This manual contains the description of the Innovator CU5-1800BTD/BRD ATSC
Transmitter/Regenerative Translator and the circuit descriptions of the boards, which
make up the system. The manual also describes the installation, setup and alignment
procedures for the system. Appendix A of this manual contains the system level
drawings for the Innovator CU5-1800BTD/BRD ATSC Transmitter/Regenerative
Translator. NOTE: Information and drawings on the Axciter, if part of your system, are
contained in the separate Axciter Instruction Manual.
Assembly Designators
Axcera has assigned assembly numbers, Ax designations such as A1, where x=1,2,3…etc,
to all assemblies, modules, and boards in the system. These designations are referenced
in the text of this manual and shown on the block diagram and interconnect drawings
provided in Appendix A.
The cables that connect between the boards within a tray or assembly and that connect
between the trays, racks and cabinets are labeled using Brady markers. Figure 1 is an
example of a Brady marked cable. There may be as few as two or as many as four
Markers on any one cable. These Brady markers are read starting furthest from the
connector. If there are four Brady Markers, this marker is the system number such as
system 1 or translator 2. The next or the furthest Brady Marker is the rack or cabinet
number on an interconnect cable or the board number within a tray. The next number
on an interconnect cable is the Tray location or number. The Brady marker closest to
the connector is the jack or connector number on an interconnect cable or the jack or
connector number on the board within a tray.
Figure 1: Brady Marker Identification
Drawing
Safety
The Innovator CU5-1800BTD/BRD ATSC Transmitter/Regenerative Translator systems
manufactured by Axcera are designed to be easy to use and repair while providing
protection from electrical and mechanical hazards. Please review the following warnings
and familiarize yourself with the operation and servicing procedures before working on the
system.
Read All safety Instructions – All of the safety instructions should be read and
understood before operating this equipment.
Retain Manuals – The manuals for the system should be retained at the system site for
future reference. Axcera provides two manuals for this purpose; one manual can be left
at the office while the other can be kept at the site.
Heed all Notes, Warnings, and Cautions – All of the notes, warnings, and cautions
listed in this safety section and throughout the manual must be followed.
Follow Operating Instructions – All of the operating and use instructions for the
system should be followed.
Cleaning – Unplug or otherwise disconnect all power from the equipment before cleaning.
Do not use liquid or aerosol cleaners. Use only a damp cloth for cleaning.
Ventilation – Openings in the cabinet and module front panels are provided for
ventilation. To ensure the reliable operation of the system, and to protect the unit from
overheating, these openings must not be blocked.
Servicing – Do not attempt to service this product yourself until becoming familiar with
the equipment. If in doubt, refer all servicing questions to qualified Axcera service
personnel.
Replacement Parts – When replacement parts are used, be sure that the parts have the
same functional and performance characteristics as the original part. Unauthorized
substitutions may result in fire, electric shock, or other hazards. Please contact the
Axcera Technical Service Department if you have any questions regarding service or
replacement parts.
Contact Information
The Axcera Field Service Department can be contacted by PHONE at 1-724-873-8100 or
by FAX at 1-724-873-8105.
Before calling Axcera, please be prepared to supply the Axcera technician with answers to
the following questions. This will save time and help ensure the most direct resolution to
the problem.
1. What are your Name and the Call Letters for the station?
2. What are the model number and type of system?
3. Is the system digital or analog?
4. How long has the system been on the air? (Approximately when was the system
installed?)
5. What are the symptoms being exhibited by the system? Include the current front
panel LCD readings and what the status LED is indicating on the front panel of
the tray. If possible, include the LCD readings before the problem occurred.
Return Material Procedure
To insure the efficient handling of equipment or components that have been returned for
repair, Axcera requests that each returned item be accompanied by a Return Material
Authorization Number (RMA#). The RMA# can be obtained from any Axcera Field
Service Engineer by contacting the Axcera Field Service Department at 1-724-873-8100
or by Fax at 1-724-873-8105. This procedure applies to all items sent to the Field
Service Department regardless of whether the item was originally manufactured by
Axcera.
