Bruksanvisning för manöverpanel CC 300/CC 300T................................... Svenska sid 2.
Läs anvisningen tillsammans med instruktionerna för bastuaggregat resp ånggenerator. Inkoppling skall utföras
av behörig el-installatör. SPARA ANVISNINGEN! Efter installation överlämnas denna till bastun/steambadets ägare
eller till den som sköter anläggningen.
Operating instructions for control panel CC 300/CC 300T....................... English page 8.
Please read this information together with the instructions supplied with the sauna heater or steam generator.
Installation work must be carried out by an authorised electrician. KEEP THIS INFORMATION IN A SAFE PLACE.
On completion of the installation work, please give these instructions to the owner or operator of the sauna/steam bath.
Gebrauchsanleitung für Kontrollgerät CC 300/CC 300T........................ Deutsch Seite 15.
Benutzen Sie diese Anleitung zusammen mit den Instruktionen für Saunaöfen und Dampfgeneratoren.
Der elektrische Anschluß ist von einem Fachmann auszuführen. ANLEITUNG AUFBEWAHREN! Nach der
Installation ist diese Anleitung dem Sauna-/Dampfbadbesitzer oder Bedienungspersonal auszuhändigen.
Instr. mode d'emploi du tableau de commande CC 300/CC 300T.........Français page 22.
Bien lire ce document ainsi que les instructions du poêle de sauna ou du générateur de vapeur. Les branchements
doivent être effectués par un électricien agréé. CONSERVER CE DOCUMENT! Après installation, le remettre au
propriétaire du sauna/hammam ou au responsable de l'entretien.
Bruksanvisning for manøversentral CC 300/CC 300T................................. Norsk side 29.
Les instruksjons- og bruksanvisningen for badstuovn og dampgenerator. Tilkobling skal utføres av autorisert
installatør. NB! TA VARE PÅ BRUKSANVISNINGEN! Etter installasjonen skal den leveres til eier av badstu/dampbad
eller til den som skal ha ansvar for driften av anlegget.
Brugsanvisning for manøvrepanel CC 300/CC 300T.................................. Dansk side 35.
Læs brugsanvisningen sammen med instruktionerne for saunaovn resp. dampbad-generator. Installation
skal foretages af autoriseret el-installatør. GEM BRUGSANVISNINGEN! Efter installation afleveres brugsanvisningen til saunaens/dampbadets ejer eller til den ansvarlige for anlægget.
Asennus- ja käyttöohjeet, käyttötaulu CC 300/CC 300T............................. Suomi sivu 41.
Lue nämä ohjeet samalla kuin saunakiukaan tai höyrygeneraattorinkin ohjeet. Asennuksen saa tehdä
vain pätevä sähköasentaja. SÄILYTÄ OHJEITA HYVIN! Anna ne asennuksen jälkeen saunan/höyrykylvyn
omistajalle tai laitteiston hoitajalle.
som motsvarar respektive knapp. 5 = Symboler/text för inställning och
visning av aktuella värden.
Knappar och display.
På manöverpanelen finns det tre knappar. Ovanför knapparna i
nederkanten på displayen visas symboler som motsvarar respektive
knapp. De ser olika ut beroende på i vilket läge panelen befinner sig i.
När pilarna syns i Menydisplayen (Bild 1) används vänster- och
högerknapp för att stega till önskad symbol. För att välja symbolen
bekräfta med mittknappen.
I Normaldisplayen (Bild 2) är vänsterknappens funktion ON/OFF och
dess symbol syns ovanför i displayens nederkant. När anläggningen är
igång är symbolen grön, när anläggningen är avstängd blir symbolen röd
och i standby-läge orange. Högerknappens funktion är belysning.
Lampsymbolen är gul när belysningen är på och vit när belysningen är
avstängd. Displayen visar även aktuell temperatur.
Genom att hålla in mittknappen en längre stund återgår panelen till
Normaldisplay om man befinner sig i annat läge.
När ett program är aktivt tryck vänsterknapp 2 sek för att stänga av aktivt
program.
Belysning.
Tänds automatiskt när anläggningen startar och släcks automatiskt när
anläggningen stänger av. Belysningen kan också tändas eller släckas
manuellt med tryck på högerknapp när lampsymbolen syns längst ned i
högra hörnet. Symbolen är vit när belysningen är släckt och gul när
belysningen är på.
Kodlås.
Förhindrar obehörig ändring av inställda värden.
Huvudströmbrytare.
På reläboxens, SE aggregatets och de mindre ånggeneratorernas
undersida finns en huvudströmbrytare som endast behöver användas då
anläggningen skall vara frånkopplad under längre tid.
Tips! Termometern i bastun placeras på sådan höjd, att visade värden
överensstämmer med de exakta siffror CC 300 visar.
Stand by.
Stand by är av stort värde för tylarier i hotell, badhus etc, där
besöksfrekvensen växlar. Under lågfrekventa perioder står anläggningen
inställd på energisnål "beredskapsvärme", som snabbt accelereras till
önskad badtemperatur vid tryck på ON alternativt extern brytare. Här
sparar Stand by funktionen stora belopp årligen.
Som framgår av nedanstående exempel finns många möjligheter att
enkelt programmera ett passande badprogram.
Exempel Stand by.
Tre olika badanläggningar som har öppet mellan klockan 800 och 2000
och med växlande besökfrekvens enligt nedanstående alternativ.
Alt. 1) Ett litet antal badgäster som kommer sporadiskt under hela öppettiden. Programmera Stand by mellan 8
badvaktmästaren) aktiverar badprogrammet genom ett tryck på CCpanelens ”ON” knapp.
Alt. 2) Ett litet antal badgäster kommer sporadiskt mellan 8
Efter klockan 14
ningsdags. Programmera Stand by mellan 8
fast ”ON” tid mellan 14
badprogrammet med ett tryck på CC-panelens ”ON” knapp.
Alt. 3) Ett stort antal badande mellan klockan 8
mellan 18
badgäster. Programmera Stand by mellan 8
fasta ”ON” tider för de välbesökta badtiderna enligt ovan. De sporadiska
badgästerna aktiverar badprogrammet med ett tryck på CC-panelens
”ON” knapp.
00
brukar anläggningen vara välbesökt fram till stäng-
00
- 2000. De sporadiska badgästerna aktiverar
00
- 2000. Resten av dagen besöks endast sporadiskt av
00
och 2000. Badgästerna (eller
00
00
och 1400 och programmera
00
- 1000, 1300- 1400 och
00
och 2000, programmera
och 1400.
INSTÄLLNINGAR
CC 300
º
22
R
Bild 2. Normaldisplay
M
EN
Initial uppstart.
Första gången manöverpanelen sätts på måste man göra vissa
inställningar. Välj först region, bekräfta med mittknapp. Därefter väljs
önskat språk, bekräfta med mittknapp. Ange sedan datum och tid.
Använd vänster- och högerknapp för att stega till önskade värden.
Bekräfta med mittknapp. Sist ställs önskad driftstid vid manuell uppstart
in. Grundinställning är 3 timmar men kan väljas mellan 1 till 24 timmar.
Stega uppåt med högerknapp (nedåt med vänsterknapp) tills önskad tid
visas i displayen. Varje knapptryck ökar eller minskar tiden med 15
minuter. För snabbare stegning håll knappen intryckt. Bekräfta med
mittknapp. Därmed är grundinställningen färdig.
2
MANUELLT TILL/FRÅNSLAG.
Inställning av badtemperatur.
Välj [Meny] i Normaldisplay och sedan temperaturmätaren. Stega uppåt
till önskad temperatur, bekräfta med [OK].
Starta anläggningen
Välj sedan retursymbolen, bekräfta med mittknapp och välj ON/OFFsymbolen för att starta ”badet”. Tryck en gång till på ON/OFF för frånslag.
Symbolen är röd när anläggningen är avstängd och grön när
anläggningen är igång.
AUTOMATISKT TILL/FRÅNSLAG.
Inställning av badtemperatur.
Välj [Meny] i Normaldisplay och sedan temperaturmätare. Stega till
önskad temperatur, bekräfta med [OK].
Starta timerfunktion
Välj [Meny] i Normaldisplay. Välj därefter [Program] och sedan [Timer].
Ställ in förvalstid (tid till start av anläggningen), bekräfta med OK.
Tillslagstid är nu aktiverad och badet startar automatiskt efter inställd tid.
Tid till start visas uppe i vänstra hörnet. Du kan när som helst stänga av
förvalstiden medan timern räknar ned genom att trycka två gånger på
ON/OFF-symbolen. Om badet har startat stänger man av genom att
trycka en gång på ON/OFF-knapp.
VECKOURSPROGRAMMERING
med olika inställningar på olika veckodagar eller med samma
inställning alla veckodagar.
Timer
Bild 3. Programdisplay
Översikt Åter
OK
R
Inställning av till/frånslag/standby, temperatur.
Välj [Meny] i Normaldisplay och sedan Program. Välj Program en gång
till i Programdisplay (se bild 3). Vid tryck på [OK] ändras markeringen
[Lägg till] till mörkblå. Man är då inne i program mode. Välj först önskad
dag (aktuell text är rödmarkerad) genom att använda piltangenterna. Det
går att välja varje enskild veckodag för sig men man kan även direkt välja
måndag-söndag (för att få samma inställning alla veckodagar), måndagfredag eller lördag-söndag. Bekräfta med [OK]. Ställ sedan in vilket
klockslag anläggningen ska starta. Varje tryck på piltangenterna stegar
tiden upp eller ned 15 minuter, tryck på [OK] när önskad starttid syns i
displayen. Välj sedan önskad stopptid och tryck [OK]. Ange om
anläggningen ska vara på, av eller standby den tid som valts. ON/OFFsymbolen väljs grön om anläggningen ska vara på, röd om anläggningen
ska vara av och orange vid standby. Vid val att anläggningen ska vara på
görs även inställning för önskad temperatur, stega med piltangenterna
och bekräfta med [OK]. För att göra en ny programmering tryck på
högerknapp en gång för att markera [Lägg till] och sedan på [OK].
