DHW OUT (only for DHW version)
8 Expansion vessel (10L) 24 Electronic expansion valve
9 Separated plate 25 H/C IN
10 Top plate 26 DHW IN (only for DHW version)
11 Pressure relief valve 27 Water filter
12 Air purge valve 28 Compressor
13 Right back plate 29 Connector holder
14 Manometer (refrigerant pressure) 30 Base plate
15 Manometer (water pressure) 31 Right front plate 1
16 Backup heater vessel (15L) 32 Right front plate 2
Luxury Air Source Heat Pump-Monobloc System
14
Page 16
External view: ENERPUMP DHW 110, ENERPUMP RK 110
Luxury Air Source Heat Pump-Monobloc System
15
Page 17
Internal view: ENERPUMP DHW 110, ENERPUMP RK 110
No. Description No. Description
1 Left front plate 19 Manometer (refrigerant pressure)
2 Air outlet grill 1 20 Manometer (water pressure)
3 Fan motor 1 21 Water pump (RS25/8)
4 Fan 1 22 Four-way valve assembly
5 Air outlet grill 2 23 Water flow switch
6 Fan motor 2 24 Three-way valve (only for DHW version)
7 Fan 2 25 H/C OUT
8 Fan motor holder 26 DHW OUT (only for DHW version)
9 Switch box 27 Electronic expansion valve
10 Condenser 28 H/C IN
11 Plate heat exchanger 29 DHW IN (only for DHW version)
12 Expansion vessel (10L) 30 Accumulator
13 Top plate 31 Connector holder
14 Separated plate 32 Compressor
15 Pressure relief valve 33 Water filter
16 Air purge valve 34 Base plate
17 Backup heater vessel (20L) 35 Right front plate 1
18 Right back plate 36 Right front plate 2
Luxury Air Source Heat Pump-Monobloc System
16
Page 18
External view: ENERPUMP DHW 143, ENERPUMP RK 143
ENERPUMP DHW 173, ENERPUMP RK 173
Luxury Air Source Heat Pump-Monobloc System
17
Page 19
Internal view: ENERPUMP DHW 143, ENERPUMP RK 143
ENERPUMP DHW 173, ENERPUMP RK 173
No. Description No. Description
1 Left front plate 19 Backup heater vessel (20L)
2 Air outlet grill 1 20 Switch box
3 Fan motor 1 21 Water pump (RS25/8)
4 Fan 1 22 Four-way valve assembly 5 Air outlet grill 2 23 Water flow switch
6 Fan motor 2 24 Three-way valve (only for DHW version)
7 Fan 2 25 H/C OUT
8 Fan motor holder 26 DHW OUT (only for DHW version)
9 Plate heat exchanger 27 Accumulator
10 Expansion vessel (10L) 28 Electronic expansion valve 11 Separated plate 29 H/C IN
12 Condenser 30 DHW IN (only for DHW version)
13 Top plate 31 Connector holder
14 Pressure relief valve 32 Compressor
15 Air purge valve 33 Water filter
16 Right back plate 34 Base plate 17 Manometer (refrigerant pressure) 35 Right front plate 1
18 Manometer (water pressure) 36 Right front plate 2
Luxury Air Source Heat Pump-Monobloc System
18
Page 20
CONTROL PARTS
Control Panel
1 2
7 3
5 4 6 8
15
9 13
11 14 12 10 17 16
No. Description No. Description
1 OPERATION LED 10 TEMPERATURE ADJUST BUTTON 2 COOLING/HEATING ‘ON’/’OFF’ BUTTON 11 DOMESTIC HOT WATER TEMPERATURE ADJUST
BUTTON (only for DHW version)
3 TIMER/ PROGRAMMING BUTTON 12 DOMESTIC HOT WATER TEMPERATURE ADJUST
BUTTON (only for DHW version) 4 HOUR ADJUST BUTTON 13 SPACE HEATING/COOLING BUTTON 5 DAY OF THE WEEK ADJUST BUTTON 14 DOMESTIC WATER HEATING BUTTON (only for
DHW version) 6 MINUTE ADJUST BUTTON 15 CLOCK SETTING BUTTON
7 TIME/TIMER ON ADJUST BUTTON 16 RESET BUTTON 8 TIME/TIMER OFF ADJUST BUTTON 17 TEMPERATURE CHECK BUTTON 9 TEMPERATURE ADJUST BUTTON
Luxury Air Source Heat Pump-Monobloc System
19
Page 21
WIRING DIRGRAM
Model: ENERPUMP DHW 72 and ENERPUMP DHW 97
(Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
20
Page 22
Model: ENERPUMP DHW 110 (Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
21
Page 23
Model: ENERPUMP DHW 143 and ENERPUMP DHW 173
(Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
22
Page 24
Remarks for heating/cooling/domestic hot water version:
-- For Two- way valve (B1 and B2) This function is reserved for two-way valve control. If an external two-way valve needs to be controlled by the heat pump system, you can use these ports according to their output signal. During space cooling mode, the ports (B1 and B2) will provide power 220-240V~ for use. During space heating or domestic hot water mode, no power is provided.
-- For Water Tank Electrical heating Driving Signal (C1 and C2) When connecting the electrical tank heater to C1 and C2, one extra contactor is needed. Please refer to below drawing.
