Tylo 1105-120, 1105-140, 1105-105, 1105-1052, 1105-1202 Installation And Operating Instructions Manual

...
INSTALLATION AND OPERATING INSTRUCTIONS
SC Control
SET TIMER
0
50
10
40
20
30
Sauna Heating
0
SET TEMPERATURE
10
9
1
8
2
7
3
6
4
5
Room Light
TEMPERATURE CONTROL
MODEL 19-8
Listed
U
Sauna heater
L
R
No. 339 B
Contactor Box
1106-XXX
Octa Heater
CB 1201-7-1
or
CB 1201-7-3
1105-XXX
Pro Heater /
1105-XXX2
Laava Heater
Sauna Heaters
Pro 10.5, 12.0, & 14.4 (Model # 1105-105, 1105-120 & 1105-140) or Laava 10.5, 12.0, & 14.4 (Model # 1105-1052, 1105-1202 & 1105-1402) or Octa 10.5, 12.0, & 14.4 (Model #1106-105, 1106-120, & 1106-140)
(With separate SC Control panel & contactor box) Read all instructions carefully before installation. Please leave all instructions and warranty with the owner.
WARNING Prolonged exposure to elevated temperatures is capable of inducing hyperthermia. Hyperthermia occurs when the internal temperature of the body reaches several degrees above the normal body temperature of
98.6°F. The symptoms of hyperthermia include an increase in the normal temperature of the body, dizziness, lethargy, drowsiness, and fainting. The effects of the hyperthermia include failure to perceive heat, failure to recognize the need to exit the room, unawareness of impending hazard, fetal damage in pregnant women, physical inability to exit the room and unconsciousness.
WARNING The use of alcohol, drugs, or medication is capable of greatly increasing the risk of fatal hyperthermia.
Page 1
WARNING
Do not take a sauna if using
alcohol, drugs or medications.
Pregnant women or persons
with poor health should
consult their physician before
using any sauna.
Caution re hazard: Do not use
the sauna room for drying
clothes, bathing suits, etc. Do
not hang towels above heater
or place any object other than
the rocks supplied on the
heater. If any darkening of the
wall around the heater is
noticed discontinue sauna use
immediately.
Inspect sauna regularly for
required maintenance to
heater, control and benches.
Replace wood surfaces which
show any signs of
deterioration.
The heater gets extremely hot
during operation and should
not be touched or burns may
result.
Minors should be adequately
supervised whenever near a
hot or warming sauna.
SECTION 1: GENERAL INFORMATION
These heaters are ETL approved by Intertek for permanent installations and electrical connections. Built with splash proof construction, the conducting parts are protected against water. All wiring must be performed in accordance with local codes. See Table 1 for wire and room size requirements.
These heaters are free standing, secured to the oor with separate controls.
4 211-8 3-G 09 -29-1 6 70 1 402 4 314 SKLE 70 H
INSTALLATION AND OPERATING INSTRUCTIONS
Page 2
SECTION 2: MOUNTING OF SAUNA HEATER
Carefully locate the heater according to the dimensions shown in Diagram 1 and bolt it to the oor. (Bolts are not supplied with the heater.) Tighten to secure the heater in place.
SECTION 3: PLACING OF ROCKS
The rocks supplied with the heater have been chosen to provide the best heater performance. Use of any other type of rock may void the heaters warranty. Never operate the heater without rocks in place! Rinse the rocks with water before placing in the heater. Place the larger rocks between the elements and the smallest rocks between the elements and the inner rock compartment of the heater. Place the rocks loosely so the air can circulate. Continue adding rocks until there is 1 layer above the heating elements. Packing the rocks too tightly may cause the heater high limit switch to trip. Attach the rock guard with the screws provided.
SECTION 4: ELECTRICAL HOOK-UP
Electrical installation must be made by a licensed electrician in accordance with the National Electrical Code and local regulations.
This heater is intended for use with SC Controls only. Use of any other control type will void the warranty and ETL listing. The control panel and contactor box must be installed in a dry location outside the sauna room. The control panel must be located to allow installation of the thermostat's temperature sensor shown in Diagram 1. The sensor wire supplied is 9 feet, but it may be extended at the control end with 2 conductor wire.
WARNING
Fire sprinkler systems used
inside any sauna room should
be properly rated for sauna
room temperatures.
Do not pour chlorinated pool
or spa water on heater.
Excessive water use on heater
may cause damage and void
warranty.
Do not install a shower in
sauna room.
Electric Shock Hazard - High
voltage exists within this
equipment. There are no user
serviceable parts in this
equipment. All installation and
service to this equipment
should be performed by
qualied licensed personnel in
accordance with local and
national codes.
