NOTE: This manual covers the following models for the North America:
GS2055-NA
TL255GS-NA
GS2055-SM-NA
TL255GS-SM-NA
Installation Manual
v2.5X
Warning: This manual contains information on limitations regarding product use and function and information on the limitations
as to liability of the manufacturer.
The Warnings on this page contain vital information. As the only individual in
contact with system users, it is the installer ’s responsibility to bring each item in
this Warning to the attention of all users of this system.
System Failures
This system has been carefully designed to be as effective as possible. There are
circumstances, however, involving fire, burglary, or other types of emergencies
where it may not provide protection. Any alarm system of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons.
Some, but not all, of the reasons may be:
Access by Intruders
Intruders may enter through an unprotected access point, circumvent a sensing
device, evade detection by moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the proper operation of the
system.
Component Failure
Although every effort has been made to make this system as reliable as possible,
the system may fail to function as intended due to the failure of a component.
Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all circumstances which could include
metal objects placed on or near the radio path or deliberate jamming or other
inadvertent radio signal interference.
Criminal Knowledge
This system contains security features which were known to be effective at the
time of manufacture. It is possible for persons with criminal intent to develop
techniques which reduce the effectiveness of these features. It is important that
your security system be reviewed periodically to ensure that its features remain
effective and that it is updated or replaced if it is found that it does not provide the
protection expected.
Failure of Replaceable Batteries
This system’s wireless transmitters have been designed to provide several years
of battery life under normal conditions. The expected battery life is a function of
the device environment, usage, and type. Ambient conditions such as high
humidity , high or low te mper ature s, or l ar ge temper at ure flu ctua tion s may re duce
the expected battery life. While each transmitting device has a low battery monitor which identifies when the batteries need to be replaced, this monitor may fail
to operate as expected. Regular testing and maintenance will keep the system in
good operating condition.
Inadequate Installation
A security system must be installed properly in order to provide adequate protection. Every installation should be evaluated by a security professional to ensure
that all access points and areas are covered. Locks and latches on windows and
doors must be secure and operate as intended. Windows, doors, walls, ceilings
and other building materials must be of sufficient strength and construction to
provide the level of protection expected. A reevaluation must be done during and
after any construction activity. An evaluation by the fire and/or police department
is highly recommended if this service is available.
Inadequate T esting
Most problems that would prevent an alarm system from operating as intended
can be found by regular testing and maintenance. The complete system should be
tested weekly and immediately after a break-in, an attempted break-in, a fire, a
storm, an earthquake, an accident, or any kind of construction activity inside or
outside the premises. The testing should include all sensing devices, keypads,
consoles, alarm indicating devices, and any other operational devices that are part
of the system.
Insufficient Time
There may be circumstances when the system will operate as intended, yet the
occupants will not be protected from an emergency due to their inability to
respond to the warnings in a timely manner. If the system is remotely monitored,
the response may not occur in time to protect the occupants or their belongings.
Motion Detectors
Motion detectors can only detect motion within the designated areas as shown in
their respective installation instructions. They cannot discriminate between
intruders and intended occupants. Motion detectors do not provide volum etric
area protection. They have multiple beams of detection an d motion can only be
detected in unobstructed areas covered by these beams. They cannot detect
motion which occurs behind walls, ceilings, floor, closed doors, glass partitions,
glass doors or windows. Any type of tampering w hether intentional or unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or any other part of the detection system will impair its proper
operation.
Passive infrared motion detectors operate by sensing changes in temperature.
However their effectiveness can be reduced when the ambient temperature rises
near or above body temperature or if there are intentional or unintentional sources
of heat in or near the detection area. Some of these heat sources could be heaters,
radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on.
Power Failure
Control units, intrusion detectors, smoke detectors and many other security
devices require an adequate power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the batteries have
not failed, they must be charged, in good condition and installed correctly. If a
device operates only by AC power, any interruption, however brief, will render
that device inoperative while it does not have power. Power interruptions of any
length are often accompanied by voltage fluctuations which may damage electronic equipment such as a security system. After a power interruption has
occurred, immediately conduct a complete system test to ensure that the system
operates as intended.
Security and Insurance
Regardless of its capabilities, an alarm system is not a substitute for property or
life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects
of an emergency situation.
Smoke Detectors
Smoke detectors that are a part of this system may not properly alert occupants of
a fire for a number of reasons, some of which follow. The smoke detectors may
have been improperly installed or positioned. Smoke may not be able to reach the
smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the
other side of closed doors. Smoke detectors may not detect smoke from fires on
another level of the residence or building.
Every fire is different in the amount of smoke produced and the rate of burning.
