INSTRUCTION MANUAL
ENGLISH
REFRIGERANT
LEAK DETECTOR
RLD10
ON
LOW BAT
HIGH
OFF
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
TABLE OF CONTENTS
INTRODUCTION ..................................................................................... 4
Features .......................................................................................... 4
Safety Notes ................................................................................... 4
INTERNATIONAL SYMBOLS ............................................................... 4
CONTROLS AND INDICATORS ........................................................... 5
OPERATING INSTRUCTIONS .............................................................. 6
Functional Description .................................................................... 6
Modes of Operation ....................................................................... 6
The LED Indicators ......................................................................... 6
MAINTENANCE ..................................................................................... 7
Periodic Service .............................................................................. 7
Cleaning .......................................................................................... 7
Cleaning and Replacing the Sensor ............................................... 7
DISASSEMBLY OF SENSOR ................................................................ 8
Calibration ...................................................................................... 8
Battery Replacement .................................................................8 - 9
TROUBLESHOOTING .............................................................................. 9
SPECIFICATIONS .................................................................................. 10
Operating Conditions ..................................................................... 10
Gasses Detected ........................................................................... 10
Physical Characteristics ................................................................ 10
Functional Characteristics ............................................................. 10
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
INTRODUCTION
The RLD10 makes pinpointing leaks as easy as one, two! Detect leaking refrigerant using the high sensitivity mode then switch to the low sensitivity mode to pinpoint its source. If background noise makes the audible tic hard to hear, you can count on the color scaled LED indicators.
FEATURES
• Auto zeros when turned on
• LED panel indicates refrigerant leak concentration
• Two position sensitivity selector
• Audible tick rate
• Long Gooseneck probe
• One-hand operation
• Automatically detects all existing refrigerant and blends
SAFETY NOTES
Before using this instrument, read all safety information carefully. In this manual the word “WARNING” is used to indicate conditions or actions that may pose physical hazards to the user. The word “CAUTION” is used to indicate conditions or actions that may damage this instrument.
NOTE: This instrument intended for use by professionals who know the hazards associated with their trade. Accordingly, this manual is oriented toward gas leak detection, not refrigerant system maintenance.
Some of the latest refrigerant systems use combustible gasses in place of halogen based gasses. We recommend that you also obtain a quality combustible gas leak detector, such as UEi’s CD100A, to determine and detect gas leaks when working with unknown substances.
WARNING
Turn this instrument off before cleaning or replacing the sensor.
Failure to do so may result in a mild electrical shock.
INTERNATIONAL SYMBOLS
4
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
CONTROLS AND INDICATORS
REFRIGERANT
LEAK DETECTOR
D
E G
RLD10
ON
LOW BAT
HIGH
LOW
OFF
F
H
I
A
B
C
A. Sensor tip guard
B. Sensor
C. Gooseneck probe
D. Earphone jack
E. Rubber boot
F. LED gas concentration indicators
G. Amplified audio gas concentration indicator
H. Power-on-indicator and low battery indicator
I. Power/mode slide switch
5
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
OPERATING INSTRUCTIONS
Functional Description
The RLD10 runs through a brief warm-up and self-calibration when it is initially turned on. Typically, you can observe the following sequence of events when the unit is turned on in fresh air:
1. The power-on indicator light glows steadily green*.
2. A single audible tic is heard. 3 The panel of light emitting diodes (LED’s) turn on and off in sequence; green,
yellow, light red, dark red (from bottom to top).
4. The bottom LED (green) flashes for about two seconds.
5. All LED’s except the power-on indicator turn off for approximately three seconds.
6. At approximately three second intervals an audible tic sounds and the lowest LED flashes.
*If the power-on indicator is a pinkish-red, the battery is becoming weak and should be replaced immediately. A low battery will adversely affect the instrument’s reliability.
Each time the instrument is put into service, you can conduct a quick functional test. Simply allow the instrument to run through its self-calibration sequence in fresh air, then expose the sensor to an uncapped permanent marker (highlighters will not work). The audio and visual indicators respond as they would if they found a small leak. Be careful not to touch the marker to the tip, or you will get a false indication until the ink dries.
