RTN 24 - RTFS 24 - RTFS 28
CTN 24 F - CTFS 24 F - CTFS 28 F
00331967 - 1a edition - 02/2004
INSTALLATION USE
AND MAINTENANCE
UK
General info
IMPORTANT
This INSTRUCTION MANUAL, which is an integral and indispensable part of the product, must be handed over to the user by the plumbers and
must be kept in a safe place for future reference. The manual must be handed over with the boiler should it be sold or transferred.
This boiler must be used for the purposes for which it has been designed. Any other use shall be considered incorrect and therefore
dangerous.
The boiler must be installed in compliance with applicable laws and standards and according to the manufacturer’s instructions given in this
manual. Incorrect installation may cause injury to persons and/or animals and damage to property. The manufacturer shall not be held liable for any
such injury and/or damage.
Damage and/or injury caused by incorrect installation or use and/or damage and/or injury due to non-observance of the manufacturer’s instructions
shall relieve UNICAL from any and all contractual and extracontractual liability.
Before installing the boiler, check that the technical data corresponds to requirements for its correct use in the system.
Check that the boiler is intact and that it has not been damaged during transport and handling. Do not install equipment which is patently damaged
and/or faulty.
Do not obstruct the air suction and/or heat dissipation grates.
Only original accessories must be used for all boilers supplied with optionals or kits (including electrical ones).
Dispose of the packaging with care as all the materials can be recycled. The packaging must therefore be sent to specific waste management
sites.
Keep the packaging out of the reach of children as it may represent a choking and suffocation hazard.
In the event of failure and/or faulty functioning, switch off the boiler. Do not attempt to make repairs: contact qualified technicians.
Original parts must be used for all repairs to the boiler.
Non-observance of the above requirement may jeopardize the safety of the boilers and expose people, animals and property to danger.
To guarantee efficiency and correct functioning of the equipment it is legally binding to service the boilers once a year according to the
schedule indicated in the relative section of this manual.
In the event of long periods of inactivity of the boiler, disconnect it from the power mains and close the gas tap (Warning! In this case the boiler’s
electronic anti-freeze function will not be operative).
Should there be a risk of freezing, add anti-freeze: it is not advisable to empty the system as this may result in damage; use specific anti-freeze
products suitable for multi-metal heating systems.
N.B.
For boilers which use gaseous fuel, if you smell gas:
- do not turn on or off electrical switches and do not turn on electrical appliances;
- do not ignite flames and do not smoke;
- close the main gas tap;
- open doors and windows;
- contact a Service Centre, qualified installer or the gas supply company.
Never use flames to detect gas leaks.
WARNING
This boiler has been built for installation in the country indicated on the technical data plate: installation in any other country may be a source
of danger for people, animals and property.
Read the warranty conditions and clauses on the warranty certificate attached to the boiler with care.
‘’WATER TREATMENT IN C.H. SYSTEM FOR CIVIL USE’’
NOTE FOR INSTALLER AND USER
1) The frequency of the cleaning of the D.H.W. heat exchanger is related to the hardness of the feeding water.
2) With a water hardness higher than 28°f (16°d) the use of antiscaling devices, whose choice will be made on the base of water characteristics, is
suggested.
3) To increase the resistance to the scaling, a D.H.W. temperature adjustment very close to that one of the actual use, is suggested.
4) The adoption of a modulating room thermostat reduces the scaling danger.
5) We advise you to verify the state of cleaness of the D.H.W. heat exchanger at the end of the first year and subsequently every two years.
2
DATA PLATE
®
General info
1
2
15
17
19
G20
2H
G20
2E
G30/G31
3+
G30 - 31
3B/P
G31
3P
1 = P.I.N. code
2 = Boiler type (only for condensing boiler)
3 = (S.N°) Serial Nr.
4 = Manufacture Date
5 = Model
6 = Appliance type
7 = Elettrical supply
8 = Maximum absorbed power - Insulation
protection
9 = (Pn) Nominal Output
3
9
12
20 - 25
20
28-30/ 37
30 - 50
37 - 50
4
/
6
16
18
mbar
mbar
mbar
mbar
mbar
IT ES IE
PT GR
TR HR
CZ SK
HU
SI
GB
CN RU RO
LV EE LT
7
10
13
20
II 2H3+
II 2H3+
II 2H3B/P
II 2H3P
II 2HS 3B/P
II 2E3P
II 2H3P
I 2H
I 2H
10 = (Pcond) Condensing Nominal Output
(only for condensing boiler)
11 = (D) Specific flow rate EN 625
12 = (Qn) Nominal heat input
13 = (Qnw) Nominal heat input for D.H.W.
system if there are different out puts
between the C.H. and D.H.W. circuits
14 = (NOx) NOx Class
15 = (PMS) Max pressure C.H. system
16 = (T max) Max Temperature C.H. system
5
20 ; 28-30/37 mbar
20 ; 28-30/37 mbar
20 ; 50 mbar
18 ; 50 mbar
25 ; 30 mbar
20 ; 50 mbar
20 ; 37 mbar
20 mbar
20 mbar
21
8
11
14
17 = (PMW) Max pressure D.H.W. system
18 = (T max) Temperature D.H.W. system
19 = Adjusted for gas type X
20 = Country of destination, Gas category,
Supply pressure
21 = EN standards applicable to the boiler
type
GAS VALVE LABEL
Translation
While connecting gas inlet pipe of the boiler to the
pipe coming from gas network, it is MANDATORY to
insert a TIGHT GASKET, whose dimensions and material
must be adequate. Connection is NOT suitable for
hemp, teflon strip or similar materials
003319 80
3
General info
For your own safety, observe these safety instructions.:
WARNING
Identifies potentially dangerous
situations.
WARNING
from risk of electric shock.
1
2
TECHNICAL FEATURES
AND DIMENSIONS .......................................................... pag.5
1.1 Technical features ................................................................... pag.5
TNwith natural draught open chamber;
TFSwith forced draught room sealed com
bustion chamber;
All versions have electronic ignition.
Models in the IVEN
IVEN 04 CTN 24 F open boiler, with electronic
ignition and instantaneous D.H.W. production;
IVEN 04 RTN 24 F open boiler, with electronic
ignition, for heating only;
IVEN 04 CTFS 24 F forced draught room sealed boiler, with electronic ignition and instantaneous D.H.W. production;
IVEN 04 RTFS 24 F forced draught room sealed boiler, with electronic ignition for heating
only;
IVEN 04 CTFS 28 F forced draught room sealed boiler with electronic ignition and instantaneous D.H.W production;
04 series are the following:
IVEN 04 is supplied with all control and sa-
fety features according to the latest laws in
force.
The main technical features of the IVEN 04
boilers are summarised below.
• Bithermal, copper, high performance heat
exchanger;
• Electronic ignition;
• Electronic flame modulation;
• Minimum output control;
• Electronic control of ignition ramp;
• Anti-freeze function;
• Pump anti-jamming function;
• Pump over run function;
• High limit thermostat (95°C);
• Three-speed circulating pump;
• Expansion vessel;
• Automatic air vent;
• C.H. system water filling valve except Fren-
ch, Belgium and England version) ;
• Safety pressure switch for low water level;
• Priority flow switch for D.H.W.;
• Tap water flow rate restrictor set at 10 li-
tres/min, for 24 kW boilers (brown) and 12
l/min, for 28 kW boilers (pink)
Note: This 10 (12) l/min flow rate
is guaranteed with a upstream
pressure of 2 bar. If the upstream
pressure is much higher than 2
A
bar, then it is possible to reduce the flow
rate to 10 (12) l/min by rotating clock-wise
the screw ‘’A’’. On the contrary, if the up-
stream pressure is lower than 2 bar it is
possible to reach the flow rate of 10 (12) l/
min by rotating counter clock-wise the
screw ‘’A’’. If, also in this case the flow
rate of 10 (12) l/min is not reacheable then
the flow restrictor can be removed from its
seat.
• Control panel with IP 44 insulation protection
• Temperature and pressure gauge;
• Warning light for: presence of power, re-
quest for heating, burner in operation, lock
out;
• ON-OFF switch;
• D.H.W. temperature selector (35/57°C) for
IVEN 04 CTN 24 F-CTFS 24 F-CTFS 28 F
+ antifrost position;
(25/57°C) for IVEN 04 RTN 24 - RTFS 24 set off only if arranged with storarage tank
• C.H. temperature selector (45/78°C) + summer/winter position.
• Reset button;
• Chimney sweeper button
• Mounting jig
• Mounting frame with valves (opt.)
• Flue gas antispillage thermostat 75°C
(IVEN 04 TN)
IVEN 04 RTFS 28 F forced draught room sealed boiler with electronic ignition for heating
only;
diverter
10Flue gas anti-spillage thermostat
11Ignition electrode
12H.L. thermostat
13 C.H. temperature sensor
14Automatic air vent
15 Circulating pump
16Filling valve (except French,
Belgium and England version)
17By-pass
MC.H. system flow
GGas inlet
RC.H. system return
M
IVEN 04 RTFS 24 - IVEN 04 RTFS 28
11
10
9
8
7
15
6
5
4
3
2
1
G
R
12
13
14
15
16
17
18
19
fig. 4
1Heating circuit safety valve
2Low water level pressure switch
3Expansion vessel
4Gas valve
5Burner nozzles
6Expansion vessel filling valve
7Ionisation electrode
8Heat exchanger
9Room sealed combustion chamber
10Flue gas extractor fan
11Air/flue coaxial duct
12Micro-switch on flue gas pressure
switch
13Flue gas pressure switch
14H.L. thermostat
15Ignition electrode
16 Heating temperature sensor
17Automatic air vent
18 Circulating pump
19Filling valve (except French,
Belgium and England version)
20By-pass
MC.H. system flow
GGas inlet
RC.H. system return
M
20
G
R
fig. 5
7
General info
1.4 - OPERATING DATA
For the following data: Nozzle - Burner pressure - Diaphragm (where applicable) - Inputs - Gas consumptions refer to pagraph SUITABILITY TO USE
OTHER GASES.
