* Hyperthermia occurs when the internal temperature of
the body reaches a level several degrees above the normal
temperature of 98.6° F. The symptoms of hypothermia include
an increase in the internal temperature of the body, dizziness,
lethargy, drowsiness and fainting. The eff ect of hyperthermia
include:
a) Failure to perceive heat;
b) Failure to recognize the need of exit the room;
c) Unawareness of impending hazard;
d) Fatal damage of pregnant women;
e) Physical inability to exit the room; and
f) Unconsciousness
• Do not take a sauna if using alcohol, drugs or medications.
• Pregnant women or persons with poor health should consult their physician before using any sauna.
• Caution fi re hazard: Do not use the sauna room for drying
clothes, bathing suits, etc. Do not hang towels above
heater or place any object other than the rocks supplied
on the heater. If any darkening of the wall around the
heater is noticed discontinue sauna use immediately.
• Inspect sauna regularly for required maintenance to heater, control and benches. Replace wood surfaces which
show any signs of deterioration.
GENERAL INFORMATION .................................................. 12
PRIOR TO USE ..................................................................... 12
The fi rst time you use the heater ............................ 1 2
Prior to each use .................................................... 12
USE ........................................................................................ 13
The control panel in general.................................... 13
Water reservoir........................................................ 13
Other functions........................................................ 13
• Electric Shock Hazard - High voltage exists within this
equipment. There are no user serviceable parts in this
equipment. All installation and service to this equipment
should be performed by qualifi ed licensed personnel in
accordance with local and national codes.
• Do not construct sauna room so as to restrict air fl ow
through the bottom of the heater.
• Packing the rocks too tightly may cause the heater high
limit switch to trip.
• Maintain minimum clearance from heater to wooden surfaces (benches, side walls, heater fence etc.). Mounting
brackets supplied. Provides proper clearance from wall
behind heater.
• Use only copper wire of the size and type indicated in the
Heater Specifi cation Chart and the temperature rating
indicated on the heater junction box.
• A guardrail or fence is required around the heater to prevent burns from accidental contact.
• The heater gets extremely hot during operation and
should not be touched or burns may result.
• Minors should be adequately supervised whenever near a
hot or warming sauna.
• Fire sprinkler systems used inside any sauna room should
be properly rated for sauna room temperatures.
• Do not pour chlorinated pool or spa water on heater.
Excessive water use on heater may cause damage and
void warranty.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a person responsible for their
safety. Children should be supervised to ensure that they
do not play with the appliance.
• All heaters and controls must be grounded per NEC to
prevent electrical shock in case of unit failure.
• Electrical outlets or receptacle must not be installed in a
sauna room.
• Do not locate benches over heater.
• For household only.
Keep this user guide!
In the event of any problems, please contact the retailer where you purchased the equipment.
Check that the following parts are included in the packaging:
15
16
12
13
3
2
4
11
14
17
18
1
19
Elite
Pure
20
WiFi
23
21
24
6
5
22
7
10
9
8
26
25
Control panel Pure is supplied with Sense Combi Pure.
Control panel Elite WiFi is supplied with Sense Combi Elite.
See separate guides.
Installation requirements
To ensure safe use of the heater, check that the following criteria
are met:
• Electrical wiring should be installed in accordance with NEC
and all state and local codes.
• Fuse size (A) and power cable size (AWG) must be suitable
for the heater (see The section called Connection/wiring
diagram, Page 9.
• The sauna ventilation must comply with the instructions in
this manual (see The section called Positioning the inlet vent,
Page 5, The section called Positioning the outlet vent, Page
5).
• The position of the sauna heater, control panel, and sensors
must comply with the instructions in this manual.
• The heater output (kW) must be suitable for the sauna
volume (cu.ft.) (See Table 1, Page 3). The minimum and
maximum volumes must not be exceeded.
• NOTE: A GFCI device is not required by ETL. A GFCI may
be installed if required by local codes. However, GFCI devices will tend to nuisance trip during use of the product.
Table 1: Voltage and sauna volume
ModelVoltageSauna volume
Sense Combi-U 7
SCU7
Sense Combi-U 8
SCU8
208 V
240 V
208 V
240 V
min. cu.ft.