Upprepa sedan ovanstående procedur. För att återgå till Normaldisplay
välj [Åter], bekräfta med [OK]. Välj [Åter] en gång till och sedan [OK]. Om
inga knapptryckningar görs återgår manöverpanelen automatiskt till
Normaldisplay efter ca: 30 sekunder. Vill man ta bort alla
förprogrammerade tider väljer man [Rensa kalender]. Man kan även
avaktivera all program tillfälligt genom att välja [Kalender AV].
För att få en enkel översikt över de program som är förprogrammerade
välj [Översikt] i Programdisplay. Där visas schemaläggningen i form av
staplar som visar rött när anläggningen är avstängd, grönt när
anläggningen är igång och gult vid standby.
Så snart man trycker på ON när anläggningen är i stand by-läge, stiger
temperaturen till den inställda badtemperaturen. Efter 1 timme återgår
anläggningen automatiskt till fortsatt stand by-temperatur. Varje nytt tryck
på ON startar 1 timmes badperiod.
Är anläggningen i OFF-läge så gäller de inställningar som gjordes vid
initial uppstart.
Om anläggningen är igång kan man manuellt stänga av med tryck på
OFF. (Stänger endast av pågående bad).
Man kan även avaktivera hela kalenderfunktionen tillfälligt vid exempelvis
någon serviceåtgärd och sedan enkelt aktivera den igen.
BAD UTANFÖR PROGRAMMERAD TID
om panelen är kodspärrad.
Tylariet kan användas vid annan tid än inprogrammerad. Med ett tryck på
ON startar 1 timmes badtid. Önskas förlängning av badperioden, trycker
man åter på ON. Anläggningen stänger automatiskt av 1 timme efter
sista knapptryckningen.
OBS! Glöm ej att kodspärra panelen.
PANELINSTÄLLNINGAR
CC 300
Display.
LCD ljusstyrka.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera
[Ljusstyrka (%)] och tryck mittknapp. Markeringen blir mörkblå och värdet
för ljusstyrkan i displayen kan ändras. Tryck [OK] för att bekräfta.
LCD Ljusstyrka vid viloläge.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera
[Ljusstyrka vid viloläge (%)] och tryck mittknapp. Markeringen blir
mörkblå och värdet för ljusstyrkan i displayen när panelen är i Stand byläge kan ändras. Tryck [OK] för att bekräfta. Fabriksinställning är 30%.
Tid till LCD viloläge.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera [Tid
till viloläge] och tryck mittknapp. Markeringen blir mörkblå och värdet går
att ställas för när ljusstyrkan i displayen ska ändras efter det att panelen
gått in i Stand by-läge. Tryck OK för att bekräfta.
Service.
Se SERVICEINSTÄLLNINGAR
Kodlås.
Välj [Meny] i Normaldisplay och sedan [Service]. Stega till [Kodlås] och
tryck på [OK]. Ange önskad kod. Stega med piltangenterna till rätt siffra
och bekräfta med [OK]. Kodlåset aktiveras automatiskt vid
programmering och går till Normaldisplay.
För att återgå till ospärrat läge, upprepa ovanstående och sätt kod till
0000.
Det går ej att ändra några inställningar när kodlåset är aktiverat. Det går
att starta och stänga av anläggningen samt tända och släcka
belysningen. Badet är igång den tid man angett i Servicemenyn under
[Bad utanför prog tid] (fabriksinställning 1 timme).
Allmän kod som alltid fungerar är 1995.
OBS! Alla inställningar skall göras innan eventuell kodspärr.
Språk.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj språk och stega
med piltangenterna till önskat språk och tryck sedan [OK].
Klocka.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj [Inställning klocka].
Ange först rätt dag, stega med piltangenterna och bekräfta med [OK].
Ställ sedan in aktuellt klockslag, först timmar och sedan minuter.
Fabriksinställning.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj [Fabriksinställning].
Välj [Ja] eller [Nej] med piltangenterna tryck sedan [OK]. Genom att välja
[Ja] försvinner alla programmeringar och egna inställningar som gjorts
och panelen får de fabriksinställningar som den hade från början.
SERVICEINSTÄLLNINGAR
CC 300
Service.
I Servicemenyn kan den som sköter anläggningen göra diverse
inställningar såsom maximal badtemperatur. Det rekommenderas dock
att behålla de fabriksinställningar som finns. Servicemenyn är belagd
med en kod för att inte obehöriga ska kunna ändra på dessa
inställningar. I Normaldisplay tryck [Meny] och sedan [Service]. Välj
[Service] och tryck koden 124.
Systeminställningar.
Maximal driftstid
[Max driftstid (h)] – Detta är den driftstid som ställdes in vid initial
uppstart. Denna tid gäller ej då anläggningen är programmerad. Går att
ställa mellan 1 till 24 timmar, fabriksinställning är 3 timmar.
Temperaturenhet
[Temperatur (C°/F)] – Denna parameter ställer in om temperaturen ska
visas i grader Celsius eller Fahrenheit.
Testmeny
Testmenyn används endast för felsökning och teknisk support via Tylö.
Max temperatur.
[Max temp (C°/F)] – Här ställer man in den maximala temperaturen som
anläggningen kan programmeras till. Vid bad i Tylarium är
maxtemperaturen 55°C.
3
Temperaturreducering vid stand by.
[Tempreducering stand by (C°/F)] – Hur mycket temperaturen skall
sjunka när anläggningen är i stand by-läge jämfört med programmerad
badtemperatur. Fabriksinsställning är 30°C.
Max gångtid vid stand by.
[Max tid stand by (min)] – När anläggningen är programmerad i stand by-
läge och man trycker på ON-knapp är badet igång så länge som den tid
man angett här. Fabriksinställning 60 minuter.
Max gångtid utanför programmerad tid.
[Bad utanför prog tid (min)] – Detta är den tid som anläggningen är igång
vid kodspårr utanför programmerad tid.
Avkalkning.
[Avkalkning (h)] – Denna parameter är en timer som räknar ned när
anläggningen är igång. Den talar om att det är dags att avkalka.
Fabriksinställning är 40 timmar.
Denna anvisning läses tillsammans med monteringsanvisning som
medföljer bastuaggregat resp. ånggenerator.
Bild A – TYLARIUM.
(Bastuaggregat typ SK, SDK, och ånggenerator typ VA/VB).
1 = bastuaggregat. 2 = fukt och temperatursensor. 3 = manöverpanel CC 300T. 4 = eventuell extern on/off-brytare. 5 = el-central.
6 = reläbox RB30/60. 7 = ånggenerator. 8 = förstärkare (amplifier).
Bild B – TYLARIUM.
(Bastuaggregat typ SE och ånggenerator typ VA/VB).
1 = bastuaggregat. 2 = fukt och temperatursensor. 3 = manöverpanel CC 300T. 4 = eventuell extern on/off-brytare. 5 = el-central.
7 = ånggenerator. 8 = förstärkare (amplifier).
Reläbox (RB).
(Reläbox används ej till SE aggregat).
Monteras utanför och på obegränsat avstånd från tylariet i ett svalt och
ventilerat utrymme. Reläboxen får inte placeras närmare än 1 meter från
CC 300T.
Skärmad svagströmsledning (LiYCY 6-ledare).
Manöverledning mellan CC 300T till reläbox, SE aggregat eller
ånggenerator skall vara skärmad svagströmsledning (LiYCY, 6-ledare).
Skärmningen anslutes till plint 12 i CC panelen.
Placering av termistor, fukt och temperatursensor.
Monteras 1500 mm från golvet (ej ovanför bastuaggregatet).
Placera sensorn så, att den varken direkt eller indirekt kan träffas av
ångstrålen.
7 = ånggenerator. 8 = förstärkare (amplifier).
Kontrollera på bastuaggregatets och på ånggeneratorns dataskylt att
anslutning sker till rätt spänning.
Glöm inte att jorda!
Bild D – kopplingsschema.
(Bastuaggregat typ SE och ånggenerator typ VA/VB med manöverpanel typ CC 300T).
1 = bastuaggregat. 2 = fukt och temperatursensor.3 = manöverpanel CC 300T. 4 = eventuell extern on/off-brytare. 7 = ånggenerator.
8 = förstärkare (amplifier).
Kontrollera på bastuaggregatets och på ånggeneratorns dataskylt att
anslutning sker till rätt spänning.
Glöm inte att jorda!
BRUKSANVISNING
CC 300T
RH%
OK
R
Förstärkare (amplifier).
Monteras utanför tylariet max 2 meter från sensorn och på obegränsat
avstånd från CC 300T. Manöverledning mellan förstärkare och CC 300T
skall vara skärmad svagströmsledning (4-ledare). Skärmningen ansluts
till plint 25 i förstärkaren.
Belysning.
Anslut belysningen enligt kopplingschema.
Tillval: extern on/off-brytare (momentan).
Placeras på valfritt avstånd från tylariet. Anslutes med
svagströmsledning till CC 300T – se kopplingsschema. Vid användande
av flera externa on/off-brytare skall dess parallellkopplas. Ett tryck på
externbrytaren startar CC300T och går så länge som önskad driftstid är
satt (Se Initial uppstart). Ett tryck till på externbrytaren stänger av
CC300T om den ej är programmerad/kodspärrad. Om CC300T är
programmerad/kodspärrad måste man stänga av med ON/OFF-knappen
på CC300T.
Placeras på valfritt avstånd från Tylariet. Anslutes med
svagströmsledning till CC 300T – se kopplingsschema. Vid användande
av flera externa on/off-brytare skall dessa parallellkopplas. Vid konstant
slutning går anläggningen så länge slutning finns mellan plint 19 och 20,
dock maximalt inställd driftstid.
Anslutning till centraldator.
