TYCO TY-B User Manual

Page 1
Worldwide
Contacts
www.tyco-fire.com
Series TY-B – 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage
General Description
The TYCO Series TY-B 2.8, 5.6, and 8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers described in herein are standard response, standard coverage, decora­tive 5 mm glass bulb-type spray sprin­klers. They are designed for use in light, ordinary, or extra-hazard commercial occupancies such as banks, hotels, shopping malls, factories, refineries, and chemical plants.
The TY-B Recessed Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) Recessed Escutcheon. The Recessed Escutcheon provides 1/2 in. (12,7 mm) of recessed adjust­ment or up to 3/4 in. (19,1 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond what would be obtained when exposed to corrosive atmo­spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently,
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
it is recommended that the end-user be consulted about the suitability of these coatings for any given corrosive envi­ronment. The effects of ambient tem­perature, concentration of chemicals, and gas/chemical velocity, should be considered as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
An intermediate level version of the Series TY-B Pendent Sprinkler can be obtained by utilizing the Series TY-B Pendent Sprinkler in combination with the Model S2 Shield.
NOTICE
The Series TY-B 2.8, 5.6, and 8.0 K-fac­tor, Upright, Pendent, and Recessed Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the perfor­mance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condi­tion. Contract the installing contrac­tor or product manufacturer with any questions.
NFPA 13 prohibits installation of 1/2 in. NPT sprinklers with K-factors greater than 5.6 in new construction. They are intended for retrofit in existing sprinkler systems only.
Sprinkler Identification Numbers (SIN)
T Y1151 ... Upright 2.8K, 1/2 in. NPT TY1251 ...Pendent 2.8K, 1/2 in. NPT TY3151 ... Upright 5.6K, 1/2 in. NPT TY3251 ...Pendent 5.6K, 1/2 in. NPT TY4151 ... Upright 8.0K, 3/4 in. NPT TY4251 ...Pendent 8.0K, 3/4 in. NPT TY48 51 ... Upright 8.0K, 1/2 in. NPT TY49 51 ...Pendent 8.0K, 1/2 in. NPT
Technical Data
Approvals
UL and C-UL Listed FM, LPCB, VdS, and NYC Approved
Refer to Table A for complete approval infor­mation, including corrosion-resistant status.
Maximum Working Pressure
Refer to Table B
Discharge Coefficient
K=2.8 GPM/psi½ (40,3 LPM/bar½) K=5.6 GPM/psi½ (80,6 LPM/bar½) K=8.0 GPM/psi½ (115,2 LPM /bar½)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table C
Recessed Escutcheon: Signal or Pure White, Grey Aluminum, Jet Black, Chrome Plated, or Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . .Brass/Copper
Sealing Assembly ..Beryllium Nickel w/ TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Bushing (K=2.8) . . . . . . . . . . . . . . . . . . . . Bronze
Page 1 of 8 JULY 2018 TFP151
Page 2
TF P151
PENDENTUPRIGHT CROSS SECTION
CEILING PLATE
1
Frame
-
Compression
5
-
* **
ESCUTCHEON
Pipe thread connections per
Temperature rating
1
Frame
-
3
-
5
-
Sealing
Compression
RECESSED PENDENTUPRIGHT PENDENT CROSS SECTION
*
*
---
Page 2 of 8
1/2" NPT
is indicated on Deector.
SEATING SURFACE
7
7/16" (11,1 mm) NOMINAL
MAKE-IN
**
2-3/16"
(55,6 mm)
WRENCH
FLATS
2-1/4"
(57,2 mm)
1-9/16"
(39,7 mm)
1
3
2
4
5
6
*
FIGURE 1
SERIES TY-B UPRIGHT (TY1151) AND PENDENT (T Y1251) SPRINKLERS
2.8 K-FACTOR, 1/2 IN. NPT, STANDARD RESPONSE
7/16" (11,1 mm) NOMINAL
MAKE-IN
(55,6 mm)
ISO 7-1 can be provided on special request.
2-3/16"
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
-
2 Button
-
2
Button
-
3
Sealing Assembly
-
Bulb
4
Temperature rating is
*
indicated on Deector.
Pipe thread connections
**
per ISO 7-1 can be provided on special request.