Modes of Operation
Your RLD10 can operate in either high sensitivity or low sensitivity mode.
Begin using your RLD10 with the power/mode slide switch in its uppermost position. This is the instrument’s most sensitive position. Move the tip along suspect tubing, seals and fittings at a rate of approximately 1/2” to 1” per second. When the sensor in the probe tip detects a refrigerant gas, the tic rate will increase and a corresponding LED indicator will begin to increase and a higher positioned LED flashes.
To pinpoint the leak, change the power/mode slide switch position from the uppermost position to the center position. This will decrease sensitivity, allowing you to get closer to the source of the leak before a maximum concentration is indicated.
If the situation calls for quiet operation, or if background noise makes it difficult to hear the built-in speaker, you can use an earphone. The jack is on the side of the instrument. Note that listening to the earphone is very loud. Your LED indicators will continue to function as normal.
The LED Indicators
There are four LED indicators along the right side of the instrument. These indicate the relative concentration of gas detected, and directly correspond to the tic rate.
When no gas is detected, the LED panel will flash a single green LED corresponding to the occasional tic. As the sensor moves closer to the source of a gas leak, the LED that corresponds to the relative gas concentration will flash each time there is an audible tic. From bottom to top, the LED’s are green, yellow, light red, and dark red.
6
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
MAINTENANCE
Periodic Service
WARNING
Repair and service of this instrument is to be performed by qualified personnel only. Improper repair or service could result in physical degradation of the instrument. This could alter the protection from electrical shock and personal injury this instrument provides to the operator. Perform only those maintenance tasks that you are qualified to do.
These guidelines will help you attain long and reliable service from your instrument:
Calibrate your instrument annually to ensure it meets original
performance specifications
Keep your instrument dry. If it gets wet, wipe dry immediately.
Liquids can degrade electronic circuits
Whenever practical, keep the instrument away from dust and dirt that can cause
premature wear
Although your instrument is built to withstand the rigors of daily use, it can be
damaged by severe impacts. Use reasonable caution when using and storing the instrument
Cleaning
Periodically clean your instrument’s case using a damp cloth. DO NOT use abrasive, flammable liquids, cleaning solvents, or strong detergents as they may damage the finish, impair safety, or affect the reliability of the structural components.
NOTE: Certain soaps may be detected by the RLD10. Check for sensitivity before using any soap, and remove as much of the residual as possible with a damp cloth.
Do not allow moisture to directly contact the speaker just inside the face of the instrument, or enter the instrument’s housing. Remove the sensor tip guard prior to cleaning it. Rinse and dry this component thoroughly before replacing.
Cleaning and Replacing the Sensor
Although the sensor is designed to offer many years of reliable service, it may become inoperable if it becomes corroded or is otherwise physically damaged.
You can clean the sensor, once it is disassembled, using denatured alcohol on the tip assembly and a bottlebrush on the metal tip housing.
Tip guard
Metal tip housing
Sensor tip
White plastic base contact
Gooseneck
7
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
DISASSEMBLY OF SENSOR
1. Turn the instrument’s power off. Mild electrical shock may result if you make contact with the sensor while power is on.
2. Remove the tip guard from the metal tip housing by twisting it clockwise while away from the Gooseneck.
3. Remove the metal tip housing from the Gooseneck by holding the Gooseneck steady while turning the tip housing counterclockwise.
• The base contact assembly may adhere to the tip housing as it comes out. If so, the tip housing will tend to spring-back clockwise with every counterclockwise turn.
• Continue turning as described until the metal housing can be lifted away from the wand. You may have to hold it in place after each turn.
• Pull the housing up just far enough to view the insulation on the white plastic base contact.
• Grip the exposed white insulation with needle-nosed pliers, holding it firm with the Gooseneck.
• Separate the metal housing away from the Gooseneck.