Nominal output
Minimum output
Actual water efficiency at full load (100%)
Min. required water efficiency at full load (100%)
Actual water efficiency at part load (30%)
Min. required water efficiency at part load (30%)
Stars No. off (According EEC Directive 92/42)
Combustion efficiency at nominal load (100%)
Combustion efficiency at part load (30%)
Stand-by losses (min.-max.)
(*)Flue gas temperature (min. - max.)
Flue gas mass flow rate (min. - max)
Excess of air l
CO
2
NOX (value according EN 297/A3 + EN 483)
NOX class
Flue losses with burner in operation (min.-max)
Flue losses with burner off
IVEN 04
kW
kW
%
%
%
%
n.
%
%
%
°C
g/s
%
%
mg/kWh
%
%
RTN 24
23,88
10,07
90,11
89,76
88,53
87,3
2
92,6
90,2
2,6 - 2,5
91,8
18-20
113,8
2,4-5,3
197
2
9,8 - 7,4
0,486
CTN 24 F
23,88
10,07
90,11
89,76
88,53
87,3
2
92,6
90,2
2,6 - 2,5
91,8
18-20
113,8
2,4-5,3
197
2
9,8 - 7,4
0,486
RTFS 24
23,94
9,95
90,34
89,76
88,60
87,14
2
93,3
87,9
1,88-2,96
112,5
13,64-14,38
67,7
3,0-7,4
157
2
12,1-6,7
0,295
CTFS 24 F
23,94
9,95
90,34
89,76
88,60
87,14
2
93,3
87,9
1,88-2,96
112,5
13,64-14,38
67,7
3,0-7,4
157
2
12,1-6,7
0,295
RTFS 28
27,45
9,80
90,01
89,88
87,43
87,32
2
93,2
86,8
1,76-3,19
87,7
17,5-17,6
60,86
2,65-7,9
163
2
13,2-6,8
0,256
CTFS 28 F
27,45
9,80
90,01
89,88
87,43
87,32
2
93,2
86,8
1,76-3,19
87,7
17,5-17,6
60,86
2,65-7,9
163
2
13,2-6,8
0,256
1.5 - GENERAL FEATURES
Appliance category
Min. water flow rate in CH circuit (Dt 20 K)
Min. pressure in CH circuit
Max. pressure in CH circuit
Water content primary circuit
Max. oper. temperature in CH mode
Min. oper. temperature in CH mode
Total capacity of expansion vessel
C.H. expansion vessel pre-loading
Max. water content CH circuit (calc. x max. T°of 82°C)
Min. water flow rate in D.H.W. circuit
Min. DHW. pressure
Max. DHW. pressure
DHW specific flow rate (Dt 30 K)
Flow restrictor
DHW production in continuous operation with Dt 45 K
DHW production in continuous operation with Dt 40 K
DHW production in continuous operation with Dt 35 K
DHW production in continuous operation with Dt 30 K*
DHW production in continuous operation with Dt 25 K*
DHW Temperature range
Electrical supply
Supply fuse
Maximun absorbed power
Insulation protection
Net weight
l/min
bar
bar
l
°C
°C
l
bar
l
l
bar
bar
l/min.
l/min.
l/min.
l/min.
l/min.
l/min.
l/min.
°C
V-Hz
A (F)
W
IP
kg
RTN 24
II
2H3+
7,2
0,5
3
3,5
81
45
8
1
183,9
-
-
-
-
-
-
-
-
-
-
230/50
4
70
X4D
37
CTN 24 F
II
2H3+
7,2
0,5
3
3,5
81
45
8
1
183,9
2,5
0,5
6
11,5
10
7,6
8,6
9,78
11,4
13,69
35 - 57
230/50
4
70
X4D
37
RTFS 24
II
2H3+
7,37
0,5
3
3,5
81
45
8
1
183,9
-
-
-
-
-
-
-
-
-
-
-
230/50
4
130
X4D
37
CTFS 24 F
II
2H3+
7,37
0,5
3
3,5
81
45
8
1
183,9
2,5
0,5
6
11,5
10
7,6
8,58
9,80
11,44
13,73
35 - 57
230/50
4
130
X4D
37
RTFS 28
II
2H3+
7,02
0,5
3
3,5
81
45
8
1
183,9
-
-
-
-
-
-
-
-
-
-
-
230/50
4
130
X4D
37
CTFS 28 F
II
2H3+
7,02
0,5
3
3,5
81
45
8
1
183,9
2,5
0,5
6
12,5
12
8,74
9,84
11,24
13,11
15,74
35 - 57
230/50
4
130
X4D
37
(*) mixed
8
Warning:If the boilers are used in low temperature heating system (ex. floor heating)
it is necessary to use a mixing valve to
avoid condensation phenomena.
DIRECTIONS FOR
2
INSTALLER
2.1 - DIRECTIONS FOR
INSTALLER
Installation info
IVEN 04 is a gas boiler which must be
installed in accordance with the latest regulations or rules in force. For the boiler
category, which changes according to the
destination country, see page 4.
NOTE:
Observe the corresponding technical rules
and the building supervisory and statutory
regulations of the country of final use when
installing and operating the system.
2.2 - INSTALLATION
2.2.1 - PACKING
IVEN 04 24 F is delivered completely assem-
bled and packed in a strong cardboard box.
Once the boiler has been unpacked check that
it is intact.
Always ensure that an appropriately
specialised company is entrusted with
installation, gas supply and flue gas
connection, commissioning and power
supply connection, as well as all servicing
and repair work.
Work on gas conduits and fittings must
only be carried out by a registered service
provider.
The system must be cleaned and serviced
once a year. This includes an inspection
of the entire system to see if it is in full
working order.
Defects and faults must be eliminated
immediately.
Please note that we can accept no liability
whatsoever for loss or injury resulting from
unauthorised adjustment or manipulation
of the system’s control or regulating
devices.
Keep the packaging material
(cardboard box, plastic strips,
plastic bag, etc.) out of the reach of children as it represents
a choking and suffocation hazard.
UNICAL refuses all liability for
injury to persons and animals
or damage to property resulting from non-observance of
the above.
In addition to the boiler packaging contains:
- a bag with:
- installation, use and maintenance
handbook,
- warranty card
- template for fixing the boiler to the wall,
- 2 dowels with screws hook to fix the boiler
to the wall,
- Only for models TFS, a diaphragm for flue
gas outlet
390
900
495
fig. 6
9
Installation info
2.2.2 - POSITIONING THE BOILER
Every boiler is supplied with special “MOUNTING JIG” with which the pipes for connection to the system, D.H.W. and gas can be
positioned when the hydraulic system is being
laid out and before the boiler is installed.
This MOUNTING JIG, comprising a sheet of
strong paper which must be fixed to the wall
chosen for the installation of the boiler, gives
all the indications needed to make the holes
in the wall using two screws with expanding
dowels.
Use the lower part of the MOUNTING JIG to
mark the exact point of the connection of the
gas supply, cold water supply pipe, D.H.W.
outlet, C.H. flow and return.
When choosing the position of the boiler:
- refer to the indications given in the section
“Flue gas evacuation system “.
- leave a clearance of 50 mm on each side
of the boiler to facilitate maintenance operations.
- check that the wall is suitable.
- avoid fixing the boiler to thin partitions.
- avoid installing the boiler above applian-
ces which might affect operation when in
use (cookers which produce greasy steam, washing machines, etc.)
- avoid installing natural draught boilers in
corrosive or very dusty atmospheres such
as hairdressers’, laundrettes, etc. as the
life of the boiler components could be significantly shortened.
MOUNTING JIGS FOR BOILER CONNECTIONS
8585
For IVEN 04 TFS
Since the temperature of the wall
on which the boiler is installed
and the temperature on the sur-
face of the coaxial duct do not
increase, in normal operating conditions, more
than 60 K, it is not necessary to keep a minimum distance from inflammable walls.
For boilers with dual suction and exhaust ducts,
place insulating material between the wall and
the pipe in the case of inflammable walls and
wall crossings.
IVEN 04 TN
Maintain distance of at least 200
mm on the sides with wall which
have inflammable materials.
ØL mm
M = C.H. system
flow
C = D.H.W.
outlet
G =Gas
F = Cold water
inlet
R = C.H. system
return
S = Safety valve
discharge
= 3/4''144
= 1/2''144
= 3/4''153,5
= 1/2''144
= 3/4''144
=195,5
CONNECTION POSITION SEEN FROM ABOVE
G
153.5
FR
Fil li ng of
C.H. system
L
M
Safety
valve discharge
C
195.5
144
fig. 7
10
2.2.3 - ASSEMBLING THE BOILER
Installation info
Before connecting the boiler to the D.H.W. and
heating system pipes, carefully clean the pipes to remove all traces of metal resulting from
processing and welding operations as well as
any oil and grease which could damage the
boiler or jeopardize its operation.
Unical refuses all liability for
injury to persons and animals or
damage to property resulting
from non-observance of the above.
2.2.4 - VENTILATION
The boiler must be installed in a suitable room
according to the rules in force and particularly:
NATURAL DRAUGHT OPEN FLUE BOILERS
(TYPE B11bs INSTALLATION and VMC)
The boliers IVEN 04 CTN 24 F, IVEN 04 RTN
24, are open flue boilers and are foreseen for
chimney connection: the air for combustion is
taken directly from the room in which it is installed.