Anslutning kan också göras till centraldator som antingen gör en kort
slutning eller konstant slutning mellan plintarna 19 och 20 i CC 300T.
Tillåten kontinuerlig inkopplingstid är max 24 timmar.
Viktigt! För att ånggeneratorns automatiska tömningsfunktion skall
fungera måste manöverpanelen vara avstängd minst 1,5 tim/dygn.
Styrning av andra Tylöprodukter.
CC300T kan med fördel styra andra Tylöprodukter. Exempel på detta är
sammankoppling med Tylö Fresh som då aktiveras när panelen är i drift.
Vid styrning av t.ex. Tylö Fresh eller annan CC-panel ska dessa kopplas
mellan plint 40 och 41 i CC 300T och plint 19 och 20 på den andra
Tylöprodukten. Se bild J för exempel.
som motsvarar respektive knapp. 5 = Symboler/text för inställning och
visning av aktuella värden.
Knappar och display.
På manöverpanelen finns det tre knappar. Ovanför knapparna i
nederkanten på displayen visas symboler som motsvarar respektive
knapp. De ser olika ut beroende på i vilket läge panelen befinner sig i.
När pilarna syns i Menydisplayen (Bild 1) används vänster- och
högerknapp för att stega till önskad symbol. För att välja symbolen
bekräfta med mittknappen.
I Normaldisplayen (Bild 2) är vänsterknappens funktion ON/OFF och
dess symbol syns ovanför i displayens nederkant. När anläggningen är
igång är symbolen grön, när anläggningen är avstängd blir symbolen röd
och i standby-läge orange. Högerknappens funktion är belysning.
Lampsymbolen är gul när belysningen är på och vit när belysningen är
avstängd. Displayen visar även aktuell temperatur och luftfuktighet.
Genom att hålla in mittknappen en längre stund återgår panelen till
Normaldisplay om man befinner sig i annat läge.
När ett program är aktivt tryck vänsterknapp 2 sek för att stänga av aktivt
program.
22
ºc
MENU
%
33
R
Bild C, E – kopplingsschema.
(Bastuaggregat typ SK, SDK och ånggenerator typ VA/VB med
manöverpanel typ CC 300T).
1 = bastuaggregat. 2 = fukt och temperatursensor. 3 = manöverpanel CC 300T. 4 = eventuell extern on/off-brytare. 6 = reläbox RB30/60.
Bild 2. Normaldisplay
5
Initial uppstart.
Första gången manöverpanelen sätts på måste man göra vissa
inställningar. Välj först region, bekräfta med mittknapp. Därefter väljs
önskat språk, bekräfta med mittknapp. Ange sedan datum och tid.
Använd vänster- och högerknapp för att stega till önskade värden.
Bekräfta med mittknapp. Sist ställs önskad driftstid vid manuell uppstart
in. Grundinställning är 3 timmar men kan väljas mellan 1 till 24 timmar.
Stega uppåt med högerknapp (nedåt med vänsterknapp) tills önskad tid
visas i displayen. Varje knapptryck ökar eller minskar tiden med 15
minuter. För snabbare stegning håll knappen intryckt. Bekräfta med
mittknapp. Därmed är grundinställningen färdig.
Belysning.
Tänds automatiskt när anläggningen startar och släcks automatiskt när
anläggningen stänger av. Belysningen kan också tändas eller släckas
manuellt med tryck på högerknapp när lampsymbolen syns längst ned i
högra hörnet. Symbolen är vit när belysningen är släckt och gul när
belysningen är på.
Kodlås.
Förhindrar obehörig ändring av inställda värden.
Huvudströmbrytare.
På reläboxens, SE aggregatets och de mindre ånggeneratorernas
undersida finns en huvudströmbrytare som endast behöver användas då
anläggningen skall vara frånkopplad under längre tid.
Tips! Termometern (hygrometern) i tylariet placeras på sådan höjd, att
visade värden överensstämmer med de exakta siffror CC 300T visar.
Stand by.
Stand by är av stort värde för tylarier i hotell, badhus etc, där
besöksfrekvensen växlar. Under lågfrekventa perioder står anläggningen
inställd på energisnål "beredskapsvärme", som snabbt accelereras till
önskad badtemperatur vid tryck på ON alternativt extern brytare. Här
sparar Stand by funktionen stora belopp årligen.
Som framgår av nedanstående exempel finns många möjligheter att
enkelt programmera ett passande badprogram.
Exempel Stand by.
Tre olika badanläggningar som har öppet mellan klockan 800 och 2000
och med växlande besökfrekvens enligt nedanstående alternativ.
Alt. 1) Ett litet antal badgäster som kommer sporadiskt under hela öppettiden. Programmera Stand by mellan 8
badvaktmästaren) aktiverar badprogrammet genom ett tryck på CCpanelens ”ON” knapp.
Alt. 2) Ett litet antal badgäster kommer sporadiskt mellan 8
Efter klockan 14
ningsdags. Programmera Stand by mellan 8
fast ”ON” tid mellan 14
badprogrammet med ett tryck på CC-panelens ”ON” knapp.
Alt. 3) Ett stort antal badande mellan klockan 8
mellan 18
badgäster. Programmera Stand by mellan 8
fasta ”ON” tider för de välbesökta badtiderna enligt ovan. De sporadiska
badgästerna aktiverar badprogrammet med ett tryck på CC-panelens
”ON” knapp.
00
brukar anläggningen vara välbesökt fram till stäng-
00
- 2000. De sporadiska badgästerna aktiverar
00
- 2000. Resten av dagen besöks endast sporadiskt av
00
och 2000. Badgästerna (eller
00
00
och 1400 och programmera
00
- 1000, 1300- 1400 och
00
och 2000, programmera
och 1400.
INSTÄLLNINGAR
CC 300T
MANUELLT TILL/FRÅNSLAG.
Inställning av badtemperatur.
Välj [Meny] i Normaldisplay och sedan temperaturmätaren. Stega uppåt
till önskad temperatur, bekräfta med [OK].
Inställning av fuktighet.
Välj droppsymbolen. Stega sedan till önskad fuktighet [(RH%)], bekräfta
med [OK]. Gränsen för hur högt man kan ställa värdet är beroende på
temperaturen.
Starta anläggningen
Välj sedan retursymbolen, bekräfta med mittknapp och välj ON/OFFsymbolen för att starta ”badet”. Tryck en gång till på ON/OFF för frånslag.
Symbolen är röd när anläggningen är avstängd och grön när
anläggningen är igång.
6
AUTOMATISKT TILL/FRÅNSLAG.
Inställning av badtemperatur.
Välj [Meny] i Normaldisplay och sedan temperaturmätare. Stega till
önskad temperatur, bekräfta med [OK].
Inställning av fuktighet.
Välj droppsymbolen. Stega sedan till önskad fuktighet [(RH%)] bekräfta
med [OK]. Gränsen för hur högt man kan ställa värdet är beroende på
temperaturen.
Starta timerfunktion
Välj [Meny] i Normaldisplay. Välj därefter [Program] och sedan [Timer].
Ställ in förvalstid (tid till start av anläggningen), bekräfta med OK.
Tillslagstid är nu aktiverad och badet startar automatiskt efter inställd tid.
Tid till start visas uppe i vänstra hörnet. Du kan när som helst stänga av
förvalstiden medan timern räknar ned genom att trycka två gånger på
ON/OFF-knappen. Om badet har startat stänger man av genom att
trycka en gång på ON/OFF-knapp.
Om fuktigheten överstiger 30% vid frånslag startar automatiskt en
”upptorkning” på ca. 20 minuter (fabriksinställning).
VECKOURSPROGRAMMERING
med olika inställningar på olika veckodagar eller med samma
inställning alla veckodagar.
Timer
Bild 3. Programdisplay
Inställning av till/frånslag/standby, temperatur/fukt.
Välj [Meny] i Normaldisplay och sedan Program. Välj Program en gång
till i Programdisplay (se bild 3). Vid tryck på [OK] ändras markeringen
[Lägg till] till mörkblå. Man är då inne i program mode. Välj först önskad
dag (aktuell text är rödmarkerad) genom att använda piltangenterna. Det
går att välja varje enskild veckodag för sig men man kan även direkt välja
måndag-söndag (för att få samma inställning alla veckodagar), måndagfredag eller lördag-söndag. Bekräfta med [OK]. Ställ sedan in vilket
klockslag anläggningen ska starta. Varje tryck på piltangenterna stegar
tiden upp eller ned 15 minuter, tryck på [OK] när önskad starttid syns i
displayen. Välj sedan önskad stopptid och tryck [OK]. Ange om
anläggningen ska vara på, av eller standby den tid som valts. ON/OFFsymbolen väljs grön om anläggningen ska vara på, röd om anläggningen
ska vara av och orange vid standby. Vid val att anläggningen ska vara på
görs även inställning för önskad temperatur och fuktighetsgrad, stega
med piltangenterna och bekräfta med [OK]. För att göra en ny
programmering tryck på högerknapp en gång för att markera [Lägg till]
och sedan på [OK]. Upprepa sedan ovanstående procedur. För att återgå
till Normaldisplay välj [Åter], bekräfta med [OK]. Välj [Åter] en gång till
och sedan [OK]. Om inga knapptryckningar görs återgår
manöverpanelen automatiskt till Normaldisplay efter ca: 30 sekunder. Vill
man ta bort alla förprogrammerade tider väljer man [Rensa kalender].
Man kan även avaktivera all program tillfälligt genom att välja [Kalender
AV].
För att få en enkel översikt över de program som är förprogrammerade
välj [Översikt] i Programdisplay. Där visas schemaläggningen i form av
staplar som visar rött när anläggningen är avstängd, grönt när
anläggningen är igång och gult vid standby.
Så snart man trycker på ON när anläggningen är i stand by-läge, stiger
temperaturen till den inställda badtemperaturen. Efter 1 timme återgår
anläggningen automatiskt till fortsatt stand by-temperatur. Varje nytt tryck
på ON startar 1 timmes badperiod.