-- For 0-10V Control
If the external controller gives a voltage control signal of 0 to +10V, the heat pump will produce water with different temperature according to a voltage-water temperature table. Once this control method is in force, the external signal will control the setting outlet temperature of space heating/cooling, the temperature setting of the wire controller is not in force anymore. This control signal is for space heating and space cooling modes.
-- For External Control
This is to connect an On/Off control signal. When the signal is on (closed), the Heat Pump can work. The running mode will be decided by the setting of the wired controller. If the signal is off (open), the Heat Pump can’t work. But if there is domestic hot water requirement the domestic hot water will not be affected by the external signal. It will always work as per the setting of wired controller of the heat pump.
-- For Buffer tank E-heater
The buffer tank electrical heater has three steps, each step is 2KW,
total 3*2=6KW.
The default setting is that:
The first is electric connected, the second and the third are electric
disconnected. The second and third are controlled by 2 switches
which marked with “step 2” and “step 3”.
“O” position means the relating step of the heater is OFF
“I” position means the relating step of the heater is ON
Luxury Air Source Heat Pump-Monobloc System
23
Page 25
Model: ENERPUMP RK 72 and ENERPUMP RK 97
(Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
24
Page 26
Model: ENERPUMP RK 110 (Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
25
Page 27
Model: ENERPUMP RK 143 and ENERPUMP RK 173
(Refer to the attached wiring diagram in the unit)
Luxury Air Source Heat Pump-Monobloc System
26
Page 28
Remarks for heating/cooling version:
-- For Two- way valve (B1 and B2) This function is reserved for two-way valve control. If an external two-way valve needs to be controlled by the heat pump system, you can use these ports according to their output signal. During space cooling mode, the ports (B1 and B2) will provide power 220-240V~ for use. During space heating or domestic hot water mode, no power is provided.
-- For 0-10V Control (A1 and A2)
If the external controller gives a voltage control signal of 0 to +10V, the heat pump will produce water with different temperature according to a voltage-water temperature table. Once this control method is in force, the external signal will control the setting outlet temperature of space heating/cooling, the temperature setting of the wire controller is not in force anymore. This control signal is for space heating and space cooling modes.
-- For External Control (C1 and C2)
This is to connect an On/Off control signal. When the signal is on (closed), the Heat Pump can work. The running mode will be decided by the setting of the wired controller. If the signal is off (open), the Heat Pump can’t work.
-- For Buffer tank E-heater
The buffer tank electrical heater has three steps, each step is 2KW,
total 3*2=6KW.
The default setting is that:
The first is electric connected, the second and the third are electric
disconnected. The second and third are controlled by 2 switches
which marked with “step 2” and “step 3”.
“O” position means the relating step of the heater is OFF
“I” position means the relating step of the heater is ON
Luxury Air Source Heat Pump-Monobloc System
27
Page 29
INSTALLATION OF THE UNIT
Installation guidelines
Precautions for selecting the location
MAKE SURE TO PROVIDE FOR ADEQUATE MEASURES IN ORDER TO PREVENT THAT THE OUTDOOR UNIT WILL BE USED AS A SHELTER FOR SMALL ANIMALS. SMALL ANIMALS MAKING CONTACT WITH ELECTRICAL PARTS CAN CAUSE MALFUNCTIONS, SMOKE OR FIRE. PLEASE KEEP THE AREA AROUND THE UNIT CLEAN.
1. Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise
will not be amplified.
2. Choose a location where the hot air discharged from the unit or the operation noise will not cause a
nuisance to the neighbors of the user.
3. Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4. There must be sufficient space for carrying the unit into and out of the site.
5. There must be sufficient space for air passage and no obstructions around the air inlet and the air
outlet.
6. Locate the unit so that the noise and the discharged hot air will not annoy the neighbors.
7. The site must be free from the possibility of flammable gas leakage in a nearby place.
8. Install units, power cords and inter-unit cables at least 3m away from television and radio sets. This
is to prevent interference to images and sounds.
9. Depending on radio wave conditions, electromagnetic interference can still occur even if installed
more that 3m away.
10. In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life
of the outdoor unit.
11. Since drain flows out of the outdoor unit, do not place anything under the unit which must be kept
away from moisture.
Selecting a location in cold climates
WHEN OPERATING THE OUTDOOR UNIT IN A LOW OUTDOOR AMBIENT TEMPERATURE, BE SURE TO FOLLOW THE INSTRUCTIONS DESCRIBED BELOW.
To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.
Never install the outdoor unit at a site where the suction side may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of the outdoor unit.
In heavy snowfall areas it is very important to select an installation site where the snow will not
affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is not affected by the snow (if necessary construct a lateral canopy).
Luxury Air Source Heat Pump-Monobloc System
28
Page 30
Installation space
Mounting the unit
When installing the outdoor unit, please refer to “Installation guidelines” to select an appropriate location.
1. Check the strength and level of the installation ground so that the unit will not cause any operating
vibration or noise after installation.
2. Prepare 4 sets of M8 foundation bolts, nuts and washers each (filed supply).
3. Fix the unit securely by means of the foundation bolts in accordance with the foundation drawing. It
is best to screw in the foundation bolts until their length remains 20mm above the foundation surface.
