Tyco Safety Canada 143G4000 User Manual

3G4000
3G (HSPA) WIRELESS ALARM
COMMUNICATOR
INSTALLATION MANUAL
V4.0
WARNING: This manual contains information on limitations regarding prod-
uct use and function and information on the limitations as to liability of the man­ufacturer. The entire manual should be carefully read.

TABLE OF CONTENTS

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Identification of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing the 3G40000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Connecting the 3G4000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Status LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operating Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Simulated Landline Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Panel Transmission Monitoring (PTM) . . . . . . . . . . . . . . . . . . . . . . . . .6
Wireless Communications Sequence . . . . . . . . . . . . . . . . . . . . . . . . .6
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Activating the Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Swinger Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Hardware Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Low Power Radio Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
CONNECT 24 Remote Programming . . . . . . . . . . . . . . . . . . . . . . . . .8
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3G4000 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
IMPORTANT
The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions. The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall before operation. Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation WARNING: Never install this equipment during a lightning storm! Instruct the end-user to:
- Not attempt to service this product. Opening or removing covers may expose the user to dangerous voltages or other risks. Any servicing shall be referred to trained service persons only.
- Use authorized accessories only with this equipment.
Do not dispose of the battery in fire or water. Disposing of the battery in a fire will cause rupture and explosion. Do not dispose of the waste battery as unsorted municipal waste. Consult your local
regulations and /or laws regarding recycling with regard to this lithium battery pack. Doing so will help protect the environment. Some of the materials that are found within the bat-
tery could become toxic if not disposed of properly and may affect the environment
.
ii
Introduction
The 3G4000 is a wireless communicator that sends alarm system information to a Sur-Gard SG-System I, II, III or IV Receiver through a 3G (HSPA) or 2G (GPRS) wireless network. This wireless communicator can be used with UL/ULC Listed compatible control units, as indicated in the manufacturer's installation instructions.
NOTE: The 3G4000 is designed to work with the Contact ID communication format as described in SIA DC­05 Standard. Before completing the field installation of the alarm monitoring system please ensure com­munication with the supervising central station is successful by sending several events and getting confir­mation that they have been received.

Features

• Compatible with 4-digit or 10-digit Contact ID communication format as described in SIA DC-05 Standard. Example of suitable compatible alarm panels: DSC Models PC1864, PC1832, PC1616, PC4020.
• Simulates landline
• Switches automatically to the 3G (HSPA) or 2G (GPRS) network in the event of landline trouble (e.g., line down)
• Wireless Signal Indicator
• Four programmable outputs
• Contains one 12V - 1.2 Ah battery
• Case Tamper Output
• Landline overvoltage protection
• Tri-band UMTS/HSPA; Quad-Band GSM/EDGE Radio
• Four programmable inputs
• 3G (HSPA)/2G (GPRS) / Internet communication with Sur-Gard SG-SystemI/II/III/IV
• Panel transmission monitoring for up to four phone numbers

Technical Specifications

The input voltage to the 3G4000 can be drawn from the UL/ULC Listed control panel or provided by an external UL/ULC Listed power supply rated for the application (external power-limited source).
NOTE: The power supply must be Class 2, Power Limited. For residential applications a suitable power adap-
tor is model DSC ADP1310-NAU (for USA) and model DSC ADP1310-NA (for Canada).

Ratings

Power Supply Ratings - Input Voltage (for long-term operation)
JP3-OFF with internal battery: ...........................13.7V
Current Consumption
Average: ...........................................120mA*
Peak: .............................................700mA*
* Plus any current drawn from the 3G4000 AUX+ terminal
Working Voltage Range ...................................7.2VDC
Battery: ...................................NiMH, rated 7.2V, 2.2Ah
Battery charging voltage: .....................................
Battery charging current: ....................................150mA
NOTE: Battery must be replaced every 3-5 years.
Operating frequency: .................................850/1900MHz
Antenna gain: .........................................2.0dBi
Environmental Specifications
Operating temperature: ............................0°C-49°C
Humidity: ............................93%RH
Maximum (non-condensing)
Mechanical Specifications
Dimensions (plastic enclosure, painted): ......125mm
× 220mm × 22mm / 4.8” × 4” × 0.875”
Weight (without battery): ................................400g
Simulated Telco Loop specifications (TIP/RING)
On-Hook Voltage: .......................................
Loop Current .......................................... 25mA
Loop Resistance ......................................
DC required
7VDC
(32°F-120°F)
/ 1.2oz
35VDC
600Ohms
1
Identification of Parts
7
NOTE:
For UL/ULC installations, connections between the alarm control panel outputs (telephone interface Tip/Ring, output relay contacts) and 3G4000 inputs (Tip/Ring, Z1-Z4) shall be r un in a mechanical protective conduit within 20ft (6m) of one another and in the same room. .

