Tyco TY-FRB Series, TY-FRB 5.6, TY-FRB 8.0, TY3631, TY4631 Quick Response

Series TY-FRB – 5.6 and 8.0 K-factor Conventional (Old Style) Sprinklers Quick Response
Worldwide
Contacts
www.tyco-fire.com
General Description
The TYCO Series TY-FRB, 5.6 and
8.0 K-factor, Conventional Sprinklers described in this technical data sheet are Quick Response, Standard Cover­age, decorative 3 mm glass bulb type spray sprinklers. These sprinklers are intended to be installed either pendent or upright and, in either position, produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and approximately 50% of the discharge directed downwards.
Conventional sprinklers are generally used with Ordinary and Extra High Hazard Class Systems, as defined by the automatic sprinkler system instal­lation rules of the country and author­ity having jurisdiction. The National Fire Protection Association (NFPA) permits the use of “Old Style Sprinklers” where special construction features require a unique water distribution, for the pro­tection of fur vaults, or to replace similar sprinklers that had been installed prior to 1955.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli­cable Approval agencies, the testing is not representative of all possible cor­rosive atmospheres. Consequently,
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and installation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The TYCO Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the NFPA, in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Numbers (SINs)
TY3631 – 5.6K, 1/2” NPT TY4631 – 8.0K, 3/4” NPT
Technical Data
Approvals
UL and C-UL Listed LPCB Approved VdS Approved NYC Approved
(Refer to Table A for complete approval information.)
Sprinklers with Polyester Finish are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi K=8.0 gpm/psi
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . .Brass/Copper
Sealing Assembly ..Beryllium Nickel w /TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
1/2
(80,6 lpm/bar
1/2
(11 5,2 l p m / b a r
1/2
1/2
)
)
Page 1 of 4 JANUARY 2017 TFP666
TFP666
* **
*
PENDENT
PENDENT
SHOWN UPRIGHT
SHOWN UPRIGHT
Pipe thread connections per
Temperature rating is
(55,6 mm)
Components:
(END "A" USED FOR
3/4" NPT MODELS)
Page 2 of 4
2-3/16"
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Design Criteria
The TYCO Series TY-FRB Conventional Sprinklers are intended for fire protec­tion systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements). The Series TY-FRB Conventional Sprinklers are only for non-recessed applications.
indicated on Deector or adjacent to orice seat on Frame.
ESCUTCHEON
PLATE SEATING
SURFACE
1-1/2"
(38,1 mm)
-
1
Frame
-
2
Button
-
3
Sealing Assembly
SURFACE
1-1/2"
(38,1 mm)
3/4"
NPT
SHOWN
4 5
****
1/2" NPT
SHOWN
ISO 7-1 can be provided on special request.
7/16" (11,1 mm)
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
6
5
4
2
3
1
ESCUTCHEON
PLATE SEATING
*
2-1/4"
(57,2 mm)
FIGURE 1
SERIES TY-FRB 5.6 K-FACTOR (TY36 31) AND 8.0 K-FACTOR (TY4631)
QUICK RESPONSE CONVENTIONAL SPRINKLERS
Installation
The Series TY-FRB Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). A maximum of 21 ft.-lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. A leak-tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.-lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.-lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Step 1. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 2). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the Wrench Flats.
(END "B" USED FOR
-
Bulb
-
Compression Screw
-
Deector6
1/2" (12,7 mm)
WRENCH RECESS
*
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
WRENCH RECESS
1/2" NPT MODELS)
FIGURE 2 W-T Y PE 6
SPRINKLER WRENCH
6
5
4
2
3
1
TFP666
Page 3 of 4
Typ e
5.6K
CONVENTIONAL
(T Y3631)
or
8.0K
CONVENTIONAL
(TY4631)
Notes:
1. UL Listed
2. C-UL Listed
3. L PCB Appr oved (LPCB R ef. No. 094a /06 & 007k /04)
4. A pproved by t he City of N ew York under ME A 354-01-E
5. VdS Approved ( For detai ls, conta ct Tyco Fire Prote ction Pro ducts, Enschede , Netherl ands, Tel. +31-53 -428-4444 / Fax + 31-53-428-3377.)
6. W here pol yester-co ated and le ad-coated sprinklers a re noted to be U L and C-UL L isted, the sprinkl ers are UL a nd C-UL L isted as Co rrosio n­Resistant Sprinklers
* Frame an d deecto r only
Temperature
Rating
135° F (57° C) Orange
155° F (68°C) Red
175°F (79 °C) Yel l ow
200°F (93°C) Green
28 6° F (141°C) Blue
Care and Maintenance
The TYCO Series TY-FRB Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like must be replaced. Also, replace any sprin­kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa­tion Section.)
Bulb
Liquid Color
Natural
Brass
Sprinkler Finish
Chrome
Plated
1, 2, 3, 4, 5 1, 2, 4
TABL E A
LABORATORY LISTINGS AND APPROVALS
Frequent visual inspections are rec­ommended to be initially performed for corrosion resistant coated sprin­klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion-resistant coating, as it may be affected by the corrosive conditions present.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso­ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install­ing contractor or product manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
Polyester*
Lead
Coated
TFP666
Page 4 of 4
P/N 57 - XXX - X - XXX
373 5.6K CONVENTIONAL (1/2” NPT) T Y36 31
393 8.0K CONVENTIONAL (3/4” NPT) T Y4631
Notes:
* Eastern Hem isphere sales onl y ** Available o nly for temperatur e ratings of 155°F (68°C) or 200°F (93°C)
SERIES TY-FRB CONVENTIONAL SPRINKLERS
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product name and Part Number (P/N).
Sprinkler Assemblies with NPT Thread Connections
Specify: (specify) SIN, Series TY-FRB Conventional Sprinkler Quick Response, (specify) SIN, K=(specify), (specify) temperature rating, with (specify) finish, P/N (specify from Table B)
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
SIN
1
3
4
5
9
SPRINKLER
FINISH
NAT URAL
BRASS
PURE WHITE (RAL9010)*
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
JET BLACK (RAL9005)**
POLYESTER
CHROME
PL AT ED
TABL E B
PART NUMBER SELECTION
TEMPERATURE
RATING
135 135° F (57° C)
155 155°F (68°C)
175 175°F ( 79° C)
200 200°F (93°C)
286 28 6° F (141°C)
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700