Tyco TY5151, TY5851, TY5251 Series Manual

Page 1
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series ELO-231B — 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
sentative of all possible corrosive at-
General Description
The 11.2 K-factor, Series ELO-231B, Standard Response, Standard Cover­age, Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprin­klers of the frangible bulb type. They are “standard response - spray sprin­klers” that produc e a hemispherical water distribution pattern below the deflector.
The 11.2 K-factor, ELO-231B Sprin­klersweresubjectedtofullscale,high­piled storage, fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor stand­ard spray sprinklers for the protection of high-piled sto ra ge .
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231B Sprinklers — making their use highly advantageous in high density applications, such as the protection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copperalloy com­ponents used in Series ELO-231B sprinklers beyond that which would otherwise be obtained when exposed to corr osiv e atmospheres. Although wax, lead, and polyester coated sprin­klers have passed the standard corro­sion tests of the applicable approval agencies, the testing is not repre-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail tooperateinafiresituationor cause it to operate prematurely.
mospheres.Consequently,itisrecom­mendedthattheenduserbe consulted with respect to the suitability of these corrosion resistant coatings for any given corrosive environment. The ef­fects of ambient temperature, concen­tration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive na­ture of the chemicalto which the sprin­klers will be exposed.
An upright intermediate level version of the Series ELO-231B Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231B Up­right Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231B Sprinklers can be obtained by utiliz­ing the Series ELO-231B Pendent SprinklerwiththeWS-2Shield.Ifthere is a possibility of the pendent interme­diate level version being exposed to mechanical damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO-231B Upright and P endent Sprinklers de­scribed herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association, in addition to the standardsof any other authorities hav­ing jurisdiction. Failure to do so may
impair the performance of these de­vices.
The owner is responsible for maintain­ing their fire protection system and de­vices in proper operating condition. The installing contractor or manufac­turer should be contacted with any questions.
Installation of Series ELO-231B Pen­dent Sprinklers in recessed escutch­eons will void all spr inkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Page 1 of 6 TFP342
MARCH, 2007
Page 2
Page2of6
TYPE TEMPERATURE BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
SPRINKLER FINISH
LEAD
COATED
WAX
COATED
TFP342
WAX
OVER LEAD
UPRIGHT
(TY5151
&
TY5851)
PENDENT
(TY5251
NOTES:
1. Listed by U nderwriters Laboratories, Inc. (UL Listed).
2. Listed by U nderwriters Laboratories, Inc. for use in Canada ( C-UL Listed).
3. Approved by Fa ctory Mutual Research C orporation (FM Approved).
4. Approved by t he City of New York under MEA 291-04-E. (a). FM Approved for a maximum ceiling temperature of 150°F/66°C.
155°F/68°C Red 200°F/93°C Green
286°F/141°C Blue
155°F/68°C 200°F/93°C
286°F/141°C
Red
Green
Blue
1, 2, 3, 4
1, 2, 3, 4
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
Model/Sprinkler Identification Numbers
TY5151 - Upright 11.2K, 3/4"NPT TY5251 - Pendent 11.2K, 3/4"NPT TY5851 - Upright 11.2K, 1/2"NPT
TY5151 is a redesignation for C5151. TY5251 is a redesignation for C5251,
G1871, and S2531. TY5851 is a redesignation for C5851.
Technical Data
Approvals
UL and C-UL Listed. FM and NYC Ap­proved. (Refer to Table A for complete approval information including corro­sion resistant status. The approvals apply to the service conditions indi­cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi (161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
RefertoTableA
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly...........
. . . . . . Beryllium Nickel w/Teflon†
Bulb(5mmdia.) ....... Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . . Bronze
1/2
1/2
)
3
3 3
3
3 3
Design Criteria
ULandC-ULListing Requirements
The 11.2 K-factor, Model ELO-231B (TY5151, TY5251 & TY5851) Sprin­klers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calculation requirements for light, ordinary, or ex­tra hazard occupancies, as well as high piled storage occupancies (solid piled, palletized,rack storage, bin box, and shelf storage including but not lim­itedtoClass I-IV and Group A plastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231B (TY5151, TY5251 & TY5851) Sprin­klers are to be installed in accordance with the applicable “control mode den­sity/area” guidelines provided by Fac­tory Mutual. (FM guidelines may differ from UL and C-UL Listing criteria.)