-
6 7
Assembly Bulb4
Screw
-
Deector
-
Bushing
Screw
6-Deector
*
*
1
3
2
4
5
1/2" NPT
UPRIGHT PENDENT CROSS SECTIONRECESSED PENDENT
**
WRENCH
FLATS
STYLE 10
RECESSED
2-7/8" (73,0 mm) DIA.
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH
FLATS
7/16" (11,1 mm) NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
1/2" NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
STYLE 10
RECESSED
ESCUTCHEON
2
-
Frame Button
Sealing Assembly
-
4
2-7/8" (73,0 mm) DIA.
POLY-STAINLESS FINISH ONLY
FIGURE 2
SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6 K-FACTOR, 1/2 IN. NPT, STANDARD RESPONSE
531
Compression Screw
-
6
DeectorBulb
*
6
Temperature rating indicated on Deector.
1
3
2
4
5
6
*
Page 3
TF P151
PENDENTUPRIGHT CROSS SECTION
1
Frame
-
Compression
5
-
CEILING PLATE
* **
Pipe thread connections per
Temperature rating
1
Frame
-
3
-
5
-
Sealing
Compression
ESCUTCHEON
*
*
ESCUTCHEON
- - -
Page 3 of 8
is indicated on Deector.
1/2" (12,7 mm) NOMINAL
MAKE-IN
(57,2 mm)
3/4" NPT
UPRIGHT PENDENT CROSS SECTIONRECESSED PENDENT
**
ISO 7-1 can be provided on special request.
2-1/4"
WRENCH
FLATS
(58,7 mm)
1-9/16"
(39,7 mm)
ESCUTCHEON
PLATE SEATING
2-5/16"
STYLE 40
RECESSED
SURFACE
2-7/8" (73,0 mm) DIA.
-
2 Button
ALL FINISHES EXCEPT POLY-STAINLESS
31 5
Sealing Assembly
- -
4
Bulb
6
1/2" (12,7 mm) NOMINAL
MAKE-IN
(57,2 mm)
WRENCH
FLATS
2-1/4"
3/4" NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-5/16"
(58,7 mm)
1-9/16"
(39,7 mm)
2
Frame
-
Button
Assembly
-
Bulb4
Compression Screw Deector
*
Screw
6-Deector
Temperature rating indicated on Deector.
*
1
3
2
4
5
6
*
1
3
2
4
5
UPRIGHT CROSS SECTIONPENDENT RECESSED PENDENT
1/2" NPT WRENCH
STYLE 40
RECESSED
2-7/8" (73,0 mm) DIA.
POLY-STAINLESS FINISH ONLY
FIGURE 3
SERIES TY-B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS
8.0 K-FACTOR, 3/4 IN. NPT, STANDARD RESPONSE
SEATING SURFACE
1
3
2
4
5
6
*
7/16" (11,1 mm) NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
**
FLATS
2-1/4"
(57,2 mm)
1-9/16"
(39,7 mm)
FIGURE 4
SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K-FACTOR, 1/2 IN. NPT, STANDARD RESPONSE
-
2
Button
-
3
Sealing Assembly
-
Bulb
4
Temperature rating is
*
indicated on Deector.
Pipe thread connections
**
per ISO 7-1 can be provided on special request.
-
6
Screw Deector
6
*
Page 4
TF P151
WRENCH
WRENCHING AREA
(END "A" USED FOR
3/4" NPT MODELS)
2-7/8" DIA.
3/4" (19,1 mm)
2-7/8" DIA.
13/16" (20,6 mm)
Page 4 of 8
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
SERIES
TY-B
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-1/4" (31,8 mm)
FIGURE 5
SERIES TY-B RECESSED PENDENT SPRINKLER
ASSEMBLY WITH TWO-PIECE 3/4 INCH TOTAL
ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN. NPT
WRENCH RECESS
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
SERIES
TY-B
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-5/16" (33,3 mm)
FIGURE 6
SERIES TY-B RECESSED PENDENT SPRINKLER
ASSEMBLY WITH TWO-PIECE 3/4 INCH TOTAL
ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 IN. NPT
RECESS
WRENCH RECESS
(END "B" USED FOR
SPRINKLER WRENCH
Poly-Stainless Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button ................L316 Stainless Steel*
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . L316 Stainless Steel*
Deflector . . . . . . . . . . . . . . . . . . . Copper/Bronze
Sealing Assembly . Gold Plated Beryllium Nickel
*Type L316 stai nless steel ( UNS 31603) per AST M A479/479M or BS EN 1008 WN1.440 4.