175
175
250
250
Sauna volume
max. cu.ft.
265
320
360
440
27
Figure 1: Sauna heater/control panel parts
1. Sauna heater
2. Herb bowl/air humidifi er
3. Herb bowl
4. Brackets
5. Warning and Caution plates for the room in multiple languages
6. Screws B 4 x 6.5 x 6 for Warning and Caution plates
17. Humidity- and temperature sensor with cover (Combi Elite)
18. Cable between heater and humidity- and temperature sensor,
RJ10 4P4C, cable length 4 m x 1 pce (Combi Elite)
19. Control panel (Elite Wifi or Pure)
20. Cable between heater and control panel, RJ10 4P4C, cable
length 5 m x 1 pce
21. Cable tie
22. Clips C 3x5 x 10 pieces
23. Modular plug 4, 4/4RJ10 x 2
24. Plastic plugs 25x5 x 3 pcs
25. Screws B6x25 x 3 pcs
26. Rock guard
27. Protection hose Ø14x150 mm x 3 pcs, for RJ10 cables (sensor, control panel, door switch)
Installation tools
The following tools and materials are needed for installation and
connection:
• level
• tape measure
• electric drill
• screw drivers
Installation planning
Before starting to install your sauna heater:
• Plan the sauna heater positioning (see the Heater positioning
- normal installation section, page 4).
• Plan the control panel positioning (see the attached instructions for the control panel for allowable positioning).
• Plan the sensor positioning (see Figure 3, page 4).
• Position the air intake vent (see the Air intake vent positioning
section, page 5).
• Position the air exhaust vent (see the Air exhaust vent positioning section, page 5).
• Plan the electrical installation (see the Connection/wiring
diagram section, page 9).
4
Compliments of www.saunasandstuff.com
3
4
2
1
Figure 2: Schematic diagram of installation
1. Sauna heater
2. Control panel
3. Sensor
4. External on/off switch (option, door contact needed for function)
DANGER! No more than one heater may be installed in the same sauna cabin.
Positioning the control panel
The control panel can be installed inside or outside of the sauna
room.
The control panel must be correctly positioned with regard to
safety distances below when installed inside the sauna room
4
2
3
1
Figure 4: Safety distance, control panel
1. Heater
2. Control panel
3. Max. 36 in
4. Min. 12 in
Positioning the heater - normal installation
Position the sauna heater:
• on the same wall as the door (or the side wall if very close to
the door wall).
• Position the heater at a safe distance from the fl oor, side
walls and interior fi ttings (see Figure 3).
Position the sensor according the picture (see Figure 3).
5
2
3
6
7
1
8
10
4
9
3
11
Figure 3: Positioning the heater - normal installation
Figure 5: Warning/Caution plate
1. Minimum distance from side wall: 4 in
2. Sensor position alt 1: 3 in from heater
3. Sensor
4. Sensor position alt 2: 3 in from heater front
5. Sensor position: 1 in from ceiling
6. Minimum distance from ceiling: 44 in
7. Minimum distance from interior fi ttings: 4 in
8. Minimum ceiling height: 75 in
9. Minimum distance: 1 in
10. Minimum distance from interior fi ttings: 2 in
11. Distance from fl oor: 7 in
Sauna room ventilation
Compliments of www.saunasandstuff.com
In a sauna, the air should be changed about 6 times an hour. See
Figure 6.
It is recommended that ventilation openings meet the requirements of UL Specifi cation 875. The minimum opening should be
determined using one of the following formulas:
For R< 31, V ≥ 9 .3
For R ≥ 31, V ≥ 0.3*R
where R = the fl oor area of the room in square feet and
V = the minimum vent size in square inches
ExampleVenting Calculation:
Room is 54 sq.ft.(9 ft. by 6 ft.) 54 is larger than 31.
Multiple 54 x 0.3 = 16.2 sq. in.
Vent size opening should be 4 in x 4 in.
Positioning the inlet vent
Install the inlet vent straight through the wall under the centerline
of the heater.
12
5
Removing the Rock Guard
Unscrew the two screws on the side of the heater and lift the
rock guard upwards, see Figure 7. (This is necessary when fi lling
the stone compartment or cleaning the fragrance holder and air
humidifi er).