Är anläggningen i OFF-läge så gäller de inställningar som gjordes vid
initial uppstart.
Om anläggningen är igång kan man manuellt stänga av med tryck på
OFF. (Stänger endast av pågående bad).
Översikt Åter
OK
R
Om fuktigheten överstiger 30% vid frånslag startar automatiskt en
”upptorkning” på ca. 20 minuter (fabriksinställning).
Man kan även avaktivera hela kalenderfunktionen tillfälligt vid exempelvis
någon serviceåtgärd och sedan enkelt aktivera den igen.
BAD UTANFÖR PROGRAMMERAD TID
om panelen är kodspärrad.
Tylariet kan användas vid annan tid än inprogrammerad. Med ett tryck på
ON startar 1 timmes badtid. Önskas förlängning av badperioden, trycker
man åter på ON. Anläggningen stänger automatiskt av 1 timme efter
sista knapptryckningen.
OBS! Glöm ej att kodspärra panelen.
PANELINSTÄLLNINGAR
CC 300T
Display.
LCD ljusstyrka.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera
[Ljusstyrka (%)] och tryck mittknapp. Markeringen blir mörkblå och värdet
för ljusstyrkan i displayen kan ändras. Tryck [OK] för att bekräfta.
LCD Ljusstyrka vid viloläge.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera
[Ljusstyrka vid viloläge (%)] och tryck mittknapp. Markeringen blir
mörkblå och värdet för ljusstyrkan i displayen när panelen är i Stand byläge kan ändras. Tryck [OK] för att bekräfta. Fabriksinställning är 30%.
Tid till LCD viloläge.
Välj [Meny] i Normaldisplay, [Service] och sedan [Display]. Markera [Tid
till viloläge] och tryck mittknapp. Markeringen blir mörkblå och värdet går
att ställas för när ljusstyrkan i displayen ska ändras efter det att panelen
gått in i Stand by-läge. Tryck [OK] för att bekräfta.
Service.
Se SERVICEINSTÄLLNINGAR
Kodlås.
Välj [Meny] i Normaldisplay och sedan [Service]. Stega till [Kodlås] och
tryck på [OK]. Ange önskad kod. Stega med piltangenterna till rätt siffra
och bekräfta med [OK]. Kodlåset aktiveras automatiskt vid
programmering och går till Normaldisplay.
För att återgå till ospärrat läge, upprepa ovanstående och sätt kod till
0000.
Det går ej att ändra några inställningar när kodlåset är aktiverat. Det går
att starta och stänga av anläggningen samt tända och släcka
belysningen. Badet är igång den tid man angett i Servicemenyn under
[Bad utanför prog tid] (fabriksinställning 1 timme).
Allmän kod som alltid fungerar är 1995.
OBS! Alla inställningar skall göras innan eventuell kodspärr.
Språk.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj språk och stega
med piltangenterna till önskat språk och tryck sedan [OK].
Klocka.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj [Inställning klocka].
Ange först rätt dag, stega med piltangenterna och bekräfta med [OK].
Ställ sedan in aktuellt klockslag, först timmar och sedan minuter.
Fabriksinställning.
Välj [Meny] i Normaldisplay och sedan [Service]. Välj [Fabriksinställning].
Välj [Ja] eller [Nej] med piltangenterna tryck sedan [OK]. Genom att välja
[Ja] försvinner alla programmeringar och egna inställningar som gjorts
och panelen får de fabriksinställningar som den hade från början.
I Servicemenyn kan den som sköter anläggningen göra diverse
inställningar såsom maximal badtemperatur. Det rekommenderas dock
att behålla de fabriksinställningar som finns. Servicemenyn är belagd
med en kod för att inte obehöriga ska kunna ändra på dessa
inställningar. I Normaldisplay tryck [Meny] och sedan [Service]. Välj
[Service] och tryck koden 124.
Systeminställningar.
Gräns för torkning av anläggning
[Torkgräns (%)] – När anläggningen stannar känner den av
luftfuktigheten i rummet. Om det är över 30% luftfuktighet
(fabriksinställning) så går anläggningen in i upptorkningsläge.
Torktemperatur
[Torkningstemperatur (°C)] – Det är den temperatur som anläggningen
har vid upptorkningsläge. Fabriksinställning är 80°C.
Torktid
[Tork tid (min)] – Det är den tid som anläggningen är igång vid
upptorkningsläge. Fabriksinställning är 20 minuter.
Minsta temperatur vid ånga
[Min temperatur ångbad (°C)]– Det är den minsta temperatur som
anläggningen måste ha för att ånggeneratorn ska starta.
Fabriksinställning är 40°C.
Maximal driftstid
[Max driftstid (h)] – Detta är den driftstid som ställdes in vid initial
uppstart. Denna tid gäller ej då anläggningen är programmerad. Går att
ställa mellan 1 till 24 timmar, fabriksinställning är 3 timmar.
Temperaturenhet
[Temperatur (C°/F)] – Denna parameter ställer in om temperaturen ska
visas i grader Celsius eller Fahrenheit.
Testmeny
Testmenyn används endast för felsökning och teknisk support via Tylö.
Max temperatur.
[Max temp (C°/F)] – Här ställer man in den maximala temperaturen som
anläggningen kan programmeras till. Vid bad i Tylarium är
maxtemperaturen 55°C.
Temperaturreducering vid stand by.
[Tempreducering stand by (C°/F)] – Hur mycket temperaturen skall
sjunka när anläggningen är i stand by-läge jämfört med programmerad
badtemperatur. Fabriksinsställning är 30°C.
Max gångtid vid stand by.
[Max tid stand by (min)] – När anläggningen är programmerad i stand by-
läge och man trycker på ON-knapp är badet igång så länge som den tid
man angett här. Fabriksinställning 60 minuter.
Max gångtid utanför programmerad tid.
[Bad utanför prog tid (min)] – Detta är den tid som anläggningen är igång
vid kodspårr utanför programmerad tid.
Avkalkning.
[Avkalkning (h)] – Denna parameter är en timer som räknar ned när
anläggningen är igång. Den talar om att det är dags att avkalka.
Fabriksinställning är 40 timmar.
TYLARIUM
Tylarium erbjuder bastubad i alla dess former. Torrbastu, Våtbastu och
Ångbastu. Eftersom den relativa luftfuktigheten ibland är högre än vid
traditionella bastubad bör nedanstående punkter beaktas.
• Har bastun fönster i dörr eller vägg, skall dörr- resp fönsterfodrets hela
nedre list strykas med båtfernissa och skarven mellan glas och list
tätas med våtrumssilikon. På så sätt förhindras eventuell kondens på
glasytorna att tränga ner i skarven.
• Lackera tröskeln och dörrhandtagen ett par gånger med båtfernissa,
så behålls träets finish och rengöringen av bastun blir mycket enklare.
Bastulavar dekorraster och ryggstöd inoljas på båda sidor med Tylö
bastuolja.
OBS! Allt övrigt trä inne i bastun skall vara obehandlat.
Fig. 1. Menu display
1 = Left button, 2 = Middle button, 3 = Right button. 4 = Symbols/text that
correspond to the respective button. 5 = Symbols/text for setting and
displaying current values.
Buttons and display.
There are three buttons on the control panel. Symbols shown above the
buttons at the bottom of the display correspond to the respective button.
These symbols differ depending on the panel’s current mode. When the
arrows are shown in the Menu display (fig. 1), use the left and right
buttons to move to the desired symbol. To select a symbol, confirm with
the middle button.
In the Normal display (fig. 2) the left button has an ON/OFF function. The
symbol for this appears at the bottom of the display above the left button.
When the facility is operational, this symbol shows green; when it is
switched off, the symbol is red; and when it is on stand-by, the symbol is
orange. The right button controls the lighting function. The lighting
symbol shows yellow when the lighting is on and white when the lighting
is off. The display also shows the current temperature.
To return to the Normal display from another mode, press the middle
button until the Normal display shows.
When a program is active, press the left button for 2 seconds to switch
off the active program.
decreases the running time by 15 minutes. To move more quickly, keep
the button depressed. Confirm the time with middle button. The basic
settings are now stored in the control panel’s memory.
Lighting.
The lighting comes on/goes off automatically when the facility starts/
shuts down. The lighting can also be controlled manually by pressing the
right button when the lighting symbol shows at the bottom right of the
display. The symbol shows white when the lighting is off and yellow when
the lighting is on.
Code lock.
Prevents unauthorised users from changing the programmed settings.
Main power switch.
This switch, on the underside of the relay box, SE sauna heater and
small steam generators, should be used only when the facility is to
remain switched off for a prolonged period of time.
Note! Place the thermometer in the sauna room at a height where the
values shown correspond exactly with the figures displayed on the CC
300T panel.
Stand-by.
The stand-by function is invaluable for Tylarium facilities in hotels, public
baths, etc., where visitor frequency varies. During off-peak hours the
equipment is set at stand-by heat, which can rapidly be raised to the
desired temperature by pressing the ON button or using an external
switch. This stand-by feature can yield substantial savings every year.
The examples below show how easy it is to program a suitable bathing
schedule.
Examples of Stand-by operation.
Here are examples of three different options for public facilities open
between 8 am to 8 pm, with varying numbers of visitors:
Option 1) A limited number of visitors use the facility sporadically
throughout the day. Program “stand-by” between 8 am and 8 pm. Bathers
(or the attendant responsible) activate the bathing cycle by pressing the
control panel’s ON button.
Option 2) A limited number of visitors use the facility sporadically
between 8 am and 2 pm. From 2 pm to 8 pm there is a steady flow of
bathers. Program “stand-by” between 8 am and 2 pm, and program a
permanent “ON” time from 2 pm to 8 pm. Visitors during the morning
activate the bathing cycle by pressing the control panel’s ON button.