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
1/2" NPT MODELS)
FIGURE 7 W-T YPE 6
w/TEFLON
Design Criteria
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the stan­dard installation rules recognized by the applicable Listing or Approval agency, such as UL Listing based on the requirements of NFPA 13 and FM Approval based on the requirements of the FM Global Loss Prevention Data Sheets. Use only the Style 10 or 40 Recessed Escutcheon, as applicable, for recessed pendent installations.
PUSH WRENCH
IN TO ENSURE ENGAGEMENT
WITH SPRINKLER
FIGURE 8 W-TYPE 7 RECESSED SPRINKLER WRENCH
Installation
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 360°F (182°C) temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint should be obtained by apply­ing a minimum-to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Obtain a leak-tight 3/4 in. NPT sprinkler joint by applying a minimum to maximum
Page 5
TF P151
Page 5 of 8
K
Sprinkler
Typ e
Temperature
Rating
Bulb
Liquid
Color
Natural
Brass
Chrome
Plated
Sprinkler Finish
PolyestercPoly-Stainless
c
8
Lead
Coated
Wax
Coated
Wax- Over-
Lead
Coated
135° F (57°C) Orange
2.8
1/2 in.
NPT
5.6
1/2 in.
NPT
Upright
(TY1151)
and Pendent (T Y1251)
Figure 1
Upright
(T Y3151)
and Pendent
(T Y32 51) Figure 2
Recessed
Pendent
(T Y32 51)a
Figure 5
155° F (6 8°C) Red
175°F (79°C) Yel low
200°F (93°C) Green
28 6°F (141° C) Blue
360°F (182°C)
135° F (57°C)
155° F (6 8°C)
175°F (79°C)
200°F (93°C)
28 6°F (141° C)
360°F (182°C)
135° F (57°C)
Mauve 1, 2
Orange
Red
Yel low
Green
Blue 1b, 2b, 3b, 5b1b, 2b, 3b, 5
Mauve N/A
Orange
155° F (6 8°C) Red
175°F (79°C) Yel low
200°F (93°C) Green
1, 2, 3
N/A N/A
1, 2, 3, 4, 5, 6, 7 1, 2 1, 2, 3, 5
1, 2, 3, 4, 5
1, 2 N/A
d
1, 2, 3, 5 1, 2, 3, 5
28 6°F (141° C) Blue 1, 2
135° F (57°C) Orange
8.0
3/4 in.
NPT
Upright
(TY4151)
and Pendent
(TY4251) Figure 3
Recessed
Pendent
(TY4251)a
Figure 6
155° F (6 8°C) Red
175°F (79°C) Yel low
200°F (93°C) Green
1, 2, 3, 4, 5, 6, 7 1, 2 1, 2, 5
1, 2, 3, 5 1, 2, 5
28 6°F (141° C) Blue 1b, 2b, 3b, 5b1b, 2b, 5
360°F (182°C) Mauve N/A
135° F (57°C) Orange
155° F (6 8°C) Red
175°F (79°C) Yel low
1, 2, 3, 4, 5
1, 2 N/A
200°F (93°C) Green
28 6°F (141° C) Blue 1, 2
135° F (57°C) Orange
8.0
1/2 in.
NPT
Upright
(TY4 851)