When equipment is sent to the field on loan, the RMA# is included with the unit. The RMA#
is intended to be used when the unit is returned to Axcera. In addition, all shipping
material should be retained for the return of the unit to Axcera.
Replacement assemblies are also sent with the RMA# to allow for the proper routing of the
exchanged hardware. Failure to close out this type of RMA# will normally result in the
customer being invoiced for the value of the loaner item or the exchanged assembly.
When shipping an item to Axcera, please include the RMA# on the packing list and on the
shipping container. The packing slip should also include contact information and a brief
description of why the unit is being returned.
Please forward all RMA items to:
AXCERA, LLC
103 Freedom Drive
P.O. Box 525
Lawrence, PA 15055-0525 USA
For more information concerning this procedure, call the Axcera Field Service Department
at 1-724-873-8100.
Axcera can also be contacted through e-mail at info@axcera.com and on the Web at
www.axcera.com.
Limited One Year Warranty for Axcera Products
Axcera warrants each new product that it has manufactured and sold against defects in
material and workmanship under normal use and service for a period of one (1) year
from the date of shipment from Axcera's plant, when operated in accordance with
Axcera's operating instructions. This warranty shall not apply to tubes, fuses, batteries,
bulbs or LEDs.
Warranties are valid only when and if (a) Axcera receives prompt written notice of
breach within the period of warranty, (b) the defective product is properly packed and
returned by the buyer (transportation and insurance prepaid), and (c) Axcera
determines, in its sole judgment, that the product is defective and not subject to any
misuse, neglect, improper installation, negligence, accident, or (unless authorized in
writing by Axcera) repair or alteration. Axcera's exclusive liability for any personal
and/or property damage (including direct, consequential, or incidental) caused by the
breach of any or all warranties, shall be limited to the following: (a) repairing or
replacing (in Axcera's sole discretion) any defective parts free of charge (F.O.B. Axcera’s
plant) and/or (b) crediting (in Axcera's sole discretion) all or a portion of the purchase
price to the buyer.
Equipment furnished by Axcera, but not bearing its trade name, shall bear no warranties
other than the special hours-of-use or other warranties extended by or enforceable
against the manufacturer at the time of delivery to the buyer.
NO WARRANTIES, WHETHER STATUTORY, EXPRESSED, OR IMPLIED, AND NO
WARRANTIES OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR
PURPOSE, OR FREEDOM FROM INFRINGEMENT, OR THE LIKE, OTHER THAN AS
SPECIFIED IN PATENT LIABILITY ARTICLES, AND IN THIS ARTICLE, SHALL
APPLY TO THE EQUIPMENT FURNISHED HEREUNDER.
DO NOT ATTEMPT TO REPAIR OR TROUBLESHOOT THIS EQUIPMENT UNLESS
YOU ARE FAMILIAR WITH ITS OPERATION AND EXPERIENCED IN
SERVICING HIGH VOLTAGE EQUIPMENT. LETHAL VOLTAGES ARE PRESENT
WHEN POWER IS APPLIED TO THIS SYSTEM. IF POSSIBLE, TURN OFF
POWER BEFORE MAKING ADJUSTMENTS TO THE SYSTEM.
RADIO FREQUENCY RADIATION HAZARD
MICROWAVE, RF AMPLIFIERS AND TUBES GENERATE HAZARDOUS RF
RADIATION THAT CAN CAUSE SEVERE INJURY INCLUDING CATARACTS,
WHICH CAN RESULT IN BLINDNESS. SOME CARDIAC PACEMAKERS MAY BE
AFFECTED BY THE RF ENERGY EMITTED BY RF AND MICROWAVE
AMPLIFIERS. NEVER OPERATE THE TRANSMITTER SYSTEM WITHOUT A
PROPERLY MATCHED RF ENERGY ABSORBING LOAD OR THE ANTENNA
ATTACHED. KEEP PERSONNEL AWAY FROM OPEN WAVEGUIDES AND
ANTENNAS. NEVER LOOK INTO AN OPEN WAVEGUIDE OR ANTENNA.
MONITOR ALL PARTS OF THE RF SYSTEM FOR RADIATION LEAKAGE AT
REGULAR INTERVALS.