Luxury Air Source Heat Pump-Monobloc System
29
Page 31
Water pipe-work
Checking the water circuit
The 3-way valve is built-in the unit. So the unit is equipped with the water inlet/outlet for hot water connection, and the water inlet/outlet for space heating/cooling. The water circuits must be provided by a licensed technician and must comply with all relevant European and national regulations.
THE UNIT IS ONLY TO BE USED IN A CLOSED WATER SYSTEM. APPLICATION IN AN OPEN WATER CIRCUIT CAN LEAD TO EXCESSIVE CORROSION OF THE WATER PIPING.
Beforecontinuingtheinstallationoftheunit,checkthefollowingpoints:
The maximum water pressure is 6 bar.
Four shut-off valves are not delivered with the unit. To facilitate service and maintenance,
please install one at each water inlet/outlet. Mind position of the shut-off valves. Orientation of the integrated drain and fill valves is important for servicing.
Drain taps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance.
Make sure to provide a proper drain for the pressure relief valve to avoid any water coming into contact with electrical parts.
Air vents must be provided at all high points of the system. The vents should be located at points which are easily accessible for servicing. An automatic air purge is provided inside the indoor unit. Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible.
Take care that the components installed in the field piping can withstand the water pressure.
Luxury Air Source Heat Pump-Monobloc System
30
Page 32
Checking the water volume and expansion vessel pre-pressure
The unit is equipped with an expansion vessel of 10 liters which has a default pre-pressure of 1 bar. To assure proper operation of the unit, the pre-pressure of the expansion vessel might need to be adjusted and the minimum and maximum water volume must be checked.
1. Check that the total water volume in the installation is 32 L minimum.
IN MOST AIR CONDITIONING APPLICATIONS THIS MINIMUM WATER VOLUME WILL HAVE A
SATISFYING RESULT. IN CRITICAL PROCESSES OR IN ROOMS WITH A HIGH HEAT LOAD THOUGH, EXTRA WATER VOLUME MIGHT BE REQUIRED
2. Using the table below, determine if the expansion vessel pre-pressure requires adjustment.
3. Using the table and instructions below, determine if the total water volume in the installation is below the maximum allowed water volume.
Installation height difference (a)
Water volume
460 L
460 L
Actions required:
7 m
No pre-pressure adjustment Required.
pre-pressure must be decreased, calculate according to
“calculating the pre-pressure of the expansion vessel”
check if the water volume is lower than maximum
allowed water volume (use graph below)
Actions required:
pre-pressure must be increased,
> 7 m
(a) Installation height difference: height difference (m) between the highest point of the water circuit and the indoor unit. If the
indoor unit is located at the highest point of the installation, the installation height is considered 0 m.
calculate according to “calculating the
pre-pressure of the expansion vessel”
check if the water volume is lower than
maximum allowed water volume (use graph
below)
Expansion vessel of the unit too small for the installation.
Calculating the pre-pressure of the expansion vessel
The pre-pressure (Pg) to be set depends on the maximum installation height difference (H) and is calculated as follows: Pg = (H/10+0.3) bar
Checking the maximum allowed water volume
To determine the maximum allowed water volume in the entire circuit, proceed as follows:
1. Determine for the calculated pre-pressure (Pg) the corresponding maximum water volume using the
graph below.
2. Check that the total water volume in the entire water circuit is lower than this value.
If this is not the case, the expansion vessel inside the indoor unit is too small for the installation.
Luxury Air Source Heat Pump-Monobloc System
31
Page 33
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the expansion vessel (1 bar), keep in mind the following guidelines:
- Use only dry nitrogen to set the expansion vessel pre-pressure.
- Inappropriate setting of the expansion vessel pre-pressure will lead to possible malfunctioning of the system. Therefore, the pre-pressure should only be adjusted by a licensed installer.
Connecting the water circuit
Water connections must be made in accordance with the outlook diagram delivered with the unit, respecting the water in- and outlet
BE CAREFUL NOT TO DEFORM THE UNIT PIPING BY USING EXCESSIVE FORCE WHEN CONNECTING THE PIPING. DEFORMATION OF THE PIPING CAN CAUSE THE UNIT TO MALFUNCTION.
Ifair,moistureordustgetsinthewatercircuit,problemsmayoccur.
Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no dust and dirt can enter.
Use a good thread sealant for the sealing of the connections.
The sealing must be able to withstand the pressures and temperatures of the system.
When using non-brass metallic piping, make sure to insulate both materials from each other to
prevent galvanic corrosion.
Because brass is a soft material, use appropriate tooling for connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
Luxury Air Source Heat Pump-Monobloc System
32
Page 34
THE UNIT IS ONLY TO BE USED IN A CLOSED WATER SYSTEM. APPLICATION IN AN OPEN WATER CIRCUIT CAN LEAD TO EXCESSIVE CORROSION OF THE WATER PIPING.
NEVER USE ZN-COATED PARTS IN THE WATER CIRCUIT. EXCESSIVE CORROSION OF THESE PARTS MAY OCCUR AS COPPER PIPING IS USED IN THE INTERNAL WATER CIRCUIT OF THE UNIT.
