WARNING: This manual contains information on limitations regarding product
use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
The equipment is fixed, wall-mounted and shall be installed in the position specified in
these instructions. The equipment enclosure must be fully assembled and closed, with
all the necessary screws/tabs and secured to a wall before operation. Internal wiring
must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
WARNING: Never install this equipment during a lightning storm!
Instruct the end-user to:
- Not attempt to service this product. Opening or removing covers may expose the user
to dangerous voltages or other risks. Any servicing shall be referred to trained service
personnel only.
- Use authorized accessories only with this equipment.
Do not dispose of the battery in fire or water. Disposing of the battery in a fire will cause
rupture and explosion.
Do not dispose of the waste battery as unsorted municipal waste. Consult your local
regulations and /or laws regarding recycling with regard to this lithium battery pack. Doing
so will help protect the environment. Some of the materials that are found within the bat-
tery could become toxic if not disposed of properly and may affect the environment
.
ii
Introduction
The 3G3070 is a wireless communicator that sends alarm system information to an SG-System III, SGSystem II, or SG-System I receiver through a GSM/GPRS wireless network. This wireless communicator can
be used with UL/ULC Listed compatible control units, as indicated in the manufacturer's installation
instructions.
NOTE: The 3G3070 is designed to work with the Contact ID communication format as described in SIA DC05 Standard. Before completing the field installation of the alarm monitoring system please ensure communication with the supervising central station is successful by sending several events and getting confirmation that they have been received.
Features
• Compatible with 4-digit or 10-digit Contact ID communication format as described in SIA DC-05
Standard. Example of suitable compatible alarm panels: DSC Models PC1864, PC1832, PC1616,
PC4020.
• Simulates landline
• Switches automatically to the GSM network in the event of landline trouble (e.g., line down)
• GSM Signal Indicator
• Four programmable outputs
• Contains one 12V - 1.2 Ah battery
• Case Tamper Output
• Landline overvoltage protection
• Dual-band GSM radio
• Four programmable inputs
• GPRS/Internet communication with Sur-Gard System III / II
• Panel transmission monitoring for up to four phone numbers
Technical Specifications
The input voltage to the 3G3070 can be drawn from the UL/ULC Listed control panel or provided by an
external UL/ULC Listed power supply rated for the application (external power-limited source).
NOTE: The power supply must be Class II, Power Limited. For residential applications a suitable power adap-
tor is model DSC ADP1310-NAU (for USA) and model DSC ADP1310-NA (for Canada).
Ratings
Power Supply Ratings - Input Voltage (for long-term operation)
NOTE: When the input voltage drops below 13.5VDC, the internal battery supplied with the 3G3070
will not be charged. In order to maintain a charged level for the internal battery, the power supply
must have a minimum voltage of 13.5V
DC
to ensure a sufficient battery charge in all conditions of use.
All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1”
(25.4mm) separation. A minimum 1/4” (6.4mm) of separation must be maintained at all points between
Power Limited wiring and all other non-Power Limited wiring. Route wires as indicated above.
3G3070
NOTE: For UL/ULC installa-
tions, connectionsbetween
the alarm control panel outputs (telephone interface
Tip/Ring, output relay contacts) and 3G3070 inputs
(Tip/Ring, Z1-Z4) shall be
run in a mechanical protective conduit within 20ft (6m)
of one another and in the
same room.
Identification of Parts
Table 1: Parts
1Metal Casing
2GSM Antenna
3GSM Antenna Mounting Hardware
4Anchor Screw Holes (3mm)
5GSM Antenna Connector
6SIM Card
7Status LEDs (see page 5)
8JP3 Current Limitation Jumper (refer to Ratings Section)
This equipment 3G3070 is fixed and shall be installed by Service Persons only (Service Person is
defined as a person having the appropriate technical training and experience necessary to be
aware of hazards to which that person may be exposed in performing a task, and of measures
available to minimize the risks to that person or other persons). It shall be installed and used
within an environment that provides the pollution degree max 2, over voltages category II, in
non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of
the relevant alarm control panel. All instructions specified within that manual must be observed.
Description
This 3G3070 manages transmissions to a central station and can simulate the landline in the event of
trouble (e.g., landline down) or even substitute the landline completely in areas where the GSM service
is provided and a landline is not available.
The 3G3070 has the capability of communicating alarm signals via the GPRS data network. This
capability ensures a fast, reliable path to central stations equipped with a Sur-Gard System III or System
II receiver. By connecting a 3G3070 to a control panel's standard PSTN interface, telephone-based
Contact ID signals are decoded and seamlessly routed through the GPRS network to any of the
compatible receiver options.
The performance of the 3G3070 depends greatly on GSM network coverage. Therefore, it should not
be mounted without first performing placement tests to determine the best location for reception
(minimum of one green LED ON). Optional antenna kits – GS15/25/50-ANT (15ft/4.6m, 25ft/7.6m or
50ft/15.2m) – are available.
The 3G3070 requires enrollment with CONNECT 24 to operate. Dealer application forms and
additional information on the CONNECT 24 Voice Response Unit (VRU) and web user interface can
be found at www.connect24.com, or at the following telephone numbers:
USA 1-888-251-7458 CANADA 1-888-955-5583
For UL Residential Fire and Burglary installations, the 3G3070 is listed as a sole means of communication
or as a back up when used in conjunction with a POTS line (dialer). For UL Residential Fire installations,
when installed in the alternate enclosure model 3G3070RF, the 3G3070 has provisions for 24-hour
standby power.
For UL Commercial Burglary installations, the 3G3070 is listed as a sole means of communication
(supervision window of 200s required at monitoring station) or as a back-up when used in conjunction
with a POTS line (dialer).