Personnel engaged in the installation, operation, or maintenance of this equipment are
urged to become familiar with the following rules both in theory and practice. It is the
duty of all operating personnel to be prepared to give adequate Emergency First Aid and
thereby prevent avoidable loss of life.
RESCUE BREATHING
1. Find out if the person is
breathing.
You must find out if the
person has stopped breathing.
If you think he is not
breathing, place him flat on
his back. Put your ear close to
his mouth and look at his
chest. If he is breathing you
can feel the air on your
cheek. You can see his chest
move up and down. If you do
not feel the air or see the
chest move, he is not
breathing.
2. If he is not breathing,
open the airway by tilting his
head backwards.
Lift up his neck with one
hand and push down on his
forehead with the other. This
opens the airway. Sometimes
doing this will let the person
breathe again by himself.
3. If he is still not breathing,
begin rescue breathing.
-Keep his head tilted
backward. Pinch nose shut.
-Put your mouth tightly over
his mouth.
-Blow into his mouth once
every five seconds
-DO NOT STOP rescue
breathing until help arrives.
LOOSEN CLOTHING - KEEP
WARM
Do this when the victim is
breathing by himself or help
is available. Keep him as
quiet as possible and from
becoming chilled. Otherwise
treat him for shock.
BURNS
SKIN REDDENED: Apply ice cold water to
burned area to prevent burn from going
deeper into skin tissue. Cover area with a
clean sheet or cloth to keep away air. Consult
a physician.
SKIN BLISTERED OR FLESH CHARRED:
Apply ice cold water to burned area to
prevent burn from going deeper into skin
tissue.
Cover area with clean sheet or cloth to keep
away air. Treat victim for shock and take to
hospital.
EXTENSIVE BURN - SKIN BROKEN: Cover
area with clean sheet or cloth to keep away
air. Treat victim for shock and take to
hospital.
mile (US statute) kilometer (km) 1.609347
inch (in) millimeter (mm) 25.4
inch (in) centimeter (cm) 2.54
inch (in) meter (m) 0.0254
foot (ft) meter (m) 0.3048
yard (yd) meter (m) 0.9144
mile per hour (mph) kilometer per hour(km/hr) 1.60934
mile per hour (mph) meter per second (m/s) 0.44704
pound (lb) kilogram (kg) 0.4535924
gallon (gal) liter 3.7854118
U.S. liquid
(One U.S. gallon equals 0.8327 Canadian gallon)
fluid ounce (fl oz) milliliters (ml) 29.57353
British Thermal Unit watt (W) 0.2930711
per hour (Btu/hr)
horsepower (hp) watt (W) 746
NOMENCLATURE OF FREQUENCY BANDS
FREQUENCY RANGE DESIGNATION
3 to 30 kHz VLF - Very Low Frequency
30 to 300 kHz LF - Low Frequency
300 to 3000 kHz MF - Medium Frequency
3 to 30 MHz HF - High Frequency
30 to 300 MHz VHF - Very High Frequency
300 to 3000 MHz UHF - Ultrahigh Frequency
3 to 30 GHz SHF - Superhigh Frequency
30 to 300 GHz EHF - Extremely High Frequency
LETTER DESIGNATIONS FOR UPPER FREQUENCY BANDS
LETTER FREQ. BAND
L 1000 - 2000 MHz
S 2000 - 4000 MHz
C 4000 - 8000 MHz
X 8000 - 12000 MHz
Ku 12 - 18 GHz
K 18 - 27 GHz
Ka 27 - 40 GHz
V 40 - 75 GHz
W 75 - 110 GHz
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
Regenerative Translator
Unpacking and Installation
Unpacking
Axcera certifies that upon leaving our facility all equipment was undamaged and in
proper working order. It is imperative that all packages be inspected immediately upon
arrival to verify that no damage occurred in transit to the site. Inspect all packages for
exterior damage and make note of any dents, broken seals, or other indications of
improper handling. Carefully open each package and inspect the contents for damage.
Verify that all materials are enclosed as listed on the packing slip. Report any shortages
to Axcera. In the event any in transit damage is discovered, report it to the carrier.
