Tyco Safety Canada 16WS4933 User Manual

WS4933 (433MHz) Series Wireless Carbon Monixide Detector

Installation and Operating Instructions

Read these instructions thoroughly before installation and use of the WS4933
The WS4933 is designed to monitor the CO gas level in residential dwellings and give early warning before potentially dangerous levels are detected. This device is intended for use with a compatible wireless alarm system. The detector consists of an electrochemical carbon monoxide sensor assembly coupled to a wireless trans­mitter. The Wireless Carbon Monoxide Alarm com­municates with the control panel and can send alarm, tamper and batter y condition messages to the system’s receiver. Caution: The detector expiry date is stamped on the detector. Af ter the expiry date, the detector should not be used - do not wait for end-of-life indication!
This carbon monoxide detector is designed for indoor use only. Do not expose to r ain or moisture. Do not knock or drop the detector. Do not open or tamper with the detector as this could cause malf unction. The detector will not protect against the r isk of carbon monoxide poisoning if not properly installed. CAUTION: This device will only indicate the pres­ence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas. This car­bon monoxide alarming device is designed to detect carbon monoxide gas from ANY source of com­bustion. It is NOT designed to detect smoke, fire or other gases unless the product has been investigated and determined to comply with applicable require­ments.
Figure 1: WS4933 Wireless CO Detector
Legend
A. Alar m L ED (see Table 1 f or LED indications) B. Test/Hush button C. Battery compartment
CAUTION: Unauthorized removal of the unit from the bracket will initiate a tamper alert.
Warnings:
The WS4933 Series wireless Carbon Monoxide detector shall be installed and used within an envir­onment that provides the pollution degree max 2 and overvoltages category I I in NON HAZARDOUS LOCATIONS, indoor only. The equipment is designed to be installed by SERVICE PERSONS only; (SERVI CE PERSON is defined as a person hav­ing the appropriate technical training and experience necessary to be aware of hazar ds to which that per­son may be exposed in performing a task and of meas­ures to minimize the risks to that person or other persons.) Failure to properly install, test and maintain a CO detector may cause it to fail, resulting in loss of life. Installation of the CO detector should not be used as a substitute for proper installation, use and maintenance of fuel burning appliances, including appropriate vent­ilation and exhaust systems.

Installation Instructions

Battery Installation
To replace the battery:
1. Remove the detector from its mounting base by twisting it counterclockwise. Remove and dis­pose of the battery according to your local reg­ulations.
2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing the new battery.
3. Install a new 3-volt CR123A Panasonic Lithium battery in the battery compartment observing correct polarity. If the battery is incorrectly inserted, remove gently with a non-conductive tool and correctly reinsert.
4. Reinstall the detector onto the mounting base by turning it clockwise.
5. After the power-up sequence, the green LED should blink once every 12 seconds to indicate normal operation. If the battery is not installed correctly, the detector will not operate and the battery may be damaged.
Enrollment
At the alarm control panel, program the 6-digit serial number of the WS4933 (located on the back of the detector). Please ref er to your control panel install­ation manual for details.
Selecting a Location
Selecting a suitable location is critical for the CO detector. The Consumer Product Saf ety Commission (CPSC) recommends to use at least one CO detector per household, located as near as possible to sleeping areas of the home, because the human body is most vulnerable to the CO gas ef fect during sleeping hours.
1
Figure 2: CO Detector Placement
Legend
A: Bedroom B: Living Room C: Kitchen D: Basement E: Garage
For added protection, install additional CO detect­ors in every separate bedroom and on every level of your home. If your bedroom hallway is longer than 14 meters (40 feet), install a CO detector at BOTH ends of the hallway. Install an additional detector 6 meters (20 feet) away from the furnace or fuel burning heat source. For maximum protection, the detector should also be located outside primary sleeping areas or at each level of your home. Mount the detector on a firm wall or ceiling. DO NOT install CO detectors:
l In locations where temperature may be below
0ºC (14ºF) or above 40ºC (104ºF).
l In locations where humidity is below 10% or
above 93% RH non-condensing.
l Near paint thinner fumes. l Near air conditioners, furnaces, stoves, fire-
places and any other ventilation source that may interfere with CO gas enter ing the detector.
l In locations where furniture or draperies may
obstruct the air flow.
l In exhaust streams f rom gas engines, vents,
flues or chimneys.
l Where dirt or dust could collect and block the
sensor and prevent it f rom working.
l In locations that can be reached by children. l In turbulent air from ceiling fans. l In close proximity to an automobile exhaust pipe
- this will damage the detector.
Mounting
The detector can be mounted on a wall or ceiling. For EN approved sites, only ceiling installation is allowed. The WS4933 must be mounted with its bracket (when it is attached to its bracket the tamper switch is pressed and the detector automatic reset is per­formed).
1. Refer to the diagram below and install using screw locations as required. Maneuver the base so the screws are at the elbow of the screw slots and secure.
2. Fit the detector inside the mounting bracket by aligning it as shown in Figure 3 (detector’s
alignment notch should be slightly off set from the mounting bracket tamper release tab), then turn the detector in a clockwise direction until it clicks into place.
3. Test the detector after completing the install­ation (as described in the TESTING THE DET ECTOR section of this manual) and refer to the alarm control panel installation manual for additional information concerning the use of wireless devices.
Figure 3: Mounting the Detector
Tamper Protection
The WS4933 includes a tamper resistant feature that prevents removal from the mounting base without the use of a tool. To engage the tamper res­istant feature, cut the small plastic tab located on the mounting bracket and then install the detector. To remove the detector f rom the base once it has been made tamper resistant, use an appropriate screwdriver to depress the square tamper release tab located on the skirt of the mounting bracket and turn the detector counterclockwise.

