Series TY-B – 2.8, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The TYCO Series TY-B 2.8, 5.6,
and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers
described in herein are standard
response, standard coverage, decorative 5 mm glass bulb-type spray sprinklers. They are designed for use in light,
ordinary, or extra-hazard commercial
occupancies such as banks, hotels,
shopping malls, factories, refineries,
and chemical plants.
The TY-B Recessed Pendent Sprinkler,
where applicable, is intended for use in
areas with a finished ceiling. It uses a
two-piece Style 10 (1/2 in. NPT) or Style
40 (3/4 in. NPT) Recessed Escutcheon.
The Recessed Escutcheon provides
1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total
adjustment from the flush pendent
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend
the life of copper alloy sprinklers
beyond what would be obtained
when exposed to corrosive atmospheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the applicable approval agencies, the testing
is not representative of all possible
corrosive atmospheres. Consequently,
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
it is recommended that the end-user be
consulted about the suitability of these
coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals,
and gas/chemical velocity, should be
considered as a minimum, along with
the corrosive nature of the chemical to
which the sprinklers will be exposed.
An intermediate level version of the
Series TY-B Pendent Sprinkler can be
obtained by utilizing the Series TY-B
Pendent Sprinkler in combination with
the Model S2 Shield.
NOTICE
The Series TY-B 2.8, 5.6, and 8.0 K-factor, Upright, Pendent, and Recessed
Pendent Sprinklers described herein
must be installed and maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association
(NFPA), in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system and
devices in proper operating condition. Contract the installing contractor or product manufacturer with any
questions.
NFPA 13 prohibits installation of 1/2 in.
NPT sprinklers with K-factors greater
than 5.6 in new construction. They are
intended for retrofit in existing sprinkler
systems only.
Sprinkler
Identification
Numbers (SIN)
T Y1151 ... Upright 2.8K, 1/2 in. NPT
TY1251 ...Pendent 2.8K, 1/2 in. NPT
TY3151 ... Upright 5.6K, 1/2 in. NPT
TY3251 ...Pendent 5.6K, 1/2 in. NPT
TY4151 ... Upright 8.0K, 3/4 in. NPT
TY4251 ...Pendent 8.0K, 3/4 in. NPT
TY48 51 ... Upright 8.0K, 1/2 in. NPT
TY49 51 ...Pendent 8.0K, 1/2 in. NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, VdS, and NYC Approved
Refer to Table A for complete approval information, including corrosion-resistant status.
*Type L316 stai nless steel ( UNS 31603) per AST M
A479/479M or BS EN 1008 WN1.440 4.
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
1/2" NPT MODELS)
FIGURE 7
W-T YPE 6
w/TEFLON
Design
Criteria
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and
Recessed Pendent Sprinklers are
intended for fire protection systems
designed in accordance with the standard installation rules recognized by
the applicable Listing or Approval
agency, such as UL Listing based on
the requirements of NFPA 13 and FM
Approval based on the requirements
of the FM Global Loss Prevention Data
Sheets. Use only the Style 10 or 40
Recessed Escutcheon, as applicable,
for recessed pendent installations.
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
FIGURE 8
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to
3/32 in. (2,4 mm) for the 360°F (182°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
7 to 14 lb-ft (9,5 to 19,0 N·m). Obtain
a leak-tight 3/4 in. NPT sprinkler joint
by applying a minimum to maximum
Page 5
TF P151
Page 5 of 8
K
Sprinkler
Typ e
Temperature
Rating
Bulb
Liquid
Color
Natural
Brass
Chrome
Plated
Sprinkler Finish
PolyestercPoly-Stainless
c
8
Lead
Coated
Wax
Coated
Wax- Over-
Lead
Coated
135° F (57°C)Orange
2.8
1/2 in.
NPT
5.6
1/2 in.
NPT
Upright
(TY1151)
and
Pendent
(T Y1251)
Figure 1
Upright
(T Y3151)
and
Pendent
(T Y32 51)
Figure 2
Recessed
Pendent
(T Y32 51)a
Figure 5
155° F (6 8°C)Red
175°F (79°C)Yel low
200°F (93°C)Green
28 6°F (141° C)Blue
360°F (182°C)
135° F (57°C)
155° F (6 8°C)
175°F (79°C)
200°F (93°C)
28 6°F (141° C)
360°F (182°C)
135° F (57°C)
Mauve1, 2
Orange
Red
Yel low
Green
Blue1b, 2b, 3b, 5b1b, 2b, 3b, 5
MauveN/A
Orange
155° F (6 8°C)Red
175°F (79°C)Yel low
200°F (93°C)Green
1, 2, 3
N/AN/A
1, 2, 3, 4, 5, 6, 71, 21, 2, 3, 5
1, 2, 3, 4, 5
1, 2N/A
d
1, 2, 3, 51, 2, 3, 5
28 6°F (141° C)Blue1, 2
135° F (57°C)Orange
8.0
3/4 in.