Smoke detectors cannot sense all types of fires equally well. Smoke d etectors
may not provide timely warning of fires caused by carelessness or safety hazards
such as smoking in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
Even if the smoke detector operates as intended, there may be circumstances
when there is insufficient warning to allow all occupants to escape in time to
avoid injury or death.
Telephone Lines
If telephone lines are used to transmit alarms, they may be out of service or busy
for certain periods of time. Also an intruder may cut the telephone line or defeat
its operation by more sophisticated means which may be difficult to detect.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or
waken someone sleeping if there is an intervening wall or door. If warning
devices are located on a different level of the residence or premise, then it is less
likely that the occupants will be alerted or awakened. Audible warning devices
may be interfered with by other noise sources such as stereos, radios, televisions,
air conditioners, other appliances, or passing traffic. Audible warning devices,
however loud, may not be heard by a hearing-impaired person.
3
Keypad Data Display2G Alarm Communicator Installlation Manual
Domain Name Service (DNS) programming is not permitted in UL/ULC listed systems.
KEYPAD DATA DISPLAY
• Section-Toggle Options: The number is displayed when Toggle is ON, the number is not displayed when Toggle is OFF . (e.g., Tog-
gle Options displays: “[
Toggle ON and OFF.
• HEX/Decimal Data: Values that are provided with two defaults, separated by a / character, use the format: hexadecimal followed by
decimal equivalent (e.g., Default [0BF5/3061]). Hexadecimal numbers are shown, with all leading zeroes, to the full field length
defined for the number.
ENTERING DATA FROM KEYPAD
To enter data at the keypad, press the number key, from the table below, to select the character that you want. Pressing the number key
repeatedly will scroll through the characters available for that key. Press the [*] key and use
selections: (Press [*] to select the Option.)
• ASCII Entry. Use this mode to enter ASCII characters from the keypad.
• Clear to End. This selection will clear the remainder of the display.
• Clear Display.This selection will completely erase all entries on the display.
• Change Case. Toggles between upper/lower depending on current selection.
NOTE: The “0” on the keypad is used to delete characters.
Table 1: Data Entry at Keypad
To enter Amer ican Standard Code for Information Interchange (ASCII) characters at the keypad, perform the following:
1. Press [*] and use [<] [>] keys to scroll to “ASCII Entry”.
2. Press [*] to select ASCII entry mode.
3. Use the
4. Press [*] to exit ASCII character entry mode and return to normal entry.
NOTE: Authorized access to Connect24 (GS2055/TL255GS) or DLS IV is required to modify any Ethernet/Cellular Programming
[<] [>] keys to scroll to display the ASCII character you want to use and press [*] to accept.
Section. Specific panel Sections must be configured for proper operation of the Communicator with the panel.
MOUNTING CONSIDERATIONS
The Cellular/Ethernet Communicator is fixed, wall-mounted unit and shall be installed in the location specified in these instructions.
The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs and it must be secured to a wall before
operation.
Internal wiring must be routed in a manner that prevents:
• Excessive strain on wire and on terminal connections,
• Interference between power limited and non power limited wiring,
• Loosening of terminal connections, or
• Damage of conductor insulation.
--3--6--
]”. Options 3 and 6 are ON, all others are OFF). Pressing keys 1 through 8 will alternately turn the
The Installer must instruct the System use r on each of the following items:
• This manual shall be used in conjunction with the Alarm controller manual; All the safety instructions specified within that manual
shall be observed.
• Do not attempt to service this product. Opening or removing covers may expose the user to dangerous
voltages or other risks.
• Any servicing shall be referred to trained service person only.
• Use authorized accessories only with this equipment.
Cellular Coverage for Alarm Communicator Operation
The HSPA/2G performance of the GS2055 and TL255GS Alarm Communicators depends greatly on Cellular network coverage. The
SCW (with internal Alarm Communicator) should not be mounted in the final location without first ensuring that Cellular radio reception is adequate for communication using the HSPA/2G paths. Perform the “Communicator Placement Test” on page 9.
4
2G Alarm Communicator Installlation ManualGeneral Information
All versions of the HSPA/2G and Ethernet Alarm Communicator, operate on a HSPA/2G network and are housed inside the Self Contained Wireless (SCW) 9055/9057. The Communicators use an Internal Antenna only.
Each version of Alarm Communicators covered by this Installation Manual are described below:
GS2055: A High Speed Packet Access/Global System for Mobile (HSPA/2G) wireless Alarm Communicator that sends alarm communication to Sur-Gard System I, II, III (SG-DRL3IP), and IV (SG-DRL4IP) central station receivers via a HSPA/2G digital cellular network.
TL255GS: Is a dual-path Cellular/Ethernet Alarm Communicator that sends alarm communication to Sur-Gard System I, II, III, and IV
central station receivers through Ethernet/Internet or a HSPA/2G digital cellular network.