Option 3) Large numbers of bathers 8–10 am, 1–2 pm and 6–8 pm. The
rest of the day, the facility is used only sporadically. Program “stand-by”
between 8 am and 8 pm and program permanent “ON” times for the peak
periods above. Visitors during off-peak times activate the bathing cycle
by pressing the control panel’s ON button.
SETTINGS
CC 300
ºc
22
MENU
R
Fig. 2. Normal display
Initial start-up.
When you switch on the control panel for the first time, you must
configure certain basic settings. First select the relevant region and
confirm your choice by pressing the middle button. Then select the
desired language and confirm with the middle button. Next, use the left
and right buttons to set the correct date and time, and confirm with the
middle button. Finally, set the running time for a manually activated
bathing cycle. (The standard setting is for 3 hours, but you can choose
1–24 hours.) Move up/down with the right/left button respectively until the
desired running time is displayed. Each button press increases/
8
MANUAL ON/OFF.
Setting the bathing temperature.
Select [MENU] in the Normal display and then select the thermometer
symbol. Use the arrow keys to enter the desired temperature and then
confirm with [OK].
Starting the bathing cycle.
Then select the Return symbol, confirm with the middle button and select
the ON/OFF symbol to start the bathing cycle. To switch the unit off,
press once more on ON/OFF. The symbol shows red when the facility is
switched off, and green when the facility is in operation.
AUTOMATIC ON/OFF.
Setting the bathing temperature.
Select [MENU] in the Normal display and then select the thermometer
symbol. Use the arrow keys to enter the desired temperature and then
confirm with [OK].
Starting the timer function.
Select [MENU] in the Normal display. Select [Program] and then [Timer].
Enter the countdown time (= time remaining before the facility is
automatically switched on) and confirm with OK.
The switch-on time has now been set and the bathing cycle will begin
automatically at the pre-set time. The countdown to the switch-on time is
shown at the top left of the display. You can switch off the countdown
function at any time by pressing twice on the button under the ON/OFF
symbol. To switch off the equipment after the bathing cycle has begun,
press just once on the ON/OFF button.
PROGRAMMING THE WEEKLY TIMER
with different settings for different days of the week, or with the
same setting for every day of the week.
Timer
Fig. 3. Program display
Översikt Åter
OK
R
Setting on/off/stand-by times and temperature.
Select [MENU] in the Normal display and then select [Program]. Select
[Program] one more time in the Program display (see fig. 3). When you
press [OK] the highlighted text [Add] changes colour to dark blue. You
are now in the Programming mode. First use the arrow keys to select the
desired weekday (current choice is shown in red). You can select each
weekday separately or choose Monday–Sunday (for the same setting on
all days), Monday–Friday or Saturday–Sunday. Confirm with [OK]. Then
set the start time. Each key press increases/decreases the time shown
by 15 minutes. Press [OK] when the desired start time is displayed. Then
set the desired switch-off time and press [OK]. Indicate whether the
facility is to be on, off or on stand-by for the time chosen The ON/OFF
symbol shows green if the facility is to be on, red if it is to be off and
orange for stand-by. When selecting the ON mode, you must also set the
desired temperature. Use the arrow keys and confirm with [OK]. To
program a new value, press the right button once to highlight [Add] and
then press [OK]. Then repeat the procedure described above. To return
to the Normal display, select [Back] and confirm with [OK]. Select [Back]
once more and then [OK]. If no buttons are pressed, the control panel
automatically reverts to the Normal display after approx. 30 seconds. To
delete all pre-programmed times, select [Clear calendar]. You can also
temporarily deactivate all programmed values by selecting [Calendar
OFF].
For a simple overview of the pre-programmed schedule select [Overview]
in the Program display. A schematic bar chart diagram shows red for
times when the facility is switched off, green when it is in operation and
yellow when it is on stand-by.
When ON is pressed while the bathing facility is in stand-by mode, the
temperature immediately begins to rise to the pre-set value for bathing.
After 1 hour, the temperature automatically reverts to the stand-by
temperature. Each time the ON button is pressed, a new 1-hour
operating cycle is started.
When the facility is in the OFF mode, the settings are those that were
entered as part of the initial start-up process.
At any time while the facility is operational, you can switch it off manually
by pressing OFF. (This switches off only the current bathing cycle.)
You can also deactivate the entire calendar function temporarily, for
example, to carry out service or maintenance, and then reactivate it.
BATHING OUTSIDE PROGRAMMED TIMES
if the control panel’s security code function has been activated.
The Tylarium can also be used at times other than those that have been
programmed. Pressing ON starts a 1-hour bathing cycle. To prolong the
bathing period, simply press ON again. The bathing cycle is terminated
automatically 1 hour after the ON button has last been pressed.
IMPORTANT! Don’t forget to use the security code to lock the panel.
PANEL SETTINGS
CC 300
Display.
LCD brightness.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [(Brightness (%)] and press the middle button. The highlighted
text then turns dark blue and the value for the brightness of the LCD
display can be changed. Press [OK] to confirm.
LCD brightness in sleep mode.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [Stand by] and press the middle button. The highlighted text
then turns dark blue and the value for the brightness of the LCD display
when the panel is on stand-by can be changed. Press [OK] to confirm.
(The factory setting is 30%.)
Countdown to LCD sleep mode.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [Stand by time] and press the middle button. The highlighted
text then turns dark blue, and you can reduce or extend the length of time
it takes before the LCD display dims after the panel has switched to
stand-by. Press [OK] to confirm.
Service.
See SERVICE SETTINGS
Code lock.
Select [MENU] in the Normal display and then [Service]. Use the arrow
keys to move to [Code lock] and press [OK]. Enter the desired code. Use
the arrow keys to display the correct combination and confirm with [OK].
The security code function is automatically activated during programming
and the panel shows Normal display.
To return to unlocked mode, repeat the above procedure and set the
code to 0000.
It is not possible to change any settings when the security function has
been activated. It is possible, however, to switch both the facility and the
lighting on and off. The bathing cycle runs for the time indicated in the
Service menu under [Time outside timer]. (Factory setting: 1 hour).
A general code that always works is 1995.
IMPORTANT! Program all settings before activating security code.
Language.
Select [MENU] in the Normal display and then [Service]. Select
language. Use the arrow keys to select the required language and then
press [OK].
Clock.
Select [MENU] in the Normal display and then [Service]. Select [Set
clock). First use the arrow keys to set the right day and confirm with [OK].
Then set the correct time; first the hour and then the minutes.
Factory settings.
Select [MENU] in the Normal display and then [Service]. Select [Factory
settings]. Use the arrow keys to select [Yes] or [No] and then press [OK].
Selecting [Yes] deletes all your own programmed settings and the panel
reverts to the original factory settings.
SERVICE SETTINGS
CC 300
Service.
The Service menu enables the bathing facility attendant to change
certain settings such as the maximum bathing temperature. However, we
recommend that the original factory settings are always retained. The
Service menu is protected by a code to prevent unauthorised users from
changing factory settings. In the Normal display press [MENU] and then
[Service]. Select [Service] and enter the code 124.
System settings.
Maximum running time
9
[Max running time (hrs)] – The running time that was set at the initial
start-up. This setting does not apply when the equipment has been
programmed. Adjustable from 1–24 hrs. Factory setting: 3 hrs.
Temperature unit
[Temperature (°C/°F)] – This feature enables you to display temperatures
in Celsius or Fahrenheit.
Test menu
The Test menu is used only for trouble-shooting and technical support
via Tylö.
Max temperature.
[Max temp (°C/°F)] – Used to set the maximum temperature to which the
facility can be programmed. For Tylarium bathing, the maximum
temperature is 55°C.
Temperature reduction during stand-by.
[Temp reduction Stand by (°C/°F)] – This is where you indicate the
reduction in temperature from the programmed bathing temperature to
the stand-by temperature. Factory setting: 30°C.
Max. running time during stand-by.
[On time Stand by (mins)) – The duration of the bathing cycle that is
initiated when the ON button is pressed while the facility is on stand-by.
Factory setting: 60 minutes.
Max running time outside programmed time.
[Time outside timer (mins)] – The duration of the bathing cycle outside
code-locked, programmed time.
Removing limescale
[De-scaling (hrs)] – Timer function that records total operating time and
counts down to signal when it is time to clean the equipment from any
limescale deposits. Factory setting: 40 hours.
In the event of a problem, please contact your Tylö
retailer.
Check the type plate on the sauna heater/steam generator to ensure that
the equipment is connected to the right supply voltage.
Do not forget to earth/ground the equipment!
Fig. D – wiring diagram.
(Sauna heater type SE and steam generator type VA/VB with control
panel type CC 300T).
1 = sauna heater. 2 = humidity/temperature sensor.3 = control panel CC 300T. 4 = external on/off switch (where applicable). 7 = steam generator.
8 = amplifier.
Check the type plate on the sauna heater/steam generator to ensure that
the equipment is connected to the right supply voltage.
Do not forget to earth/ground the equipment!
OPERATING INSTRUCTIONS
CC 300T
Shielded low-current cable (LiYCY 6-core).
Use only a shielded low-current cable (LiYCY, 6-core) between the CC
300T and the relay box, SE sauna heater or steam generator. Connect
the shielding to terminal 12 on the CC panel.
Location of thermistor, humidity/temperature sensor.
Install 1500 mm above floor level (but not directly above a sauna heater).
Place the sensor so that it does not risk being affected directly or
indirectly by a jet of steam.
Amplifier.
Install outside the Tylarium, no more than 2 metres from the sensor, but
at any distance from the CC 300T panel. Use only a shielded low-current
cable (4-core) between the amplifier and the CC 300T. Connect the
shielding to terminal 25 on the amplifier.
Lighting.
Connect the lighting as indicated in the wiring diagram.
Optional external on/off-switch (quick-break).
May be placed at any distance from the Tylarium. Connect to the CC
300T using a low-current cable – see wiring diagram. If more than one
external on/off switch is used, the switches must be connected in
parallel. Press once on the external switch to start the CC300T, which
then remains in operation for as long as the running time has been set.