NPT
Upright
(TY4151)
and
Pendent
(TY4251)
Figure 3
Recessed
Pendent
(TY4251)a
Figure 6
155° F (6 8°C)Red
175°F (79°C)Yel low
200°F (93°C)Green
1, 2, 3, 4, 5, 6, 71, 21, 2, 5
1, 2, 3, 51, 2, 5
28 6°F (141° C)Blue1b, 2b, 3b, 5b1b, 2b, 5
360°F (182°C) MauveN/A
135° F (57°C)Orange
155° F (6 8°C)Red
175°F (79°C)Yel low
1, 2, 3, 4, 5
1, 2N/A
200°F (93°C)Green
28 6°F (141° C)Blue1, 2
135° F (57°C)Orange
8.0
1/2 in.
NPT
Upright
(TY4 851)
and
Pendent
(TY4951)
Figure 4
155° F (6 8°C)Red
175°F (79°C)Yel low
200°F (93°C)Green
28 6°F (141° C)Blue
1, 2, 3, 4, 5, 6N/AN/A
360°F (182°C) Mauve
NOTES
1. Listed by Underwriters Labo ratories, Inc. (UL).
2. Listed by Unde rwriter s Laborato ries, Inc. fo r use in Canada (C -UL).
3. A pproved by FM Gl obal (FM Appr ovals).
4. A pproved by the L oss Prevention Certic ation Board ( LPCB Ref. No. 007k /03).
5. A pproved by the C ity of New York unde r MEA 354- 01-E.
6. VdS Approved. (Fo r details, co ntact John son Control s, Enschede , Netherlan ds, Tel. 31-53-428- 4444 / Fax 31-53 -428-3377 )
7. A pproved by the Lo ss Preventio n Certic ation Board ( LPCB Ref. No. 094 a/05)
8. W here Polyes ter Coated, Le ad Coated, Wax C oated, and Wa x-over-Lead Coa ted Sprinkl ers are noted to be UL and C-UL L isted, the sp rinklers a re UL and C-UL L isted as
Corro sion-Res istant Spr inklers. W here Lead Coa ted, Wax Coate d, and Wax-over-L ead Coated Sp rinklers a re noted to be FM Ap proved, the sprinklers a re FM Approved a s
Corrosion-Resistant Sprinklers.
a. Installe d with Style 10 (1/2 in. NP T) or Style 40 (3/4 in. NPT) 3 /4 in. Tota l Adjustmen t Recesse d Escutcheo n, as applica ble
b. 150°F ( 66°C) maximum ceiling temperature
c. Frame and de ector only
d. Not Applicable (N/A)
b
b
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
TABLE A
LABORATORY LISTINGS AND APPROVALS
Page 6
TF P151
Page 6 of 8
KTyp e
Natural Brass
Chrome
Plated
Sprinkler Finish
Polyester
1
Lead
Coated
Wax
Coated
Wax-Over-Lead
Coated
2.8
1/2 i n.
NPT
5.6
1/2 i n.
NPT
8.0
3/4 in.
NPT
8.0
1/2 i n.
NPT
NOTES
1. Frame an d deector on ly
2. The maximum working pre ssure of 250 ps i (17,2 bar) onl y applies to the Listing by Und erwriter s Laborato ries, Inc. (UL), the Listing by Underwr iters Labo ratories, I nc. for use in
Canada (C-UL), and the A pproval by the C ity of New York.
3. Not Applicable (N/A)
Upright (TY1151)
and
Pendent (TY1251)
Upright (TY3151)
and
Pendent (TY3251)
Recessed Pendent
(T Y32 51)
Upright (TY4151)
and
Pendent (TY4251)
Recessed Pendent
(TY4251)
Upright (TY4851)
and
Pendent (TY4951)
175 psi (12,1 bar)N/A
250 psi (17,2 bar)
or
175 psi (12,1 bar)
175 psi (12,1 bar)
175 psi (12,1 bar)N/A
175 psi (12,1 bar)
2
3
TABLE B
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
MAXIMUM WORKING PRESSURE
torque of 10 to 20 lb-ft (13,4 to
26,8 N·m). Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the escutcheon plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Series TY-B Upright and Pendent
Sprinklers Installation
The Series TY-B Upright and Pendent
Sprinklers must be installed in accordance with the following instructions:
Step 1. Install pendent sprinklers in the
pendent position. Install upright sprinklers in the upright position.
Step 2. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 7).
For wax-coated sprinklers, use an
8 or 10 in. adjustable wrench. With
reference to Figure 1 to 4, apply the
W-Type 6 Recessed Sprinkler Wrench
or an adjustable wrench, as applicable,
to the sprinkler wrench flats.
Wax Coated Sprinklers
When installing wax-coated sprinklers
with an adjustable wrench, take care to
prevent damage to the wax coating on
the sprinkler wrench flats or frame arms
and, consequently, exposure of bare
metal to the corrosive environment:
• Open the jaws of the wrench sufficiently wide to pass over the wrench
flats without damaging the wax
coating.
