u::Lux NetCon, NetCon Power User Manual

Page 1
u::Lux NetCon & u::Lux NetCon Power
Manual
www.u-lux.com office@u-lux.com
u::Lux GmbH Rechtes Salzachufer 42 5020 Salzburg Austria
Page 2
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 2/10
Contents
General Information ................................................................................................................................................... 3
Mounting ................................................................................................................................................................... 3
Mounting order .......................................................................................................................................................... 5
Startup ....................................................................................................................................................................... 5
Startup order .............................................................................................................................................................. 5
Practical example ....................................................................................................................................................... 6
Network wiring .......................................................................................................................................................... 7
Technical Data............................................................................................................................................................ 8
Hazard warnings ........................................................................................................................................................ 9
CE – marking ............................................................................................................................................................. 9
Guarantee................................................................................................................................................................... 9
Ordering Information ................................................................................................................................................. 9
Version Management ................................................................................................................................................10
Page 3
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 3/10
General Information
The u::Lux NetCon or u::Lux NetCon Power is a 4 port, 100-Mbit/s-Ethernet Switch. The 4 ports are equipped with RJ45 jacks and have the designation LAN1 – LAN4. LAN1 and LAN2 serve for connecting up to 10 u::Lux Switches RJ45. LAN3 and LAN4 are generally used for connections to the control centre or the computer. The following details apply equally for the u::Lux NetCon and u::Lux NetCon Power, except in case of an explicit distinction between the models. The energy supply of the u::Lux NetCon is carried out via direct voltage through the connections – VCC and +VCC. The voltage has to be sufficiently filtered (max. voltage ripples 2VSS) and it must be within the following range:
u::Lux NetCon
48V DC
u::Lux NetCon Power
22V –
30V DC
Mounting
The mechanical assembly of the u::Lux NetCon is effected on a 35mm top-hat rail which has to be mounted horizontally. Therefore a flap is provided on the bottom part of the housing. If the flap is pulled forwards (screwdriver) the u::Lux NetCon can be easily placed on the top-hat rail.
Page 4
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 4/10
The installation width is 35mm. There are ventilation slots on the top and the bottom of the housing which provide heat exchange. Please note that these vents are not covered and a sufficient distance to adjacent components is kept.
The housing height is approx. 80mm. Please note that for the Ethernet-connections (on the front) there will be added approx. 50mm additionally to the housing depth. Altogether a free installation depth of approx. 130mm is necessary. Please take this into consideration when selecting an appropriate junction box (wall cabinet).
Page 5
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 5/10
Mounting order
1. u::Lux NetCon or u::Lux NetCon Power must snap into place on the top-hat rail.
2. Connect the network cable (not included in the scope of delivery) for the u::Lux Switch RJ45 to LAN1 or/and LAN2.
We recommend the use of a Patchpanel (taking into account the potential equalization) so that a shielded network cable can be lead to ground or to get a better ground-contact from the installation cable to the Patch cable. When indicated, already existing local connecting instructions must absolutely be obeyed.
3. For the control or cascading connect the network cable (not included in the scope of
delivery) to LAN3 or/and LAN4.
4. Connect the energy supply. A plug connector (Phoenix - MSTBA 2,5/ 2-ST-5,08) is included in the scope of delivery. Connect the negative supply voltage of the energy supply to Pin – VCC and the positive supply voltage to +VCC (see Chapter General Information).
Startup
After connecting the power supply all green LEDs have to illuminate. With these LEDs the presence of the following voltages is indicated:
1. Energy supply with supply voltage VCC.
2. Internal voltage generation 3,3 volts.
3. Internal voltage generation 48 volts (on ports LAN1 and LAN2).
If a network cable is connected to each of LAN1 – LAN4 and a physical connection (LINK) is established, the corresponding yellow LED illuminates permanently. As soon as there is traffic on the connection (ACTIVITY) it will be signalized by this flashing LED. Regarding the LAN ports we recommend the connection of the following network subscribers:
LAN1: is used exclusively to connect up to 10 u::Lux Switches RJ45. LAN2: is used exclusively to connect up to 10 u::Lux Switches RJ45. LAN3: is used to connect a PLC control or to connect another u::Lux NetCon Power module
(cascading) or a computer.
LAN4: is used to connect a PLC control or to connect another u::Lux NetCon Power module
(cascading) or a computer.