(See ‘Initial start-up’.) The next time you press the external switch, this
will turn off the CC300T – unless it has been pre-programmed or is
protected by a security code. If the CC300T has been pre-programmed
or is protected by a security code, it must be switched off by pressing the
ON/OFF button on the control panel.
May be placed at any distance from the Tylarium. Connect to the CC
300T using a low-current cable – see wiring diagram. If more than one
external on/off switch is used, the switches must be connected in
parallel. When connected to receive a constant signal, the facility
remains operational for as long as contact closure is maintained between
terminals 19 and 20, but only up to the maximum running time that has
been set.
Connection to a central computer.
The unit can also be connected to a central computer that transmits a
momentary contact closure (short impulse) or constant signal between
terminals 19 and 20 in the CC 300T. The maximum permissible running
time is 24 hours.
Important! In order for the steam generator’s automatic emptying
function to work, the control panel must be switched off for at least 1.5
hours each day.
RH%
OK
R
12
Fig. 1. Menu display
1 = Left button, 2 = Middle button, 3 = Right button. 4 = Symbols/text that
correspond to the respective button. 5 = Symbols/text for setting and
displaying current values.
Buttons and display.
There are three buttons on the control panel. Symbols shown above the
buttons at the bottom of the display correspond to the respective button.
These symbols differ depending on the panel’s current mode. When the
arrows are shown in the Menu display (fig. 1), use the left and right
buttons to move to the desired symbol. To select a symbol, confirm with
the middle button.
In the Normal display (fig. 2) the left button has an ON/OFF function. The
symbol for this appears at the bottom of the display above the left button.
When the facility is operational, this symbol shows green; when it is
switched off, the symbol is red; and when it is on stand-by, the symbol is
orange. The right button controls the lighting function. The lighting
symbol shows yellow when the lighting is on and white when the lighting
is off. The display also shows the current temperature/humidity.
To return to the Normal display from another mode, press the middle
button until the Normal display shows.
When a program is active, press the left button for 2 seconds to switch
off the active program.
Controlling other Tylö products.
The CC300T can also be used to control other Tylö products, such as a
Tylö Fresh fragrance dispenser, which can be activated while the panel is
in operation. Wiring for Tylö Fresh or other CC-panels must be
connected between terminals 40 and 41 on the CC 300T and terminals
19 and 20 on the other Tylö product. See Fig. J for an example of this.
Fig. C, E – wiring diagram.
11
%
33
R
Fig. 2. Normal display
22
ºc
MENU
Initial start-up.
When you switch on the control panel for the first time, you must
configure certain basic settings. First select the relevant region and
confirm your choice by pressing the middle button. Then select the
desired language and confirm with the middle button. Next, use the left
and right buttons to set the correct date and time, and confirm with the
middle button. Finally, set the running time for a manually activated
bathing cycle. (The standard setting is for 3 hours, but you can choose
1–24 hours.) Move up/down with the right/left button respectively until the
desired running time is displayed. Each button press increases/
decreases the running time by 15 minutes. To move more quickly, keep
the button depressed. Confirm the time with middle button. The basic
settings are now stored in the control panel’s memory.
Lighting.
The lighting comes on/goes off automatically when the facility starts/
shuts down. The lighting can also be controlled manually by pressing the
right button when the lighting symbol shows at the bottom right of the
display. The symbol shows white when the lighting is off and yellow when
the lighting is on.
Code lock.
Prevents unauthorised users from changing the programmed settings.
Main power switch.
This switch, on the underside of the relay box, SE sauna heater and
small steam generators, should be used only when the facility is to
remain switched off for a prolonged period of time.
Note! Place the thermometer (hygrometer) in the Tylarium at a height
where the values shown correspond exactly with the figures displayed on
the CC 300T panel.
Stand-by.
The stand-by function is invaluable for Tylarium facilities in hotels, public
baths, etc., where visitor frequency varies. During off-peak hours the
equipment is set at stand-by heat, which can rapidly be raised to the
desired temperature by pressing the ON button or using an external
switch. This stand-by feature can yield substantial savings every year.
The examples below show how easy it is to program a suitable bathing
schedule.
Examples of Stand-by operation.
Here are examples of three different options for public facilities open
between 8 am to 8 pm, with varying numbers of visitors:
Option 1) A limited number of visitors use the facility sporadically
throughout the day. Program “stand-by” between 8 am and 8 pm. Bathers
(or the attendant responsible) activate the bathing cycle by pressing the
control panel’s ON button.
Option 2) A limited number of visitors use the facility sporadically
between 8 am and 2 pm. From 2 pm to 8 pm there is a steady flow of
bathers. Program “stand-by” between 8 am and 2 pm, and program a
permanent “ON” time from 2 pm to 8 pm. Visitors during the morning
activate the bathing cycle by pressing the control panel’s ON button.
Option 3) Large numbers of bathers 8–10 am, 1–2 pm and 6–8 pm. The
rest of the day, the facility is used only sporadically. Program “stand-by”
between 8 am and 8 pm and program permanent “ON” times for the peak
periods above. Visitors during off-peak times activate the bathing cycle
by pressing the control panel’s ON button.
SETTINGS
CC 300T
MANUAL ON/OFF.
Setting the bathing temperature.
Select [MENU] in the Normal display and then select the thermometer
symbol. Use the arrow keys to enter the desired temperature and then
confirm with [OK].
Setting the humidity level.
Select the water droplet symbol. Use the arrow keys to enter the desired
humidity (RH%). Confirm with [OK]. Note! The value for the maximum
humidity varies according to the bathing temperature selected.
Starting the bathing cycle.
Then select the Return symbol, confirm with the middle button and select
the ON/OFF symbol to start the bathing cycle. To switch the unit off,
press once more on ON/OFF. The symbol shows red when the facility is
switched off, and green when the facility is in operation.
AUTOMATIC ON/OFF.
Setting the bathing temperature.
Select [MENU] in the Normal display and then select the thermometer
symbol. Use the arrow keys to enter the desired temperature and then
confirm with [OK].
Setting the humidity level.
Select the water droplet symbol. Use the arrow keys to enter the desired
humidity [(RH%)]. Confirm with [OK]. Note! The value for the maximum
humidity varies according to the bathing temperature selected.
Starting the timer function.
Select [MENU] in the Normal display. Select [Program] and then [Timer].
Enter the countdown time (= time remaining before the facility is
automatically switched on) and confirm with OK.
The switch-on time has now been set and the bathing cycle will begin
automatically at the pre-set time. The countdown to the switch-on time is
shown at the top left of the display. You can switch off the countdown
function at any time by pressing twice on the button under the ON/OFF
symbol. To switch off the equipment after the bathing cycle has begun,
press just once on the ON/OFF button.
If the humidity level exceeds 30% when the equipment is switched off, an
automatic drying cycle will be activated. This takes about 20 minutes
(factory setting).
PROGRAMMING THE WEEKLY TIMER
with different settings for different days of the week, or with the
same setting for every day of the week.
Select [MENU] in the Normal display and then select [Program]. Select
[Program] one more time in the Program display (see fig. 3). When you
press [OK] the highlighted text [Add] changes colour to dark blue. You
are now in the Programming mode. First use the arrow keys to select the
desired weekday (current choice is shown in red). You can select each
weekday separately or choose Monday–Sunday (for the same setting on
all days), Monday–Friday or Saturday–Sunday. Confirm with [OK]. Then
set the start time. Each key press increases/decreases the time shown
Timer
Översikt Åter
OK
R
12
by 15 minutes. Press [OK] when the desired start time is displayed. Then
set the desired switch-off time and press [OK]. Indicate whether the
facility is to be on, off or on stand-by for the time chosen The ON/OFF
symbol shows green if the facility is to be on, red if it is to be off and
orange for stand-by. When selecting the ON mode, you must also set the
desired temperature and humidity. Use the arrow keys and confirm with
[OK]. To program a new value, press the right button once to highlight
[Add] and then press [OK]. Then repeat the procedure described above.
To return to the Normal display, select [Back] and confirm with [OK].
Select [Back] once more and then [OK]. If no buttons are pressed, the
control panel automatically reverts to the Normal display after approx. 30
seconds. To delete all pre-programmed times, select [Clear calendar].
You can also temporarily deactivate all programmed values by selecting
[Calendar OFF].
For a simple overview of the pre-programmed schedule select [Overview]
in the Program display. A schematic bar chart diagram shows red for
times when the facility is switched off, green when it is in operation and
yellow when it is on stand-by.
When ON is pressed while the bathing facility is in stand-by mode, the
temperature immediately begins to rise to the pre-set value for bathing.
After 1 hour, the temperature automatically reverts to the stand-by
temperature. Each time the ON button is pressed, a new 1-hour
operating cycle is started.
When the facility is in the OFF mode, the settings are those that were
entered as part of the initial start-up process.
At any time while the facility is operational, you can switch it off manually
by pressing OFF. (This switches off only the current bathing cycle.)
If the humidity level exceeds 30% when the equipment is switched off, an
automatic drying cycle will be activated. This takes about 20 minutes
(factory setting).
You can also deactivate the entire calendar function temporarily, for
example, to carry out service or maintenance, and then reactivate it.
BATHING OUTSIDE PROGRAMMED TIMES
if the control panel’s security code function has been activated.
The Tylarium can also be used at times other than those that have been
programmed. Pressing ON starts a 1-hour bathing cycle. To prolong the
bathing period, simply press ON again. The bathing cycle is terminated
automatically 1 hour after the ON button has last been pressed.
IMPORTANT! Don’t forget to use the security code to lock the panel.
PANEL SETTINGS
CC 300T
Display.
LCD brightness.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [(Brightness (%)] and press the middle button. The highlighted
text then turns dark blue and the value for the brightness of the LCD
display can be changed. Press [OK] to confirm.
