Ultravation Ume12242t, Ume1224t, Ume19242t, Ume1924t Owner's Manual

Page 1
ULTRAMAX UME 24v
AIR DISINFECTION SYSTEMS w/ ODOR REDUCING
TECHNOLOGY (PCO)
OWNERS GUIDE
Models: UME-1224T/ UME-1924T / UME-12242T/ UME-19242T – 24VAC Power Input with Remote Mount Lamps
Page 2 – Shipping and Packing List, Safety Precautions Page 3-4 – General Application Guidelines and Recommended Installation Page 5 – Installation Steps for Remote Lamp Mounting, Remote Lamp Replacement, and External Mounting of Power Supply Page 5 – Installation Steps for Remote Lamp Mounting, Remote Lamp Replacement, and Internal Mounting of Power Supply Page 6 - Installation Steps for Re-Fresh PCO Module Page 7 - Maintenance and Troubleshooting, Power Consumption, Replacement Part Number, and Warranty
LEAVE FOR HOMEOWNER
DC-IH-0201
Page 2
Shipping and Packaging List:
UME Electrical Housing
Ultra-Ion Re-fresh PCO module w/ gasket and
UME- 1224T, 12242T, 1924T, 19242T
mounting Hardware
6- ¾ inch 5/16 self tapping sheet metal screws
Warning Label
Residential Warranty Card
**1224T and 1924T Series- One 12” or 17” T3
Lamp
**12242T and 19242T Series- Two 12” or 17” T3 Lamp
*1 or 2 T3 Lamp mounting plate w/ mounting Hardware
*1 or 2 T3 Lamp mounting bracket assembly
* Number depends on 1 or 2 T3 Lamps ** T3 Lamp gasket included
Safety Precautions:
It is recommended that this unit be installed and maintained by a trained technician:
WARNING: UV Hazard. Always protect eyes from ultraviolet light. NEVER look at UV lamps in operation. Unplug or disconnect power before re­lamping or servicing.
WARNING: Severe eye damage or temporary blinding may occur.
WARNING: DO NOT operate outside of Air Handler. Mount lamp base to duct first.
WARNING: No openings in duct are allowed which would give direct line-of-sight to the UV light.
In the event of accidental breakage or replacement of the ultraviolet lamp, please ensure that the lamp is disposed of in accordance with local and state environmental laws regarding fluorescent lamps containing mercury.
Notice:
All wiring inside of the duct or air handling system in direct line of site of the UV lamp must be shielded with aluminum foil tape or equivalent non-combustible material. When installing this unit, select a mounting location that prevents ultraviolet light exposure to plastic flexible duct liner or other plastic components with unknown resistance to ultraviolet light. Ultraviolet light may cause color shift or structural degradation of plastic HVAC components
The 24VAC units must be powered by a dedicated independent 24VAC isolation transformer with a minimum rating of 40VA or 60VA depending on specific unit power consumption (see chart on page 7).
www.ultravation.com
2
Page 3
General application guidelines for Ultramax Economy Ultraviolet air
purification systems
Ultravation manufactures several configurations
of Ultraviolet disinfection products to meet any
installation criteria. Ultravation two lamp
ultraviolet systems are designed to adequately
treat up to a 5 ton system or 3,500 sq ft.
Whenever possible use a two lamp configuration
with the longest lamp length possible for the
installation.
Ultravation suggests mounting on the exit side of
the HVAC system before the ductwork branches
off. This will ensure that the airborne
contaminants reaching the ultraviolet purification
system and the Re-Fresh Odor reduction module
have been reduced to an acceptable Micron size
by the HVAC systems filter.
Ultravation Ultramax products have been designed for peak performance in the cooler temperatures commonly found in the supply
plenum of a typical HVAC system.
www.ultravation.com
3
Page 4
y
Recommended Installation
Exclusive Re-Fresh PCO odor reduction Module - reduces odor, VOC’s and bacteria. Simply add more for greater odor reduction. Produces no ozone or other hazardous gases!
Patented T3 lamp technology provides 40% more UV than the competition
Mounting Plate with gasket material provides a safe
Patented lamp safety connection, prevents accidental exposure to harmful UV ra
s.
Heavy Duty extruded aluminum commercial grade power housing. Available in single and dual lamp configurations in a variety of incoming voltages including 24VAC and 120v (UME)
Full 10 year warranty
6 Ft. remote lamp leads
(select models)
allow for the flexibility required for most installs.
www.ultravation.com
4
Page 5
Installation steps for remote lamp mounting, remote lamp replacement, and external mounting of power supply:
1. Determine a suitable location to install unit housing. Mounting location should be of sufficient strength as to support the unit; otherwise reinforcement of the ductwork may be necessary. Lift into place against ductwork. Fasten unit in place with four self- tapping screws (supplied).
2. Select location for UV lamp module. Drill a 1” hole. Mount mounting plate over drilled hole with screws provided. Insert UV lamp module into hole. Attach to HVAC system with 2 self-drilling screws (provided).