The room can have both a direct ventilation
(i.e. with ventilation openings facing outwards) or an indirect ventilation (i.e. with ventilation openings facing an adjacent room) provided that the following requirements are complied with:
Direct ventilation:
- The room has to have a ventilation ope-
ning of, at least,
6 cm² /kW of installed input (see input table on par. 2.7) and, in no case, lower than
100 cm² and made directly onto an external wall.
- The opening has to be as close as possi-
ble to the floor.
- It should not be possible to close it and it
should be protected with a grate not reducing its usefull ventilation section.
- A correct ventilation can be optained also
through the addition of more openings, provided the addition of the different sections
is not less than that really needed.
Do not use solvents which
could damage the components.
To install the boiler:
- Fix with tape the paper template to the wall
- make two Ø 12 holes in the wall and insert
the hooks;
- position the junction points for the connection of the gas supply pipe, cold water supply pipe, D.H.W. outlet, CH flow and return
in the positions shown by the template. ;
- fit the boiler onto the support hooks;
- In case it is not possible to make a ventilation opening close to the floor, it will be
necessary to increase its usefull section
of at least 50%.
- If an open fire is present in the same room
it needs an indipendent air supply, otherwise the installation of a type B appliance
is not permitted.
- If in the room there are other devices which need air for their operation (e.g. a wall
exhauster) the section of the ventilation
opening has to be the properly sized.
Indirect ventilation
In case it is not possible to make a room ventilation opening on an external wall, it is possible to have an indirect ventilation, sucting
the air from an adjacent room, making an opening in the lowest part of a door.
This solution is possible only if:
- The adjacent room is not a bed room
- The adjacent room is not a common part
of the building and is not a room with fire
danger (e.g. a fuel deposit, a garage, etc..)
FORCED DRAUGHT ROOM SEALED BOILER
(TYPE C12 - C32 - C42 - C52 - C62 - C82)
The IVEN 04 CTFS 24 F - IVEN 04 RTFS 24 IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 are
forced draught, room sealed boilers; so they
do not need particular ventilation openings for
- connect the boiler to the gas pipe, domestic cold and hot water pipes, CH flow and
return pipes.
- connect to electrical supply
the combustion air, in the room in which they
are installed.
FORCED DRAUGHT, OPEN FLUE BOILER
(TYPE B22)
If the IVEN 04 CTFS 24 F - IVEN 04 RTFS 24
- IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 are
installed in a room according to the chimney
configuration on type B22, the same ventilation requirements established in paragraphs
Direct ventilation and Indirect ventilation
apply.
2.2.5 - FLUE GAS DISCHARGE
SYSTEM
NATURAL DRAUGHT OPEN FLUE BOILERS
Connection to the chimney
A good chimney is very important for the correct functioning of the boiler; it must therefore
conform with the following requirements:
- it must be made from waterproof material
and be resistant at the temperature of the
flue gas and relative condensate;
- it must have sufficient mechanical stren-
gth and low thermal conductivity;
- it must be perfectly sealed to prevent cooling due to parasite air inlets;
- it must be as vertical as possible and the
end section must have a chimney cap
which guarantees efficient and constant
evacuation of the combustion products;
- the chimney must have a diameter not
smaller than that of the boiler’s draught diverter; for chimneys with a square or
rectangular section, the internal section
must be 10% larger than the section of the
connection duct to the draught diverter.
- starting from the draught diverter, the duct
must have a vertical section with a length
more than twice the diameter, before getting into the chimney.
11
Installation info
Direct emission into the atmosphere
Natural draught boilers can discharge combustion products directly into the atmosphere
using a duct, which goes through the outside
walls of the building, connected to a flue
exhaust terminal.
The exhaust duct must also comply with the
following requirements:
- the sub-horizontal part inside the building
must be as short as possible (no more than
1 m);
- for boilers with vertical discharge, such as
boilers IVEN 04 CTN 24 F, IVEN 04 RTN24, there must be no more than 2 direction
changes;
- it must receive the discharge from a single
boiler;
- the part going through the wall must be
protected by a sheath duct; the part of the
sheath duct facing the inside of the building must be sealed and the part facing
outwards must be open;
- the final section, on which the draught terminal will be fixed, must protrude from the
wall of the building for a length of at least
twice the diameter of the duct;
- the draught terminal must overlap the connection to the boiler by at least 1.5 m (see
fig. 8).
2 Ø min.
Pendenza
min. 3%
Ø
1,5 m min.
2 Ø
DIMENSIONALS FOR CONNECTING FLUE GAS DUCT
1 m max.
200
210
Ø 130
1,5 m min.
2 Ø
Ø
2 Ø min.
Pendenza
min. 3%
> 3 Ø
1 m max.
> 3 Ø
fig. 8
WARNING:
The boiler is fitted with an automatic safety
reset device as protection against spillage of
combustion products inside the building.
If this device is activated the boiler will cut off
and a fault will be indicated by the lockout
(warning light G) fig. 35.
After the cooling down of the smoke thermostat it will be possible to restart the boiler by
pressing the reset button L fig. 35.
12
It is absolutely forbidden to
by-pass the smoke thermostat.
If the boiler cuts off regularly, it
is necessary to ask a technician for a check
of the flue gas exhaust duct. This duct may
be obstructed or may be unsuitable for the
discharge of flue gas into the atmosphere.
UNICAL refuses all liability for
damage caused as a result of incorrect installation, use, modifica-
tion of the boilers or for non-observance of
the instructions provided by the manufacturer
or applicable installation regulations
fig. 9
2.2.6 - SMOKE DISCARGE AND
AIR SUCTION DUCT
CONFIGURATION
C12, C32, C42, C52, C62,
C82 - B22
C12 Boiler designed for connection to hori-
zontal exhaust and suction terminals
directly into the atmosphere
using coaxial or dual ducts. The distance between the air intake duct and the
flue gas outlet duct must b e at least
250 mm and both end sections must
be located within a 500 mm square.
C32 Boiler designed for connection to verti-
cal discharge and suction outlets directly
into the atmosphere
using coaxial or dual ducts. The distance between the air intake duct and the
flue gas outlet duct must b e at least
250 mm and both end sections must
be located within a 500 mm square.
Installation info
type
C12
type
C32
type
C42 Boiler designed for connection to col-
lective chimneys including two ducts,
one for the suction of combustion air and the other for the exhaust
of the combustion products,
through coaxial or dual ducts.
The chimney must comply with relevant applicable law provisions.
C52 Boiler with separate combustion air
suction and combustion product
exhaust ducts.
These ducts can discharge into areas with different pressure.
The dual ducts must not be located
on two opposite walls.
C62 Boiler that has to be connected to a
system of air supply and smoke of approved type and sold apart.
C82 Boiler designed for connection to an air
supply terminal and fitted to an individual or shared chimney.
The chimney must comply with relevant applicable law provisions.
C42
type
C52
type
C62
B22 Boiler designed for connection to an
external flue gas evacuation duct, with
the air for combustion taken from the
room in which the boiler is installed.
For this type of installation the boiler
house follows the same installation requirements used for the open type boilers.
Note: type B22
is not approved by
Turkish market.
type C82
type B22
SEPARATE
13
Installation info
2.2.7 - POSITIONING OF TERMI
NALS FOR TYPE ‘’C’’
BOILERS
Pursuant to the directives of regulations in
force, discharge of forced draught boilers can
POSITIONING OF TERMINALS FOR "FORCED DRAUGHT" BOILERS
POSITIONING OF THE TERMINALdistances in mm.
Under a windowA600
Under a ventilation openingB600
Under a gutterC300
Under a balcony (1)D300
From an adjancent windowE400
From an adjacent ventilation openingF600
From vertical or horizontal air pipes or drains (2)G300
From an external corner of the buildingH300
From an internal corner of the buildingI300
From the ground or from another floorL2500
Between two vertical terminalsM1500
Between two horizontal terminalsN1000
From a facing front surface without opening or teminals within a radius
of 3 mt. from smoke outlet pointO2000
As above, but with openings or terminals within a radius of 3 mt. from
smoke outlet pointP3000
either take place through the roof or directly
outwards the room they are installed in. The
following distances shall be considered for
terminals proper positioning:
Min.
NOTES
(1) Terminals below a practicable balcony shall be arranged in such a way as to assure that the total run of smokes, from their outlet from
terminal up to outlet from balcony external perimeter, including the height of protection baluster, if any, is not less than 2 m.
(2) Distances of not less than 500 mm shall be adopted in placing the terminals, due to the proximity to materials subject to the action of
products of combustion such as plastic gutters or waterspouts, wooden jetties, etc.) unless adequate screeening measures are taken for
the said materials.
FLUE TERMINAL POSITIONING
14
fig. 10
2.2.8 - SMOKE EVACUATION Ø 80
WITH AIR SUCTION
FLANGE - Type B22
(see par. 2.2.6)
Note: For evacuation system with 80 mm dia.
and a lenght between 0.5 m and 4 m, it
is necessary to introduce a diaphragm
of 44 mm dia. supplied with the boiler in
the plastic bag, into the fun outlet adap-
tor (see fig. 11).
The maximum allowed length for a smo-
ke pipe of Ø80 mm dia. is 20 m (for
IVEN 04 RTFS 24 e IVEN 04 CTFS 24
F) and 25 m (for IVEN 04 RTFS 24 e
IVEN 04 CTFS 28 F), included a wide
radium curve and one smoke terminal.
For this type of installation the chim-
ney has to serve just one boiler, i.e. the
boiler must have its indipendent smo-
ke duct.
Installation info
Diaphragm
Ø 44 mm
fig. 11
WARNING:
For the installation where there
is a freezing risk it is dia. suggested to insulate the smoke
both in case it discharges from a vertical wall
or in a chimney.
duct 80 mm on all its length,
Fitting of the diaphragm Ø44
fig. 12
15
Installation info
2.2.9 - DISCHARGE OF FLUE
GAS INTO
COAXIAL DUCTS
Ø 100/60 mm
Typ e C1 2
The minimum length of horizontal co-axial
ducts is 0.5 metres. The maximum allowable
length of horizontal co-axial ducts is 3 me-tres; for each additional bend the maximum
allowable length must be reduced by 1 metre.
