Tycon Power Systems UPS-AL48-180-900 Quick Install Manual

UPS-AL48-180-900
900W UPSPro®
Wireless Base Stations
Surveillance Cameras
Communications Tow-
ers
Radio Towers
Congratulations! on your purchase of the UPSPro® 900W Backup Power System. Please take a moment to review this Qwik Install Guide before use. Please also review other user guides that are included in the package.
Operation Modes: AC/DC Grid, Solar Ready (May require blocking diode on solar panels)
Key Features: Industrial Strength, Weatherproof, Key Lock,
24VDC or 48VDC Output, 60A MPPT Battery Charge Controller,
72V 900W AC/DC Power Supply, 8640Wh Backup Capacity
Safety: For your own protection, follow these safety rules.
Perform as many functions as possible on the ground Do not attempt to install on a rainy, windy or snowy day or if
there is ice or snow accumulation at the install site or if the site is wet.
Make sure there are no people, pets, etc. below if you are
working on a roof or ladder.
Recommended Tools: Phillips and Small Flat Blade Screwdriv-
ers, adjustable wrench
Please help preserve the environment and return any used batteries to an authorized depot
2
Qwik Install
STEP 1: Prepare a foundation to provide level support for the enclo­sure.
STEP 2: Place enclosure on the foundation. Install 8 batteries in the box. Use a rope tied to the battery tabs to lower batteries into the box. Connect all 8 batteries in series configuration for either 24VDC or 48VDC (See Wiring Diagram Below and near the end of this booklet)
STEP 3: Install DIN rail adapters to the
60A MPPT Battery Charge Controller.
STEP 4: Install DIN rail to enclosure using the two screws provided. Install MPPT battery charge controller to DIN Rail.
3
STEP 5: Remove the black cover from the MPPT controller to access
the wire connection screws. Connect the temperature probe to the con­troller and place it on the batteries for temperature compensated charg­ing.
STEP 6: Remove the fuses from the battery cables and connect the battery cables to the batteries and the MPPT Charge Controller BAT+ and BAT– connections.
STEP 7: Make sure to set the AC input voltage selector on the 72V 900W AC/DC Power Supply to either 115 or 230 depending on your AC voltage source. The 900W Power Supply can sit in the bottom of the
enclosure next to the batteries. Connect the Power Supply DC output
wires to the MPPT Charge Controller PV+ and PV– inputs. The Brown wire is V+. Make sure to observe proper polarity.
STEP 8: Connect normal loads to the MPPT Charge Controller load output. Maximum load is 20A Max. If connecting an inverter or motor, it’s best to connect directly to the batteries.
STEP 9: Double check connections and then re-install the fuses in the battery cables. You may see a spark when connecting the fuse. This is normal. Once the MPPT charge controller is connected to the batteries,
it’s display should turn on and you will see status on the screen.
Warning: Battery should always be connected first and discon­nected last from the MPPT charge controller.
STEP 10: Route any external wires
through the cable glands on the back of the enclosure. Tighten the cable glands on the wires to make weatherproof connec­tions. Plug unused holes using the sup­plied hole plugs. If any cable glands are installed but unused, cut a short piece of
wire and tighten in the cable gland to seal
it.
If desired, attach a security cable/chain through the features on the back of the enclosure to an existing pole/tree.
STEP 11: To turn on the load output, long press the SET button on the MPPT charge controller. Turn on the 72V 900W AC/DC power supply. The MPPT charge controller will show PV input is active and the batter­ies will start charging after 1-2 minutes. When the AC/DC power supply is charging, both LED will be red and the unit fan will come on. This is
normal.
STEP 12: The enclosure comes with a thermostatically (45C) con­trolled ventilation fan. Connect this fan directly to the batteries.
4
Battery Voltage (DC)
24V or 48V (customer configure)
Input Voltage (AC)
120/240VAC, 50/60Hz, 5A Max.
Capacities (Amp Hr)
24V 360Ah, 48V 180Ah
Avail Storage Capacity (Watt Hr)
8640Wh
Max Output Power
900W
Suggested Maximum Load
750W
Maximum Instantaneous Load
20A 500msec
Battery Type
Valve Regulated Sealed Lead Acid / GEL
Battery Life
5 years
Battery Cable Fuse
6 x 32mm Ceramic 30A 250V
Controller Type
60A MPPT Solar Controller with Status Display
and 20A Load with on/off switch
Maximum Solar Panel Size
1600W @ 24V Battery, 3200W @ 48V Battery
Controller Display Status
Battery Voltage, Charging Voltage, Charging
Current, Load Current, Temperature
Overcharge Protection
28.8V @ 24V Battery, 57.6V @ 48V Battery
Over-discharge protection
22V @ 24V Battery, 44V @ 48V Battery
Over-discharge recovery voltage
25.2V @ 24V Battery, 50.4 @ 48V Battery
Controller Self Consump­tion
<1.2W
Enclosure Type
Ground Mount, Key Lock, Aluminum Diamond
Plate
Enclosure External Size
68” x 19” x 25” (1732 x 483 x 635mm)
Operating Temperature
-40°C to +65°C (-40°F to 149°F)
System Weight (without
batteries)
78lbs (35kg)
Battery Weight
8 x 68lbs (31kg)
Certifications
Individual components used have CE Certifica-
tions. Batteries have CE and UL.
Warranty
3 Years
Specifications
5
TECH CORNER
Additional Information you may find useful
Solar Ready: The system is solar ready. You may need to add a 100V 30A blocking diode between the solar panel and the PV input to avoid reverse current from the 72V AC/DC power supply going back into the solar panels.
Batteries: The batteries are maintenance free and should last about 5 years in normal operation. The charge controller will automatically do a balance charge on the batteries periodically.
Enclosure: We recommend making extra keys in case the enclosure keys are lost.
NOTES
Accessories
TP-SC-BT1 RS232 to Bluetooth adapter.
Allows for wireless monitoring and con­trol of the MPPT solar charge controller up to 15m.
Uses a smartphone app available for Android and IOS devices
Completely weatherproof for outdoor mounting
Low Cost
6
7
Limited Warranty
The UPS-AL48-180-900 Backup Power System is supplied with a lim­ited 36 month warranty which covers material and workmanship de­fects. This warranty does not cover the following:
Parts requiring replacement due to improper installation, misuse, poor site conditions, faulty power, etc.
Lightning or weather damage.
Physical damage to the external & internal parts.
Products that have been opened, altered, or defaced.
Water damage.
Usage other than in accordance with instructions and the normal
intended use.
Tycon Systems Inc. 14641 S 800 W Suite A Bluffdale, UT 84065 support@tyconsystems.com
PH: 801-432-0003
Remote Station Monitor
TPDIN-Monitor-WEB2
Qty 4: Voltmeters and current meters
Web Based: allows station monitoring
over the internet.
Qty 4:10A relays for controlling power to devices, starting a generator, etc.
Measures internal and external tempera-
tures
Intuitive user interface and graphical set­up
SNMP compatability
Shunt compatible for measuring very
high currents
Email Alerts
Programmable functionality
8