3. Plug the rubber lamp connector fully onto the installed
UV lamp assembly. Be sure the 4 pinholes are orientated properly to the 4 mating pins of the lamp.
4. Connect power wires to 24VAC off HVAC system. THIS
SHOULD BE DONE IN ACCORDANCE WITH ALL STATE AND LOCAL ELECTRICAL AND BUILDING CODES.
Note: The T3 UV lamp assembly can be removed independently, simply by removing the 2 screws in the lamp base.
Note: the pins are in a rectangular patent and can only be mated in 2 positions. See the illustration of the T3 lamp 4-pin connector.
Installation steps for remote lamp mounting, remote lamp replacement, and internal mounting of power supply:
1. Mount power supply inside air handler out of the air stream as much as possible. Place the power supply as close to the control panel as possible for connecting to 24VAC connections.
2. To utilize the internal mounting bracket - first install the bracket inside the air handler in a location that will position the UV lamp such that it bathes the entire surface to be treated. Next plug the lamp connector onto the lamp.
Push the lamp connector and lamp into the bracket as shown. This will hold the lamp in place.
3. Connect power wires to 24VAC off HVAC system.
THIS SHOULD BE DONE IN ACCORDANCE WITH ALL STATE AND LOCAL ELECTRICAL AND BUILDING CODES.
www.ultravation.com
5
Page 6
Installation steps for Exclusive Re-Fresh PCO odor reduction Module:
1. Find a location adjacent to the UV lamps to mount the
PCO module. To activate the PCO module it requires UV light shinning on its surface. PCO module can be mounted within inches of the UV light, or if necessary the module can be within 2 ft. of direct UV light and still be activated.
2. To mount the PCO module you will need to drill one 2 1/2” diameter hole. The base plate of the module will need to be screwed to the duct or air handler with the 4 screws supplied.
3. The PCO module measures 16” inches long by 2 ½” diameter. The surface area of the module relates directly to the amount of VOC’s it can eliminate. If necessary the Module can be trimmed to a shorter length to accommodate installation in the air handler.
It is beneficial to install additional PCO modules in the area of the UV lights, thereby increasing the airborne bacteria disinfection rate and the removal of VOC’s. modules may be installed completely internally.
Also the PCO
www.ultravation.com
6
Page 7
Maintenance:
Maintenance typically consists of an annual replacement of the ultraviolet lamps. UV lamps undergo a photochemical process during operation. This slowly reduces the amount of UV light generated to disinfect against airborne pathogens.
When installing new lamps, ensure that the lamp glass is free from any fingerprints or debris, as this may alter the path of the UV energy. Use rubbing alcohol and a dry cloth to remove any surface contaminants.
Troubleshooting:
The Ultravation air disinfection equipment is designed to provide many years of trouble free operation. In the unlikely event of a problem, please contact your local dealer or Ultravation directly. Before calling for service, you should have your Model No; Serial No; Manufacturing Date.
If you are troubleshooting the unit, check the following:
Verify the unit has correct power (24VAC or 120VAC depending on Model Number used) Lamp is securely plugged into their sockets, no loose wires. If possible try new lamps in Unit to see if they light. Verify if in fact the UV lamps are on or off. Do not look at
the UV light without proper eye protection.
Power Consumption:
Model
Number of
Lamps
Power
Consumption
UME -1224T 1-12 inch straight 19 Watts (.16 A @ 24VAC)
UME -1924T 1-17 inch straight 29 Watts (.25 A @ 24VAC) UME -12242T 2-12 inch straight 38 Watts (.32 A @ 24VAC) UME -19242T 2-17 inch straight 58 Watts (.49 A @ 24VAC)
Replacement Parts:
Model
Description Replacement Part
Number
UME 12” T3 Lamp ASIH1001 UME 17” T3 Lamp ASIH1003 UME 5 Amp Fuse EL-PP-0044 UME Ultra-ion Re-fresh PCO Module 94-004
Warranty:
Ultravation warrants this product against any defects in material or workmanship for a period of 10 years after date of consumer purchase, with the exception of the Ultraviolet Lamp, which is warranted for a period of one year after date of consumer purchase.
This warranty does not include damage to the unit from accident, misuse or improper installation. If this product should become defective during the warranty period, Ultravation will elect to repair or replace the product free of charge.
Ultravation will return repaired or replaced warranted products pre-paid, provided that the product was delivered pre-paid. Ultravation shall have no responsibilities for charges incurred by the customer for installation or removal of warranted items. Liability is limited only to the replacement or repair of this product
This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. All returns must be accompanied by a return authorization number, which may be obtained by contacting Ultravation, Inc.
Ultravation, Inc. ~ P.O. Box 234 ~ 218 Jones Drive ~ Brandon, Vermont 05733 Phone: 802-247-0034 ~ Fax: 802-247-0033 ~ www.ultravation.com
The 24VAC units must be powered by a dedicated independent 24VAC isolation transformer with
a minimum rating of 40VA.
www.ultravation.com
7