• Before wrench tightening the sprinkler, adjust the jaws of the wrench
to contact only the sprinkler wrench
flats.
• After wrench tightening the sprinkler, loosen the wrench jaws before
removing the wrench.
After Installation
After installation, complete the
following:
• Inspect the sprinkler wrench flats
and frame arms and retouch (repair)
the wax coating whenever the coating has been damaged and bare
metal is exposed.
• Retouch the wax coating on the
wrench flats by gently applying a
heated 1/8 inch diameter steel rod
to the damaged areas of wax, to
smooth it back over areas where
bare metal is exposed.
NOTICE
Only retouching of the wax coating
applied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point it can begin to melt the wax,
and appropriate precautions need to be
taken when handling the heated rod in
order to prevent the installer from being
burned.
Page 7
TF P151
Page 7 of 8
Series TY-B Recessed Pendent
Sprinklers
The Series TY-B Recessed Pendent
Sprinklers must be installed in accordance with the following instructions:
Step 1. After installing the Style 10
or 40 Mounting Plate, as applicable,
over the sprinkler threads and with
pipe thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 8). With reference to Figure 3 or
4, apply the W-Type 7 Recessed Sprinkler wrench to the sprinkler wrench
flats.
Step 3. After the ceiling is installed or
the finish coat is applied, slide on the
Style 10 or 40 Closure over the Series
TY-B Recessed Pendent Sprinkler
and push the Closure over the Mounting Plate until its flange contacts the
ceiling.
Care and
Maintenance
The TYCO Series TY-B 2.8, 5.6, and
8.0 K-factor, Upright, Pendent, and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
The owner must assure that the sprinklers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, nonoperation in the event of a fire or inadvertent operation may result.
Absence of an escutcheon, which is
used to cover a clearance, may delay
the time to sprinkler operation in a fire
situation.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Installation Section.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association,(e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler are recommended
to be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national codes.
Page 8
TF P151
Page 8 of 8
P/N 57 – XXX – X – XXX
SIN
530
2.8K UPRIGHT (1/2 in. NPT)
531
2.8K PENDENT (1/2 in. NPT )
570
5.6K UPRIGHT (1/2 in. NPT)
571
5.6K PENDENT (1/2 in. NPT )
590
8.0K UPRIGHT (3/4 in. NPT)
591
8.0K PENDENT (3/4 in. NPT)
560
8.0K UPRIGHT (1/2 in. NPT)
561
8.0K PENDENT (1/2 in. NPT)
NOTES
1. Only avai lable on TY3151, TY3251, TY4151, and T Y4251.
2. Eastern He misphere sa les only.
3. Available in onl y 8.0K, 155°F (68°C) or 200°F (93° C); requires le ad time to manufacture.
4. Available only for 8.0 K-factor T Y4151 and TY4251 for use in de luge systems (“OPEN” indic ates sprink ler assembly without gl ass bulb, but ton, and sealing assemb ly).
T Y1151
TY1251
TY 3151
TY 3251
T Y4151
T Y4251
T Y48 51
T Y49 51
1NATURAL BRASS
2
3
4
5
6
7LEAD COATED
8
9CHROME PLATED
SPRINKLER
FINISH
POLY-STAINLESS GREY
ALUMINUM (RAL9007)
POLYESTER
PURE WHITE (RAL9010)2
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
JET BL ACK (RAL9005)3
POLYESTER
WA X COATED
286°F (141°C) MAX
WAX- OVER- LEAD
286°F (141°C) MAX
1
TEMPERATURE
RATIN G
135135°F (57°C)
155155°F (6 8°C)
175175° F ( 79 °C)
200200°F (93°C)
28628 6°F (141°C )
360360°F (182°C)
000OPEN
4
TABLE C
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-B (specify SIN),
(specify K-factor), (specify Upright
or Pendent) Sprinkler with (specify)
temperature rating, (specify) finish or
coating, P/N (Refer to Table C)
Recessed Escutcheon
Specify: Style (10 or 40) Recessed
Escutcheon with (specify*) finish, P/N
(specify*)
Specify: (specify color, below) Colorcoded Wax Sticks for retouching
(specify temperature rating) temperature-rated Series TY-B Sprinklers, P/N
(specify)
Black for 135°F ( 57°C) ......P/ N 56 -065-1-135
Red for 155°F (68°C) .......P/N 5 6- 065 -1-155
Yellow for 175°F (79°C) .....P/N 56-0 65 -1-175
Blue for 20 0°F (93°C )
and 286°F (141°C) .........P/ N 5 6- 06 5-1-
286
Note: Each wax stick is suitable for
retouching up to 25 sprinklers.
The wax used for 286°F (141°C) sprinklers
is the same as for 200°F (93°C) sprinklers.
Therefore, the 286°F (141°C) sprinkler
is limited to the same maximum ceiling
temperature as the 200°F (93°C) sprinkler
which is 150°F (66°C).
1400 Pennbrook Parkway, La nsdale, PA 19446 | Telephone +1-215-36 2-0700