Owner's Instructions

Testing the Detector
Note: Before testing, notify the central station. Test the detector by pressing the Test/Hush button. The red LED flashes and the sounder emits a tem­poral 4 pattern. T he keypad indicates that the detector is in alarm.
Maintenance
Press the detector's TEST/Hush button once ever y week to ensure proper operation of the detector. When low battery alarm exists (see specifications) immediately replace the battery. Once a month, use a vacuum cleaner to keep the air vents free of dust.
2
Audible and Visual Indications
The tricolored LED (green, yellow, red) and a sounder on the detector provide local visual and aud­ible indication of the detector’s status as listed in Table 1.
Sounder (does
not pulse the
Status LEDs
Green
Normal
Alarm/Test
Detector Trouble
Low Battery
Detector End of Life
Powerup
Tamper
Table 1: Detector Status and Indication
flash every 12 seconds
Red f lash every 12 seconds
Yellow flash every 6 seconds
Yellow flash every 12 seconds
Yellow flash every 23 seconds
Green, yellow, red flash sequence every 12 seconds
Green, yellow, red flash sequence every 12 seconds
sounder and
LED con-
currently)
Off
ANSI S3.41 temporal 4 (press button to hush for 5 minutes)
One 100ms chirp every 45 seconds
One 100ms chirp every 45 seconds (press button to hush for 12 hours)
One 100ms chirp every 45 seconds
One 100ms chirp at end of power-up sequence
Off Tamper
Radio Sig-
nalling
Normal (none)
Alarm
Fault
Low battery
Fault
None
Specifications
End of life:
Operating frequency:
Audible signal (temp 4 tone):
Operating current:
Temperature range:
Operating humidity range:
Transmitted messages:
Power source:
Battery supervision:
Battery life expectancy:
Low battery threshold:
7 year s (see date stamped on back of detector)
433MHz
85 dBA min. in alarm (at 10ft (3m))
10 μA
0°C to 40°C (32°F to 104°F)
15% to 95% Relative Humidity, non-condensing
CO gas alarm, low battery, tamper, trouble message as a result of sensor end of life or sensor trouble, supervision.
One 3-volt CR123A Panasonic Lithium Battery (included)
Automatic transmission of battery status data as part of any transmitted message.
5 year s (under typical use). Note: Constant exposure to temperature or humidity extremes may r educe battery life.
2.3 V
You should know about Carbon Monox­ide.
Carbon monoxide, also known as "CO" by the chem­ical form, is considered to be a highly dangerous poisonous gas, because it is colorless, odorless or tasteless and very toxic. In general, biochemistry phenomena have shown that the presence of CO gas inhibits the blood's capacity to transport oxygen throughout the body, which can eventually lead to brain damage. I n any enclosed space (home, office) even a small accumulation of CO gas can be quite dangerous. Although many products of combustion can cause discomfort and adverse health ef fects, it is CO gas which presents the greatest threat to lif e. Carbon monoxide is produced by the incomplete combustion of fuels such as natural gas, propane,
3
Loading...
+ 4 hidden pages