Moreover, the duct must have a downward dip
of 1% towards the outlet point to prevent rain
water from getting into the duct.
Up to 1 m
Ø 80/125
Up to 2 m
Typ e C3 2
The minimum length of vertical coaxial ducts
is 0.5 metres. The maximum allowable length
of vertical coaxial ducts is 4 metres excluding the stack (Ø80/125); for each additional
bend the maximum allowable length must be
reduced by 1 metre.
The diaphragm Ø 44 supplied with the boiler must be inserted in the flue gas exhaust
pipe as shown in figure 13, for installations with horizontal coaxial pipe up to 1
m and with vertical coaxial pipe up to 2 m.
VERTICAL FLUE DUCT WITH
COAXIAL DUCT Ø 80/125
Tipo C32
The minimum length of vertical co-axial ducts
is 1,2 metres. The maximum allowable length
of vertical coaxial ducts is 6 metres excluding the stack (Ø80/125); for each additional
bend the maximum allowable length must be
reduced by 1 metre.
The diaphragm Ø44 supplied with the boiler must be inserted in the flue gas exhaust
pipe, as shown in figure 14, for installations with a coaxial pipe up to 2,5 m.
Ø 60/100
Up to 2,5 m
Diaphragm
Ø 44
Rubber foam
gasket
fig. 13
Ø 80/125
Ø 80/125
16
Diaframma Ø 44 mm
Rubber foam
gasket
Diaphragm
Ø 44
fig. 14
Installation info
DIMENSIONS FOR CONNECTING TO COAXIAL FLUE GAS DUCTS
95
245
100
fig. 15
2.2.10 - FLUE GAS DISCHARGE
AND AIR SUCTION WITH
DUAL DUCTS WITH 80 mm
DIAMETER
NB: The maximum allowable pressure loss,
irrespective of the type of installation, must
not exceed 50 Pa (for per IVEN 04 RTFS 24 /
CTFS 24 F) and 60 Pa (for IVEN 04 RTFS 28
/ CTFS 28 F)
For all installations with a pressure loss of the
ducts not exceeding 20 Pa, the diaphragm
supplied with the boiler must be installed inside the flue gas outlet pipe (see fig. 16).
WARNING! In case the flue duct
has to cross walls or floors, or if
it is easily reachable, it is necessary to foresee a convenient
insulation of such a duct. The
flue duct, during the operation
of the boiler can reach temperatures higher than 120°C.
IMPORTANT
Flue gas pressure switch operation
The boiler is fitted with a device controlling flue gas pressure.
This device shuts down the boiler in the
event of a malfunction.
Up to
∆∆
∆ P = 20 Pa
∆∆
Diaphragm
Ø 44
Rubber foam
gasket
This situation is not indicated by the emergency light.
The safety device needs to be reset by
switching OFF and ON.
fig. 16
17
Installation info
DIMENSIONS FOR CONNECTING THE AIR INTAKE AND THE FLUE GAS DISCHARGE
WITH DUAL DUCTS
85
85
85
85
245
Ø 80
85
85
160
245
85
CONFIGURAZIONI RELATIVE ALLE TUBAZIONI SIA DI SCARICO CHE DI ASPIRAZIONE Ø 80
Example N.1 (fig. 18)
Primary air suction from perimeter wall and
flue gas discharge on roof.
Maximum allowable pressure loss:
50 Pa (IVEN 04 TFS 24)
60 Pa (IVEN 04 TFS 28)
Example N.1
500
>
_
fig. 17
18
Hmin. = 150 mm
fig. 18
Installation info
Example N.2 (fig. 19)
Primary air suction from perimeter wall and
flue gas discharge from the same outside perimeter wall.
Maximum allowable pressure loss:
50 Pa (IVEN 04 TFS 24)
60 Pa (IVEN 04 TFS 28)
CALCULATION OF PRESSURE LOSSES
FOR DISCHARGE AND SUCTION DUCTS
Bear in mind the following parameters when
calculating pressure losses:
- for each metre of duct with Ø 80 (both
suction and discharge) the pressure loss
is 2 Pa;
- for each 90° Ø 80 (R=D) bend with long
radius, the pressure loss is 2 Pa;
- for each 90° Ø 80 (R=½ D) bend with
short radius, the pressure loss is 6 Pa in
suction and 8 Pa in discharge;
- for the Ø 80 L = 0.5 m horizontal air inlet
terminal, the pressure loss is 3 Pa;
- for the Ø 80 L = 0.6 m horizontal
discharge end section, the pressure loss
is 5 Pa;
- 2 short radius 90° Ø 80 curves + 1
adapter Ø 80, the pressure loss is 14
Pa.
NB: These values refer to discharges through original UNICAL non-flexible and smooth
ducts.
Example N.2
Example of check using wide radius
bends:
- 2 Ø 80 long radius 90° bends + 1 adapter
Ø 80
(14 Pa)
- (TFS 28) 17 mt duct Ø 80 x 2 =
(34 Pa)
- (TFS 24) 12 mt duct Ø 80 x 2 =
(24 Pa)
135
250 min.
45
fig. 19
- 2 90° Ø 80 long radius bends x 4 =
8 Pa
- horizontal Ø 80 air inlet terminal =
3 Pa
- horizontal Ø 80 terminal =
5 Pa
Tot. pressure loss (TFS 28) = 60 Pa
Tot. pressure loss (TFS 24) = 50 Pa
2.2.11- MEASUREMENTS OF
COMBUSTION EFFICIENCY
Ducts Ø 80 type B22 (C)
Coaxial ducts (A)
Dual ducts Ø 80 (B)
To determine combustion efficiency the following measurements must be made:
- the combustion air temperature measured
in hole 2 (see fig. 20).
- the flue gas temperature and CO2 % mea-
sured in hole 1 (see fig. 20).
Make these measurements with the boiler
running in a steady state condition.
Sonda
analizzatore
C
Aria
Fumi
Fumi
1
2
Sonda
analizzatore
Sonda
analizzatore
B
A
Sonda
analizzatore
2
1
1
2
Sonda
analizzatore
Aria
fig. 20
19
Installation info
2.2.12 - CONNECTION TO THE GAS
MAINS
The supply pipe must have a section which is
the same as or greater than the one used in
the boiler.
Comply with the applicable local installation
requirements which shall be considered as
having been incorporated in full in this manual.
Before opening the internal gas supply system;
i.e. before connecting the gas meter, all seals
must be checked.
If any part of the system is concealed the seals
must be checked before the pipes are covered.
The seal test must be conducted using air or
nitrogen at a pressure of at least 100 mbar.
The commissioning of the boiler also includes the following operations and checks:
- Opening of the gas gate valve and venting
2.2.13 - HYDRAULIC CONNECTION
Before installing the boiler we recommend that
the system be cleaned to remove any impurities which could originate from components
and which could risk damaging the circulating
pump and heat exchanger.
Note: The use of solvents could damage
the components of the heating circuit.
of the air contained in the piping and appliances, proceding appliance by appliance
- Check, with the gate valve of all the appliance Off, that there are no gas leaks.
During the 2nd quarter of a hour from the
beginning of the test no pressure reduction is to be detected on the gas pressure
While connecting gas inlet pipe of the boiler to the pipe coming from
gas network, it is MANDATORY to insert a TIGHT GASKET, whose
dimensions and material must be adequate. Connection is NOT sui-
AVVERTENZA!
rantees always minimum flow rate throught
the heat exchanger, also in the case, for instance, that all the thermostatic valves fitted
on the radiators, are closed. It is possible to
adjust the by-pass by acting onto the adjusting screw (see fig. 21)
We recommend that the discharge of the safety valve mounted in the boiler be conveyed
into the sewer.
If this precaution is not taken, activation of
the safety valve may result in flooding of the
room where the boiler is installed.
table for hemp, teflon strip or similar materials
gauge. If gas leaks have to be found, use
only water soap solution or any other specific gas leak detector which can be available on the market. Never look for gas leaks using a nacked flame.
The hardness of the supply water affects the
frequency of the cleaning of the heat exchanger.
To OPEN the
By-pass
rotate the screw
anti-clockwise
PRELIMINARY OPERATIONS:
Act on the coupled spring (located in the lower
part) and remove the two screws (located in
the upper part) in order to remove the casing.
Note:The control panel can be moved in two positions beyond the normal position ‘’D’’, that is to say high
and low position, in order to make
the maintenance operations easy.
Move the control panel in the high position for
the hydraulic connection. Remove the three
screws "A" fixing the panel and then place
the panel in correspondence to the low holes
"B" and fix the panel.
After having carried out the connections, restore the panel's normal position.
HEATING
The heating flow and return must be connected
to the relevant ¾” connections of the boiler M
and R (see fig. 7).
When determining the size of the heating circuit pipes it is essential to bear in mind the
pressure losses induced by radiators, any thermostatic valves, radiator cut-off valves and
the configuration of the system.
In the boiler, onto a bass group positioned,
between the flow and return an automatic bypass device is fitted (about a differential valve with a flow rate of about 150 l/h) which gua-
UNICAL shall not be held responsible for damage caused by non-observance of this technical precaution.
D.H.W.
Outlet and inlet of D.H.W. must be connected
to the relevant ½” connections of the boiler C
and F (see fig. 7).