WHEN USING A 3-WAY VALVE OR A 2-WAY VALVE IN THE WATER CIRCUIT. THE RECOMMENDED MAXIMUM CHANGEOVER TIME OF THE VALVE SHOULD BE LESS THAN 60
SECONDS.
Charging water
1. Connect the water supply to a drain and fill valve.
2. Make sure the automatic air purge valve is open (at least 2 turns).
3. Fill with water until the water manometer indicates a pressure of approximately 2.0 bar. Remove air in the circuit as much as possible using the air-purge valves. Air present in the water circuit might cause malfunctioning of the optional backup heater.
4. Regarding units with an optional backup heater: Check that the backup heater vessel is filled with water by opening the pressure relief valve. Water must flow out of the valve.
NOTE
During filling, it might not be possible to remove all the air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required.
The water pressure indicated on the water manometer will vary depending on the water-temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might dispose some excessive water through the pressure relief valve.
Water quality must be according to EN directive 98/83 EC.
Piping insulation
The complete water circuit, inclusive all piping, must be insulated to prevent condensation during cooling operation and reduction of the cooling and heating capacity. If the temperature is higher than 30°C and the humidity is higher than RH 80%, then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing.
Luxury Air Source Heat Pump-Monobloc System
33
Page 35
Field wiring
WARNING
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local and national legislation.
Switch ‘off’ the power supply before making any connections.
All field wiring and components must be installed by a licensed electrician and must comply
with relevant European and national regulations.
The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below.
Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
Be sure to establish an earth. Do not earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Be sure to install an earth leakage protector.
Failure to do so may cause electrical shock.
Wiring overview
The table below gives a wiring overview of the required field wiring.
6kw, 8kw, 11kw 14kw, 16kw Power supply AWG8 (8.5mm2) *3 AWG8 (8.5mm2) *4 Communication cable 0.75mm2 *2
Luxury Air Source Heat Pump-Monobloc System
34
Page 36
SYSTEM SET-UP
As the unit is designed to satisfy various installation environments, it is important to set up system correctly. If not configured correctly, improper operation or degrade of performance can be expected.
DIP switch setting overview
CAUTION
TURN ‘OFF’ THE ELECTRIC POWER SUPPLY BEFORE SETTING DIP SWITCH. WHENEVER ADJUSTING THE DIP SWITCH, TURN OFF ELECTRIC POWER SUPPLY TO AVOID AN
ELECTRIC SHOCK.
DIP switch introduction
The DIP switches are located on the indoor and outdoor switch box PCBs. They allow configuration of model selection, system priority, fast check and power supply.
Indoor PCB DIP Switch Introductions:
SW1-2:
SW3-4:
Code
Remarks:
SW3 setting: The self-check function is special designed for on-line production fast check. Please always put it on the default setting during normal use.
Code
6kw/8kW 11kW 14kW 16kW
ON
1 Self-check, Fast Check Normal Mode 2 Reserved Reserved
Outdoor PCB DIP Switch Introductions:
ON OFF
1
380-415V 3N Power Supply 220-240V Power Supply
2
Reserved Reserved
OFFDefault
Luxury Air Source Heat Pump-Monobloc System
35
Page 37
Wired controller DIP Switch Introductions:
- on the backside of the wired controller
Code
ON OFF (Default)
1 External control signal valid External control signal NOT valid 2 0~10V control signal valid On/Off control signal valid
1). ON/OFF control signal
When the signal is on (closed), the Heat Pump can work. The running mode will be decided by the setting of the wired controller. The heat pump will not monitor the setting temperature of the wired controller. If the signal is off (open), the Heat Pump can’t work. But if there is domestic hot water requirement the domestic hot water will not be affected by the external signal. It will always work as per the setting of wired controller of the heat pump.
2). 0~10V voltage control signal
The external controller gives a signal of 0 to +10V, the heat pump will produce water with different temperature according to a voltage-water temperature table. Once this control method is in force, the external signal will control the setting outlet temperature of space heating/cooling, the temperature setting of the wire controller is not in force anymore. This control signal is for space heating and space cooling modes.
VoltageWatertemperaturetableforspaceheatingmode
Signal (Input
Voltage)
Setting water outlet
temp.
Signal (Input Voltage)
Setting water outlet
temp.
0V Waiting
0.5V
1.0V
1.5V
2.0V
2.5V
3.0V
3.5V
4.0V
4.5V
5.0V
22°C 24°C 26°C 28°C 30°C 32°C 34°C 36°C 38°C 40°C
5.5V
6.0V
6.5V
7.0V
7.5V
8.0V
8.5V
9.0V
9.5V
10.0V
42°C 44°C 46°C 48°C 50°C 52°C 54°C 56°C 58°C 60°C
Luxury Air Source Heat Pump-Monobloc System
36
Page 38
VoltageWatertemperaturetableforspacecoolingmode
Signal (Input
Voltage)
Setting water outlet
temp.