The dual path Communicator can be used as either a backup or primary Communicator. The Communicator supports Internet Protocol
(IP) transmission of panel and internal events over Ethernet/Internet and/or HSPA/2G.
For North America the following model names are available: GS2055-NA, TL255GS-NA, G S 2 0 55-SM- N A , and TL255GS-SM-NA.CAUTION:
• Do not stay close to the equipment during device operation and to do not touch any exposed wires and other conductive surfaces,
• Recycle the battery according to the local rules and regulations.
NOTE: Prior to installation of the GS2055 or TL255GS Communicator, confirm with your local carrier that the HSPA/2G network is
available and active in the area where the Communicator will be installed, and that the loc ation provides a radio signal strength
that is adequate for uninterrupted service.
FEATURES
• 128-bit Advanced Encryption Standard (AES) encryption via HSPA/2G and Ethernet/Internet.
• Activating, initializing and remote programming through Connect 24.
• Back up or primary HSPA/2G alarm communication.
• Does not require an external HSPA/2G antenna.
• Ethernet LAN/WAN 10/100 BaseT (TL255GS only).
• Full event reporting to central station.
• Fully redundant Ethernet/Internet and HSPA/2G Dual-path Alarm Communication (TL255GS only).
• Individual Ethernet and/or HSPA/2G Periodic test transmission.
• 2-way audio (listen-in feature) provided over Cellular.
• Integrated call routing.
• Remote Firmware upgrade capability of the Communicator and Panel Firmware via Ethernet and/or HSPA/2G radio.
• Dual-Band Operation: 850 MHz, and 1900 MHz. (North America only)
• CID and SIA format reporting.
• Subscriber Identity Module (SIM) card included with Communicator. (North America only)
• Supervision heartbeats via HSPA/2G and/or Ethernet/Internet.
UL/ULC INSTALLATION REQUIREMENTS
• For ULC Residential fire and burglary applications the GS2055/TL255GS can be used as primary communication channel via either
Cellular or Ethernet (as applicable) or as a back-up in conjunction with the Digital Alarm Communicator Transmitter (DACT). Test
transmission every 24hours shall be enabled on each channel.
• For UL Residential fire and burglary applications the GS2055/TL255GS can be used as primary communication channel via either
Cellular or Ethernet, or as a back-up in conjunction with the DACT. (30 day test transmission is required on each channel).
COMMUNICATOR FREQUENCY BANDSFOR NORTH AMERICA
Table 2: 2G Frequency Bands
Transmit DirectionCellular 850 North AmericaPCS 1900 North America
Transmit Frequency824 MHz to 849 MHz1850 MHz to 1910 MHz
Receive Frequency869 MHz to 894 MHz1930 MHz to 1990 MHz
Table 3: 2G Frequency Bands
Transmit Direction
Transmit Frequency824 MHz to 849 MHz1850 MHz to 1910 MHz
Receive Frequency869 MHz to 894 MHz1930 MHz to 1990 MHz
Power Supply Ratings
Input Voltage3.5 / 3.9 / 4.2 VDC (min / NOM / MAX) from the SCW panel
Current Consumption75 mA100 mA
Standby Current (@ 3.7V)75 mA100 mA
Alarm (Transmitting) Current)400 mA @ 3.7V during transmission
Antenna Specifications
Dual band Antenna See Table 2 and Table 3
Environmental Specifications
Operating Temperature0°C - 49°C (32°F- 120°F)
Humidity5% ~ 85% relative humidity, non-condensing
Mechanical Specifications
Board Dimensions (mm)109 x 110
Weight (grams)6065
GS2055
Cellular Only
TL255GS
Ethernet and Cellular
HARDWARE COMPATIBILITY
Table 5: Compatibility
Communicator
GS2055
TL255GS
Products or components of products, which perform communications functions only shall comply with the requirements applicable to
communications equipment as specified in UL60950 or CAN/CSA-C22.2 No. 60950-1, Information Technology Equipment - Safety Part 1: General Requirements. Where network interfaces are internal to the control unit or receiver, compliance to CAN/CSA-C22.2
No. 60950-1 is adequate. Such components include, but are not limited to: hubs; routers; NIDs; Third party communications service
providers; DSL modems; and Cable modems.
Receiver/
ControlPanel
Receiver
Control PanelSCW9055/SCW9057 V1.00
Description
SG System I, v1.14+
SG System II, v2.11+
SG-DRL3-IP, v2.3+
SG-DRL4-IP, v1.2+
SOFTWARE COMPATABILITY
The Communicator is compatible with the following software:
• Connect24 Using: Simple Messaging System (SMS) Protocol.
