Ultra Low Flow AQUAMIST Nozzles
Type ULF AM24
Automatic (Closed)
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Ultra Low Flow AQUAMIST
Nozzles Type ULF AM24 are closed
(automatic) nozzles intended for use
with engineered, water-mist systems.
They are low-pressure nozzles that
utilize a single fluid jet impinging on a
diffuser to produce a spray having a
range of water droplet sizes suitable
for the control of Class A fires.
It is recommended that the end user be
consulted with respect to the suitability of the materials of construction and
finish for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and
gas/chemical velocity should be considered, at a minimum, along with the
corrosive nature to which the nozzles
may be exposed.
NOTICE
The Type ULF AM24 AQUAMIST
Nozzles described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION
(NFPA), in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the performance of these devices.
The design of individual water-mist
systems can vary considerably,
depending on the characteristics and
nature of the hazard and the basic
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
purpose of the water-mist system.
Because of these variations, the design
of water-mist systems for fire protection must only be performed by experienced designers who thoroughly
understand the limitations as well as
capabilities of such systems.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Technical
Data
Discharge Coefficient
K = 9,2 LPM/bar
Thread Connection
1/2 in. NPT
Response Time Index
Quick Response
Finish
Natural Brass
Chrome Plated
Pure White
Signal White
Temperature Ratings
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Inlet Strainer . . . . . . . . . . . . . . . . . . . . . . Copper
Orifice Insert . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Ejection Spring . . . . . . . . . . . . . . Stainless Steel
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Glass
Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Loading Screw . . . . . . . . . . . . . . . . . . . . .Bronze
The smallest waterway (orifice) diameter of the Orifice Insert is nominally
4,4 mm (0.172 in.). The diameter of the
Inlet Strainer perforations is nominally
3,2 mm (0.125 in.).
1/2
(0.64 GPM/psi
1/2
)
Design
Criteria
Obtain guidance for the design of a
water-mist system that utilizes the
TYCO Type ULF AM24 AQUAMIST
Nozzles from the Technical Services
department.
The Type ULF AM24 can only be
installed in non-recessed applications.
Installation
The TYCO Type ULF AM24 AQUAMIST
Nozzles must be installed in accordance with this section.
General Instructions
Do not install any bulb type nozzle if
the bulb is cracked or there is a loss
of liquid from the bulb. With the nozzle
held horizontally, a small air bubble
should be present. The diameter of
the air bubble is approximately 1,6 mm
(1/16 in.) for the 57°C (135°F) to 2,4 mm
(3/32 in.) for the 93°C (200°F) temperature ratings.
A leak-tight 1/2 inch NPT nozzle joint
should be obtained by applying a minimum-to-maximum torque of 9,5 to
19,0 N·m (7 to 14 lb-ft). Higher levels
of torque can distort the nozzle inlet
and cause leakage or impairment of
the nozzle.
For flush installations, use the Style 20
Escutcheon.
Step 1. Install the Type ULF AM24
Nozzle in the pendent position as
shown in Figure 1.
Step 2. With pipe-thread sealant
applied to the pipe threads, handtighten the nozzle into the nozzle fitting.
Step 3. Tighten the nozzle into the
nozzle fitting using only the W-Type 6
Nozzle Wrench, refer to Figure 2. With
reference to Figure 1, apply the wrench
to the Nozzle Wrench Flats.
Page 1 of 2 SEPTEMBER 2018 TFP2224
![](/html/ce/ce26/ce26745700693dd1c53ad6e8214a9580f1259e74549366a951ca61da62c70bb2/bg2.png)
TFP2224
Diffuser
Bulb
Button
Frame
Strainer
Components:
Orice
Insert
Ejection
Spring
Loading
Screw
Sealing
Assembly
-
-
-
-
-
-
-
-
-
2
9
8
6
7
4
5
3
1
DIFFUSER
SHAPE
WRENCH
FLATS
ESCUTCHEON
PLATE SEATING
SURFACE
1/2"
NPT
11,1 mm
(7/16")
NOMINAL
MAKE-IN
17,5 mm
(11/16")
17,5 mm
(11/16")
41,3 mm
(1-5/8")
31,0 mm
(1.22")
58,7 mm
(2-5/16")
2
1
3
6
5
7
4
9
8
Page 2 of 2
TYPE ULF AM24 AQUAMIST NOZZLE
FIGURE 1
NOMINAL DIMENSIONS
Ordering
Note: Do not attempt to compensate for insufficient adjustment in the
escutcheon plate by under or overtightening the nozzle. Re-adjust the
position of the nozzle fitting to suit.
Absence of an escutcheon, which is
used to cover a clearance hole, can
delay the time to nozzle operation in a
fire situation.
Care and
Maintenance
The TYCO Type ULF AM24 AQUAMIST
Nozzles must be maintained and serviced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Nozzles which are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic nozzles must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified nozzles must be replaced.
Nozzles that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the nozzle with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the nozzles - before, during,
and after installation. Nozzles damaged
1400 Pennbrook Parkw ay, Lansd ale, PA 194 46 | Teleph one +1-215-362-070 0
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on;
TEFLON is a regi stered tradema rk of DuPont
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any nozzle that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section.)
Frequent visual inspections are recommended to be initially performed for
nozzles installed in potentially corrosive atmospheres to verify the integrity of the materials of construction
and finish as they may be affected by
the corrosive conditions present for a
given installation. Thereafter, annual
inspections per applicable standards
are required, in addition to inspections required by the authority having
jurisdiction.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 20, 25, and
750), in addition to the standards of
any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any
questions.
Water-mist fixed systems should be
inspected, tested, and maintained by
a qualified Inspection Service in accordance with local requirements and/or
national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N.)
Type ULF AM24 AQUAMIST Nozzles
Specify: Type ULF AM24 AQUAMIST
Nozzle with (specify finish), temperature rating (specify), P/N (specify):
Natural Brass
57° C (135°F ) ..................49 -210-1-135
68°C (15 5°F ) ..................49 -210-1-155
79°C (175°F ) ..................49- 210 -1-175
93°C (200°F) ..................49-210-1-200
Chrome Plated
57° C (135°F ) ..................49-210-9-135
68°C (15 5°F ) ..................49-210-9-155
79°C (175°F ) ..................49-210 -9-175
93°C (200°F) ..................49-210-9 -200
Signal White* (RAL9003)
57° C (135°F ) ..................4 9-210 - 4-135
68°C (15 5°F ) ..................4 9- 210 - 4-15 5
79°C (175°F ) ..................49-210 -4-175
93°C (200°F) ..................49-210-4-200
Pure White** ( RAL9010)
57° C (135°F ) ..................4 9-210 -3-135
68°C (15 5°F ) ..................4 9- 210 - 3-15 5
79°C (175°F ) ..................49-210 -3-175
93°C (200°F) ..................49-210-3-200
* Previou sly known a s Bright Wh ite
** Eastern Hemis phere sales only
Nozzle Wrench
Specify: W-Type 6 Nozzle Wrench,
P/N 56-000-6-387
Escutcheon
Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770
Temperature
Rating
57° C (13 5°F ) Orange
68°C (155° F) Red
79°C (175°F) Yel low
93°C (200°F) Green
Bulb Fluid
Color
TABL E A
TE M PE R ATU R E R ATIN G
SELECTION
(USE ONLY
END "A")
FIGURE 2
W-TYPE 6 NOZZLE WRENCH