and Pendent
(TY4951) Figure 4
155° F (6 8°C) Red
175°F (79°C) Yel low
200°F (93°C) Green
28 6°F (141° C) Blue
1, 2, 3, 4, 5, 6 N/A N/A
360°F (182°C) Mauve
NOTES
1. Listed by Underwriters Labo ratories, Inc. (UL).
2. Listed by Unde rwriter s Laborato ries, Inc. fo r use in Canada (C -UL).
3. A pproved by FM Gl obal (FM Appr ovals).
4. A pproved by the L oss Prevention Certic ation Board ( LPCB Ref. No. 007k /03).
5. A pproved by the C ity of New York unde r MEA 354- 01-E.
6. VdS Approved. (Fo r details, co ntact John son Control s, Enschede , Netherlan ds, Tel. 31-53-428- 4444 / Fax 31-53 -428-3377 )
7. A pproved by the Lo ss Preventio n Certic ation Board ( LPCB Ref. No. 094 a/05)
8. W here Polyes ter Coated, Le ad Coated, Wax C oated, and Wa x-over-Lead Coa ted Sprinkl ers are noted to be UL and C-UL L isted, the sp rinklers a re UL and C-UL L isted as Corro sion-Res istant Spr inklers. W here Lead Coa ted, Wax Coate d, and Wax-over-L ead Coated Sp rinklers a re noted to be FM Ap proved, the sprinklers a re FM Approved a s Corrosion-Resistant Sprinklers.
a. Installe d with Style 10 (1/2 in. NP T) or Style 40 (3/4 in. NPT) 3 /4 in. Tota l Adjustmen t Recesse d Escutcheo n, as applica ble b. 150°F ( 66°C) maximum ceiling temperature c. Frame and de ector only d. Not Applicable (N/A)
b
b
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
TABLE A
LABORATORY LISTINGS AND APPROVALS
Page 6
TF P151
Page 6 of 8
K Typ e
Natural Brass
Chrome
Plated
Sprinkler Finish
Polyester
1
Lead
Coated
Wax
Coated
Wax-Over-Lead
Coated
2.8
1/2 i n.
NPT
5.6
1/2 i n.
NPT
8.0
3/4 in.
NPT
8.0
1/2 i n.
NPT
NOTES
1. Frame an d deector on ly
2. The maximum working pre ssure of 250 ps i (17,2 bar) onl y applies to the Listing by Und erwriter s Laborato ries, Inc. (UL), the Listing by Underwr iters Labo ratories, I nc. for use in Canada (C-UL), and the A pproval by the C ity of New York.
3. Not Applicable (N/A)
Upright (TY1151)
and
Pendent (TY1251)
Upright (TY3151)
and
Pendent (TY3251)
Recessed Pendent
(T Y32 51)
Upright (TY4151)
and
Pendent (TY4251)
Recessed Pendent
(TY4251)
Upright (TY4851)
and
Pendent (TY4951)
175 psi (12,1 bar) N/A
250 psi (17,2 bar)
or
175 psi (12,1 bar)
175 psi (12,1 bar)
175 psi (12,1 bar) N/A
175 psi (12,1 bar)
2
3
TABLE B
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
MAXIMUM WORKING PRESSURE
torque of 10 to 20 lb-ft (13,4 to 26,8 N·m). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Do not attempt to compensate for insufficient adjustment in the escutch­eon plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.
Series TY-B Upright and Pendent Sprinklers Installation
The Series TY-B Upright and Pendent Sprinklers must be installed in accor­dance with the following instructions:
Step 1. Install pendent sprinklers in the pendent position. Install upright sprin­klers in the upright position.
Step 2. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 7). For wax-coated sprinklers, use an 8 or 10 in. adjustable wrench. With reference to Figure 1 to 4, apply the W-Type 6 Recessed Sprinkler Wrench or an adjustable wrench, as applicable, to the sprinkler wrench flats.
Wax Coated Sprinklers
When installing wax-coated sprinklers with an adjustable wrench, take care to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environment:
• Open the jaws of the wrench suffi­ciently wide to pass over the wrench flats without damaging the wax coating.
• Before wrench tightening the sprin­kler, adjust the jaws of the wrench to contact only the sprinkler wrench flats.
• After wrench tightening the sprin­kler, loosen the wrench jaws before removing the wrench.
After Installation
After installation, complete the following:
• Inspect the sprinkler wrench flats and frame arms and retouch (repair) the wax coating whenever the coat­ing has been damaged and bare metal is exposed.
• Retouch the wax coating on the wrench flats by gently applying a heated 1/8 inch diameter steel rod to the damaged areas of wax, to smooth it back over areas where bare metal is exposed.
NOTICE
Only retouching of the wax coating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point it can begin to melt the wax, and appropriate precautions need to be taken when handling the heated rod in order to prevent the installer from being burned.