• Connect24 Remote Flash. Using: Internet Protocol (IP) using Trivial File Transfer Protocol (TFTP).
COMMUNICATOR PRE INSTALLATION CONFIGURATION
CONNECT24™1 ACCOUNTAND SIM CARD ACTIVATION
(Before Installation)
Installation of the Communicator requires activation with Connect24 before operation. Dealer application forms and additional infor-
mation on the Connect24 Voice Response Unit (VRU) and graphical user interface (GUI) can be found at http://www.Connect24.com
or by telephone at: USA 1-888-251-7458 or CANADA 1-888-955-5583.
IMPORTANT: Prior to installing a GS2055 or TL255GS Communicator, contact your monitoring station to determine if it is a master
re-seller or visit http://www.Connect24.com to become an authorized dealer. In either instance, you will receive a Profile Number,
Installer ID Number, and an Installer Password. Perform the following pre installation:
1. Retrieve the installer account and password from the master reseller, or from Connect24 directly.
2. Connect your browser to the Connect 24 website at: http://www.Connect24.com or call VRU number.
3. Log in to the Connect24 website using your installer account and password.
4. Perform the following steps in a Connect24 session to activa te th e SIM card and initialize programming:
a. Navigate to the Initialize an account section.
b. Select Profile (This information will be provided by the master reseller or by Connect24).
c. Select Product Module.
d. Enter the SIM card number.
e. Click Next then enter in all relevant information as required.
f. Confirm all inform ation is entered correctly before submitting.
5. Repeat Step 4 to program another SIM card (i.e. another Subscriber), or log out from Connect24.
6. When you are at the physical installation site, the Communicator will automatically connect and download its programming from
Connect24 once the unit is initialized.
1. Connect24, DSC, and DLS IV are Registered Trademarks of Tyco International Ltd. and its respective Companies. All Rights Reserved.
NOTE: Following initial installation, you can log in to the Connect24 website at any time to re-configure the Communicator remotely ,
using the account created for this installation. For more information, refer to the Connect24 website.
Before leaving the installation site, the Communicator GS2055 or TL255GS shall be connected via an APPROVED (acceptable
to the local authorities) Network Interface Device (NID) (e.g., for UL Installations, U60950 listed NID). All wiring shall be performed according to the local electrical codes.
ENCRYPTION
The Communicator uses 128 Bit AES Encryption. Encryption can only be enabled from the monitoring station receiver. Each receiver
can independently have encryption enabled or disabled. When encryption is enabled, the central station will configure the device to
encrypt communications the next time the Communicator module performs a communication to that receiver.
NOTE: Packets will start being encrypted only after the next event is sent to that receiv er, or if the unit is restarted.
COMMUNICATOR CONFIGURATIONWITH SCW
NOTE: The Alarm Communicator is installed in the
SCW prior to shipment by Digital Security Controls
(DSC). The Factory Installation includes insertion of
the SIM card. The SCW should not be mounted in its
final location without performing a Communicator
Test to ensure adequate HSPA/2G coverage for the
GS2055 and TL255GS Alarm Communicators
INSTALLATION LOCATION
The Communicator shall be installed in an indoor
location only.
This HSPA/2G/Ethernet Communicator shall be
installed by Service Personnel only. (Service Person is
defined as a person having the appropriate technical
training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and can also take measures to minimize the
risks to that person or other persons). The Communicator shall be installed and used within an environment that provides the pollution degree max 2, over
voltages category II, in non-hazardous, indoor loca-
tion Manual of the alarm control panel which is connected to the HSPA/2G/Ethernet Communicator. All instructions specified within
the control panel manual must be observed.
All the local rules imposed by local electrical codes shall be observed and respected during installation.
INSTALLING CAT 5 CABLE (TL255GS ONLY)
A Category 5 (CAT 5) ethernet cable must be run from a source with Ethernet/Internet
connectivity to the Communicator module, inside the Self Contained Wireless Control
Panel cabinet. The Communicator end of the cable must have an RJ-45 plug, which connects to the Communicator’s RJ-45 jack. All requirements for installation of CAT5 ethernet cable must be observed for correct operation of the Communicator, including, but
not limited to, the following:
• Do NOT strip off cable sheathing more than required for proper termination.
• Do NOT kink/knot cable.
• Do NOT crush cable with cable ties.
• Do NOT untwist CAT5 pairs more than 1.2cm (½”).
• Do NOT splice cable.
• Do NOT bend cable at right angles or make any other sharp bends.
tions only. T his manua l shall be used wit h the Instal la-
NOTE: CAT5 specification requires that any cable bend must have a minimum 5 cm (2
NOTE: The Ethernet cable shall not be visible when the installation is complete unless
in.) bend radius. Maximum length of CAT 5 cable is 100m (328 ft.).
the install is a surface mount installation.