Signal (Input Voltage)
0V Waiting
0.5V
1.0V
1.5V
2.0V
2.5V
3.0V
3.5V
4.0V
4.5V
5.0V
5°C 6°C 7°C 8°C
9°C 10°C 11°C 12°C 13°C 14°C
5.5V
6.0V
6.5V
7.0V
7.5V
8.0V
8.5V
9.0V
9.5V
10.0V
Setting water outlet
temp.
15°C 16°C 17°C 18°C 19°C 20°C 21°C 22°C 23°C 24°C
Luxury Air Source Heat Pump-Monobloc System
37
Page 39
Pre-operation checks
Checks before initial start-up
SWITCH OFF THE POWER SUPPLY BEFORE MAKING ANY CONNECTIONS.
After the installation of the unit, check the following before switching on the circuit breaker:
1. Field wiring
Make sure that the field wiring between the local supply panel and domestic hot water tank has been carried out according to the instructions, according to the wiring diagrams and according to European and national regulations.
2. Fuses or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified. Make sure that neither a fuse nor a protection device has been bypassed.
3. Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4. Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
5. Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
6. Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7. Refrigerant leakage
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
8. Power supply voltage
Check the power supply voltage on the local supply panel. The voltage must correspond to the voltage on the identification label of the unit.
9. Air purge valve
Make sure the air purge valve is open (at least 2 turns).
10. Pressure relief valve
Check if the backup heater vessel is completely filled with water by operating the pressure relief valve. It should purge water instead of air.
OPERATING THE SYSTEM WITH THE BACKUP HEATER VESSEL NOT COMPLETELY FILLED WITH WATER WILL DAMAGE THE BACKUP HEATER!
11. Shut-off valves
Make sure that the shut-off valves are correctly installed and fully open.
OPERATING THE SYSTEM WITH CLOSED VALVES WILL DAMAGE THE PUMP!
Luxury Air Source Heat Pump-Monobloc System
38
Page 40
Setting the pump speed
The pump speed can be selected on the pump. The default setting is high speed (III). If the water flow in the system is too high (e.g., noise of running water in the installation) the speed can be lowered (I or II). The available external static pressure (ESP, expressed in mH2O) in function of the water flow (l/min) is shown in the graph below.
Model RS15/6 and RS25/8
Luxury Air Source Heat Pump-Monobloc System
39
Page 41
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
BEFORE CARRYING OUT ANY MAINTENANCE OR REPAIR ACTIVITY, ALWAYS SWITCH ‘OFF’ THE CIRCUIT BREAKER ON THE SUPPLY PANEL, REMOVE THE FUSES OR OPEN THE PROTECTION DEVICES OF THE UNIT. MAKE SURE THAT BEFORE STARTING ANY MAINTENANCE OR REPAIR ACTIVITIES THE POWER SUPPLY TO THE OUTDOOR UNIT IS SWITCHED ‘OFF’.
Thedescribedchecksmustbeexecutedatleastonceayear.
1. Water pressure
Check if the water pressure is above 0.3 bar. If necessary add water.
2. Water filter
Clean the water filter.
3. Water pressure relief valve
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter-clockwise:
If you do not hear a clacking sound, contact your local dealer.
In case the water keeps running out of the unit, close both the water inlet and outlet shut-off
valves first and then contact your local dealer.
4. Pressure relief valve hose
Check that the pressure relief valve hose is positioned appropriately to drain the water.
5. Backup heater vessel insulation cover
Check that the back-up heater insulation cover is fastened tightly around the back-up heater vessel.
6. Domestic hot water tank pressure relief valve (field supply)
Appliesonlytoinstallationswithadomestichotwatertank.
Check for a correct operation of the pressure relief valve on the domestic hot water tank.
7. Domestic hot water tank booster heater
Appliesonlytoinstallationswithadomestichotwatertank.
It is advisable to remove lime build up on the booster heater to extend its life span, especially in regions with hard water. To do so, drain the domestic hot water tank, remove the booster heater from the domestic hot water tank and immerse in a bucket (or similar) with lime-removing product for 24 hours.
8. Indoor unit switch box
Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring.
Check for a correct operation of contactors (with the use of an ohmmeter). All contacts of these contactors must be in open position.
Luxury Air Source Heat Pump-Monobloc System
40
Page 42
TROUBLESHOOTING
This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
General guidelines
Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring. Before contacting your local dealer, read this chapter carefully, it will save you time and money.
WHEN CARRYING OUT AN INSPECTION ON THE SWITCH BOX OF THE UNIT, ALWAYS MAKE SURE THAT THE MAIN SWITCH OF THE UNIT IS SWITCHED ‘OFF’.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer/installer.
If the pressure relief valve is not working correctly and needs to be replaced, always reconnect the flexible hose attached to the pressure relief valve, to avoid water dripping out of the unit!
General symptoms
Symptom 1: The unit is turned ‘on’ but the unit is not heating or cooling as expected
Possible causes Corrective action
The temperature setting is not correct. Check the controller set point. The water flow is too low.
The water volume in the installation is too low.
• Check that all shut off valves of the water circuit are completely open.
• Check if the water filter needs cleaning.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the pump speed setting is on the highest speed.
• Make sure that the expansion vessel is not broken
• Check that the resistance in the water circuit is not too high for the pump. Make sure that the water volume in the installation is above the minimum required value.