34
Figure 6: Positioning the air intake and exhaust vents
1. Inlet vent position.
2. Outlet vent position through the sauna wall.
3. Outlet vent position through the cavity.
4. Outlet vent position via duct.
Positioning the outlet vent
Position the outlet vent
• at the maximum possible distance from the air intake vent,
e.g. diagonally (see Figure 6).
• high on the wall or in the ceiling (see Figure 6).
• so that it vents into the space that the door and air intake
vent open into.
Figure 7: Removing the Rock Guard
Room construction
For safety and reliability, the following rules must be addressed.
• The enclosed WARNING: Reduce the risk of overheating
… warning plate must be mounted on or alongside the door
outside the sauna room at about eye level. Use the supplied
screws.
• The enclosed CAUTION: Reduce the risk of fi re … caution
plate must be mounted on the interior wall above the heater.
Use the supplied screws.
• No permanent locking or latch system is to be used on the
sauna door.
• Acceptable door fi ttings are: magnetic catches, friction catches, spring or gravity loaded closures. The door must always
open outwards.
• No shower may be installed in a sauna room.
• No electrical receptacle shall be installed inside the sauna
room.
• The heater should not be operated without its container properly fi lled with rocks and the rock guard in place.
• If an intercom speaker is installed, it should be away from the
heater and as close to the fl oor as possible.
• If a room light is installed, it should be a surface mounted
bracket type. Wall mounted lights should be about 70” above
the fl oor. Ceiling mounted lights should be of an approved
type with a junction box that is remote to the fi xture itself.
Use only a fi xture that uses A.F. or fi xture type internal wiring.
A 60 watt bulb should provide suffi cient lighting.
• Fire sprinkler systems installed inside any sauna room should
be properly rated for sauna room temperatures.
• Always mount the heater according to these installation
instructions.
The outlet vent must have the same area as the inlet vent.
Ensure that the outlet vent is open.
Mechanical ventilation is not recommended due to the risk of poor
air exchange, which can negatively aff ect the heater temperature
cut-out.
6
Compliments of www.saunasandstuff.com
Typical wall construction
Figure 8: Typical wall construction
INSTALLATION
Sauna heater installation
1. Attach the bracket and spacers to the wall following the specifi ed dimensioning (see Figure 9). -
3
4
2
3
1
Figure 10: Opening/closing the cover
Connect the heater using standard wiring (Fk or EKK) approved
for fi xed installation.
Any single wires (Fk) must be protected in electrical conduits (VP)
to the heater.
4. Connect the main supply electrical cable (1) to the terminal
(2) (see Figure 11) according to the wiring diagram (see the
Connection/wiring diagram section, page 9).
11
6
4
9
3
5
1
10
7
2
Figure 9: Bracket with screws and spacers
1. 26.3 in
2. 11.0 in
3. 7.3 in
4. 9.0 in (minimum distance)
It is easiest to prepare for installation with the heater lying down.
To install the heater:
2. Remove the cover to the water reservoir and lay the heater
down with the front facing upwards (see Figure 10).
3. Undo the screws and open the cover (see Figure 10).
WARNING! Always check that the heater is connected to the correct main/phase voltage!
8
Figure 11: Circuit board
1. Electrical cable
2. Terminal for connection of electrical cable
3. Cable grommet (x6)
4. Control panel cable
5. Modular contacts for connection
of control panel, sensor etc.
6. Sensor cable
5. Run the cables for the control panel and the temperature
sensor through the cable grommets (3). Connect the control
panel cable (4) to one of the four RS485 contacts (positions
6-9) (see Figure 11) according to the wiring diagram (see the
Connection/wiring diagram section, page 9 fi g.19).
6. Connect the humidity- and temperature sensors cable (6) to
one of the four RS485 contacts (positions 6-9) (5) according
to the wiring diagram (see the Connection/wiring diagram
section, page 9 fi g. 19).
7. Light cable (if connected)
8. Terminal for connection of
light (if connected)
9. Strain relief connector for
cables to modular contacts
(x2)
10. Strain relief connector for
electrical cable
11. Protection hose for RJ10
cables
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.