D
A
To CLOSE the
By-pass
rotate the
screw
clockwise
fig. 21
B
C
fig. 22
20
DIAGRAM FLOW RATE/MANOMETRIC HEAD AVAILABLE FOR THE CH SYSTEM
Note: The boiler is delivered with the by-pass in OPEN position.
fig. 23
21
Installation info
WARNING
Depending on the hardness of
the supply water, it is important to assess the convenience of installing a domestic
device to dose water treatment products which can be
used to treat the drinking water.
It is always advisable to treat
the water if the supply water has
a hardness value of more than
28°f.
As far as concerns the positioning size of the "E" stirrup, you
have to consider the template
in the figure 7 (size 730.5 mm optional kit).
2.2.14 - ARRANGEMENTS FOR A
D.H.W. TANK (for boiler types
providing only heating)
This Kit permits an only heating boiler (type
IVEN 04 RTN 24, RTFS 24 or RTFS 28.) to
produce sanitary warm water (through the use
of an external D.H.W. tank).
PRELIMINARY OPERATIONS
Act on the coupled spring (located in the lower
part) and remove the two screws (located in
the upper part) in order to remove the shell.
In order to install such a kit, you have to move
the control panel in the lower position. Then
unloose the three fixing screws "A" two on
the side and one on the back of the panel board, and place the panel in correspondence to
the upper holes "C" and fix the panel.
INSTALLATION WITH PRE-PIPING KIT
(OPTIONAL 00360808)
ARRANGEMENTS FOR A CONNECTION TO AN EXTERNAL D.H.W. TANK
If the boiler is already installed, go on with the
emptying of the boiler
- Relate for the discharge connection of the
safety valve a plastic pipe with hose adapter, whose length can
reach a drain.
- Remove the components from 1 to 6 of fig.
25/A and assemble the components from
1 to 6 contained in the kit and shown in the
fig. 25 B; also remove the minimum pressure switch from the C.H. flow group and
place it on manifold of the diverting valve.
- Connect electrically the connector from the
panel board to the actuator of the diverting
valve. See detail "F"
fig. 25.
- Connect the cable of the D.H.W. sensor
from the panel board (colour BLUE BROWN, see detail "G") to the cable of
the D.H.W.sensor kept in the kit (which has
to be placed in the sheath of the external
D.H.W. tank) through two terminals provided with the kit.
22
2
COMPONENTS TO BE ADDED
1 - ELECTRIC DIVERTING VALVE
2 - ACTUATOR
3 - FLOW PIPE TO D.H.W. TANK
4 - RETURN PIPE FROM D.H.W. TANK
5 - FLOW PIPE TO DIVERTING VALVE
6 - MINIMUM PRESSURE WITCH
2
3
6
1
4
5
B
F
G
E
fig. 25
2.2.15 - ELECTICAL CONNECTIONS
Installation info
The electrical connections of Logamax are
shown in the clause ‘’WIRING DIAGRAMS’’
(par. 2.3 - pag. 24)
The boiler must be connected to
the mains supply at
230 V - 50 Hz. This connection is
to be perfectly done, as foreseen
by the IEC and local rules and must be earthed.
This fundamental requirement for safety purposes must be checked; in case of doubt,
ask for a professionally qualified technician
to check the electrical system.
UNICAL disclaims all liability for damage or
injury caused by failure to earth the system
properly.
Gas, domestic water and central heating
pipes are not suitable for earthing purposes.
The boiler is supplied with 1.5 m long
3x0,75mm² cord.
A double pole switch with a distance between
the contacts higher than 3 mm, must be installed upstream the boiler to enable all maintenance operations to be carried out safely.
Access to the electrical terminal strip
- WARNING! Switch off the electrical sup-
ply
- Remove the casing.
- Remove the four screws (A) and the cover
(B) in order to get access to the connections area.
Connection of the ON/OFF room thermostat (RT)
- Approach the connector Y1.
- Remove the existing jumper and connect,
on its place the room thermostat cable,
passing it through one of the cable clamps avaible.
Connection of the room modulating thermostat (OT)
- Approach the connector Y1.
- Connect the room thermostat cable, passing it through one of the cable clamps
avaible.
- The modulating chronothermostat is to be
connected exactly to the same terminal of
the ON/OFF room thermostat; in this case
the jumper JP2 has to be changed of position (see. par 2.3.2).
For a multi-zones temperature control it is not
possible to install the modulating chronothermost.
A
B
Replacement of the feeding cord
Should the feeding cord be replaced, you have
to use the original cable code 00610308.
- Approach the feeding connector Y2.
- Introduce the feeding cord through the extractable cable clamp.
- Extract the connector Y2 and proceed with
the connections according to the positions
and to the colours. The female faston of
the earth wire must be introduced in the
male faston GND1.
TABLE OF RESISTANCE VALUES AS A FUNCTION OF THE TEMPERATURE
OF THE HEATING SENSOR (SR) AND D.H.W. SENSOR (SS)
Relation between the temperature (°C) and nominal resistance (Ohm)
of the heating sensor SR and D.H.W. sensor SS
Example:At 25°C, the nominal resistance is 10067 Ohm
At 90°C, the nominal resistance is 920 Ohm
23
Installation info
2.3WIRING DIAGRAM
2.3.1ACTUAL WIRING DIAGRAM
E. RIV.
OT/ RT
LPG NAT
A4
543
21
L
N
F1
21
A9
A8
6
GND5
GND4
GND3
GND2
GND1
4321
321
7
654321
CTN 24 F /
CTFS 24 F / CTFS 28 F
7
(L1)
654321
(N)
RTN 24 - RTFS 24 - RTFS 28
5
FS1
A6
1234
Y1
1
4 32
A5
Y2
A7
6
543
217
A8
A3
OTRT
JP2
765
4321
654321
A2
JP1
OT/ RT
N
A1
Y1
Y2
L
(L1 )
(N )
E. ACC. 1
BROWN
BLUE
YEL LOW-G REEN
P
TEFLON WHITE
FS1
654321
GREEN
C.H.
RED
WHI T E
D.H. W.
BROWN
BLUE
YELLOW-GREEN
M
230V-50Hz
MDV
A6
P
RTF 2 4 / RTF 28
CTFS 24 F / CTFS 28 F
BLUE
BROWN
ORANGE
BLACK
BLUE
BLACK
YELLOW-GREEN
WHITE
RED
GRE EN
BROWN
BLUE
YELLOW-GREE N
E. ACC. 2
TEFLON RED
TEFLON RED
IGNITION
TRASFORMER
SUPPLY
GIA /V ER
(V2)
VALVE
(L2)
(L1)
C
NCNA
N
VPV
L
MODU LATING
PE
VG
(V1)
VALVE
SAFETY
tank)
SS= D.H.W. sensor (only for CTN-CTFS)
SS *= D.H.W. sensor (only for boiler with external D.H.W.
MVD=Motor 3 way valve (optional for only heating boiler).
A5
5432154321
IGT
P5
MI N
P4
Max P
P3
DHW
P2
SW2
SW1
RESET
SWEEPER
LOCKOU T
LD4
FLAME
LD3
CH
LD2
A4
RTN 24 / CTN 24 F
4
321
RFT 24 F / RFT 28
CTFS 24 F / CTFS 28 F
4
321
RTN 24/ CTN 24 F
A3
ON
CH
LD1
P1
543216
RTN 24 / RTFS 24
A2
54321432 1
6
CTN 24 F /
CTFS 24 F / CTFS 28 F
WHI TE
TA
21
A7
BLU
BROWN
N
L
YELLOW-GREEN
POWER S UPPLY
230 V - 5 0 H z
NERO
BLUE
BLUE
WHITE
WHITE
BLUE
BLUE
TLTFTL
V= Fan (only for TFS)
WHITE
WHITE
BROWN
WHITE
BROWN
BLUE
BLAC K
RED
RED
BROWN
WHI T E
BLACK
1
BROWN
NA
COM
BROWN
BLU E
SS *
SSFLSRDK
2
IG
LEGENDA
A1...A8 = Connectors
(only for TN)
PV= Fan pressure switch (only for TFS)
TL=H.L. Thermostat
TF= Flue-gas spillage thermostat
P= Circulating pump
DK= Minimum water pressure switch
SR= C.H. sensor
FL= Rotary flow switch (only for CTN-CTFS)
Y1= Room thermostat 24 V connector
Y2= Electrical supply connector
IG= ON/OFF switch
TA= Room thermostat (optional)
VG= Gas valve
E. RIV = Ionisation electrode
E. ACC = Ignition electrode
fig. 26
24
2.3.2 - JUMPER LOCATION
They are placed on the modulation card and
their purpose is to settle basic operational functions.
In order to get access to the jumper:
- WARNING! switch off electrical supply.
- Remove the casing.
- Remove the four screws (A) and the cover
(B) in order to get access to the connections area.
A
B
LPG
LPG
JP1
NA T
NA T
JP1:For nat. gas boilers, the jumper is on
NAT.
For LPG boilers, the jumper is on LPG.
Installation info
RT
RT
JP2
OT
OT
JP2: SETTLEMET OF THE CHRONOTHERMOSTAT TYPE
For modulating chronothermostat the jumper
is on OT
For ON / OFF thermostat (delivery condition)
the jumper is in RT.
2.4 - FILLING THE
SYSTEM
EAfter completing all the connections of the
system the heating circuit can be filled.
This filling operation must be performed with
care as follows:
- open the air vents of the radiators and check that the automatic air vent in the boiler
is works properly;
- gradually open the water tap and check
operation of any automatic air vents installed in the system;
- close the air vents on the radiators as soon
as water comes out;
- use the pressure gauge on the boiler to
check that the pressure has reached the
value of 0.8/1bar;
- close the water inlet tap and then release
the air again through the radiator air vents;
- after switching on the boiler and after the
system has reached the correct temperature, stop the pump and repeat the air relief operations;
- let the system cool down and then adjust
the water pressure to 0.8/1 bar.