7
Inserting/Removing the SIM Card2G Alarm Communicator Installlation Manual
1.Remove the front cover of the SCW Control Panel to access SIM
card holder.
2.Remove power from the SCW and disconnect the backup battery
connections.
3.On the SIM card holder push gently to slide the cover towards
OPEN as indicated by the arrow on SIM holder. This will unlatch
the SIM card holder on the side furthest from edge of the Communicator. See Figure 1.
4.Lift up the SIM card holder from the side that is not hinged.
NOTE: The SIM card can be damaged by bending or scratching contacts. Use caution when handling the SIM card.
5. Insert or remove the SIM card, noting the orientation of the notc hes on the SIM card and the SIM card holder.
6. When inserting a SIM card, insert the card in the proper orientation and gently push the SIM card holder down and slide the holder
as indicated by the arrow on SIM holder, to LOCK.
7. Apply AC power to panel, and replace the panel cover.
COMMUNICATOR RESET
The Communicator can be reset by cycling the power on the SCW.
ESTABLISHINGA COMMUNICATION CHANNELWITHTHE SCW PANEL.
The Communicator interfaces to the SCW through a keyed 16 pin Ribbon cable. See Table 6 . The key prevents incorrect connection of
the ribbon cable connector to the SCW and Communicator. The pinout for the Ribbon cable is provided in the Table below:
Establishing a communication channel between the Communicator and the SCW is critical to ensuring the desired operation of the two
units. The following steps must be completed during the on-site installation. Program the following to ensure that the Communicator
and the panel will work together as intended.
Initial Programming of Communicator and SCW
1. Enter
[*][8][Installer Code] [Section Number]
appropriate Programming Worksheets.
NOTE: When programming Toggle Options, the toggle is ON when the number is displayed and OFF when the number is not dis
played. (e.g., [1---5---], Toggle Options 1 and 5 are ON, all others are OFF).
2. Panel Section [167] Cellular/Ethernet Interface Communications ‘Wait for ACK’: Default value is: 060 seconds.
3. When the communicator is installed with the SCW panel, 4 telephone number are available to backup one another. You can set up
these 4 telephone numbers to perform in one of two ways: Backup dialling or Alte rnate dialling.
a. Backup dialling: each of the 4 telephone numbers will make 5 dialling attempts in turn, before an FTC trouble is displayed on the
keypad.
b. Alternate dialling: each telephone number makes 1 dialling attempt before moving on to the next number, cycling through each
of the 4 numbers for a total of 5 times each. If all 4 numbers fail the 5 attempts, an FTC trouble is displayed on the keypad.
4. Panel Sections [301], [302], [303], and [305] can be configured as Primary communication paths.
a. Panel Sections [302], [303], and [305] may also be configured for backup or redundant communications by using Panel Section(s)
[383] or [351] - [376]. Refer to the SCW panel Installation Manual for more information.
b. If a valid telephone number is programmed, communications will use Public Switched Te lephone Network (PSTN). Entering a 4
digit hexadecimal value for a telephone number will change the call routing to the Communicator, as determined by the number
programmed:
DCAAF:Internal (All Receivers). Signals will be routed depending on Section [851] [006] programming.
DCBBF:Ethernet Receiver 1 (Primary). (Not available for GS2055).
DCCCF:Ethernet Receiver 2 (Backup). (Not available for GS2055).
NOTE: Add a single ‘F’ as a suffix to the 4 digit hex number to populate the unused remainder of the 32 character field.
5. Panel Section [350]: If any of the phone numbers have been programmed as DCAA, DCBB, DCCC, DCDD, or DCEE, panel Section [350] must be set to [04] if SIA format or [03] if Contact ID (CID) format is used by control panel.
6. Panel Section [382]: Toggle Option [5], ‘GS/IP Module Enabled’, must be set to ON.
for panel programming. Record any values that are m o dified from their default, in the
8
2G Alarm Communicator Installlation ManualSMS Command and Control Functions
7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel DLS session through Cellular or Ethernet data
channel.
NOTE: Keep a record of the SIM card telephone number, it is required by users for SMS Command and Control functions. (The num-
ber can be recorded in the Programming Wo rksheets Section of this document, under Option [996]) Due to the nature of the
SIM card activation process with Cellular network carriers, it can take up to 24 hours for SIM card activation to be complete.
SMS COMMANDAND CONTROL FUNCTIONS
SMS Command and Control is available on SCW9055/57 panels. Users can send SMS text messages from their mobile phone to the
GSM phone number assigned to their system. Commands are only accepted from telephone numbers that have been programmed in
Sections [311]-[318]. The system will reject messages sent from telephone numbers that are not on the programmed list.