Axcera is not responsible for damage caused by the carrier. If the equipment is not
going to be installed immediately, return all items to their original packaging for safe
storage. Save all packing material for future use. If equipment is ever removed from
the site, the original packaging will ensure its safe transport.
Installation
The Innovator CXB Series systems are designed for simple installation. Expensive test
equipment is not required for installation and set up and to keep a system operational.
Prior to installing the product, review the following items. Check that they have been
installed, tested and/or inspected.
Building Structure
Electrical Systems
Heating and Air Conditioning
Receive Antenna or Satellite Dish and input cabling
Optional ASI to S310 Converter if needed
Transmit Antenna and output transmission line
The Innovator CXB Series systems are 17” (43.2cm) wide standard rack mountable
trays. They are supplied with side mounted Tray Slides for ease of installation and
removal. The CU5, CU30, CU50, CU100 & CU125 systems are 3 RU, 5.25” (13.3cm),
high. The CU250 and CU500 systems are 9 RU, 15.75” (40cm) high, which is 3 RU,
5.25” (13.3cm) for the CU50 driver and 6 RU, 10.5” (26.7cm) for the 250 watt or the 500
Watt Innovator CXB Series amplifier tray. The CU1000 systems are 15 RU, 26.25”
(66.7cm) high, which is 3 RU, 5.25” (13.3cm) for the CU50 driver and 12 RU, 21”
(53.4cm) for the two Innovator CXB Series amplifier trays. The CU1500 systems are 21
RU, 36.75” (93.3cm) high, which is 3 RU, 5.25” (13.3cm) for the CU50 driver and 18 RU,
31.5” (80cm) for the three Innovator CXB Series amplifier trays. The CU1800 systems
are 27 RU, 47.25” (120cm) high, which is 3 RU, 5.25” (13.3cm) for the CU50 driver and
24 RU, 42” (106.7cm) for the four Innovator CXB Series amplifier trays.
Also needed for FCC compliance operation is an ATSC filter on the broadcast channel
that connects to the output of the CU5 thru CU1800 systems. Space must be provided
for the ATSC filter and in some systems, for the splitter, combiner, and low pass filter
whose dimensions will vary depending on manufacturer and channel. Refer to the
vendor supplied information included with your ATSC filter for specific dimensions. In
the CU250 and higher power systems, a low pass filter is connected after the amplifier
tray(s) and the ATSC mask filter. Space must be provided for the low pass filter whose
dimensions will vary depending on manufacturer and channel. Refer to vendor supplied
information included with your low pass filter for specific dimensions. Make sure that
the space provided for the CX Series equipment is sufficient and includes the splitters,
combiners and external filters. Check that any additional equipment, which is included
Instruction Manual, Rev. 0 11
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
Regenerative Translator
in the system that extends above or to the side of the mounting rack, has sufficient
clearance space. Refer to the custom racking plan for the system, if prepared, for
detailed information.
Tray Slide Installation
If the system is pre-mounted in a cabinet skip this section. Locate the tray slides included
in the installation material for your system. See Figure 2 and the manufacturers
instructions, included with the tray slides, for the cabinet mounting instructions of the tray
slides. Install the left tray slide into the left side of the cabinet (as viewed from the rear).
Allow 3 RU, 5.25” (13.3cm) of space between the trays for a CU5, 30, 50, 100 or 125
systems. In high power systems, allow a space of 3 RU, 5.25” (13.3cm) for the CU50
driver and 6 RU, 10.5” (26.7cm) for each of the Innovator CXB Series amplifier trays in
higher power systems. Space must also be provided for the splitter, combiner, ATSC
filter and low pass filter, if present, whose dimensions will vary depending on the
manufacturer and the output channel.
Secure the left tray slide by connecting it to the front and rear mounting bars using No. 10
screws and the bar nuts that have been provided. Install the tray slide on the right side of
the cabinet (as viewed from the rear) making sure that it is aligned with the tray slide on
the left side. Secure the slide by connecting it to the front and rear mounting bars using
No. 10 screws and the bar nuts that have been provided. Repeat this process for any
other trays if purchased. With both slides in place, slide the tray or trays into the cabinet.
