Tyco TY-L Series, TY3311 Quick Start Manual

Worldwide
Contacts
Series TY-L – 5.6 K-factor Horizontal Sidewall Sprinkler Standard Response, Standard Coverage
www.tyco-fire.com
General Description
TYCO Series TY-L 5.6K Standard Response, Standard Coverage, Hori­zontal Sidewall (HSW) Sprinklers are solder-type spray sprinklers designed for use in light and ordinary hazard, commercial occupancies such as banks, hotels, shopping malls, offices, etc. They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Hori­zontal sidewall sprinklers are com­monly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations where piping across the ceiling is not desirable.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is not representative of all possible cor­rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentra­tion of chemicals, and gas/chemical velocity, should be considered, as a
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Series TY-L Sprinklers described herein must be installed and main­tained in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condi­tion. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Numbers (SINs)
TY3311 – HSW 5.6K, 1/2” NPT
TY3311 is a redesignation for Star SIN S1803 and Gem SIN G3113.
Technical Data
Approvals
UL and C-UL Listed FM Approved (Refer to Table A for complete approval information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table A.
1/2
(80,6 lpm/bar
1/2
)
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Strut ........................MONEL
Deflector. . . . . . . . . . . . . . . . . . . . . Bronze
Hook................. Bronze/MONEL
Fusible Element . . . . . . . . Solder, Copper,
Stainless Steel
Ejection Spring. . . . . . . . . . Stainless Steel
Sealing Button . . . . . . . Bronze w/TEFLON
Operation
A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached, the alloy melts, the balls are forced toward each other releasing the tension mech­anism, allowing the sprinkler to operate.
Design Criteria
TYCO Series TY-L 5.6K Standard Response, Standard Coverage, Hori­zontal Sidewall (HSW) Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recog­nized by the applicable listing or approval agency (e.g., UL Listing is based on NFPA 13 requirements). The Series TY-L HSW Sprinklers must be installed with a deflector­to-ceiling distance of 4 to 6 inches (100 to 150 mm). To meet this requirement, the centerline of the sprinkler waterway must be located 4-5/16 to 6-5/16 inches (110 to 160 mm) below the ceiling. Installation of the Series TY-L HSW Sprinklers in recessed escutcheons will void all manufacturer’s warranties, as well as possibly void the sprinkler’s approvals and/or listings.
Page 1 of 4 AUGUST 2018 TFP120
TFP12 0
WRENCH
WRENCHING
CENTERLINE
WATERWAY
(9,5 mm)
(11,1 mm)
(38,1 mm)
(63,5 mm)
1/2"
Page 2 of 4
1-1/2"
7/16"
3/8"
TOP
WRENCHING
FLANGES
5
6
7
7/16" (11,1 mm)
NOMINAL MAKE-IN
1-7/8"
(47,6 mm)
4
2-1/2"
NPT
RECESS
AREA
ESCUTCHEON
PLATE SEATING
SURFACE
3
2 1
FIGURE 2 W-T Y P E 9
SPRINKLER WRENCH
After installation, the sprinkler wrench flats and frame arms must be inspected and the wax coating retouched (repaired) whenever the coating has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gently applying a heated 1/8 inch diameter steel rod to the areas of wax
OF
SPRINKLER
that have been damaged, to smooth it back over areas where bare metal is exposed.
SERIES TY-L (TY3311) HORIZONTAL SIDEWALL SPRINKLER
FIGURE 1
5.6K, 1/2 INCH NPT, STANDARD RESPONSE
Installation
TYCO Series TY-L 5.6K Standard Response, Standard Coverage, Hori­zontal Sidewall (HSW) Sprinklers must be installed in accordance with this section.
General Instructions
A leak-tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft. (9,5 to 19,0 Nm). A maximum of 21 lb-ft. (28,5 Nm) of torque may be used to install sprin­klers with 1/2 NPT connections. Higher levels of torque may distort the sprin­kler inlet and cause leakage or impair­ment of the sprinkler.
Do not attempt to make up for insuf­ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.
Horizontal Sidewall Sprinklers
The Series TY-L HSW Sprinklers must be installed in accordance with the following instructions:
Note: Series TY-L HSW Sprinklers must be installed with their centerline of waterway parallel to the ceiling and perpendicular to the back wall surface. The word “TOP” on the deflector must face upwards toward the ceiling.
Step 1. After installing an escutcheon (as applicable) over the sprinkler pipe threads and with pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure 2), except that an 8 or 10 inch adjustable crescent wrench is to be used for wax coated sprinklers. With reference to Figure 1, the W-Type 9 Sprinkler Wrench is to be applied to the wrench area, or as applicable, an adjustable wrench is to be applied to the wrenching flanges.
When installing wax coated sprinklers with an adjustable wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damaging the wax coating.
Before wrench-tightening the sprin­kler, the jaws of the wrench are to be adjusted to just contact the sprinkler wrench flats. After wrench-tightening the sprinkler, loosen the wrench jaws before removing the wrench.
NOTICE
Only retouching of the wax coating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precau­tions need to be taken, when handling the heated rod, in order to prevent the installer from being burned.
If attempts to retouch the wax coating with complete coverage are unsuc­cessful, additional wax can be ordered in the form of a wax stick (the end of which is color-coded). Only the correct color-coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previ­ously described, touch the rod to the area requiring additional wax with the rod angled downward, and then touch the wax stick to the rod approximately 1/2 inch away from the area requiring retouching. The wax will melt and run down onto the sprinkler.
Loading...
+ 2 hidden pages