When the received SMS text matches a valid Section message, the function is performed on the control panel. Text messages are not
case sensitive and extra spaces are ignored. A User Access Code may be required for som e SM S messages.
The User can send just the partition number or the complete label.(e.g., “Away arm Partition 2 1234” is treated the same as
“away arm 2 1234 ”).
The SMS Message format is in 3 parts: Command, Partition Label (or only the partition number), and Access Code.
If an Access Code is included in the message, it is sent to the control panel for validation, along with the requested function.
If the panel is configured to require an Access Code and the code is not sent (or invalid) the panel will fail the function (unsuccessful).
If the panel fails the function, an SMS response message is sent to the user . The SMS respon se will echo the command sensat, followed
by the label “unsuccessful”. (e.g., “night arm partition 2 1234 unsuccessful”).
The partition label or partition number may be excluded from the SMS request in a single partition system (e.g., disarm 9123).
NOTE: The GSM phone number can be viewed in Section [851],[996], and/or [851],[229] or by User entering *6, then scrolling down
to “SMS Programming” and scrolling down to “Cellular phone No”.
LABEL PROGRAMMINGfor SMS MESSAGE
Programmable Labels can not be modified in Connect24, use DLS IV for label programming only, if labels need to be modified. Before
initiating remote programming, record your network’s Public IP Address and port for incoming DLS IV connections.
1. Run the DLS IV software on your computer. DLS IV will connect to the unit, using the Public IP address, and make an Ethernet connection. If the Ethernet connection fails, DLS IV will report an error and prompt you to connect using Cellular.
NOTE: If required, download the DLS IV software fr om DSC: http://www.dsc.com/index.php?n=library#self. If you select Cellular
connection, DLS will request Connect24 to send an outgoing SMS message to the unit.
2. Connect24 will confirm that the account has DLS service and will provide the Public IP address and port number of the DLS server
in an SMS message.
3. Type the SMS message text into your cell phone and send it to the Communicator’s Cellular telephone number. Click OK.
NOTE: The Cellular phone number can be read from Communicator Section [851][996] and/OR [851][229].
4. SMS message will establish a connection to your computer’s DLS IV software (to change programming labels only).
5. Create an account for the panel/Communicator, select the Communicator type (e.g., SMS - TL255GS) and enter all relevant information in SMS section.
NOTE: The Cellular telephone number will also be required by the user, to send SMS Interactive messages to their system.
6. Program the account information, th en click Global Download and choose SMS as the Connection Type. Click OK.
7. The download path configured in Programming Section [005] Toggle Option[4] determines the Cellular or Ethernet path to be used.
COMMUNICATOR PLACEMENT TEST
(GS2055/TL255GS only)
1. Using the keypad enter the installer mode: * 8 [installer code] [850].
2. View and record the number of bars showing on the SCW LCD.
3. Compare with the number of bars indicated in the “CSQ Levels” column shown in Table 7 .
4. If 3 or more bars are shown, the location is GOOD and no further action is required.
5. If the location is BAD, move the SCW to various suitable locations until 3 or more bars are obtained
Table 7: Communicator CSQ Levels
Signal
Strength
No Signal0-108.8Check if Cellular coverage is active in your area.
1 Bar1 to 4-108d to -103L ocation is BAD. Not suitable for Cellular operation.
2 Bars5 to 6-102 to -99
3 Bars7 to 10-98d to -91Location is GOOD.
4 Bars11 to 13-90 to -85Location is GOOD
5 Bars14 and higher-84 and higher Location is GOOD.
CSQ LevelSignal Level dBmInstaller Action
Location is FAIR. If the average signal strength is CSQ is 5, the system may not communicate
events successfully to the Monitoring Station. Installer should consider relocation, if possible.
9
System Options2G Alarm Communicator Installlation Manual
The Programming Sections described in this document can be viewed at the SCW LCD. To start programming enter: [*][8][installer
code] [851][# # # ], Where ### is the 3 digit Section number referenced in this section. The Programming Worksheets at the end of
this document can be used to record the new values when programming changes have been made from the default values.
Programming Sections are accessed through Connect24. Installers may review/record programming Options at the panel.NOTE: Ethernet/Cellular Programming Sections accessed through the panel are for display purposes only. Configuration changes
must be done using Connect24.
SYSTEM OPTIONS
[001] Ethernet IP Address
Default (000.000.000.000)
Enter the IP address of the Communicator. Ensure that the IP address is unique to your Communicator on the local network. Format is 4
fields, each field is a 3 digit decimal number . Valid range: 000-255. If an IP address is programmed in this Section, the unit will operate
with Static IP (DHCP disabled). Sections [002] and [003] must also be programmed when using Static IP addresses.