Figure 2: Chassis Trak Cabinet Slides
AC Input Connections
Refer to Figures 3 and 4 that follow for the location of the jacks and connectors of the
system. The CU3, CU30, and CU50 systems will operate with an input voltage of 85253VAC. CU100/125 systems operate on 185-253VAC. Check that the AC switch, located
on the rear of the tray above the AC power jack, is OFF. Connect the AC power cord
supplied with the tray from J6 on the rear of the tray to the AC source. If your system
has the optional ASI to S310 Converter, check that it is connected to the AC source.
If your system is a CU250 or CU500, it also contains one 250 Watt or 500 Watt amplifier
tray. In CU1000 and higher power systems, multiple 500 Watt amplifier trays are
included. Each amplifier tray is configured for 230 VAC operation only. Check that the
ON/OFF circuit breaker, located on the rear panel under the AC power jack, is OFF.
Connect the AC power cord supplied with the tray from J10 on the rear of the tray to the
Instruction Manual, Rev. 0 12
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
Regenerative Translator
230 VAC source. Refer to Table 1 for the voltage and current requirements for CXB
Systems.
Instruction Manual, Rev. 0 13
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
J1
J11
J6
J9
J8
J2
J13
Regenerative Translator
Table 1: CXB Series Digital Systems Typical AC Input and Current Requirements.
System O/P Power
CU5 10 Watts 180 Watts
CU30 30 Watts 300 Watts
CU50 50 Watts 475 Watts
Power
Consumption
Voltage Current
115 VAC 1.6 Amps to the Cabinet
230 VAC .8 Amps to the Cabinet
115 VAC 2.7 Amps to the Cabinet
230 VAC 1.4 Amps to the Cabinet
115 VAC 4.2 Amps to the Cabinet
230 VAC 2.1 Amps to the Cabinet
CU100 100 Watts 780 Watts 230 VAC 3.4 Amps to the Cabinet
CU125 125 Watts 900 Watts 230 VAC 4 Amps to the Cabinet
CU250 250 Watts 1700 Watts 230 VAC 7.4 Amps to the Cabinet
CU500 500 Watts 3400 Watts 230 VAC 14.8 Amps to the Cabinet
CU1000 1000 Watts 6300 Watts 230 VAC 27.4 Amps to the Cabinet
CU1500 1500 Watts 9700 Watts 230 VAC 42.2 Amps to the Cabinet
CU1800 1800 Watts 11000 Watts 230 VAC 47.9 Amps to the Cabinet
Input and Output Connections
The input and output connections to the system are made to the jacks mounted on the
rear panels of the CU5 thru CU125 systems, the drivers for the CU250 and high power
systems, and to the 250 Watt and 500 Watt amplifier trays. The CU5 thru CU125
systems and the drivers for the CU250 and higher power systems accept an On Channel
RF signal (BRD) or a SMPTE-310 (BTD) input and output a digital RF ON Channel signal.
Refer to Figure 3 and to Table 2 that follow for the locations and information on the jacks
and connectors.
J12
J10
Figure 3: Rear View CU5 thru CU125 and the driver for the CU250 and higher power
systems
Table 2: Connections for the CU5 thru CU125 and the driver for the CU250 & higher
power Systems
Port Type Function Impedance
J1 BNC
J2 BNC
Input A: On Channel RF Input (BRD) –78 to –8 dBm or
SMPTE-310 Input (BTD)
Input B: On Channel RF Input (BRD) –78 to –8 dBm or
SMPTE-310 Input (BTD)
AC Input: AC input connection to 85-264VAC Source and
On/Off circuit breaker
N/A
Instruction Manual, Rev. 0 14
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
J1
J3
J4
J2
CB1
CB2
J5
Regenerative Translator
Port Type Function Impedance
J11
J12
9 Pos
Male D
15 Pos
Female D
J13 RJ-45
J14 RJ-45
Power Monitoring: Interface to System and external
amplifier trays, if present. Also provides an interlock for
N/A
the Reject Load (if used).
Remote: Remote control and status indications N/A
Serial: Provides communication to System and to external
amplifier trays, if present.
Ethernet: Optional Ethernet connection. May not be
present in your tray.