Luxury Air Source Heat Pump-Monobloc System
41
Page 43
Symptom 2: The unit is turned ‘on’ but the compressor is not starting (space heating or domestic water heating)
Possible causes Corrective action
The unit must start up out of its operation range (the water temperature is too low).
In case of a low water temperature, the system utilizes the backup heater to reach the minimum water temperature first.
• Check that the backup heater power supply is correct
• Check that the backup heater thermal fuse is closed.
• Check that the backup heater thermal protector is not activated.
• Check that the backup heater contactors are not broken.
Symptom 3: Pump is making noise (cavitation)
Possible causes Corrective action
There is air in the system. Purge air. Water pressure at pump inlet is too low.
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the manometer is not broken.
• Check that the expansion vessel is not broken.
• Check that the setting of the pre-pressure of the expansion vessel is correct (refer to: "Setting the pre-pressure of the expansion vessel").
Symptom 4: The water pressure relief valve opens
Possible causes Corrective action
The expansion vessel is broken. Replace the expansion vessel. The water volume in the installation is too high.
Make sure that the water volume in the installation is under the maximum allowed value (refer to: "Checking the water volume and expansion vessel pre-pressure").
Symptom 5: The water pressure relief valve leaks
Possible causes Corrective action
Dirt is blocking the water pressure relief valve outlet.
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise:
• If you do not hear a clacking sound, contact your local dealer.
• In case the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your local dealer.
Luxury Air Source Heat Pump-Monobloc System
42
Page 44
Symptom 6: Space heating capacity shortage at low outdoor temperatures
Possible causes Corrective action
Backup heater operation is not activated.
Check the backup heater is turned ‘on’. Check whether or not the thermal protector of the backup heater has been activated. Check whether or not the thermal fuse of the backup heater
is blown. Too much heat pump capacity is used for heating domestic hot water (applies only to installations with a domestic hot water tank).
Check that the 'space heating priority temperature' field
settings are configured appropriately:
- Make sure that the space heating priority is enabled
Error codes
When a safety device is activated, the user interface LED will be flashing, and an error code will be displayed.
A list of all errors can be found in the table below.
Code Error code description Possible reasons Correction methods
E0 HE outlet sensor failure
* The unit cannot run in H/C mode, but can run in DHW mode.
E1 Water tank temp sensor
failure * The unit cannot run in DHW mode, but can run in H/C mode.
E2 HE inlet sensor failure
* The unit cannot run in H/C mode, but can run in DHW mode.
E3 Water outlet sensor
failure * The unit cannot run in H/C mode, but can run in DHW mode.
E4 Outdoor heat exchanger
sensor failure * The unit stops running.
1) HE outlet sensor open circuit
2) HE outlet sensor short circuit
3) Main PCB damaged
1) Water tank sensor open circuit
2) Water tank sensor short circuit
3) Main PCB damaged
1) HE inlet sensor open circuit
2) HE inlet sensor short circuit
3) Main PCB damaged
1) HE inlet sensor open circuit
2) HE inlet sensor short circuit
3) Main PCB damaged
1) Outdoor heat exchanger sensor open circuit
2) Outdoor heat exchanger sensor short circuit
3) Main PCB damaged
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
Luxury Air Source Heat Pump-Monobloc System
43
Page 45
E5 Outdoor ambient temp
sensor failure * The unit stops running.
E6 TH temp sensor failure
* The unit stops running.
E7 TL temp sensor failure
* The unit stops running.
E8 Indoor ambient temp
sensor failure * The unit keeps running, but display the error code.
E9 T2 temp sensor failure
* The unit stops running.
Ea Communication failure
between indoor and controller * The unit stops running.
Eb Communication failure
between indoor and outdoor * The unit stops running.
Ec Indoor EEPROM failure
* The unit stops running.
Ed Controller clock IC failure
* The error code disappeared 10 seconds later, clock function and
1) Outdoor ambient temp sensor open circuit
2) Outdoor ambient temp sensor short circuit
3) Main PCB damaged
1) TH temp sensor open circuit
2) TH temp sensor short circuit
3) Main PCB damaged
1) TL temp sensor open circuit
2) TL temp sensor short circuit
3) Main PCB damaged
1) Indoor ambient temp sensor open circuit
2) Indoor ambient temp sensor short circuit
3) Main PCB damaged
1) T2 temp sensor open circuit
2) T2 temp sensor short circuit
3) Main PCB damaged
1) Communication failure between indoor and controller
2) Controller damaged
3) Main PCB damaged
1) Communication failure between indoor and outdoor
2) Main PCB damaged
3) Outdoor PCB damaged
1) Indoor EEPROM chip damaged
2) Data of indoor EEPROM error
1) Chip of controller clock IC damaged
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the sensor connection
2) Replace the sensor
3) Replace the main PCB
1) Check the connection wiring (4 cores wiring)/ports between controller and indoor PCB, and check if the controller back side wirings are connected correctly. Replace the wiring or reconnect the ports
2) Replace the controller
3) Replace the main PCB
1) Check the connection wiring (2 cores wiring)/ports between outdoor PCB and main PCB, and check if they are connected correctly. Replace the wiring or reconnect the ports
2) Replace the controller
3) Replace the main PCB
1) Replace the EEPROM chip
2) Check If the chip installed correctly, or replay the chip
1) Replace the chip or replace the controller
Luxury Air Source Heat Pump-Monobloc System
44
Page 46
timer function invalided.
