Series TY-FRB – 5.6 and 8.0 K-factor
Conventional (Old Style) Sprinklers
Quick Response
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-FRB, 5.6 and
8.0 K-factor, Conventional Sprinklers
described in this technical data sheet
are Quick Response, Standard Coverage, decorative 3 mm glass bulb type
spray sprinklers. These sprinklers are
intended to be installed either pendent
or upright and, in either position,
produce a spherical water discharge
pattern with approximately 50% of
the discharge directed upwards and
approximately 50% of the discharge
directed downwards.
Conventional sprinklers are generally
used with Ordinary and Extra High
Hazard Class Systems, as defined by
the automatic sprinkler system installation rules of the country and authority having jurisdiction. The National Fire
Protection Association (NFPA) permits
the use of “Old Style Sprinklers” where
special construction features require a
unique water distribution, for the protection of fur vaults, or to replace similar
sprinklers that had been installed prior
to 1955.
Corrosion-resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmospheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the applicable Approval agencies, the testing is
not representative of all possible corrosive atmospheres. Consequently,
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
it is recommended that the end user
be consulted with respect to the suitability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the NFPA, in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY3631 – 5.6K, 1/2” NPT
TY4631 – 8.0K, 3/4” NPT
Technical
Data
Approvals
UL and C-UL Listed
LPCB Approved
VdS Approved
NYC Approved
(Refer to Table A for complete approval
information.)
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resistant
Sprinklers.
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB Conventional
Sprinklers are intended for fire protection systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency (e.g., UL Listing is
based on NFPA 13 requirements). The
Series TY-FRB Conventional Sprinklers
are only for non-recessed applications.
indicated on Deector
or adjacent to orice
seat on Frame.
ESCUTCHEON
PLATE SEATING
SURFACE
1-1/2"
(38,1 mm)
-
1
Frame
-
2
Button
-
3
Sealing
Assembly
SURFACE
1-1/2"
(38,1 mm)
3/4"
NPT
SHOWN
4
5
****
1/2"
NPT
SHOWN
ISO 7-1 can be provided on
special request.
7/16" (11,1 mm)
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
6
5
4
2
3
1
ESCUTCHEON
PLATE SEATING
*
2-1/4"
(57,2 mm)
FIGURE 1
SERIES TY-FRB 5.6 K-FACTOR (TY36 31) AND 8.0 K-FACTOR (TY4631)
QUICK RESPONSE CONVENTIONAL SPRINKLERS
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) to 3/32
inch (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). A maximum
of 21 ft.-lbs. (28,5 Nm) of torque may be
used to install sprinklers with 1/2 NPT
connections. A leak-tight 3/4 inch NPT
sprinkler joint should be obtained with
a torque of 10 to 20 ft.-lbs. (13,4 to 26,8
Nm). A maximum of 30 ft.-lbs. (40,7
Nm) of torque is to be used to install
sprinklers with 3/4 NPT connections.
Higher levels of torque may distort the
sprinkler inlet and cause leakage or
impairment of the sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the Wrench Flats.
(END "B" USED FOR
-
Bulb
-
Compression
Screw
-
Deector6
1/2" (12,7 mm)
WRENCH RECESS
*
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
WRENCH RECESS
1/2" NPT MODELS)
FIGURE 2
W-T Y PE 6
SPRINKLER WRENCH
6
5
4
2
3
1
TFP666
Page 3 of 4
Typ e
5.6K
CONVENTIONAL
(T Y3631)
or
8.0K
CONVENTIONAL
(TY4631)
Notes:
1. UL Listed
2. C-UL Listed
3. L PCB Appr oved (LPCB R ef. No. 094a /06 & 007k /04)
4. A pproved by t he City of N ew York under ME A 354-01-E
5. VdS Approved ( For detai ls, conta ct Tyco Fire Prote ction Pro ducts, Enschede , Netherl ands, Tel. +31-53 -428-4444 / Fax + 31-53-428-3377.)
6. W here pol yester-co ated and le ad-coated sprinklers a re noted to be U L and C-UL L isted, the sprinkl ers are UL a nd C-UL L isted as Co rrosio nResistant Sprinklers
* Frame an d deecto r only
Temperature
Rating
135° F (57° C)Orange
155° F (68°C)Red
175°F (79 °C)Yel l ow
200°F (93°C)Green
28 6° F (141°C)Blue
Care and
Maintenance
The TYCO Series TY-FRB Sprinklers
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installation Section.)
Bulb
Liquid Color
Natural
Brass
Sprinkler Finish
Chrome
Plated
1, 2, 3, 4, 51, 2, 4
TABL E A
LABORATORY LISTINGS AND APPROVALS
Frequent visual inspections are recommended to be initially performed
for corrosion resistant coated sprinklers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion-resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the installing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
Polyester*
Lead
Coated
TFP666
Page 4 of 4
P/N 57 - XXX - X - XXX
3735.6K CONVENTIONAL (1/2” NPT)T Y36 31
3938.0K CONVENTIONAL (3/4” NPT)T Y4631
Notes:
* Eastern Hem isphere sales onl y
** Available o nly for temperatur e ratings of 155°F (68°C) or
200°F (93°C)
SERIES TY-FRB CONVENTIONAL SPRINKLERS
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: (specify) SIN, Series
TY-FRB Conventional Sprinkler Quick
Response, (specify) SIN, K=(specify),
(specify) temperature rating, with
(specify) finish, P/N (specify from Table
B)