Series TY-FRL – 5.6 and 8.0 K-factor
Upright and Pendent Intermediate Level Sprinklers
Quick Response
General
Description
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers are automatic sprinklers of the quick response
solder type. They are standard spray
sprinklers intended for use in fire sprinkler systems designed in accordance
with the standard installation rules
recognized by the applicable listing
or approval agency (e.g., UL Listing is
based on NFPA requirements). Both
the Pendent and Upright Sprinklers
produce a hemispherical water distribution pattern below the deflector.
Intermediate level sprinklers are primarily designed for use in rack storage
sprinkler systems where their thermally
sensitive elements must be shielded
from the water spray of higher elevation sprinklers that could operate
earlier during a fire. Intermediate level
sprinklers are also used in other applications such as beneath open gridded
catwalks.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
NOTICE
The Series TY-FRL Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY312 3 ........... Upright 5.6K, 1/2 in. NPT
TY3221 ...........Pendent 5.6K, 1/2 in. NPT
TY4123 ........... Upright 8.0K, 3/4 in. NPT
TY4221 ...........Pendent 8.0K, 3 /4 in. NP T
TY3123 is a redesignation for Star SIN
S1991 and Gem SIN G8986
TY3221 is a redesignation for Star SIN
S1865 and Gem SIN G8972
TY4123 is a redesignation for Star SIN
S1993 and Gem SIN G8153
TY4221 is a redesignation for Star SIN
S1867 and Gem SIN G8172
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table A for complete approval
information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficients
K=5.6 gpm/psi½ (80,6 lpm/bar½)
K=8.0 gpm/psi½ (115, 2 l p m / b a r½)
Temperature Ratings
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . . . . . . . Nickel
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TEFLON
Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Page 1 of 4 AUGUST 2018 TFP355
![](/html/7d/7d2a/7d2a5e24a733e44fce7042926fd28cf27b53af8a2e37fe0838777b64eb77a76c/bg2.png)
TFP355
FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT
Pipe thread connections per
Order Pendent Series TY-FRL Sprinkler and
FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT
Page 2 of 4
Temperature rating
is indicated on
Deector or Shield
4-1/8" (104,8 mm) DIA.
2-3/4"
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
Pipe thread connections per
ISO 7-1 can be provided on
special request
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
WRENCH
AREA
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
Order Pendent Series TY-FRL Sprinkler and
Model S4 Shield Package separately for
pendent assembly (Ref. Ordering Procedure)
4-1/8" (104,8 mm) DIA.
1/2" NPT
SECTION)
DEFLECTOR
**
*
SPEEDNUT
FIGURE 1
SERIES TY-FRL UPRIGHT (TY3123) & PENDENT (TY3221) INTERMEDIATE LEVEL SPRINKLERS
5.6K, QUICK RESPONSE, 1/2” NPT
is indicated on
Deector or Shield
ISO 7-1 can be provided on
special request
Model S4 Shield Package separately for
pendent assembly (Ref. Ordering Procedure)
O-RING
2-11/16"
PENDENT
SERIES
TY-FRL
†
4-1/8" (104,8 mm) DIA.
2-13/16"
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
SERIES TY-FRL UPRIGHT (TY4123) & PENDENT (TY4221) INTERMEDIATE LEVEL SPRINKLERS
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
WRENCH
AREA
8.0K, QUICK RESPONSE, 3/4” NPT
Design
Criteria
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers are
intended for fire protection systems
designed in accordance with the standard installation rules recognized
by the applicable listing or approval
agency (e.g., UL Listing is based on
the requirements of NFPA 13, and FM
Approval is based on the requirements
of FM Approvals’ Loss Prevention Data
Sheets).
4-1/8" (104,8 mm) DIA.
3/4" NPT
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
SECTION)
DEFLECTOR
FIGURE 2
**
*
Operation
The fusible link (heat collector) assembly is comprised of two halves that
are joined together by a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate, allowing the sprinkler to operate.
SPEEDNUT
O-RING
2-15/16"
PENDENT
SERIES
TY-FRL
†