NOTE: Default for this Section is Dynamic Host Configuration Protocol (DHCP) enabled. When enabled, the DHCP Server will set
[002] Ethernet IP Subnet Mask
Default (255.255.255.000)
Enter the Ethernet IP Subnet Mask of the Communicator. Format is 4 fields, each field is 3 digits. Valid range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the subnet mask for this Section and the
[003] Ethernet Gateway IP Address
Default (000.000.000.000)
Enter the Ethernet Gateway IP address of the Communicator. The gateway IP address is required when a router is used on the local network to reach the destination IP address specified in Section [001]. Format is 4 fields, each field is a 3 digit decimal number. Valid
range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the Gateway IP address for this Section and the programmed value will be
[004] Receiver Supervision Interval
Default (0087/135)
When receiver supervision is enabled (ON) in Section [005] Toggle Option [3], the unit sends heartbeats to Ethernet Receiver 1 or Cellular Receiver 1 to test the communications path. Use this Section to set the interval time (in seconds) when heartbeats will be sent to
the receivers. Valid range 000A-FFFF seconds. If the programmed value is less than (000A/10) seconds, supervision is disabled.
• Receiver Window: This is the supervision timeout that must be configured at the central station recei v er.
• Recommended Values: This is the recommended heartbeat interval that should be programmed into the Communicator.
• For ULC installations, the Daily test transmission must be enabled over each available communication channel Sections [125] and
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised
Default (OFF)
(TL255GS only).
ON: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet Receiver 1 based on the supervision interval pro-
grammed in Section [004].
OFF: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver once every hour , reg ardless
of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until ACK. If no event or heartbeat ACK is received after
(Receiver Supervision Interval + 75 seconds), Supervisory trouble is indicated.
NOTE: Ethernet Receiver 2 can not be supervised.
[2] Cellular Receiver 1 Supervised
Default (OFF)
ON: Cellular Receiver 1 will be supervised and heartbeats will be sent to Cellular Receiver 1 based on the supervision interval programmed in Section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 seconds. Failure to ACK 2 consecutive heartbeats will reset the radio.
OFF: Cellular Receiver 1 will not be supervised. When disabled, heartbeat is not sent to the receiver. Supervisory trouble is indicated.
NOTE: Cellular Receiver 2 can not be supervised.
[3] Supervision Type
Default (OFF)
ON: Heartbeat 1 (Commercial Supervision). This supervision type is suitable for applications where swap detection is required on the
supervisory packet.
OFF: Heartbeat 2 (Residential Supervision). This supervision type is suitable for applications where supervision of the communication
path to the receiver is required. (no swap detection).
values for: IP Address [001], Subnet Mask [002], and Gateway [003]. Programming an IP address in this Section will disable
DHCP (Static IP).
programmed value will be ignored.
ignored.
[225]. When programming with Connect24, the recommended intervals will be programmed automatically when the required window is selected.
NOTE: Commercial supervision is more data intensive than residential supervision and should only be u sed when required to meet the
approval for the installation.
[4]Primary Path
Default (OFF - TL255GS) (ON - GS2055)
ON: Cellular channel is the primary path. Ethernet channel is the secondary path, if it exists.
OFF: Ethernet channel is the primary path in a dual Communicator. Cellular channel is the secondary path.
[5] Redundant Communications
Default (OFF) (TL255GS only)
ON: Events will be communicated to Ethernet Receiver 1 and Cellular Receiver 1 at the same time. Events will be communicated to
Ethernet Receiver 2 and Cellular Receiver 2 at the same time. As long as the event is successfully communicated to 1 of the 2 paths
(Ethernet or Cellular) the Communicator will move on to the next event.
NOTE: Do not configure Ethernet Receiver 1 and Cellular Receiver 1 to communicate using a common receiver configuration (i.e.,
identical Receiver IP address and Receiver Remote Port). OFF: Events will be communicated to the receivers individually.
Toggle should be OFF when guaranteed message delivery to both receivers is required.
[6]Remote Firmware Upgrade
Default (ON)
ON: The Communicator module firmware can be remotely upgraded using the Ethernet/Cellular paths.
OFF: The Communicator module firmware can not be remotely upgraded. Local firmware upgrade is still possible.
[7] Alternate Test Transmissions
Default (OFF).
ON: When the periodic test transmi ssi on interval occurs, the test transmission will alternate between being sent to the primary and sec-
ondary receivers with each test transmission interval.
OFF: When the periodic test transmission interval occurs, the test transmission will be sent to the programmed receivers, based on the
settings of the periodic test transmission reporting codes.
[8]Cellular Low Signal Trouble.