EE Controller EEPROM
failure
1) Chip of controller EEPROM damaged
1) Replace the chip or replace
the controller * The error code disappeared 10 seconds later, auto restart function invalided.
P0 High pressure protection
* The unit stops running.
1) Too small cooling water flow or a high temperature
2) The uncompressed gas is in refrigerant system
3) Too much refrigerant
1) Check if the water pump
works in good condition or
readjust water control valve
2) Discharge and then recharge
the refrigerant
3) Discharge some refrigerant.
P1 Low pressure protection
* The unit stops running.
1) Too less refrigerant
2) The electronic expansion valve assembly damaged
1) Add some refrigerant
2) Replace the electronic
expansion valve assembly
P2 Wrong phase sequence
protection
1) Wrong phase connection (only for 3 phases power supply)
1) Correct the phase
connection * The unit stops running.
P3 Absence phases
protection * The unit stops running.
P4 Water flow switch failure
* The unit stops running.
1) Absence one phase connection (only for 3 phases power supply)
1) Water pump damaged
2) Too less water in the system
3) Water flow switch damaged
1) Check if the power supply
cord in open circuit, or if one
wiring loosed off
1) Check the water pump, if
needed replace one
2) Check if the water
supplement is ok
3) Check the water flow switch,
if needed replace one
P5 Plate heat exchanger too
1) Too low ambient temperature low temp. protection * The unit stops running.
** After E failure, renew the safety by turning the unit ‘OFF’ and back ‘ON’. And P failure will renew automatically
if the failure is eliminated.
*** In case this procedure for resetting the safety is not successful, contact your local dealer.
Luxury Air Source Heat Pump-Monobloc System
45
Page 47
TECHNICAL SPECIFICATION
Heating
TECHNICAL DATA
Nominal capacity kW Refer to the nameplate
6kw 8kw 11kw 14kw 16kw
Power input kW Refer to the nameplate
Cooling
Nominal capacity kW Refer to the nameplate
Power input kW Refer to the nameplate
DHW
Nominal capacity kW Refer to the nameplate
Power input kW Refer to the nameplate
Max. power input
(+3 steps backup heater) kW
2.6(+6) 3.1(+6) 4.3(+6) 5.4(+6) 5.88(+6)
Max. current(+backup heater) A 11.5(+26) 13.6(+26) 18.8(+26) 8.2(+26) 8.9(+26)
Starting current
(without soft start kit) A
Starting current
(with soft start kit) A
Leakage current A
45 63 63 63 63
18 25.2 25.2 --- ---
0.75mA/kW 0.75mA/kW 0.75mA/kW 0.75mA/kW 0.75mA/kW
Power supply V/Ph/Hz 230/1/50 230/1/50 230/1/50 380/3/50 380/3/50
Max. leaving water
temperature (without using
backup heater) °C 60
Soft start kit Optional Optional Optional No No
Refrigerant
Type R410A
Charge/Kg 2.5 2 2.5 3.5 3.5
Compressor
Type Rotary Rotary Rotary Scroll Scroll
Brand TOSHIBA TOSHIBA TOSHIBA DAIKIN DAIKIN
Heat exchanger Type High efficicency hydrophilic fin-tube heat exchanger
Refrigerant
circuit
Electronic
expansion valve
Brand Saglnomiya Saglnomiya Saglnomiya Saglnomiya Saglnomiya
Fan motor power
input
W 95±10% 95±10% (65±10%)x2 (95±10%)x2 (95±10%)x2
Size of fan mm 500x145 500x145 430x154 500x154 500x145
Air flow m3/h 3800 3800 4900 7400 7400
Pressure
range
0--3.5MPa 0--3.5MPa 0--3.5MPa 0--3.5MPa 0--3.5MPa
Brand WILO
Water circuit
Gas manometer
Heat exchanger Type Stainless steel plate heat exchanger
Water pump
Model RS15/6 RS25/8
Power input
(H/M/L) /w 93/67/46 151/113/81
Max. water
head /m (H/M/L speed) 6/4/2.5 (H/M/L speed) 7.8/6.8/4.8
Luxury Air Source Heat Pump-Monobloc System
46
Page 48
Dimensions
(Net)
Dimensions
(Packing)
Net weight kg 120 130 155 165 170
Gross weight kg 130 140 162 175 180
Noise level dB(A) 53 53 55 58 58
Max. water
flow /m3/h (H/M/L speed) 3.4/2.5/1.5 (H/M/L speed) 6/5/3
3-way valve Type T type electromotion
Type stopcock/brass
Flow switch