N/A
N/A
J15
Front
Panel
BNC
RF Sample: Output Sample from Output Detector Board.
In a CU30, CU50, CU100 & CU125, the sample level at J15
is approximately 60dB down from the output power level of
50 Ohms
the tray.
J16
Front
Panel
9 Pos
Female D
Serial: Used to load equalizer taps into the modulator. N/A
If your CU BTD system contains an Optional ASI to S310 Converter, connect the ASI
output of the STL to the ASI in jack on the rear panel of the converter. Connect the
SMPTE-310 Output from the SMPTE 310 Out jack on the rear panel of the converter
module to the input jack J1 on the rear panel of the CU5 thru CU125 Tray and the Driver
Tray for the CU250 and higher power systems.
Figure 4: Rear View CU250 and CU500 Amplifier Tray
Table 3: Connections for the CU250 and CU500 Amplifier Tray
Port Type Function Impedance
J1 N RF Input: On Channel RF from CU driver tray 50Ω
7/16”
J2
(1.1cm)
RF Output: On Channel RF Output 50Ω
Din
J3 IEC AC Input: AC input connection to 230VAC Source N/A
J4 9 Pos D
Remote: Amplifier Control Interface
(Connects to J11 on the driver tray)
N/A
Instruction Manual, Rev. 0 15
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
Regenerative Translator
Port Type Function Impedance
J5 RJ-45 Serial data N/A
J8
Front
Panel
BNC
RF Sample: Output Sample from Combiner thru Control
Board. In a CU500, the sample level is approximately 70dB
down from the output power level of the tray.
50Ω
Refer to Figures 3 and 4, and Tables 2 and 3 for detailed information on the jacks and
connectors. Connect the On Channel RF Input (BRD), –78 to –8 dBm, or the SMPTE-310
Input (BTD), to the 50Ω BNC input jack J1, located on the rear panel of the CU5 thru
CU125 systems and the driver trays for the CU250 and higher power systems.
If used, connect the external 10 MHz reference input to the 50Ω BNC 10 MHz input jack
J6 located on the rear panel of the CU5 thru CU125 systems and the drivers for the
CU250 and higher power systems. If used, connect the external 1 PPS reference input
to the 50Ω BNC 1 PPS input jack J7 located on the rear panel of the CU5 thru CU125
systems and the drivers for the CU250 and higher power systems.
The digital RF ON Channel output of the CU5 thru CU125 systems and the driver trays is
at J9 the 50Ω “N” connector RF output jack located on the rear panel. In CU5 thru
CU125 systems, the output of the tray at J9 connects to the digital mask filter and then
to the antenna for your system. In CU250 and higher power systems, the output of the
driver tray at J9 is connected to J1 the 50 Ohm “N” connector RF input jack located on
the rear panel of the 250 Watt, 500 Watt amplifier tray or to a splitter in multiple
amplifier systems. Check that the system power metering interface cable is connected
from J11 the 9 position “D” connector located on the rear panel of the driver tray to J4
the 9 position “D” connector located on the rear panel of the 250 Watt or 500 Watt
amplifier tray. This cable provides the control, status and operating parameters of the
amplifier tray to the driver tray. The digital RF ON Channel output of the amplifier tray
is at J2 the 50Ω “7/16” (1.1cm) Din connector RF output jack located on the rear panel
that connects directly to the low pass filter, the digital mask filter and then to the
antenna for your system in single amplifier systems or to a combiner and then the low
pass filter, the digital mask filter and finally to the antenna in multiple amplifier systems.
Instruction Manual, Rev. 0 16
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Unpacking and Installation
Regenerative Translator
This page intentionally left blank
Instruction Manual, Rev. 0 17
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Initial On Site
Regenerative Translator Turn On Procedure
Initial On Site Turn On Procedure
After the Innovator CXB Series tray or trays are installed and all input, output and AC
connections are made, the system is ready for the initial on site turn on. Check that the
output of the CU5, CU30, CU50, CU100, or CU125 tray is connected to an appropriate rated
load or to the digital mask filter and the antenna for your system. If your system is a CU250
or higher power system, check that the output of the amplifier tray or the combiner assembly
is connected to an appropriate rated load or to the low pass filter, the digital mask filter and
the antenna for your system. Check that the main AC power to the System is ON.