Page 7
TF P151
Page 7 of 8
Series TY-B Recessed Pendent
Sprinklers
The Series TY-B Recessed Pendent Sprinklers must be installed in accor­dance with the following instructions:
Step 1. After installing the Style 10 or 40 Mounting Plate, as applicable, over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 8). With reference to Figure 3 or 4, apply the W-Type 7 Recessed Sprin­kler wrench to the sprinkler wrench flats.
Step 3. After the ceiling is installed or the finish coat is applied, slide on the Style 10 or 40 Closure over the Series TY-B Recessed Pendent Sprinkler and push the Closure over the Mount­ing Plate until its flange contacts the ceiling.
Care and Maintenance
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this action.
The owner must assure that the sprin­klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non­operation in the event of a fire or inad­vertent operation may result.
Absence of an escutcheon, which is used to cover a clearance, may delay the time to sprinkler operation in a fire situation.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal­lation Section.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this doc­ument, as well as with the applicable standards of the National Fire Protec­tion Association,(e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.
Automatic sprinkler are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
Page 8
TF P151
Page 8 of 8
P/N 57 – XXX – X – XXX
SIN
530
2.8K UPRIGHT (1/2 in. NPT)
531
2.8K PENDENT (1/2 in. NPT )
570
5.6K UPRIGHT (1/2 in. NPT)
571
5.6K PENDENT (1/2 in. NPT )
590
8.0K UPRIGHT (3/4 in. NPT)
591
8.0K PENDENT (3/4 in. NPT)
560
8.0K UPRIGHT (1/2 in. NPT)
561
8.0K PENDENT (1/2 in. NPT)
NOTES
1. Only avai lable on TY3151, TY3251, TY4151, and T Y4251.
2. Eastern He misphere sa les only.
3. Available in onl y 8.0K, 155°F (68°C) or 200°F (93° C); requires le ad time to manufacture.
4. Available only for 8.0 K-factor T Y4151 and TY4251 for use in de luge systems (“OPEN” indic ates sprink ler assembly without gl ass bulb, but ton, and sealing assemb ly).
T Y1151
TY1251
TY 3151
TY 3251
T Y4151
T Y4251
T Y48 51
T Y49 51
1 NATURAL BRASS
2
3
4
5
6
7 LEAD COATED
8
9 CHROME PLATED
SPRINKLER
FINISH
POLY-STAINLESS GREY
ALUMINUM (RAL9007)
POLYESTER
PURE WHITE (RAL9010)2
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
JET BL ACK (RAL9005)3
POLYESTER
WA X COATED
286°F (141°C) MAX
WAX- OVER- LEAD 286°F (141°C) MAX
1
TEMPERATURE
RATIN G
135 135°F (57°C)
155 155°F (6 8°C)
175 175° F ( 79 °C)
200 200°F (93°C)
286 28 6°F (141°C )
360 360°F (182°C)
000 OPEN
4
TABLE C
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product name and Part Number (P/N).
Sprinkler Assemblies with NPT Thread Connections
Specify: Series TY-B (specify SIN), (specify K-factor), (specify Upright or Pendent) Sprinkler with (specify) temperature rating, (specify) finish or coating, P/N (Refer to Table C)
Recessed Escutcheon
Specify: Style (10 or 40) Recessed Escutcheon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sh eet TFP770
Sprinkler Wrenches
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001
Wax Sticks (for retouching wrench­damaged wax coating)
Specify: (specify color, below) Color­coded Wax Sticks for retouching (specify temperature rating) tempera­ture-rated Series TY-B Sprinklers, P/N (specify)
Black for 135°F ( 57°C) ......P/ N 56 -065-1-135
Red for 155°F (68°C) .......P/N 5 6- 065 -1-155
Yellow for 175°F (79°C) .....P/N 56-0 65 -1-175
Blue for 20 0°F (93°C )
and 286°F (141°C) .........P/ N 5 6- 06 5-1-
286
Note: Each wax stick is suitable for retouching up to 25 sprinklers.
The wax used for 286°F (141°C) sprinklers is the same as for 200°F (93°C) sprinklers. Therefore, the 286°F (141°C) sprinkler is limited to the same maximum ceiling temperature as the 200°F (93°C) sprinkler which is 150°F (66°C).
1400 Pennbrook Parkway, La nsdale, PA 19446 | Telephone +1-215-36 2-0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; TEFLON is a regi stered tradema rk of DuPont