LCD brightness in sleep mode.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [Stand by] and press the middle button. The highlighted text
then turns dark blue and the value for the brightness of the LCD display
when the panel is on stand-by can be changed. Press [OK] to confirm.
(The factory setting is 30%.)
Countdown to LCD sleep mode.
Select [MENU] in the Normal display, [Service] and then [Display].
Highlight [Stand by time] and press the middle button. The highlighted
text then turns dark blue, and you can reduce or extend the length of time
it takes before the LCD display dims after the panel has switched to
stand-by. Press [OK] to confirm.
Service.
See SERVICE SETTINGS
Code lock.
Select [MENU] in the Normal display and then [Service]. Use the arrow
keys to move to [Code lock] and press [OK]. Enter the desired code. Use
the arrow keys to display the correct combination and confirm with [OK].
The security code function is automatically activated during programming
and the panel shows Normal display.
To return to unlocked mode, repeat the above procedure and set the
code to 0000.
It is not possible to change any settings when the security function has
been activated. It is possible, however, to switch both the facility and the
lighting on and off. The bathing cycle runs for the time indicated in the
Service menu under [Time outside timer]. (Factory setting: 1 hour).
A general code that always works is 1995.
IMPORTANT! Program all settings before activating security code.
Language.
Select [MENU] in the Normal display and then [Service]. Select
language. Use the arrow keys to select the required language and then
press [OK].
Clock.
Select [MENU] in the Normal display and then [Service]. Select [Set
clock). First use the arrow keys to set the right day and confirm with [OK].
Then set the correct time; first the hour and then the minutes.
Factory settings.
Select [MENU] in the Normal display and then [Service]. Select [Factory
settings]. Use the arrow keys to select [Yes] or [No] and then press [OK].
Selecting [Yes] deletes all your own programmed settings and the panel
reverts to the original factory settings.
SERVICE SETTINGS
CC 300T
Service.
The Service menu enables the bathing facility attendant to change
certain settings such as the maximum bathing temperature. However, we
recommend that the original factory settings are always retained. The
Service menu is protected by a code to prevent unauthorised users from
changing factory settings. In the Normal display press [MENU] and then
[Service]. Select [Service] and enter the code 124.
System settings.
Limit for automatic drying cycle
[Dryup limit (%)] – When the facility switches off, it measures the relative
humidity in the room. If this exceeds 30% (factory setting), the equipment
initiates a drying cycle.
Drying temperature
[Dryiup temperature (°C)] – The ambient temperature in the facility during
the drying cycle. Factory setting: 80°C.
Drying time
[Dryiup time (mins.)] – The duration of the drying cycle. Factory setting:
20 minutes.
Minimum temperature for steam generation
[Min. temp. steam (°C)] – The lowest temperature at which the steam
generator starts. Factory setting: 40°C.
Maximum running time
[Max running time (hrs)] – The running time that was set at the initial
start-up. This setting does not apply when the equipment has been
programmed. Adjustable from 1–24 hrs. Factory setting: 3 hrs.
Temperature unit
[Temperature (°C/°F)] – This feature enables you to display temperatures
in Celsius or Fahrenheit.
Test menu
The Test menu is used only for trouble-shooting and technical support
via Tylö.
Max temperature.
[Max temp (°C/°F)] – Used to set the maximum temperature to which the
facility can be programmed. For Tylarium bathing, the maximum
temperature is 55°C.
Temperature reduction during stand-by.
[Temp reduction Stand by (°C/°F)] – This is where you indicate the
reduction in temperature from the programmed bathing temperature to
the stand-by temperature. Factory setting: 30°C.
Max. running time during stand-by.
[On time Stand by (mins)) – The duration of the bathing cycle that is
initiated when the ON button is pressed while the facility is on stand-by.
Factory setting: 60 minutes.
13
Max running time outside programmed time.
[Time outside timer (mins)] – The duration of the bathing cycle outside
code-locked, programmed time.
Removing limescale
[De-scaling (hrs)] – Timer function that records total operating time and
counts down to signal when it is time to clean the equipment from any
limescale deposits. Factory setting: 40 hours.
TYLARIUM
A Tylarium gives you full freedom to enjoy all types of sauna bathing –
dry saunas, wet saunas and steam saunas, too. As the relative humidity
in a Tylarium tends to be higher than in traditional sauna bathing, you are
kindly requested to take note of the following advice.
• Treat the lower mouldings of any windows in sauna room doors or
walls with boat varnish, and seal the gap between the pane of glass
and the moulding with bathroom silicone. This prevents any
condensation on the glass from seeping into the gap.
• Treat threshold and door handles with a couple of coats of boat
varnish. This preserves the finish of the wood and makes cleaning the
sauna much simpler. Oil sauna benches, skirting panels and backrests
on both sides with Tylö sauna oil.
IMPORTANT! Leave all other wood in the sauna room untreated.
In the event of a problem, please contact your Tylö
retailer.
die dem jeweiligen Knopf entsprechen. 5 = Symbole/Text für Einstellung
und Anzeige aktueller Werte.
Knöpfe und Display.
Auf dem Kontrollgerät sitzen drei Knöpfe. Über den Knöpfen sind am
unteren Rand des Displays Symbole zu sehen, die dem jeweiligen Knopf
entsprechen. Diese Symbole sehen je nach Betriebslage des
Kontrollgeräts unterschiedlich aus. Wenn die Pfeile im Menüdisplay zu
sehen sind (Abb. 1) kann man mit dem linken und rechten Knopf zum
gewünschten Symbol gelangen. Zur Auswahl eines Symbols ist dieses
mit dem Mittelknopf zu bestätigen.
Im Normaldisplay (Abb. 2) ist die Funktion des linken Knopfes ON/OFF,
und dessen Symbol ist am unteren Displayrand zu sehen. Wenn die
Anlage eingeschaltet ist, ist dieses Symbol grün, bei ausgeschalteter
Anlage wird das Symbol rot und die Standby-Anzeige leuchtet orange.
Der rechte Knopf dient dem Ein- und Ausschalten der Beleuchtung. Das
Lampensymbol ist bei eingeschalteter Beleuchtung gelb, bei
ausgeschalteter Beleuchtung weiss. Das Display zeigt auch die aktuelle
Temperatur an.
Bleibt der Mittelknopf längere Zeit eingedrückt, wird das Kontrollgerät
wieder in Normaldisplay-Lage zurückversetzt, falls es sich in einer
anderen Displaylage befunden hat.
Wenn ein Programm aktiv ist, 2 Sekunden lang den linken Knopf
drücken, um das Programm auszuschalten.
ºc
22
MENU
R
manuellem Start einstellen. Die Betriebszeit ist ab Werk auf drei Stunden
eingestellt, lässt sich aber auf 1 bis 24 Stunden einstellen. Der Wert lässt
sich mit dem rechten Knopf erhöhen (bzw. mit dem linken Knopf
senken), bis die gewünschte Betriebszeit im Display angezeigt wird. Mit
jedem Knopfdruck erhöht bzw. verringert sich die Betriebszeit um 15
Minuten. Zur schnelleren Wertumstellung, den Knopf eingedrückt halten.
Betriebszeit mit dem Mittelknopf bestätigen. Damit ist die
Grundeinstellung abgeschlossen.
Beleuchtung.
Leuchtet automatisch bei Einschalten der Anlage und erlischt
automatisch bei Ausschalten der Anlage. Die Beleuchtung lässt sich
auch manuell ein- bzw. ausschalten. Hierzu den rechten Knopf drücken,
wenn unten rechts im Display das Lampensymbol zu sehen ist. Das
Symbol ist bei ausgeschalteter Beleuchtung weiß, bei eingeschalteter
Beleuchtung gelb.
Codesperre.
Verhindert unbefugtes Ändern der eingestellten Werte.
Hauptsromschalter.
Auf der Unterseite der Relaisbox, des SE-Saunaofens und der kleineren
Dampfgeneratoren sitzt ein Hauptschalter, der nur auszuschalten ist,
wenn die Anlage längere Zeit außer Funktion gesetzt werden soll.
Tipp! Die Höhe, in der das Thermometer in der Saunakabine angebracht
wird, ist so zu wählen, dass die angezeigten Werte exakt mit den auf
dem Display des CC 300 angezeigten Zahlen übereinstimmen.
Standby.
Die Standby-Funktion ist wichtig für Tylariums in Hotels, Hallenbädern
usw. mit wechselnder Besucherfrequenz. Während besucherschwachen
Zeiten ist die Anlage auf die energiesparende „Bereitschaftswärme“
eingestellt. Durch Drücken der ON-Taste bzw. des externen Schalters
erhöht sich die Temperatur schnell auf die eingestellte Badetemperatur.
Diese Standby-Funktion spart im Laufe eines Jahres große
Energiekosten.
Wie aus den folgenden Beispielen hervorgeht, gibt es zahlreiche
Möglichkeiten zur Programmierung eines passenden Badeprogramms.
Beispiele Standby.
Unsere Beispiele beziehen sich auf drei verschiedene Saunaanlagen, die
im Laufe ihrer Öffnungszeit von 800 bis 2000 unterschiedliche
Besucherfrequenzen haben.
Alt. 1) Kleinere Gruppen von Saunabesuchern kommen sporadisch
während der gesamten Öffnungszeit. Standby-Funktion von 800 bis 2000
programmieren. Die Saunabesucher (oder ein Bademeister) aktivieren
das Badeprogramm durch Drücken der ON-Taste am Kontrollgerät.
Alt. 2) Kleinere Gruppen von Saunabesuchern kommen sporadisch von
800 bis 1400. Nach 1400 Uhr ist die Sauna bis zu ihrer Schließung stark
besucht. Standby-Funktion von 800 bis 1400 programmieren und die
Sauna danach von1400 bis 2000 Uhr in Betriebsstatus ON betreiben.
Saunabesucher, die bis 14 Uhr kommen, aktivieren das Badeprogramm
durch Drücken der ON-Taste am Kontrollgerät.