If you have a CU5, CU30, CU50, CU100 or CU125 system, push ON the switch located on the
rear panel of the tray above the AC power jack. The large fan mounted on the rear panel of
the tray should operate. If your system is a CU250 or higher power system, switch ON the
ON/OFF circuit breakers located on the rear panel of the amplifier tray(s) mounted on each side
of the AC input power jack. The two fans mounted in the amplifier tray should operate.
The Operate/Standby LED and Status LEDs on the CU5, CU30, CU50, CU100 or CU125 should
be Green indicating the system is in Operate and performing normally. The Operate/Standby
LED showing Amber indicates the System is in Standby. The Status LED showing a blinking Red
LED indicates a Fault is occurring now. The Status LED showing Amber indicates that a Fault
occurred since the last time the Fault indications were reset.
If your system is CU250 or higher power, the Enable LED and Status LEDs on the 250 or 500
Watt Amplifier Tray should be Green indicating the system is in Operate and performing
normally. The Enable LED showing Amber indicates the System is in Standby. The Status LED
should be Green indicating no faults in system. If the Operate/Standby LED shows Amber it
indicates that the System is in Standby. If the Status LED is blinking Red it indicates a Fault is
occurring now. If the Status LED shows Amber it indicates that a Fault occurred since that last
time the Fault indications were reset. The output power is factory set according to customer
request and does not need adjusted. If a problem occurs, call Axcera field support at 1-724873-8100 for information on modifying the power level of the system.
NOTE: The RF System Interlock is provided on J12, a D connector, located on the rear panel
of the CU3, CU30, CU50, CU100 or CU125 tray. The RF System Interlock at J12-5
provides the customer with a means of connecting the system to protection circuits,
for the loads, thermal switches, combiners, or the antenna, in the output of your
system, that will place the system in Standby if the protection circuit opens. The
Reject Load Interlock at J11-6 provides the customer with a means of connecting the
system to protection circuits, for the reject load in multiple amplifier systems, which
will place the system in Standby if the protection circuit opens. If the interlocks are
not used in your system, a plug with a jumper from J11-5 to J11-9, ground, for RF
system Interlock and another plug with a jumper from J11-6 to J11-9, for Reject Load
Interlock, need to be connected. These jumpers provide the RF System and Reject
Load Interlocks, which allow the system to go to operate. Without the jumpers, the
system will remain in Standby.
Instruction Manual, Rev. 0 18
Innovator CU5-1800BTD/BRD ATSC Transmitter/ Initial On Site
Regenerative Translator Turn On Procedure
Typical System Operating Parameters
Typical Operating Parameters for a CU3
Parameter Typical Reading
Forward Power 100%
Reflected Power <5%
Power Supply Voltage 24 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Pin Attenuator Voltage 1 Volt to 5 Volts
Typical Operating Parameters for a CU30
Parameter Typical Reading
Forward Power 100%
Reflected Power <5%
Power Supply Voltage 28 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Pin Attenuator Voltage 1 Volt to 5 Volts
Typical Operating Parameters for a CU50
Parameter Typical Reading
Forward Power 100%
Reflected Power <5%
Power Supply Voltage 30 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Pin Attenuator Voltage 1 Volt to 5 Volts
Typical Operating Parameters for a CU100/125
Parameter Typical Reading
Forward Power 100%
Reflected Power <5%
Power Supply Voltage 39 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Pin Attenuator Voltage 1 Volt to 5 Volts
Typical Operating Parameters for a CU50 used as a Driver
Parameter Typical Reading
Forward Power 20-70% (Depending on output power level of system)
Reflected Power <3%
Power Supply Voltage 30 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Pin Attenuator Voltage 1 Volt to 5 Volts
Typical Operating Parameters for the external Amplifier Tray(s)
in a CU250 or higher power System
Parameter Typical Reading
Forward Power 100%
Reflected Power <5%
Power Supply Voltage 30 Volts
Heatsink Temperature 20º to 30º F above ambient temperature
Instruction Manual, Rev. 0 19
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.