(a)
(a)
† Registered trademark of DuPont.
Page 3
TFP342
Temperature rating is indicated on deflector.
*
Pipe thread connections per ISO 7/1 can be provided on
**
special request.
2-13/16"
(71,4 mm)
TYP.
WRENCH
FLATS
**
1/2"
NPT
THREAD
RELIEF
**
3/4"
NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
3/4"
NPT
Page 3 of 6
**
1 2 3 4 5 6
Components:
-
1
Frame
-
2
Seal Assembly
-
3
Cap
-
Bulb
4
-
5
Compression Screw
-
Deflector
6
*
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
TY5851
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
TY5151
PENDENT
TY5251
CROSS
SECTION
FIGURE 1
11.2 K-FACTOR SERIES ELO-231B
UPRIGHT - 3/4" NPT (TY5151), UPRIGHT - 1/2" NPT (TY5851), AND PENDENT - 3/4" NPT (TY5251) SPRINKLERS
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the
Installation
The Series ELO-231B Sprinklers must be installed in accordance with the fol­lowing instructions:
"FITTINGSIDE"
TOWARDS SPRINKLER
FITTING
fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble shouldbe present. The diameter of the
NOTES
WRENCH
RECESS
(END "A")
air bubble is approximately 1/16 inch (1,6 mm) for the 155°F/68°C to 3/32 inch (2,4 mm) for the 286°F/141°C temperature ratings.
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
A leak tight 3/4 inch NPT sprinklerjoint should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi­mum of 30 ft.lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. A leak tight 1/2 inch NPT sprinkler joint should be ob­tained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maximum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT con­nections. Higher levels of torque may distort the sprinkler inlet and cause leakageor impairment of the sprinkler.
Do not attempt to make-up for insuffi­cient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.
The Series ELO-231B Upright and Pendent Sprinklers must be installed in accordance with the following in­structions.
Step 1. Pendent sprinklers a re to be
installed in the pendent position, and upright sprinklers are to be installed in the upright position.
Step 2. With pipe thread sealant ap­plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 3 Sprinkler Wrench (Ref. Figure 2), except that an 8 or 10 inch adjustable Crescent wrench is to be used for wax coated sprinklers. With reference to Figure 1 , the W-Type 3 Sprinkler Wrench or the adjustable Crescent wrench, as applicable is to be applied to the wrench fla t s .
When installing wax coated sprinklers with the adjustable Crescent wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of
Page 4
Page4of6
TFP342
bare metal to the corrosive environ­ment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damag­ing the wax coating. Before wrench tighteningthe sprinkler, the jaws ofthe wrench are to be adjusted to just con­tact the sprinkler wrench flats. After wrenchtightening the sprinkler,loosen the wrench jaws before removing the wrench.
After installation, the sprinkler wrench flats and frame arms must be in­spected and the w ax coating re­touched (repaired) whenever the coat­ing has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gen­tly applying a heated 1/8 inch diameter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap­plied to the wrench flats and frame arms is permitted, and the retouching is to be perf or med only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precautions need to be taken, when handling the heated rod, in order to prevent the installer from being burned.
If attempts to retouch the wax coating with c omplete coverage are unsuc­cessful, additional wax canbe ordered in the form of a wax stick (the end of which is color coded). Only the correct color coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel r od heated as previously de-
scribed, touch the rod to the area re­quiring additional wax with the rod an­gled downward, and then touch the wax stick to the rod approximatel y one-half inch away from the area re­quiring retouching. The wax will melt
and run down onto the sprinkler.
