Tyco ELO-231B, TY5251, TY5851, TY5151 Series Manual

Worldwide
Contacts
Series ELO-231B – 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
www.tyco-fire.com
General Description
TYCO Series ELO-231B 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprinklers of the frangible bulb type. They are standard response, spray sprinklers that produce a hemi­spherical water distribution pattern below the deflector.
The 11.2 K-factor, ELO-231B Sprinklers were subjected to full-scale, high-piled storage fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231B Sprinklers, making their use highly advantageous in high density applications, such as the pro­tection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copper alloy components used in Series ELO-231B Sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although wax, lead, and polyester coated sprin­klers have passed the standard corro­sion tests of the applicable approval agencies, the testing is not repre­sentative of all possible corrosive atmospheres. Consequently, it is rec­ommended that the end-user be con­sulted with respect to the suitability of these corrosion resistant coatings
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/ chemical velocity, should be consid­ered, as a minimum, along with the cor­rosive nature of the chemical to which the sprinklers will be exposed.
An upright intermediate level version of the Series ELO-231B Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231B Upright Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231B Sprinklers can be obtained by utilizing the Series ELO-231B Pendent Sprinkler with the WS-2 Shield. If there is a pos­sibility of the pendent intermediate level version being exposed to mechanical damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231B Upright and Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Installation of Series ELO-231B Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Sprinkler Identification Numbers (SINs)
Refer to Table A for sprinkler identifica­tion numbers.
Page 1 of 6 AUGUST 2018 TFP342
TFP342
TY5851
TY5251
SECTION
TY5151
(71,4 mm)
1/2" (12,7 mm)
Compression
Components:
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2" NPT
SERIES ELO-231B 11.2K UPRIGHT 3/4 INCH NPT (TY5151), UPRIGHT 1/2 INCH NPT (TY5851), AND
PENDENT 3/4 INCH NPT (TY5251) SPRINKLERS, STANDARD RESPONSE
Technical Data
Approvals
UL and C-UL Listed FM Approved NYC Approved
Refer to Table C for specific details on laboratory and approvals, including corrosion-resistant status. The approv­als apply to the service conditions indi­cated in the Design Criteria section.)
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb (5 mm dia.) . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Additional Technical Data
Refer to Table A for additional techni­cal data.
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4"
NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar)
Temperature Rating °F (°C)
Thread Size 3/4 in. NPT or 1/2 in. NPT
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Note:
1. Refer to Table C for laboratory listings and approvals.
1
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
TECHNICAL DATA
Design Criteria
UL and C-UL Listing Requirements
TYCO Series ELO-231B 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers are to be installed in accordance with NFPA 13 standard sprinkler position and area/ density flow calculation requirements for light, ordinary, or extra hazard occu­pancies, as well as high-piled storage occupancies (solid-piled, palletized, rack storage, bin box, and shelf storage including but not limited to Class I-IV
1
3/4"
1
NPT
2
3
4
5
6
CROSS
TY5151 - Upright 3/4 in. NPT TY5251 -Pendent 3/4 in. NPT TY5851 - Upright 1/2 in. NPT
TY5151 is a re-de signation for Ce ntral SIN C5151. TY5251 is a re-desi gnation for Cent ral, Gem , and Star SINs C5251, G1871, and S2531, respecti vely. TY5851 is a re-designati on for Central SIN C5851.
11. 2 G P M /psi½ (161,4 LPM/bar½)
155 ºF (68 ºC)1
200 ºF (93 ºC)
286 ºF (141 ºC)
2
3 4 5
6
TABL E A
and Group A plastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems. Refer to Table B for additional information.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231B Sprinklers are to be installed in accor­dance with the applicable control mode density/area guidelines provided by FM Global.
Note: FM Approval guidelines may differ from UL and C-UL Listing criteria.
-
Frame
-
Seal Assembly
-
Cap
-
Bulb
­Screw
-
Deector
Temperature
*
rating is indicated on deector.
*