WARNING
The minimum water pressure
switch does not give electrical
impulse to the burner to ignite when the pressure is lower than 0.4 bar. The pressure of the
water in the C.H. system must not be lower
than 0.8/1bar; if this value is lower use the
water filling tap on the boiler to adjust the pressure.
This must be performed when the system is
cold. Use the temperature and pressure gauge on the boiler to read the pressure value of
the circuit.
NB: After a given period of inactivity and
without electrical supply the pump could be
blocked.
Before switching on the boiler it is important
to restart the pump as follows: loosen the protection screw in the centre of the pump motor,
insert a screwdriver in the hole and then manually rotate the pump shaft clockwise.
Once the pump has been restarted tighten the
protection screw and check that there are no
water leaks.
WARNING
Once the protection screw has been removed
a little water may leak out. Before replacing
the casing of the boiler dry any wet surfaces.
FILLING TAP
fig. 27
2.5 - STARTING THE BOILER
PRELIMINARY CHECKS
Before starting the boiler check that:
- the boiler installation has been made in
accordance with all the applicable regulations concerning water and gas installation,
smoke evacuation and electrical installation
- the flue gas exhaust duct and its terminal
are installed correctly: when the boiler is
switched on there must be no leakage
of any combustion products from any
seals;
- the supply voltage of the boiler is 230 V50 Hz;
- the system is correctly filled with water
(pressure at the gauge 0.8/1 bar);
- any gate valves taps of the system are
open;
- the mains gas corresponds to that with
which the boiler has been calibrated: otherwise, convert the boiler to use the gas
available (see section: “MODIFICATION
FOR OTHER GASES “): this operation
must be performed by qualified technicians;
- the gas supply tap is open;
- there are no gas leaks;
- the external mains switch is on;
- the boiler’s safety valve is not locked;
- there are no water leaks.
SWITCHING ON AND OFF
To switch on and off the boiler follow the indications in the “Users’ Instructions”.
25
Adjustment info
2.6ADJUSTING THE
BURNER
All the instructions below are for the exclusive use of qualified technicians.
All the boilers leave the factory calibrated and
tested.
If it is necessary to change the calibration following changes in the type of gas or adaptation to the supply network conditions, it is
necessary to recalibrate the gas valve.
To correctly regulate the gas valve, follow the
steps below:
1) Maximum output adjustment
- check the value of the supply pressure (see
table NOZZLES - PRESSURES);
- Unloose the screw ''D'' on the pressure test
nipple downstream the gas valve (fig. 30)
and connect a pressure gauge as shown
in figure 30;
- set the ''B'' knob (onto the panel board) to
max. position (fig.35);
- check that the room thermostat contact
TA is closed;
- Switch on the power supply to the boiler
and depress the ''chimney sweeper'' switch
''H fig. 35'' on the panel board: in this way
the boiler will operate at maximum output;
- when the burner is ignited, check that the
“MAXIMUM” pressure value corresponds
to that indicated on the table “NOZZLES PRESSURES”: if it does not, correct it by
removing the screw plug “A” (fig. 28) and
by turning screw “B” (fig. 29) CLOCKWISE
to increase, and ANTICLOCKWISE to decrease
Pressure
test nipple
upstream
gas valve
Pressure test
nipple ''D''
downstream
gas valve
Plug of max pressure
adjust screew
A
fig. 28
Maximum pressure
adjust screw ''B''
B
fig. 29
PRESSURE TEST
NIPPLE
D
fig. 30
2) Minimum output adjustment
- Depress a second time the ''chimney swee-
per'' switch ''H fig. 35'' on the panel board:
in this way the boiler will operate at minimum output;
- when the burner is ignited, check the “MI-
NIMUM” pressure value corresponds to that
indicated in the table “NOZZLES - PRESSURES ”;
- correct the value, if necessary, turning the
MIN GAS potentiometer 2 on the PCB
using a screwdriver (see fig.31).
3) Completion of the basic adjustement
- check the minimum and maximum pres-
sure values of the gas valve;
- if necessary make any fine adjustments
- Disactivate the ''chimney sweeper'' func-
tion switching Off and On again through
the ‘’A’’ switch fig. 35.
- Remove the plastic pipe from pressure test
nipple and close the inner screw;
- Using a soapy solution check for gas
leaks.
CLOCKWISE
ANTICLOCKWISE
1
CLOCKWISE
2
3
ANTICLOCKWISE
CLOCKWISE
ANTICLOCKWISE
26
1
2
3
fig. 31
2.7 - MODIFICATION FOR
OTHER GASES
Adjustment info
The boilers are manufactured for the type of
gas specifically required upon order.
Any subsequent conversion must be performed by qualified technicians who will use the
kits supplied by Unical and perform the conversion and required adjustments for correct
preparation of the boiler for use.
To convert the boiler from one type of gas to
another proceed as follows:
for conversion from natural gas to LPG
- remove the main burner;
- disassemble injectors “1” (fig. 32) of the
main burner and replace them with those
with a diameter corresponding to the new
type of gas (see table “INJECTORS PRESSURES”);
- reassemble the main burner;
- position the jumper on the modulation PCB
in the panel board as shown in fig. 33
- remove plug ‘’A’’ (fig.28) on the gas valve
and fully tighten max pressure adjustment
screws ‘’B’’ (fig.29)
- check the pressure value upstream the gas
valve (see table “INJECTORS - PRESSURES”) and adjust the pressure of the burner as indicated in section “ADJUSTING
THE BURNER”
- check that the burner is functioning pro-
perly;
- check that there are no gas leaks.
- tighten the plug ”A” (fig.28) of the max
pressure adjustment screw
- when the conversion is completed, fill in
label supplied with the kit with the information required and stick it onto the boiler
alongside the data plate.
for conversion from LPG to natural gas
- remove the main burner;
- disassemble injectors “1” (fig. 32) of the
main burner and replace them with those
with a diameter corresponding to the new
type of gas (see table “INJECTORS PRESSURES”);
- reassemble the main burner;
- position the jumper on the modulation PCB
in the panel board as shown in figure 33;
- remove plug ‘’A’’ (fig.28) on the gas valve
- check the pressure value upstream the gas
valve (see table “INJECTORS - PRESSURES”) and adjust the burber pressure as
indicated in section “ADJUSTING THE
BURNER”;
- check that the burner is functioning properly;
- check that there are no gas leaks.
- tighten the plug “A” (fig.28) of the max
pressure adjustment screw;
- when the conversion is completed, fill in
label supplied with the kit with the information required and stick it onto the boiler
alongside the data plate.
The pressures at the burner indicated in the following table must be checked after the boiler has been operating for 3 minutes.
Tipe of
gas
Natural gas
Propan
Butan
Tipe of
gas
Natural gas
Propan
Butan
Tipe of
gas
Natural gas
Propan
Butan
Nominal
Output
(kW)
10,07 - 23,88
10,07 - 23,88
10,07 - 23,88
Nominal
Output
(kW)
9,95 - 23,94
9,95 - 23,94
9,95 - 23,94
Nominal
Output
(kW)
9,8 - 27,45
9,8 - 27,45
9,8 - 27,45
Nominal
input
(kW)
11,5 - 26,5
11,5 - 26,5
11,5 - 26,5
Nominal
input
(kW)
11,5 - 26,5
11,5 - 26,5
11,5 - 26,5
Nominal
input
(kW)
11,5 - 30,5
11,5 - 30,5
11,5 - 30,5
IVEN 04 CTN 24 F - IVEN 04 RTN 24
Supply
pressure
(mbar)
20
37
28-30
IVEN 04 CTFS 24 F - IVEN 04 RTFS 24
Supply
pressure
(mbar)
20
37
28-30
IVEN 04 CTFS 28 F - IVEN 04 RTFS 28
Supply
pressure
(mbar)
20
37
28-30
Ø
Nozzles
(mm)
1,25
0,75
0,75
Ø
Nozzles
(mm)
1,25
0,75
0,75
Ø
Nozzles
(mm)
1,25
0,78
0,78
No. of
Nozzles
14
14
14
No. of
Nozzles
14
14
14
No. of
Nozzles
14
14
14
Diaphragme
Diaphragme
Diaphragme
Ø
(mm)
-
-
-
Ø
(mm)
-
-
-
Ø
(mm)
-
-
-
Burner pressure
min.
(mbar)
2,1
6,4
4,6
Burner pressure
min.
(mbar)
2,0
6,2
4,8
Burner pressure
min.
(mbar)
2,1
4,4
3,7
max
(mbar)
11,0
32,1
25,8
max
(mbar)
10,8
35,3
27,1
max
(mbar)
13,8
35,5
27,4
consump-
1,22 m³/h
0,89 kg/h
0,91 kg/h
consump-
1,22 m³/h
0,89 kg/h
0,91 kg/h
consump-
1,23 m³/h
0,89 kg/h
0,91 kg/h
Gas
tion
min.
Gas
tion
min.
Gas
tion
min.
Gas
consump-
tion
max.
2,80 m³/h
2,06 kg/h
2,09 kg/h
Gas
consump-
tion
max.
2,80 m³/h
2,06 kg/h
2,09 kg/h
Gas
consump-
tion
max.
3,24 m³/h
2,37 kg/h
2,40 kg/h
27
Adjustment info
2.8ADJUSTEMENT OF
THE OUTPUT TO
THE C.H. SYSTEM'S
NEEDS
Connect the pressure gauge to the burner as
previously shown in fig. 30, switch on the boiler in heating mode and proceed as follows:
- Wait about 50 sec. to allow the burner pres-
sure to reach the standard operating value.
- Check the pressure value and through the
diagrams of fig. 34 estimate if the boiler
output is correct for heating needs.