The model CB 7-3 contactor box is required for use with a three phase heater, the model CB 7-1 contactor box is required for use with a single phase heater. To determine the correct wire size, refer to Table 1. Use copper supply wire only, suitable for minimum 90 degrees C. The heater must be grounded! See the heater and control wiring diagrams for proper connections.
SECTION 5: TEMPERATURE SENSOR
Feed the "low voltage" sensor wire from the control to the sensor location. Senor wire must be routed completely seperate (as per low voltage electrical wiring codes) from any wiring carrying over 50 volts. It may be necessary to drill holes to string the wire through the studs or ceiling joists. Route wires into control box and connect to terminals #2 and #3 at the thermostat terminal block. Using a at tip screwdriver, unsnap sensor cover from sensor as shown in Diagram 2. Mount sensor horizontally to the nished wall directly above heater using two (2) screws (provided) as shown in Diagrams 1 & 3.
SECTION 6: HEATER SCREEN (GUARD RAIL)
Install a wooden heater guard to prevent the sauna bather from accidentally touching the sauna heater. Install the heater guard rail with the height clearances and dimensions shown in Diagram 1.
Do not construct sauna room
so as to restrict air ow
through the bottom of the
heater.
Packing the rocks too tightly
may cause the heater high
limit switch to trip.
4 211-8 3-G 09 -29-1 6 70 1 402 4 314 SKLE 70 H
49½"
min.
INSTALLATION AND OPERATING INSTRUCTIONS
DIAGRAM 1
Pro Heater
1105-XXX
2"
5"
min.
Sensor
78"
min.
5"
min.
High Limit Control Reset
1x1"
wooden
2½"
post
min.
¾ x 4"
wooden
2½"
rail
min.
Page 3
BOLTS
27"
max.
OBSERVING MINIMUM DISTANCES IS REQUIRED TO REDUCE THE RISK OF FIRE
Locate the sensor 2" from ceiling directly above the heater.
Room light outlet box
70" up from the floor.
Locate the control outside the sauna room.
Locate CB 7-1 or 7-3 contactor box outside the sauna room. (See Note 1)
Power input to
contactor box.
Note 1: The contactor box may be mounted anywhere outside the sauna room. A location should be selected so the front cover is accessible for service and the noise of the contactor pulling in will not be a nuisance.
4 211-8 3-G 09 -29-1 6 70 1 402 4 314 SKLE 70 H
Provide a service loop into the sauna room to the proposed heater location.
High Limit Reset
49½"
min.
INSTALLATION AND OPERATING INSTRUCTIONS
DIAGRAM 1
Laava Heater
1105-XXX2
2"
4-1/2"
min.
Sensor
78"
min.
2"
min.
High Limit Control Reset
1x1"
wooden
1"
post
min.
¾ x 4"
wooden
1"
rail
min.
Page 4
BOLTS
27"
max.
OBSERVING MINIMUM DISTANCES IS REQUIRED TO REDUCE THE RISK OF FIRE
Locate the sensor 2" from ceiling directly above the heater.
Room light outlet box
70" up from the floor.
Locate the control outside the sauna room.
Locate CB 7-1 or 7-3 contactor box outside the sauna room. (See Note 1)
Power input to
contactor box.
Note 1: The contactor box may be mounted anywhere outside the sauna room. A location should be selected so the front cover is accessible for service and the noise of the contactor pulling in will not be a nuisance.
4 211-8 3-G 09 -29-1 6 70 1 402 4 314 SKLE 70 H
Provide a service loop into the sauna room to the proposed heater location.
High Limit Reset
INSTALLATION AND OPERATING INSTRUCTIONS
DIAGRAM 1 Continued
Octa Heater
Page 5
46¾"
min
2"
Sensor
BOLTS
30"
max.
78"
min.
High Limit Control Reset
3
1/4
min.
3
1/4
"
¾
"
min.
"
1x1"
wooden
post
min.
¾
min.
"
¾ x 4"
wooden
rail
OBSERVING MINIMUM DISTANCES IS REQUIRED TO REDUCE THE RISK OF FIRE
Locate the sensor 2" from ceiling directly above the heater.
Room light outlet box
70" up from the floor.
Locate the control outside the sauna room.
Locate CB 7-1 or 7-3 contactor box outside the sauna room. (See Note 1)
Power input to
contactor box.
Note 1: The contactor box may be mounted anywhere outside the sauna room. A location should be selected so the front cover is accessible for service and the noise of the contactor pulling in will not be a nuisance.
High Limit Reset
4 211-8 3-G 09 -29-1 6 70 1 402 4 314 SKLE 70 H
Provide a service loop into the sauna room to the proposed heater location.
Loading...
+ 10 hidden pages