Tycon Power UPS-ST12-50 User Manual

UPS-ST12 / 24 / 48
UPSProBackup
Power System
Wireless Base Stations
Surveillance Cameras
Remote Gate Control
Up to 192W loads
Congratulations! on your purchase of the UPSPro outdoor backup power system. Please take a moment to review this Qwik Install Guide before assembly or battery installation.
DANGER! Avoid Powerlines!
You Can Be Killed!
When following the instructions in this guide take extreme care to avoid contact with overhead power lines, lights and power circuits. Contact with power lines, lights or power circuits may be fatal. We rec­ommend to install no closer than 20 feet to any power lines.
Safety: For your own protection, follow these safety rules.
Perform as many functions as possible on the ground Do not attempt to install on a rainy, windy or snowy day or if
there is ice or snow accumulation at the install site or if the site is wet.
Make sure there are no people, pets, etc. below when you are
working on a roof or ladder.
Recommended Tools: Phillips Scr ewdriver, 13mm and
10mm Open End Wrench, 8mm nut driver, Flat Blade Screwdriv-
Please help preserve the environment and return used batteries to an authorized depot
Qwik Install
STEP 1: Add Grounding Wire
Between Door and Enclosure: Remove plastic covers on cop­per studs on inside of door and inside of enclosure. Add jumper wire between 2 copper studs and use copper washers and nuts to secure.
STEP 2: Add wire feedthrus into
the bottom connector plate. Attach the connector plate to the bottom of
the enclosure using self tapping screws provided.
STEP 3: Install hole plug in drain hole in bottom right corner of the en-
closure.
STEP 4: If p ole moun ting the enclosure, assemble the pole mount kit to the back of the enclosure and mount the enclosure to a pole using the 6 hose clamps provided. The enclosure can also be wall mounted using the 4 holes in the back of the enclosure.
2
STEP 5: Insert the battery platform in
the bottom of the enclosure. The bat-
tery platform has cutouts so wires can be routed under the battery as needed.
STEP 6: Mount any ext ra equ ip­ment that will reside inside the enclo-
sure. Equipment can be mounted to removable backplate or to a plate mounted to the door rails.
STEP 7: Install the b atter ies in the enclosure. If using multiple bat­teries, connect in parallel for 12V output or connect in series for 24V output.
12V 200Ah battery configuration is shown here.
For 12V 100Ah two batteries are connected in parallel with Plus(+) connected to
Plus(+) and Minus(-) con-
nected to Minus(-).
For 12V 200Ah the 100Ah configuration is doubled with separate battery connection wires to controller.
24V two battery and 24V and 48V four battery con­figurations are shown be­low: Batteries are connect-
ed in series, with Plus(+)
connected to Minus(-).
3
24VDC Four Battery 48VDC Four Battery
STEP 8: If batteries ar e installed on their side make
sure to apply an insulator to the top of the battery termi­nal to prevent the battery terminals from shorting to the metal enclosure in case the battery shifts inside the en­closure during an earthquake.
STEP 9: Set the proper voltage on the AC input of the controller by removing the metal tab and then switch­ing the input voltage to 120VAC or 240VAC depending on your source voltage. Be sure to replace the metal tab to ensure that somebody doesnt accidentally switch the voltage as this will damage the controller.
STEP 10: Connect the b attery cab les t o the con troller , then to the battery. Be sure to observe proper polarity. Black wire connects to bat­tery negative terminal and BATTERY(-) terminal on the controller.
4
STEP 11: When a battery is connected p rop erly the B ATT LED
will be green. Make sure that the Battery Type is selected correctly and
never change the battery type during charging or this could damage the controller. Use GEL for GEL or AGM batteries. Use WET for standard lead acid wet cells. Tycon recommends using only GEL or AGM batter­ies for best performance.
The controller has battery overdischarge protection to disconnect the load if the battery voltage (charge) is too low. The LOAD LED will be on when the battery charge is within safe limits and the LOAD output is turned on.
LED Indicators
LOAD (Load Pow er i s Turned On = Green) PWR (AC Pow er On = Yell ow ) BATT ( Batt ery is Connected = Green)
CHD ( Battery is Ful ly Charged = Green)
CHG ( Battery is Charging = Yellow) WET / GEL – Switch is positioned to WET(Green) or GEL
(Yellow)
STEP 12: Switch off con troller and connect AC to the controller. Be sure to follow local regulations for outdoor 120/240VAC connec­tions.
STEP 13: Connect the load t o th e controller LOAD terminals. Be sure to observe proper polarity. Switch on the controller to activate the charging.
STEP 14: Plug or Tighten all w ire feedthrus. If they dont tighten on
a small diameter wire, you can wrap some electrical tape around the wire in the seal area to increase its diameter and make a better seal. The enclosure needs some small amount of venting so be sure NOT to seal all holes and feedthrus with silicon.