- If not, act on the adjuster ''1 CH-POWER''
(fig. 31) on the panel board and turn it to
reach the desired value (clockwise to increase, or anticlockwise to reduce the
pressure).
- Then establish the pressure value corre-
sponding to the required output.
Example:
Assuming that the heating system which is
using a IVEN CTN 24 F boiler has a total absorption of 17 kW. Using the graph ‘’A’’ in fi-
gure 34 it is possible to determine the burner
pressure, which will be:
GAS PRESSURE BURNER DIAGRAM CORRESPONDING TO
THE SYSTEMS OUTPUT
IVEN 04 CTN 24 F - IVEN 04 RTN 24 (A)
30
25
24, 0 3
20
15
Output kW
10,01
10
5
0
0123456789
Natural gas G20 - 20 mbar
0
Propan 37 mbar
0
2,1
6,9
10
5
5,3
15202530
10
5 10152025303540
Butan 28-30 mbar
IVEN 04 CTFS 24 F - IVEN 04 RTFS 24 (B)
30
25
24,5
10,4
11
34,2
3540
27,6
12131415
- 6,18 mbar if the boiler runs on natural gas
- 20,5 mbar if the boiler runs on propan gas.
- 16,3 mbar if the boiler runs on butan gas.
Acting on potentiometer 1 - CH POWER set
the pressure resulting from the diagram.
20
15
10
Output kW
9,95
5
0
0123456789
Natur al G20 - 20 mbar
0
Propan 36 mbar
0510152025303 5
Butan 28-30 mbar
1,710,6
10
5
4,8
20253 03 5
15
10
11
27,3
IVEN 04 CTFS 28 F - IVEN 04 RTFS 28 (C)
30
28
25
20
15
Output kW
10
9,8
5
0
0123456789
1,7
11
10
Natur al gas G20 - 20 mbar
12131415
40
12131415
13,8
28
0
Propan 36 mbar
0
Butan 28-30 mbar
510
3,6
5
1520
1015
25
3035
2025
27,5
fig. 34
Service info
2.9FINDING CHART AND CORRECTIVE ACTIONS
In the table of faults and corrective actions, we intend to give some technical informations related to the solution of faults wich can happen
during the operation or the putting into operation.
BOILERS STATUS
The boiler is in lock-out position and the red
light G is on.
INCONVENIENT:
The burner does not ignite because there
is no spark at the ignition electrodes
After the removal of the fault’s cause press
the reset button on the control panel to restore
The boiler is in lock-out position and the red
light G is on.
INCONVENIENT:
The burner does not ignite even if there is
the spark at the ignition electrode
After the removal of the fault’s cause press
the reset button on the control panel to restore
The boiler is in lock-out position and the red
light G is on.
INCONVENIENT:
The burner ignites for a few seconds and
then goes out
After the removal of the fault’s cause press
the reset button on the control panel to restore
POSSIBLE CAUSES
a) The ignition transformer is faulty
b) The ignition leads are interrupted or discon-
nected
c) The ignition electrodes have the insulator
broken or are in short circuit with earth
d) The electronic board is faulty
a) The gas shut-off valve is closed
b) The plug to the gas train is not connected
c) the soft light is incorrectly adjusted
d) The gas train is faulty
a) The detection electrode cable is faulty or not
connected
b) The detection electrode is broken inside the
insulator (if only the insulator is broken does
not matter)
c) The detection electrode is in short circuit with
earth
d) The input at the minimum rate is not enough
e) The PCB does not detected the flame
SOLUTIONS
a) Replace the transformer
b) Reconnect or replace the ignition leads
c) Replace the electrode(s)
d) Replace the electronic PCB
a) Open the gas shut-off valve
b) Plug the pluginto the gas train
c) Adjust the pot.meter nr. 3 in a clock wise
direction to increase in anticlockwise direction to decrease the gas quantity during ignition.
d) Replace the gas train
a) Reconnect or replace the cable
b) Replace the electrode
c) Reposition the electrode
d) Check the burner input at minimum rate
e) Replace the electronic PCB
The boiler is in lock-out position and the red
light G is on.
INCONVENIENT:
The boilers does not try to make the ignition procedure because:
- The smoke thermostat has cut the circuit (only for boilers Logamax U014 - Logamax U014 K - Logamax U014 VMC - Logamax U014 K VMC)
- The H.L. thermostat has cut the circuit
After the removal of the fault’s cause press
the reset button L on the control panel to
restore
The boiler is in permanent lock-out.
The red light G in on and the green light F is
blinking
INCONVENIENTS: The smoke pressure
switch did not give the permission for the
burner ignition
Reset from this status can be done by
swtching OFF and ON the main switch A
a)* The chimney draught is not correct
b) The H.L. thermostat has cut in.
An over heating of the heat exchanger occurrend.
a)* The flue gas pressure switch is faulty.
b)* The silicon pipes are disconnected or bro-
ken.
c)* There is insufficient combustion air suction
or flue gas discharge.
d)* The fan does not work.
e)* The PCB is faulty
* These conditions are detected as ignition failure (vedi 2.10.3)
a) Check the chimney and the combustion air
intake grates
b) Check the temperature sensor and ascer-
tain that the pump is not blocked
a) Check the good operation of the air pres-
sure switch and replace if necessary..
b) Reconnect or replace the silicone pipes.
c) Check all the air/smoke ducts, clean or
replace if necessary.
d) Replace the fan.
e) Replace the electronic PCB
29
Service info
BOILERS STATUS
The boilers is in permanent lock-out. The red
light G is off
INCONVENIENT:
The heating sensor detects a temperature
higher than 81°C
The reset is automatically done after the removal of the fault’s cause.
The boiler is in permanent lock-out. The red
light G is off
INCONVENIENTS:
a) - The heating sensor detects a
temperatur lower than 2°C
b) - The D.H.W. sensor detects a temperatur higher than 62°C
c) - The PCB does not detected the presence of either or both temperature sensor
d) - e) - f) The minimum water pressure
switch does not give the burner the permission to ignite.
The boiler does not operate in D.H.W. mode
INCONVENIENT:
The D.H.W. flow switch does not operate
POSSIBLE CAUSES
a) Water does not circulate in the heating sy-
stem. Pipes are blocked, the thermostatic valves are closed or the system gate valves are
closed.
b) The circulation pump is blocked or is faulty
a) The boiler may be frozen. (2.10.7)
b) The D.H.W. sensor is faulty. (2.10.6)
c) One or both temperature sensors are discon-
nected or faulty. (2.10.5 or 2.10.6)
d) There is insufficient water pressure in the
C.H. system (2.10.2)
e) The minimum water pressure switch is
disconnected.
f) The The minimum water switch is faulty.
a) There are insufficient pressure or flow rate in
the D.H.W. system.
b) The flow switch sensor is disconnected or
faulty.
c) The flow switch is disconnected.
d) The flow switch is faulty.
SOLUTIONS
a) Check the status of the system
b) Check the pump.
a) Heat the boiler inside until the temperatu-
re exceeds 2°C.
b) Replace D.H.W. sensor.
c) Reconnect or replace it.
d) Set the correct pressure value.
e) Reconnect it.
f) Replace it.
a) Check the D.H.W. system.
b) Reconnect or replace it.
c) Reconnect it.
d) Replace it.
* These conditions are detected as error codes (see 2.10.2 - 2.10.5 - 2.10.6 - 2.10.7)
WARNINGThe adjustments of the pot. meter 1-2-3 are
THIS ADJUSTEMENTS MUST
BE CARRIED OUT SOLELY BY
TRAINED TECHNICIANS
The uncontrolled adjustment of the pot.
meter can jeopardize the correct operation of the boiler
To accede to the trimmer it is necessary to
dismantle the electrical panel
carried out by the constructor.
1. Adjustment of maximum
output in heating mode
It allows to adapt the boiler output to the actual C.H. needs by
adjusting the burner pressure:
1
By rotating the trimmer 1
clockwise the pressure increases;
By rotating anticlockwise the
pressure decreases.
2. Adjustment of the
modulation current
Allows to adjust the minimum gas
pressure
3. Adjustment of the soft
light
Allows to adjust the burner
pressure at the ignition time.
3
30
2
2.10 FAILURE CODES
Service info
In case of failure the burner is automatically switched off, and the
cobination of different LEDs on the panel board (E.F.G. see fig. 34)
show the fault code.
Each fault is characterised by a priority level: if different failures
are detected at the same time, the code of the highest priority one
is shown.
The following failure codes are recognised:
2.10.1 - LOCKOUT (priority 7)
Description:
Lockout of the flame control due to H.L. thermostat or smoke
thermostat cut-off or loss of flame signal.
2.10.2 - LACK OF WATER (priority 6)
Description:
Insufficient water pressure: intervention of minimum water pressure switch.
2.10.3 - IGNITION FAILURE (priority 5)
Description:
No flame has been detected within 20" from the start of the ignition
procedure and the burner control lockout has not intervened.
WARNING:
If within the end of the ignition there is no flame detection the
boiler goes into permanent lockout.
To reset it will be necessary to push the reset button.
LED
E
FG
CH MODE (E)
FLAME (F)
LOCKOUT (G)
LED
E
FG
CH MODE (E)
FLAME (F)
LOCKOUT (G)
LED
E
FG
CH MODE (E)
FLAME (F)
LOCKOUT (G)
Status
OFF
OFF
ON
Status
OFF
OFF
BLINK
Status
OFF
BLINK
ON
2.10.4 - WRONG FLAME DETECTION (priority 4)
Description:
False flame has been detected at ignition start-up
2.10.5 - CH TEMPERATURE SENSOR (priority 3)
Description:
CH sensor interruption or short circuit.
2.10.6 - DHW TEMPERATURE SENSOR (priority 2)
Description:
DHW sensor interruption or short circuit. This failure is not detected if DHW mode is disabled.
