Tyco Safety Canada 02WLS916NB User Manual

WLS916-433 Series
T
Wireless Smoke Detector
Installation and Operating Instructions
Read this instruction sheet thoroughly
before installation and use of the
WLS916-433 Wireless Smoke Detector
Introduction
The WLS916-433 is a wireless photoelectric smoke detector with a fixed temperature heat detector and an internal piezoelectric alarm. Three version are available: US version (UL), Canadian ver­sion (ULC) and an International version (EU).
LED /Test Bu tto n
Piezo Sounder
Align ment Mark s
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke or heat alarm condition. During this sequence the unit also performs self diagnostics, and checks for tampers and faults. During normal operation the LED will flash every 48 seconds and the sounder will not sound.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity of approximately 2.5%/ft. obscuration. The smoke detector will go into alarm when the signal level exceeds the 'alarm' threshold and automatically restore when the signal level falls below the alarm 'restore' threshold. During an alarm the LED will flash 1/second and the sounder will sound the the evacuation temporal pattern (UL, EU) or continuous beeps (ULC).
The smoke detector has a preset warning threshold at 75% of the alarm threshold. If the signal level stays above this threshold, but below the alarm threshold, for more than 120 seconds, the detec­tor will go into the 'warning' state. If the signal level falls below the early warning 'restore' threshold, the detector will restore to its normal state automatically. If the signal level rises above the alarm threshold, the detector will go into alarm. The LED will flash and the sounder will chirp every 48 seconds when in the warning state.
Note: This feature is intended to provide a warning if the environ­ment is persistently close to the alarm threshold and provide more time to investigate and either escape or correct the situation.
Smoke - Drift Compensation The detector automatically compensates for long-term environ­mentally induced changes to maintain a constant smoke sensitivity. When the drift compensation has reached its high or low limit of adjustment, the detector will go into the trouble state.
Heat Alarm The heat detector will go into alarm when the heat signal level exceeds the heat alarm threshold (135ºF/57.22ºC); and will auto­matically restore when the heat signal level falls below the heat alarm threshold (restore). During an alarm the LED will flash 1/sec­ond and the sounder will sound the the evacuation temporal pat­tern (UL, EU) or continuous beeps (ULC).
Batteries
The WLS916-433 is powered by two, 3 V
Do NOT use batteries other than those listed.
The low battery threshold is set so that the batteries will provide not less than 14 days of operation and at that point the detector will send a 'low battery' signal. If the battery is still low 7 days after falling through the low battery threshold, the horn will 'chirp' once every 48 seconds until battery failure. During the first 7 days after low battery detection, (non-chirp period), if the detector is tested or goes into alarm, the horn will 'chirp' once the test or alarm is restored and remain 'chirping' until battery failure.
Tamper
The removal of the detector from the mounting plate initiates a 'tamper' transmission. The tamper condition is restored after the detector is mounted on the plate.
Wireless Transmissions
A supervisory message is transmitted at 64 minute intervals (12 minutes in EU models) to the control panel. If the signal is not received the control panel determines that the detector is missing.
The detector transmits the following:
Alarm / Alarm Restore - (heat or smoke alarm). Transmitted at time of occurrence.
Tamper / Tamper Restore - (tamper switch activated) 10 second maximum delay on restore before transmission.
Low Battery - (battery voltage falls below threshold). The batteries are tested & transmitted at the time of a supervisory or other transmissions.
Trouble - (detector fault or sensor compensation limit reached). Troubles are transmitted at the time of occurrence (one trouble per supervisory interval).
DC lithium batteries.
F
A
R
D
Installation Instructions
1 Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1M (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULS-S553­M86 or other appropriate national standards for installation rec­ommendations. Do NOT locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke. Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit. Do NOT locate detectors in areas of high humidity. Do NOT locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install Smoke detectors in accordance with paragraph 2.1.1.1 of NFPA 72, Chapter 2.
“2-2.1.1.1 Smoke detectors shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics. In new construction, a smoke detector also shall be installed in each sleeping room.”
2 Mount Smoke Detector Backplate
Locking Tab
Mounting Hol es
2 Install Batteries
Insert Last
Secure backplate to the mounting surface using the screws provided. Note: Avoid mounting on uneven sur­faces or electrical boxes. Warping of the backplate can result in a tamper.
Install batteries in the sequence indi­cated. Use only 3 V ies from the following approved
Insert First
sources:
DC CR123A batter-
Tekcell
Ever Ready
Panasonic
4 Test Unit
The test can be initiated by pressing the test button or activating the internal reed switch with a magnet for a minimum of 5 sec­onds. Alarm activation will be indicated by the flashing LED, The Sounder, and transmission of the alarm reporting code to the cen­tral station. The detector will restore to normal after the test but­ton is released or the magnet removed.
Note: Allow a minimum of 20 seconds between test activations
Note: If the detector is in one of the following states when a test is
initiated; it will not enter an alarm state.

1. Tamper, (detector not installed on mounting plate).

2. Compensation Trouble.

3. Failure of Heat or Smoke detector.

4. Other internal faults that could prevent a smoke or heat alarm

Device Enrollment
The 6 digit serial number located on the back of the smoke detec­tor housing must be enrolled into the alarm control panel with Installer programming. Refer to the receiver Installation Manual for details.
Mounting
Detector Installation:
Position the detector on to the base plate using the detector and base plate alignment marks. Press the detector gently in place while rotating the detector clockwise until the detec­tor snaps into place. Remove the side tab from the locking tab to lock in place.
Removal:
Depress tab with a small slotted screwdriver. Rotate detector counter­clockwise until the alignment marks line up. Remove detector.
Compensation Reset
Cleaning, replacement of the smoke sensor, or other environmen­tal changes may change the background signal/noise of the detec­tor; this requires the drift compensation be reset. Compensation trouble is one of the faults indicated when the LED indicator is OFF while the sounder is chirping.

1. Remove batteries

2. Power up unit while pressing the test button.

The tamper switch must not be pressed.
3. The LED will flash when 5 seconds has elapsed. Release the test button within 2 seconds of the LED flash.
4. The LED will flash every 2 seconds for 1 minute. During this period, the detector must be mounted.
Allow an additional 2 minutes for the detector to make background level checks

5. Test the detector to verify normal operation.

Loading...
+ 2 hidden pages