Figure 1 - Parts

4A
NOTE:
For UL/ULC installations,
NOTE: For UL/ULC installations,
connections between the alarm
connections between the alarm
control panel outputs (telephone
control panel outputs (telephone
interface Tip/Ring, output relay
interface Tip/Ring, output relay
contacts) and 3G4000 inputs
contacts) and 3G4000 inputs
(Tip/Ring, Z1-Z4) shall be run in
(TIP/RING/Z1/Z2) shall be run in
a mechanical protective conduit
a mechanical protective conduit
within 20ft (6m) of one another
within 20ft (6m) of one another
and in the same room
and in the same room.
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.4mm) of separation must be maintained at all points between Power Limited wiring and all other non-Power Limited wiring. Route wires as indicated above.
1

Table1:Parts

2
M
TH2
FIDB1
TIP RING T1 R1

Parts

SERIAL NUMBER
1000X500
CON5
53 64
ANT1
REV02
UA674
ROUT
ROUT
A
2
ARE
INHIBITINHIBIT
OPEN OPEN
SW1
Z1 PGM1 Z2 PGM2

1 Plastic Casing 2 Anchor Screw Holes (3mm) 3 SIM Card Holder 4 3G Antenna

4A 3G External Antenna (Optional)*

5 3G (HSPA) Radio Module 6 Antenna Connector 7 Antenna Mounting Hardware 8 Tamper Switch

9 Status LEDs (see page 5) 10 Terminal Blocks 11 PC-Link Connector 12 Battery Connector 13 Cable Entry 14 7.2V - 2.2Ah Battery

* Use only DSC provided antenna.

JK1
EA R A
TH3
FIDB2
C97
C96
C95
INHI
ROUT
BI
C94
T
AREA
8
9
PCLINK
CON2
SI
FIDB4
+
CON1
TH1
-
-
+
DC IN
10 11 12
13
14
2
2
This equipment 3G4000 is fixed and shall be installed by Service Persons only (Service Person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task, and of measures available to minimize the risks to that person or other persons). It shall be installed and used within an environment that provides the pollution degree max 2, over voltages category II, in non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of the relevant alarm control panel. All instructions specified within that manual must be observed.

Description

This 3G4000 manages transmissions to a central station and can simulate the landline in the event of trouble (e.g., landline down) or even substitute the landline completely in areas where the 3G or 2G wireless service is provided and a landline is not available.
The 3G4000 has the capability of communicating alarm signals via the 3G or 2G data network. This capability ensures a fast, reliable path to central stations equipped with a Sur-Gard SG-System I / II / III / IV Receiver. By connecting a 3G4000 to a control panel's standard PSTN interface, telephone-based Contact ID signals are decoded and seamlessly routed through the 3G or 2G network to any of the compatible receiver options.
The performance of the 3G4000 depends greatly on wireless network coverage. Therefore, it should not be mounted without first performing placement tests to determine the best location for reception (minimum of one green LED ON). Optional antenna kits – GS15/25/50-ANT (15ft/4.6m, 25ft/7.6m or 50ft/15.2m) – are available.
The 3G4000 requires enrollment with CONNECT 24 to operate. Dealer application forms and additional information on the CONNECT 24 Voice Response Unit (VRU) and web user interface can be found at www.connect24.com, or at the following telephone numbers:
USA 1-888-251-7458 CANADA 1-888-955-5583
For UL Residential Fire and Burglary installations, the 3G4000 is listed as a sole means of communication or as a back up when used in conjunction with a POTS line (dialer). For UL Residential Fire installations, when installed in the alternate enclosure for 3G4000RF, the 3G4000 has provisions for 24-hour standby power.
For UL Commercial Burglary installations, the 3G4000 is listed as a sole means of communication (supervision window of 200s required at monitoring station) or as a back-up when used in conjunction with a POTS line (dialer).
The 3G4000 shall be powered from any compatible listed control unit or compatible listed power supply that complies with the ratings specified on page 1. The power supply shall be listed for burglary applications and provide a minimum of 4 hours standby power capabilities. An example of a suitable listed compatible control unit is the DSC Model PC1864 with an AUX output rated 11.1 - 12.6VDC. An example of a suitable Listed power supply is DSC Model PC5204 with an AUX output rated 11.6 - 12.6VDC.
For ULC Commercial Fire Monitoring installations the 3G4000 is listed as a passive communication system when used in conjunction with a POTS line (dialer). Fire alarms shall be sent simultaneously over both communication methods (wireless network and PSTN).
For ULC Commercial Burglary installations the 3G4000 is listed as a passive communication system with communication line security level P2 when used as a back up in conjunction with a POTS line (dialer).
For ULC Residential Fire and Burglary installations the 3G4000 is listed as a sole means communication or as a back up when used in conjunction with a POTS line (dialer).
3
Loading...
+ 15 hidden pages