Tyco Safety Software House PH, PI37, RMXIC, 4000, PI26 Users Manual

RM-iC Series

Quick Start
Installation Guide
Version E0
Part Number UM-068
April 2006
PRODUCT

Specifications

The RM-iC series readers provide an enclosed RM-4 board and attached iCLASS read head, available in the following styles:
RM1-iC - enclosed RM-4 and attached iCLASS read head
RM2-iC - enclosed RM-4 with keypad and attached iCLASS read head
RM2L-iC - enclosed RM-4 with keypad, LCD display, and attached iCLASS read
head.
The RM-iC Quick Start Installation Guide provides a synopsis of installation and connection information for RM-iC series readers. Refer to the Readers, Inputs, and Outputs (RIO) Guide for in-depth technical and installation information.
The following specifications apply to all RM-iC series readers:
Power: 12VDC, 300 mA
Cable: Belden 9841
Cable distance from iSTAR or apC: 4,000 ft.
Temperature
Indoor: 32° F to 120° F (0° C to 49° C)
Outdoor: -31° F to 151 ° F (-35 ° C to 66° C)
Qualified on 26-bit, 35-bit, 37-bit, and 32-bit MIFARE serial number formats.
NOTE

Standards

UL has only evaluated the 26-bit HID card format for this unit.
RM-iC series readers are Underwriters Laboratories Inc. (UL), Listed to Standard UL 294, Access Control System Units, Fifth Edition. RM-iC series readers must be wired in accordance with the National Electrical Code (ANSI/NFPA 70), local codes, and the authorities having jurisdiction.
1

Installation

INSTALLATION
Installing the Mount
Plate
Installing an RM-iC series reader involves:
1. Installing the mount plate
2. Wiring the components
3. Connecting and grounding the cable shields on the reader bus
4. Setting the RM-4 (reader) address
5. Installing the ARM-1 relay board (optional)
6. Installing the heater kit. (optional)
Figure 1 shows RM-iC standard housing, mount plate, and gasket. All RM-iC series readers conform to the same housing, mount plate, and gasket dimensions.
Housing screws
Requires a security screwdriver
Standard Housing
Standard mount plate
Gasket
FIGURE 1. Standard Housing and Mount Plate
Figure 2 shows mount plate dimensions.
5.45"
Wiring access
1.54"
1.82"
2.73"
3.64"
3.92"
FIGURE 2. Mount Plate Dimensions
4.11"
3.66"
2.47"
1.29"
.83"
8x
Mounting hole
0.156" Thru, 0.280” Countersink
4.94"
2
Installation
This device has been approved for outdoor use when properly installed with RM Heater Kit Installation (P.N. 130-915) and the supplied gasket material. Position the gasket with the RM plate so that the mounting holes are properly aligned. Ensure that the gasket is placed between the mounting surface and mating surface of the RM plate. Fasten the RM plate to the mounting surface with the gasket material in between. Install the gasket so that no gaps or wrinkles are present.
Wiring the Inputs,
Outputs, Reader Bus
Figure 3 shows RM-4 P1 and P5 wiring.
FIGURE 3. RM-4 Wiring Requirements