Default (OFF)
This option masks the Low Signal trouble from the Cellular trouble event.
ON: A Cellular Trouble event is transmitted to receiver when the radio signal level falls below threshold level (average CSQ level is 5
or less).
OFF: A Cellular Trouble event is not transmitted to rece iver when the radio si gnal le vel falls below threshold level (average CSQ level
is 5 or less).
[006] System Toggle Options 2
[1] Ethernet 1 Receiver Enabled.
Default (ON) (OFF for GS2055).
ON: Ethernet Receiver 1 is enabled.
OFF: Ethernet Receiver 1 is disabled.
[2] Ethernet 2 Receiver Enabled.
Default (ON) (OFF for GS2055).
ON: Ethernet Receiver 2 is enabled.
OFF: Ethernet Receiver 2 is disabled.
[3] Reserved. ( ).
[4] Cellular 1 Receiver Enabled.
(ON).
Default
ON: Cellular Receiver 1 is enabled.
OFF: Cellular Receiver 1 is disabled.
[5] Cellular 2 Receiver Enabled.
(ON).
Default
ON: Cellular Receiver 2 is enabled.
OFF: Cellular Receiver 2 is disabled.
[6] Reserved ( ).
[7] DLS Over Cellular.
Default (ON).
NOTE: Program this toggle as OFF if you want to completely disable DLS from using the Cellular path.
ON: DLS is enabled on the Cellular path.
OFF: DLS is disabled on the Cellular path.
NOTE: If this T og gle is OFF, DLS sessions will occur on the Ethernet path only, regardless of Primary Path set in Section [005] Toggle
Option [4]. If it is ON then the Communicator will connect to the Primary path first for DLS and if the session fails, the Secondary path will be used.
[8] Reserved ( ).
[007] DNS Server IP 1
Default (000.000.000.000)
Programming this Section is not permitted on a UL/ULC listed system.
Enter the IP address for DNS Server 1. Format is 4 fields, each field is a 3 digit decimal. Valid range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP Server will configure the address. If an address is programmed and
DHCP is used, the address that you program will be used instead of the DHCP address.
[008] DNS Server IP 2
Programming this Section is not permitted on a UL/ULC listed system.
Default (000.000.000.000)
Enter the IP address for DNS Server 2. Format is 4 fields, each field is a 3 digit decimal. Valid range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP Server wi ll assign this value . If an address is programmed and DHCP
is used, the address that you program will be used instead of the DHCP address.
PROGRAMMING OPTIONS
[010] System Toggle Option
Default (Disable)
[1] This bit is used to enable/disable two way audio over 2G.
[011] Installer Code
Default (CAFE)
Program your installer code for this Communicator module. The installer code will be required when programming the Communicator
module. Valid range: 0000 - FFFF.
[012] DLS Incoming Port
Default (0BF6/3062)
The DLS Incoming Local Port (listening port) is the port DLS IV will use when connecting to the Communicator. If a router or gateway
is used, it must be programmed with a Transmission Control Protocol (TCP) port forward for this port to the Communicator module IP
address. Valid range: 0000 - FFFF.
[013] DLS Outgoing Port
Default (0BFA/306 6)
The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request has been sent to the Communicator. Use this Section to set the value of the local outgoing port. The value must be changed if the Communicator is located behind a firewall and must be
assigned a particular port number, as determined by your network administrator. In most cases, changing the default value or configuring your firewall with this port is not required.
Valid range: 0000-FFFF.
NOTE: If Section [006] Toggle Option [7] is ON. DLS will use the Primary path for session. If Section [006] Toggle Option [7] is OFF
[020] Time Zone
Default (00)
Use Column 2 (Offset Hours) to find your local Time Zone. Record the two digit HEX value from Column 1 (HEX Value) on the same
row. Program this HEX value for your Time Zone. Valid range is 00 - FF.
Table 8: World Wide Time Zones
DLS will use the Ethernet path, if available.
HEX
Value
Offset
Hours
Std
Abbrev
Location
HEX
Value
Offset
Hours
Std
Abbrev
Location
01-12BITBaker Island Time475.5ISTIndian Standard Time
05-11
09-10
NUTNiue Time485.75NPTNepal Time
SSTSomoa Standard Time
HASTHawaii-Aleutian Standard TimeEKST
XJTXinjiang Standard Time
East Kazakhstan Standard
Time
THATTahiti TimeLKTSri Lanka Time
TKTTokelau TimeVOSTVostok Time
496
CKTCook Island TimeOMSKOmsk Standard Time
0B-9.5MITMarquesas Island TimeNOVTNovosibirsk Time
0D-9
AKSTAlaska Standard TimeBTTBhutan Time
GITGambier Island TimeBIOTBritish Indian Ocean Time
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.