Alt. 3) In den Zeiten von 800 bis 1000, 1300- 1400 und 1800- 2000 Uhr
ist die Sauna gut besucht. Zu den übrigen Zeiten kommen nur
sporadische Besucher. Standby-Funktion von 800 bis 2000
programmieren und Betriebsstatus ON für die oben genannten Zeiten mit
hoher Besucherfrequenz programmieren. Die sporadischen
Saunabesucher aktivieren das Badeprogramm durch Drücken der ONTaste am Kontrollgerät.
EINSTELLUNGEN
CC 300
Abb. 2. Normaldisplay
Erste Inbetriebnahme.
Beim ersten Einschalten des Kontrollgeräts sind gewisse Einstellungen
vorzunehmen. Zunächst die Region wählen und mit dem Mittelknopf
bestätigen. Danach gewünschte Sprache wählen und mit dem
Mittelknopf bestätigen. Als nächstes Datum und Zeit einstellen. Mit dem
linken und rechten Knopf die gewünschten Werte wählen und mit dem
Mittelknopf bestätigen. Zuletzt die gewünschte Betriebszeit bei
MANUELLES EIN-/AUSSCHALTEN.
Einstellen der Badetemperatur.
Im Normaldisplay [Menü] und danach Thermometer-Symbol wählen.
Gewünschte Temperatur einstellen und mit [OK] bestätigen.
Anlage einschalten
Danach das ENTER-Symbol wählen, mit dem Mittelknopf bestätigen und
das ON/OFF-Symbol drücken, um die Anlage einzuschalten. Zum
Ausschalten der Anlage erneut auf ON/OFF drücken. Das Symbol
leuchtet rot, wenn die Anlage ausgeschaltet ist, und grün, wenn sie
eingeschaltet ist.
15
AUTOMATISCHES EIN-/AUSSCHALTEN.
Einstellen der Badetemperatur.
Im Normaldisplay [Menü] und danach das Thermometer-Symbol wählen.
Gewünschte Temperatur einstellen und mit [OK] bestätigen.
Timerfunktion starten
Im Normaldisplay [Menü] wählen. Danach [Programm] und schließlich
[Zeitschalt] wählen. Einschaltzeit (Zeit bis zum Einschalten der Anlage)
einstellen und mit OK bestätigen.
Jetzt ist der Zeitpunkt eingestellt, zu dem sich die Anlage automatisch
einschaltet. Die verbleibende Zeit bis zum Einschaltzeitpunkt wird oben
links im Display angezeigt. Die Timerfunktion lässt sich jederzeit durch
zweimaliges Drücken der Taste unter der ON/OFF-Symbole ausschalten.
Hat sich die Anlage bereits eingeschaltet, lässt sie sich durch einmaliges
Drücken der ON/OFF-Taste ausschalten.
WOCHENPROGRAMMIERUNG
erlaubt unterschiedliche Einstellungen für unterschiedliche
Wochentage oder dieselbe Einstellung für alle Wochentage.
Timer
Översikt Åter
OK
R
Die gesamte Kalenderfunktion lässt sich auch vorübergehend
desaktivieren (z.B. für eine Servicemaßnahme) und danach wieder
aktivieren.
BADEN AUSSERHALB PROGRAMMIERTER
ZEITEN
wenn das Kontrollgerät durch einen Code gesichert ist.
Das Tylarium lässt sich auch außerhalb der programmierten Zeiten
anwenden. Bei einmaliger Betätigung der ON-Taste startet eine
einstündige Badeperiode. Zur Verlängerung der Badeperiode, erneut auf
ON drücken. Eine Stunde nach dem letzten Betätigen der ON-Taste
schaltet sich die Anlage automatisch ab.
HINWEIS! Nicht vergessen, das Kontrollgerät durch die Codesperre zu
sichern.
EINSTELLUNGEN DES
KONTROLLGERÄTS
CC 300
Display.
LCD-LEUCHTSTÄRKE.
Im Normaldisplay [Menü], danach [Service] und schließlich [Display]
wählen. [Lichtstärke (%)] wählen und auf den Mittelknopf drücken. Das
Symbol wird dunkelblau und der Wert der Display-Leuchtstärke lässt sich
ändern. Einstellung mit [OK] bestätigen.
Abb. 3. Programmdisplay
Einstellung von Ein/Aus/Standby, Temperatur.
Im Normaldisplay [Menü] und danach Programm wählen. Im
Programmdisplay erneut Programm wählen (siehe Abb. 3). Auf [OK]
drücken. Das Symbol [Add] wird dunkelblau. Jetzt befinden Sie sich im
Programm-Modus. Mit den Pfeiltasten den ersten gewünschten Tag
wählen (der aktuelle Text ist rot gekennzeichnet). Man kann jeden
Wochentag einzeln wählen, oder aber direkt Montag-Sonntag wählen
(um dieselbe Einstellung für alle Wochentage zu programmieren),
Montag–Freitag oder Samstag–Sonntag wählen. Mit [OK] bestätigen.
Danach die Uhrzeit einstellen, zu der sich die Anlage einschalten soll. Mit
jedem Drücken der Pfeiltaste erhöht sich die Zeit um 15 Minuten. Wenn
die gewünschte Zeit im Display erscheint, diese mit [OK] bestätigten.
Danach gewünschte Ausschaltzeit wählen und mit [OK] bestätigen.
Wählen Sie, ob die Anlage zu dem angegebenen Startzeitpunkt
eingeschaltet oder auf Standby sein soll. Das ON/OFF-Symbol ist grün,
wenn die Anlage eingeschaltet sein soll, rot, wenn die Anlage
ausgeschaltet sein soll, und orange, wenn die Anlage auf Standby
stehen soll. Bei Einschalten der Anlage ist auch die gewünschte
Temperatur einzustellen. Mit den Pfeiltasten den gewünschten Wert
wählen und mit [OK] bestätigen. Um eine neue Programmierung
vorzunehmen, erneut auf den rechten Knopf drücken, um [Add] zu
kennzeichnen und danach mit [OK] bestätigen. Danach die oben
beschriebene Vorgehensweise wiederholen. Um wieder ins
Normaldisplay zu gelangen, [Zurück] wählen und mit [OK] bestätigen.
Erneut [Zurück] wählen und mit [OK] bestätigen. Wenn keine Tasten
bestätigt werden, stellt sich die Kontrolleinheit nach etwa 30 Sekunden
automatisch auf Normaldisplay um. Um alle programmierten Zeiten zu
löschen, wählen Sie [Kalender löschen]. Man kann auch alle Programme
vorübergehend desaktivieren, indem man [Kalender AUS] wählt.
Um eine einfache Übersicht über die vorprogrammierten Programme zu
aufzurufen, im Programmdisplay [Übersicht] wählen. Daraufhin wird in
Form von Stapeln angezeigt, wann die Anlage ausgeschaltet (rot),
eingeschaltet (grün) oder auf Standby ist (orange).
Sobald man im Standby-Modus auf ON drückt, steigt die Temperaturen
auf die voreingestellte Temperatur. Nach einer Stunde sinkt die
Temperatur automatisch wieder auf die Standby-Temperatur. Jede
Betätigung der ON-Taste startet eine neue, einstündige Badeperiode.
Wenn die Anlage in OFF-Stellung ist, gelten die bei der ersten
Inbetriebnahme gemachten Einstellungen.
Wenn die Anlage eingeschaltet ist, kann man sie durch Drücken der
OFF-Taste manuell ausschalten. (Dadurch wird nur die laufende
Badeperiode ausgeschaltet).
LCD-Leuchtstärke in Standby
Im Normaldisplay [Menü], danach [Service] und schließlich [Display]
wählen. [Standby (%)] wählen und auf den Mittelknopf drücken. Die
Kennzeichnung wird dunkelblau und der Wert für die DisplayLeuchtstärke im Standby lässt sich ändern. Einstellung mit [OK]
bestätigen. Ab Werk ist dieser Wert auf 30 % eingestellt.
Zeit bis Standby-LCD.
Im Normaldisplay [Menü], danach [Service] und schließlich [Display]
wählen. [Stand by zeit] wählen und auf den Mittelknopf drücken. Die
Markierung wird dunkelblau. Jetzt kann man einstellen, nach welcher
Zeit sich die Leuchtstärke des Displays verringern soll, nachdem das
Kontrollgerät in Standby-Modus gegangen ist. Einstellung mit [OK]
bestätigen.
Service.
Siehe SERVICEEINSTELLUNGEN
Codesperre.
Im Normaldisplay [Menü] und danach [Service] wählen. [Codesperre]
wählen und auf OK drücken. Gewünschten Code eingeben. Mit den
Pfeiltasten die entsprechenden Zahlen eingeben und mit [OK]
bestätigen. Die Codesperre wird bei Programmierung automatisch
aktiviert und das Normaldisplay erscheint wieder.
Um die Codesperre zu desaktivieren, den Code auf 0000 stellen.
Bei aktivierter Codesperre ist die Anlage gegen unbefugtes Ändern der
Einstellungen gesichert. Man kann lediglich die Anlage und die
Beleuchtung ein bzw. ausschalten. Die Anlage bleibt für die im
Servicemenü unter [Bad nicht progr. Zeit] angegebene Dauer
eingeschaltet (Werkseinstellung = 1 Stunde).
Ein allgemeiner Code, der immer funktioniert, ist 1995.
HINWEIS! Vor Programmierung der Codesperre sind alle
Einstellungen zu programmieren.
Sprache.
Im Normaldisplay [Menü] und danach [Service] wählen. Sprache wählen.
Mit den Pfeiltasten gewünschte Sprache auswählen und mit [OK]
bestätigen.
Uhr.
Im Normaldisplay [Menü] und danach [Service] wählen. [Einstellung Uhr]
wählen. Zuerst mit den Pfeiltasten den aktuellen Tag einstellen und mit
[OK] bestätigen. Danach die aktuelle Uhrzeit einstellen – erst Stunden
und dann Minuten.
16
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.