Care and Maintenance
Series ELO-231B Sprinklers must be maintained and serviced in accord­ance with the following instructions:
NOTES
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the af­fected fire protection system must be obtained from the proper authorities and all personnel who maybe affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modi­fied sp rinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid dam­age to the sprinklers — before,during, and after installation. Sprinklers dam­aged by dropping, striking, wrench twist/slippage, or the like, must be re­placed.Also, replace anysprinklerthat has a cracked bulb or that has lost liquid from its bulb (ref. Installation Section Note).
Frequent visual inspections are rec­ommendedtobeinitiallyperformedfor corrosionresistantsprinklers,after the installation has been completed, to verify the long term potential integrity of the sprinkler coatings. Thereafter, annual inspecti ons per NFPA 25 should suffice; however, instead of in­specting from the floor level, a random sampling of close-up visual inspec­tions should be made, so as to better determine the exact sprinkler condi­tion and the long term integrity o f the corrosion resistant coating, as it may beaffected by the corrosive conditions present.
The owner is responsible for the in­spection, testing, and maintenance of their fire protection system and de­vices in compl ianc e with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in­stalling contractor or sprinkler manu­facturer should be contacted relative to any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code.
Limited Warranty
Products manufactured by Tyco Fire & Building Products (TFBP) are war­ranted solely to the original Buyer for ten (10) years against defects in mate­rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten ( 10) years from date of shipment by TFBP. No warranty is given for products or com­ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeensubject to misuse, improper installation, corrosion, or which have not been installed, maintained, modi­fied or repaired in accordance with ap­plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defectiveshall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizesanyperson to assume for it, any other obligation in connection with the sale of products or parts of prod­ucts.TFBPshallnotberesponsiblefor sprinkler system design errors or inac­curate or incomplete information sup­plied by Buyer or Buyer’s repre­sentatives.
In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,special or consequential dam­ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price.
Theforegoingwarrantyismadeinlieu of any and all other warranties, ex­press or implied, including warranties ofmerchantability and fitnessfora par­ticular purpose.
This limited warranty sets forth the ex­clusive remedy for claims based on failure of or defect in products, materi­als or components, whether the claim is made in contract, tort, strict liability or any other legal theory.
Page 5
TFP342
Page 5 of 6
Ordering
Procedure
A Part Number (P/N) is not specified
when ordering sprinklers with thread
connections per ISO 7/1.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies
with NPT Thread Connection:
Specify: (specify SIN), 11.2 K-factor,
(specify temperature rating), Series
ELO-231B Standard Response ( spec-
ify Pendent or Upright) Sprinkler with
(specify finish), P/N (specify from Ta-
ble B).
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001.
Wax Sticks:
(for retouching wrench damaged
wax coating)
Specify: (Specify color) color coded
Wax Stick for retouching (specify tem-
perature rating) temperature rated Se-
ries ELO-231B Sprinklers, P/N (spec-
ify).
P/N 50 — XXX — X — XXX
SPRINKLER
TYPE NATURAL BRASS1
510 9
512 PENDENT
501 UPRIGHT
UPRIGHT
3/4" NPT (TY5151)
3/4" NPT (TY5251)
1/2" NPT (TY5851)
CHROME PLATED 6 7 8
LEAD COATED
WAX OVER LEAD
WAX COATED
286
TABLE B
PRODUCT SYMBOL NUMBER SELECTION
11.2 K-FACTOR SERIE S ELO-231B
STANDARD RESPONSE UPRIGHT AND PENDENT SPRINKLERS
TEMPERATURE
RATING
155°F/68°C155 200°F/93°C200
286°F/141°C
Red for 155°F . . . . . . . . . . . . . P/N 56-065-1-155
Blue for 200°F and
286°F. . . . . . . . . . . . . . . . . P/N 56-065-1-286
NOTES
Each wax stick is suitable for retouch­ing up to twenty-five sprinklers.
The wax used for 286°F sprinklers is the same as for 200°F sprinklers, and, therefore,the 286°F sprinkler is limited tothesamem aximum ceiling tempera­ture as the 2 00°F sprinkler (i.e., 150°F).
Page 6
Page6of6
TFP342
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Loading...