Rated water flow m3/h 1.2 1.7 1.8 2.5 2.9
Expansion vessel
Backup heater
vessel capacity /L 15 20
Air purge valve Brand Castel
Pressure relief
valve
Backup heater
Water
manometer
inlet/outlet pipe inch BG1“
Permitted
pressure MPa 0.6
HxWxD mm 1062x1138x480 1062x1138x480 1270x1204x480 1477x1198x480 1477x1198x480
HxWxD mm 1190x1205x510 1190x1205x510 1390x1271x510 1600x1265x510 1600x1265x510
Flow check
point / m3/h 0.3
Type squareness closed type
capacity /L 10
Brand Castel
Pressure set
point 6 bar
Quantity
*Power 3*2kW
Pressure
range 0--1.5MPa
NOTES:
Capacities and power inputs based on the following conditions:
- Heating: Water Inlet/Outlet temperature 30°C /35°C. Outdoor air dry bulb/wet bulb temperature 7°C /6°C
- Cooling: Water Inlet/Outlet temperature 23°C /18°C. Outdoor air dry bulb temperature 35°C
- Domestic Hot Water: Water temperature in the tank 40°C. Outdoor air dry bulb/wet bulb temperature 7°C /6°C
Luxury Air Source Heat Pump-Monobloc System
47
Page 49
TEMPERATURE SENSOR R-T CONVERSION TABLE
B25/50=4100±1% R(25)=10K
-20 115.2660 -4.0 21 12.0561 69.8 62 2.1907 143.6
-19 108.1460 -2.2 22 11.5000 71.6 63 2.1124 145.4
-18 101.5170 -0.4 23 10.9731 73.4 64 2.0373 147.2
-17 96.3423 1.4 24 10.4736 75.2 65 1.9653 149.0
-16 89.5865 3.2 25 10.0000 77.0 66 1.8963 150.8
-15 84.2190 5.0 26 9.5507 78.8 67 1.8300 152.6
-14 79.3110 6.8 27 9.1245 80.6 68 1.7665 154.4
-13 74.5360 8.6 28 8.7198 82.4 69 1.7055 156.2
-12 70.1698 10.4 29 8.3357 84.2 70 1.6469 158.0
-11 66.0898 12.2 30 7.9708 86.0 67 1.8300 152.6
-10 62.2756 14.0 31 7.6241 87.8 71 1.5907 159.8
-9 58.7079 15.8 32 7.2946 89.6 72 1.5367 161.6
-8 56.3694 17.6 33 6.9814 91.4 73 1.4848 163.4
-7 52.2438 19.4 34 6.6836 93.2 74 1.4350 165.2
-6 49.3161 21.2 35 6.4002 95.0 75 1.3870 167.0
-5 46.5725 23.0 36 6.1306 96.8 76 1.3111 168.8
-4 44.0000 24.8 37 5.8736 98.6 77 1.2908 170.6
-3 41.5878 26.6 38 5.6296 100.4 78 1.2542 172.4
-2 39.8239 28.4 39 5.3969 102.2 79 1.2133 174.2
-1 37.1988 30.2 40 5.1752 104.0 80 1.1739 176.0
0 35.2024 32.0 41 4.9639 105.8 81 1.1360 177.8
1 33.3269 33.8 42 4.7625 107.6 82 1.0996 179.6
2 31.5635 35.6 43 4.5705 109.4 83 1.0645 181.4
3 29.9058 37.4 44 4.3874 111.2 84 1.0307 183.2
4 28.3459 39.2 45 4.2126 113.0 85 0.9982 185.0
5 26.8778 41.0 46 4.0459 114.8 86 0.9668 186.8
6 25.4954 42.8 47 3.8867 116.6 87 0.9366 188.6
7 24.1932 44.6 48 3.7348 118.4 88 0.9075 190.4
8 22.5662 46.4 49 3.5896 120.2 89 0.8795 192.2
9 21.8091 48.2 50 3.4510 122.0 90 0.8525 194.0
10 20.7184 50.0 51 3.3185 123.8 91 0.8264 195.8
11 19.6891 51.8 52 3.1918 125.6 92 0.8013 197.6
12 18.7177 53.6 53 30.7075 127.4 93 0.7771 199.4
13 17.8005 55.4 54 2.9590 129.2 94 0.7537 201.2
14 16.9341 57.2 55 2.8442 131.0 95 0.7312 203.0
15 16.1156 59.0 56 2.7382 132.8 96 0.7094 204.8
16 15.3418 60.8 57 2.6368 134.6 97 0.6884 206.6
17 14.6181 62.6 58 2.5397 136.4 98 0.6818 208.4
18 13.9180 64.4 59 2.4168 138.2 99 0.6186 210.2
19 13.2631 66.2 60 2.3577 140.0 100 0.6297 212.0
20 12.6431 68.0 61 2.2725 141.8
Resistance
Resistance
Resistance
Luxury Air Source Heat Pump-Monobloc System
48
Page 50
Logbook for F-gases
General information
Customer name: Reference No.
Model name:
Location where unit is installed:
Refrigerant type: Refrigerant quantity installed (kg):
Installation company: Date of installation:
Installer:
Refrigerant additions
Date Engineer Amount added, kg Reason for addition
Refrigerant removals
Date Engineer Amount removed,
kg
Leak tests
Date Engineer Test results Follow up actions required
Follow-up actions
Date Engineer Related to test on Actions taken
Testing of automatic leak detection system (if fitted)
Reason for removal. What was done with
recovered refrigerant?
Date Engineer Test results Comments
Luxury Air Source Heat Pump-Monobloc System
49
Loading...