The 3G3070 shall be powered from any compatible listed control unit or compatible listed power supply that
complies with the ratings specified on page 1. The power supply shall be listed for burglary applications and
provide a minimum of 4 hours standby power capabilities. An example of a suitable listed compatible control
unit is the DSC Model PC1864 with an AUX output rated 11.1 - 12.6VDC. An example of a suitable Listed
power supply is DSC Model PC5204 with an AUX output rated 11.6 - 12.6VDC.
For ULC Commercial Fire Monitoring installations the 3G3070 is listed as a passive communication
system when used in conjunction with a POTS line (dialer). Fire alarms shall be sent simultaneously over
both communication methods (GSM network and PSTN).
For ULC Commercial Burglary installations the 3G3070 is listed as a passive communication system with
communication line security level P2 when used as a back up in conjunction with a POTS line (dialer).
For ULC Residential Fire and Burglary installations the 3G3070 is listed as a sole means communication
or as a back up when used in conjunction with a POTS line (dialer).
ATTENTION: The 3G3070 is equipped with a current limiter that limits current demand on the
12V
DC power input to 120mA. The current limiter is enabled by default (see Part #8 in 'Identifica-
tion of Parts’ on page 3) with JP3 in the OFF position. The current limiter can be disabled
(bypassed) with JP3 in the ON position. When the 3G3070 12V
Alarm Panel Aux+ output, DSC recommends that the current limiter be active to limit the demand
from the panel. If the alarm panel is intended to supply all of the current demand, you must
ensure that the panel can supply 500mA and that the current limiter is disabled. When the 3G3070
is transmitting, the current demand exceeds 120mA (500mA). With the current limiter in place,
the additional current demand is supplied by the 3G3070 battery.
NOTE: With the current limiter active, there is a risk of discharging the 3G3070 battery when
transmission frequency is high. The back up battery must always be connected to the device when
the current limiter is enabled.
If power to the 3G3070 is supplied by an external power supply (recommended 13.8 VDC, 0.7A), the
current limiter must be disabled to allow the full current demand to be supplied. In this configuration
the 3G3070 battery is not required.
DC power input is supplied by the
3
Installing the 3G3070
CONNECT 24 Enrolment Information
Only authorized dealers can enrol a 3G3070 with CONNECT 24. Dealer application forms and additional
information on the CONNECT 24 Voice Response Unit can be found at the CONNECT 24 website
www.connect24.com. Please contact CONNECT 24 at the number below for assistance:
USA 1-888-251-7458 CANADA 1-888-955-5583
NOTE: Steps 1 and 2 should be completed before turning on the 3G3070 unit.
NOTE: Before inserting or removing the SIM card, please ensure the unit is turned off.
STEP 1 - Activate Your SIM Card
Your SIM card must be activated with Connect 24 prior to use. Please call the Voice Response Unit
(VRU) at least 24 hrs prior to installation at 1-866-910-3865.
STEP 2 - Initialize the 3G3070 with Connect 24
Call the VRU at the toll-free number. Follow the voice prompts and enter your profile number, installer
ID number, installer PIN number and central station number. Ensure that all information is available and
at hand before calling the VRU. This information can be found in your VRU Enrollment Package.
STEP 3 - Determine the Best Signal Location
1. Unscrew the four screws securing the front panel to the cabinet. Remove the front panel.
2. Fit the GSM antenna [2]. Ensure the GSM antenna mounting hardware is fastened securely [3].
3. Attach the GSM radio module with the GSM antenna connector. Ensure that the connector is secure.
4. Turn on the 3G3070 and check the signal strength.
5. Connect the battery to the RED and BLK battery leads.
6. Connect the DC power source to +/- 12V terminals.
7. Allow the unit to power up.
NOTE: The green LEDs will indicate the signal strength. The bottom green LED must be on for the
location to be acceptable. Please refer to the ‘Status LEDs’ section for more information.
8. Power down the 3G3070 by removing the DC power source and battery leads.
STEP 4 - Connect the 3G3070
1. Using the cabinet, mark the four screw locations. Drill the anchor screw holes.
NOTE: Check for cable conduits and water pipes before drilling.
2. Using anchor screws (not provided), mount the cabinet to the wall.
3. Run the cables through the cable entry [13] or through the cabinet knockouts.
4. Complete the connections on the terminal blocks [11].
NOTE: Ensure that power and Telco circuit connections are made only after the cabinet has been
secured to the building or structure, and has been connected to the protective earth ground.
Descriptions of the terminals can be found in the ‘Connecting the 3G3070’ section.
5. Reattach the front cover [1] securely to the cabinet.
NOTE: Please refer to Figure 2 at the end of this manual for wiring diagram.
Connecting the 3G3070
(1) Earth Ground - This terminal must be connected to the Mains Earth, in order to comply with the
Telecommunications Network Safety Standards (Overvoltage Protection Requirements).
TIP (2) / RNG (3) External Telephone Line - These terminals must be connected directly to the
incoming telephone line.
T1 (4) / R1 (5) Internal Telephone Line - These terminals must be connected to the TIP and RING of
the control panel.
COM (6,14) Common - This terminal is connected internally to Power Ground.
PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs - These
outputs can be activated by programmed events. Refer to ‘Activating the Outputs’ for details. The
maximum current sink of each output must not exceed 50mA.
NOTE: Electrical current drawn from this terminal is drawn directly from the power supply. This
must be added to the 3G3070 current when determining the total draw on the host panel or
power supply. Jumper JP3 does not limit the electrical current available on this output.
4
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.