Startup order
1. Control of the green LED. All 4 LEDs have to illuminate.
Page 6
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 6/10
2. Control of the yellow LED. Depending on the connected network subscriber and depending on the traffic the LEDs illuminate or flash. The yellow LED must not illuminate or flash on an unoccupied port (LAN1 – LAN4).
Practical example
The installation and energy supply of 40 u::Lux Switches RJ45 is required. All u::Lux Switches RJ45 shall be connected to a control.
A maximum of 2x10 u::Lux Switches RJ45 per u::Lux NetCon Power can be supplied with energy. Therefore 2 units of u::Lux NetCon Power are required for the energy supply of all 40 u::Lux Switches RJ45. The u::Lux Switches RJ45 are connected to the ports LAN1 and LAN2 of the u::Lux NetCon Power. Both ports of LAN3 are connected to each other (cascading). One of the two LAN4 ports forms the connection to the control (PLC); the other one can be used for a connection to a computer.
If you use more than 2 u::Lux NetCon Power modules, we recommend to wire the supply connections separate to the power supply and not together as shown in the image.
Page 7
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 7/10
Network wiring
An u::Lux Switch line may not exceed the total length of 200 m because of the cable resistance (voltage drop). We recommend not exceeding the max. length of 50 m of a single sub segment.
Page 8
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 8/10
Technical Data
Supply : Direct voltage with a ripple of max. 2VSS
u::Lux NetCon
48V u::Lux NetCon Power
22V - 30V
Power consumption: max. 1,5W (without connection of u::Lux Switch RJ45) max. 48 W (with connection of 2 x 10 pieces of u::Lux Switches RJ45) Connections: 1 x supply (+VCC or –VCC, Phoenix MSTB 2,5/ 2-ST-5,08
2 x Ethernet RJ45 jacks with 48V supply (LAN1 and LAN2 -> each via Pins 4+5 [–VCC] and 7+8 [+VCC])
2 x Ethernet RJ45 jacks without 48V supply (LAN3 and LAN4) 1 x ground connection (via metal bracket on the bottom of the housing)
Displays: At the network connections per port there is a yellow LED for
„LINK“ or “ACTIVITY” and respectively a green LED for displaying the voltages VCC, 3V3 und 2x 48V.
Network: 100BaseT Ambient temperature: -10 °C to +40°C Storage temperature: -30 °C to +80°C Protection type: IP30 Protection class: III Assembly type: Vertical on horizontal top-hat rail (35mm) Installation dimensions: 95mm x 35mm x 76mm Housing materials: UPPER PART: synthetic mat. LEXAN UL94-V0, self-extinguishing
Colour: RAL 7035 light grey Ambient temperature: up to +100°C LOWER PART: synthetic mat. NORYL UL94-V0, self-extinguishing Colour: RAL 7021 black-grey Temperature range: up to +100°C FOIL: made of polyester DIN 42 115, fine grained Foil with sanded look, horizontal sanding direction
Page 9
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 9/10
Hazard warnings
Attention! Assembly and installation of electrical devices may only be performed by a qualified electrician. Strictly observe the prevailing accident prevention measures. Failure to observe the installation instructions may result in damage to the device, fire or other dangers. u::Lux NetCon or u::Lux NetCon Power are devices which do not correspond to the PoE standard.
CE – marking
The CE marking is exclusively addressed to the governmental supervising authorities of the Member States and facilitates the free movement of goods. The CE marking does not represent any guarantee of specific features.
Guarantee
The guarantee complies with the statutory requirements. Technical changes and error reserved.
Ordering Information
u::Lux NetCon Power order number 10962 u::Lux NetCon order number
Page 10
u::Lux NetCon / u::Lux NetCon Power - Manual
Version:
1.07
01.10
.2014
Page: 10/10
Version Management
Version
Date
Name
Notes
1.00 12.12
.2012 KH Creation of the document
1.01 17.12.2012
THSI
Correction
/
Release
1.02 18.12.2012
AK
Correction/Release
1.03 14.01.2013
KH
Addition
(Network connections via p
atchpanel
) 1.04 21.01.2013
KH
Addition
(Connections
) 1.05 14.01.2014
THSI
Addition
of new order numbers
1.06 07.07.2014
KH
u::Lux switch
-
> u::Lux switch RJ45
1.07 01.10.2014
AK
Contact updated
Loading...