4. The sensor tip will commonly remain in the metal housing, and must be forced out from the top (toward the Gooseneck end) with a toothpick or similar instrument.
Replace or clean the sensor as desired then reassemble in reverse order. Proper function depends on the unit’s electrical contacts. Make sure the tip assembly is making good contact with the base and there is good metal-to-metal contact on the tip housing-to­Gooseneck connection.
Calibration
When properly maintained, your instrument is sensitive to refrigerant leaks as small as .4 ounces per year. To ensure your instrument is performing at its peak, send it to the UEi factory or a qualified instrument calibration facility for annual certification.
Battery Replacement
Always use a fresh replacement battery of the specified size and type. Immediately remove the old or weak battery from the meter and dispose of it in accordance with your local disposal regulations. Batteries can leak chemicals that corrode electronic circuits. If your meter is not going to be used for a month or more, remove and store the battery in a place that will not allow leakage to damage other materials.
Replace battery when:
• The green “READY” light begins to glow red
• No lights or other activity occurs upon turning the instrument on
• Tic rate quickly begins to increase when no refrigerant is being detected*
*An increase in tic rate may be experienced if the unit remains on for a long period. This is a normal response to decreasing battery life. Turn the unit off and allow it to recalibrate in fresh air if this occurs.
8
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
To install a new battery, follow these procedures:
1. Remove the battery cover.
2. Remove the battery using a coin or screwdriver.
3. Replace the battery, observing indicated polarity.
TROUBLESHOOTING
If I See This Malfunction I Should Check For
Instrument does not turn on
Instrument does not tic after it is switched on, but the lights work
Appropriate indicators do not light
The tic rate does not increase when the sensor is exposed to refrigerant or other detectable gas
Tic rate increases during use
Tic rate remains fast after warm up
The green power-on indicator appears red
This unit contains no user serviceable parts beyond those listed in the table. In the event your instrument is physically damaged or does not function properly after taking the listed action, please return the instrument to UEi following the warranty and service instructions.
Battery voltage Replace low battery
Mode switch position
Earphone jack
Battery voltage Replace low battery
Airflow to sensor Clear restriction
Sensor connection
Sensor contamination Clean or replace sensor
Reduced battery voltage
Moisture in sensor cavity Disassemble and dry sensor
Moisture in sensor cavity Disassemble and dry sensor
Battery voltage Replace low battery
Battery voltage Replace low battery
Then Take This Corrective Action
Place firmly in Low or High position
Remove earphone plug or debris inserted in receptacle
Clean and tighten sensor component contacts
Cycle off (5 seconds) and back on (Recalibrates to compensate for decreasing voltage)
9
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
SPECIFICATIONS
Operating Conditions
To ensure accurate readings from your RLD10, use it only when ambient air is within this range:
Temperature: 32˚ to 120˚F Humidity: 0 to 80% RH (non condensing)
Gasses Detected
The RLD10 detects a wide variety of refrigerants. The following list represents a portion of the refrigerants and gasses detected:
R11 R12 R13 R22 R23 R113 R114 R134A R500 R502 Halons R404A SF6 Perchlorethylene Blends R410A
Physical Characteristics
Size: Height by Width by Depth (with probe wrapped around boot)
Probe length: fully extended 18 1/2” (47cm)
Weight (battery installed) 14.1 OZ (400g)
Functional Characteristics
Power requirements One 9 volt alkaline battery
Average battery life (Continuous use) Approximately 8 hours
Leak detection sensitivity
Sensor Corona discharge
Duty cycle Continuous
Typical response time
Warm up period 10 second average
Sensor output (voltage/current)
Visual level indicators
8” x 4” x 1 1/2”
.4 OZ/year (11 grams/year) R134A using LS20 leak standard
Less than 1 second (allows for 1”/sec seek rate)
A. No-load high voltage: 2500V ±10% B. Current: 24 mA C. Loaded high voltage: 2400V ±50V (loaded with 100.0 MΩ)
Four tic-rate scaled LED indicators changing from green to yellow to light red to red (indicating relative, not specific quantities)