2.10.7 - FROST (priority 1)
Description:
Freezing of the heat exchanger is detected if CH sensor < 2°C;
ignition in inhibited until CH sensor reaches 5°C.
E
FG
EF G
E
FG
EFG
CH MODE (E)
FLAME (F)
LOCKOUT (G)
CH MODE (E)
FLAME (F)
LOCKOUT (G)
CH MODE (E)
FLAME (F)
LOCKOUT (G)
CH MODE (E)
FLAME (F)
LOCKOUT (G)
LED
LED
LED
LED
Status
OFF
ON
ON
Status
ON
OFF
BLINK
Status
BLINK
OFF
BLINK
Status
BLINK
BLINK
BLINK
31
Service info
3
USERS' INSTRUCTION
3.1 - CONTROL PANEL
IVEN 04 CTN 24 F - IVEN 04 CTFS 24 F - IVEN 04 CTFS 28 F
A =On / Off switch
B =Summer / Winter switch + C.H. tempe-
rature control
C =D.H.W. temperature control (+ Antifrost
protection
ON / OFF switch (A)
- With the switch in the I position
the electrical supply is ON
- With the switch in the 0 position the electrical supply is OFF
Summer/Winter switch + C.H.
temperature control (B)
MIN
You can select which mode to
use by turning this knob.
MAX
If the knob is in the following position – – it indicates that
the boiler is working only for do-
MIN
MAX
EF
IV E N
04
MAX
GH
of an eventual external storage tank IVEN RTN RTFS)
D =Power on lamp (green)
E =C.H. request lamp (green)
mestic hot water production
and that the temperature can
be adjusted turning knob ''C''.
If the knob is set within the range indicated by the arrow on
MIN
the illustration it means that the
boiler always gives priority to
the production of domestic hot
MAX
water (if it is requested) and
controls the temperature of the
water of the heating circuit from
a minimum of 45°C to a maximum of 78°C.
L
fig. 35
F =Burner on lamp (green)
G =Burner lockout warning lamp (red)
H =Chimney sweeper push button
L =Reset button
D.H.W. temperature control
(C) (Only for IVEN CTN/
CTFS)
If the knob is set within the
MIN
range indicated by the arrow
MAX
on the illustration it means is
possibile to adjust the domestic hot water temperature.
The temperature can be controlled from a minimum of
35°C to a maximum of 57°C.
32
Service info
D.H.W. temperature control
(C) + No Frost (Only for IVEN
MIN
RTN / RTFS when combined
with an external D.H.W. tank)
If the knob is set within the
MAX
range indicated by the arrow
on the illustration it means is
possibile to adjust the D.H.W.
temperature from a minimum
of 25°C to a maximum of
57°C.
The reference to the knob in
the position points out that the
boiler's sanitary circuit is not
in operation (in that case there is no production D.H.W.). If
in the mean time the B knob
is in the position the antifreeze protection of an external D.H.W. tank is activated.
ting request. If at the same time
there is a request for domestic hot
water the lamp switches off.
Burner ON lamp (Green) (F)
When this lamp is illuminated it
indicates that the burner is on,
both for central heating or for domestic hot water production.
Burner lockout warning lamp
(G)
The function of this lamp is to signal that the burner’s control is in
lockout position, due to
- lack of gas or
- H.L. thermostat cut-out due to an
over-heating of the boiler (95°)
In the first case, if the burner does
not fire, it will be necessary to
verify if the gas gate valve is
ture of the H.L. thermostat 95°C
to drop at least of 25 K.
Chimney-sweeper push button
(H)
This button allows the starting of
chimney-sweepers function, that
is to say that the boiler works at
maximum power (or at minimum
power) in order to allow adjustment’s operations and combustion's tests.
By pushing one time the button,
the boiler works at maximum output. ( )
By pushing the button while the
boiler works at maximum output,
the boiler will work at minimum output. ( )
open.
MIN
when a D.H.W. storage tank
is not fitted, the knob (C)
Note: for IVEN RTN/RTFS
must be positioned and
MAX
must stay onto the
symbol
In the second case due to a lack
of circulation or to an excessive
scaling deposit in the heat
exchanger the H.L. thermostat
could shut down the boiler at 95°C.
To go back to the boiler normal
operation switch OFF and ON the
boiler via the A switch.
Power ON lamp (Green) (D)
When this lamp is illuminated it indicates that the boiler
is connected to the mains supply.
CH request lamp (Green) (E)
If this lamp is illuminated it
indicates that there is a hea-
3.2SWITCHING
ON / OFF
SWITCHING ON
B
MIN
MAX
For the operation of the boiler in the WINTER
mode the knob ''B'' reference must be positioned within the range indicated by the arrow
on the figure shown above. The limit of the
arrow corresponds to the minimum and maximum temperature values of 45°C and 78°C.
Reset Button (L)
In the first case, which we previously described, in order to relight the boiler it will be necessary
to press the button (L) using a nail
or something like that.
In the second case, before pressing the button (L), it will be necessary to wait for the tempera-
Note: If a room thermostat is fitted, set it to
the desired temperature.
B
MIN
MAX
For the operation the boiler in SUMMER mode,
only for domestic hot water production, the
knob ''B'' reference has to be positioned on
the SUN and the D.H.W. temperature
value has to be adjusted using the knob ''C''.
C
D.H.W. temperature adjustment range for the models:
IVEN 04 CTN/CTFS
MIN
C
MIN
SWITCHING OFF
Switch off the boiler by acting on the switch
''A''.
MAX
D.H.W. temperature adjustment range for the models:
IVEN 04 RTN/RTFS
when conbined with an
external D.H.W. tank.
MAX
Shut off the gas cock upstream the
boiler in case a prolonged inactivity period of the same is expected.
33
Service info
3.3ANTI FROST
PROTECTION
B
MIN
MAX
The boiler is fitted with an anti-freeze system
which is automatically activated when the temperature of the boiler water drops below 6°C:
the burner is automatically switched on and
the pump started until the temperature of the
water in the boiler reaches 16°C.
C
MIN
MAX
3.4IMPORTANT
SUGGESTION
AND NOTES
The boiler must be serviced once a year by
qualified personnel.
Correct maintenance allows the boiler to work
optimally, respecting the environment and
without endangering people, animals and property.
Only qualified and technical personnel can
make adjustment onto the gas valve.
No-one, including qualified personnel, is
authorized to make modifications to the
boiler.
Check regularly the pressure of the boiler water through the pressure gauge fitted onto the
panel board, and restore it, if necessary.
If some fault appears during the operation, the
boiler is automatically put in lockout position
and the red warning lamp (G) lights. In this
case proceed as follows:
- Ascertain that the gas cock is open and that
there is gas in the gas pipe (try to ignite a gas
cooker)
- If so, wait one minute before resetting the
boiler by depressing the L push button. If the
boiler does not start and goes into lockout
position after three times, ask for a service or
for a qualified technician.
If the boiler goes into lockout position frequently, indication of a repeatetive fault in the operation, ask for a service or for a qualified technician
WARNING
In case an open flue boiler (TN) the burner
lockout can be due to the intervention of the
smoke thermostat (antispillage thermostat). In
A similar function prevent an external D.H.W.
tank from freezing when in conjunction with a
IVEN RTN-CTN if the C knob is positioned
on .
WARNING!
This anti-freezing protection
does not work when the boiler
is disconnected from the electrical supply and/or the gas is closed.
This system protects the boiler and the eventual DHW tank from the freezing, but it does
not protect the C.H. and sanitary circuits.
Moreover special anti-freeze products suitable for the multimetal installations can effectively protect the heating system from the freeze.
Do not use the anti-freeze products for car's
engines because they can damage the wa-
this case to restart the boiler it is necessary
to depress the reset push button L.
This fault, if repeated in the time, means of a
bad chimney operation. Ask a qualified technician for a check.
If the boiler remains inactive and disconnected
from the power supply for long periods it may
be necessary to unlock the pump.
This operation, which entails disassembling
the outside casing and working on internal
parts of the boiler, must be performed by qualified personnel.
It is possible to prevent the pump from
blocking by adding special filming products
suitable for multi-metal systems to the water.
If the boiler is not disconnected from the mains
power supply the pump will not block because the boiler’s PCB has an anti-jamming programme. In this case the pump goes into operation for a 5 seconds after 24 hour of inactivity.
The boiler has a temperature and pressure
gauge which allows you to check the temperature and pressure of the water in the heating
system.
The pressure of the water must be around 1
bar when the C.H. system is cold.
If this value drops then use the filling cock to
adjust to the correct value.
WARNING
After adjusting the pressure, close the tap without over-tightening
it. If the tap is not closed properly the pressure could rise, resulting in the safety valve opening and the water leaking.
ter sealing gaskets.
The anti-freeze protection system, which is
above described, can not work when, for any
reasons, there is no electricity or gas supply.
When the temperature detected by the heating sensor is under 2 °C, the boiler's operation is automatically inhibited until the temperature raises again to 5 °C.
To ascertain that the heat exchanger is not
frozen, open the warm water taps. When you
get water (cold too), you can suppose that the
exchanger is not frozen. On the contrary, when
you get no water, the exchanger is frozen. In
that case it is necessary to apply to a service
technician which. will work to thaw the heat
exchanger using a hair dryer.
WARNING
The anti-frost protection is operational only if the boiler is con-
nected to the mains supply and the gas cock
is open
Information for the user
The user can access only the parts of the boiler
which can be reached without the need for tools and/or implements: it is therefore forbidden to disassemble the outer casing of the
boiler and tamper with the interior parts.
La Unical declina ogni responsabilità per le possibili inesattezze se dovute ad errori di trascrizione o di stampa. Si riserva altresì il diritto di apportare
ai propri prodotti quelle modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche essenziali.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.