STEP 15: Make sure lid gasket is clean and free from any parti­cles, then carefully close the cover, making sure that wires are clear of the seam and hinge area. Use the special key to close the two cover locks.
TECH CORNER
Additional Information you may find useful
1. CONTROLLER: The controller turns off power to the load at 10.7V for the 12V model and 21.5 for the 24V model and 40V for the 48V model. It reconnects when the battery reaches 12.6V for the 12V model and 25.2V for the 24V model and 51V for the 48V model. This protects battery from overdischarge and increases battery life and performance. Note: The load will turn on immediately as soon as AC power is re­stored.
2. CAPACITY: The UPSPro UPS-ST12 is rated at 144W load output.
5
SPECIFICATIONS
Load Voltage
Max Load Min Load
Capacity
Battery Type
Battery Life
Charge Voltage
Over-discharge protection
VAC +/- 10%
Input Current
Enclosure Type
Operating Temp
UPS-ST12 UPS-ST24 UPS-ST48
12V +/-0.5 24V +/- 0.5 48V +/- 0.5
12A (144W) 8A (192W) 4A (192W)
1A 1A 1A
1 battery 51Ah
600VA
2 battery 102Ah
1200VA
4 battery 204Ah
2400VA
Valve Regulated Sealed Lead Acid / GEL
WET Equalize =
14.6V, Float =
13.2V GEL Equalize =
14.2V, Float =
13.5V
10.7V Load Off
12.6V Load On
Selector Switch 120VAC / 240VAC , 50/60Hz
3.5A @ 115VAC / 1.8A @ 240VAC
2 battery 51Ah
1200VA
4 battery 102Ah
2400VA
5 Years
WET Equalize =
28.8V, Float =
26.4V GEL Equalize =
28.4V, Float = 27V
21.5V Load Off
25.2V Load On
Powder Coat Steel
-30°C to +60°C
Subject to change without notice
4 battery 51Ah
2400VA
WET Equalize = 58V, Float = 53V GEL Equalize =
56.8V, Float = 54V
40V Load Off 51V Load On
The UPS-ST24 and UPS-ST48 are rated at 192W load output.
3. VENTING: The enclosure is vented thru the wire feedthrus and vari- ous hole plugs in the bottom of the enclosure. Dont make these airtight with silicon
4. BATTERY MAINTENANCE: The batteries used in the UPSPro sys-
tems dont require any maintenance. They should last up to 5 years in
normal use. Note: Never store batteries for any length of time in a dis-
charged state or it will kill the battery.
5. BATTERY OVERDISCHARGE: We highly recommen d hooking
all equipment loads to the controller voltage output. This output will dis­connect the load if the battery voltage drops below the set voltage and this will protect the battery from over-discharge. If batteries get com­pletely discharged because the equipment was connected directly to the battery, you will reduce the battery life. Discharged batteries will freeze at very low temperatures.
6
6. ACCESSORIES: Tycon al so offers a variety of voltage conver-
sion products to meet almost any need. Just visit tyconpower.com for
more info.
Compatible Solar Panel Kits
Tycon Power Systems Solar Panel kits come with High Performance solar panels, battery charge controller, side of pole mounts and outdoor rated connection cabling. Solar panels have a 25 year output warranty. Pole mounts and panels are designed for wind loads to 90MPH. Note: Solar
panel kits are only available for 12V and 24V
Battery
Sys­tems.
TPSKxx-85Wxx choose 12 or 24. 85W Solar Panel, Controller, Pole Mount, Cable
TPSKxx-120Wxx choose 12 or 24. 120W Solar Panel, Controller, Pole Mount, Cable
TPSKxx-240Wxx choose 12 or 24. 240W Solar Panel, Controller, Pole Mount, Cable
Solar Kits 6 Hours Peak Sun 3 Hours Peak Sun
TPSKxx-85W 20W continuous 10W continuous
TPSKxx-120W 30W continuous 15W continuous
TPSKxx-240W 60W continuous 30W continuous
7
Compatible Wind Turbine
TPW-400DT-12/24 400W 12V or 24V Auto voltage se­lect Wind Turbine
Includes controller
Good low wind perfor-
mance
Self braking in high wind
80MPH survivability
Sealed and maintenance
free
Limited Warranty
The UPSProproducts are supplied with a limited 24 month warranty which covers material and workmanship defects. This warranty does not cover the following: Parts requiring replacement due to improper installation, misuse,
poor site conditions, faulty power, etc.
Lightning or weather damage.
Physical damage to the external & internal parts. Products that have been opened, altered, or defaced. Water damage for units that were not mounted according to user
manual. Usage other than in accordance with instructions and the normal intended use.
8000026 Rev 2 UPS-ST UPSProQwik Install Guide