Tyco TY5151, TY5851, TY5251 Series Manual

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series ELO-231B — 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
sentative of all possible corrosive at-
General Description
The 11.2 K-factor, Series ELO-231B, Standard Response, Standard Cover­age, Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprin­klers of the frangible bulb type. They are “standard response - spray sprin­klers” that produc e a hemispherical water distribution pattern below the deflector.
The 11.2 K-factor, ELO-231B Sprin­klersweresubjectedtofullscale,high­piled storage, fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor stand­ard spray sprinklers for the protection of high-piled sto ra ge .
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231B Sprinklers — making their use highly advantageous in high density applications, such as the protection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copperalloy com­ponents used in Series ELO-231B sprinklers beyond that which would otherwise be obtained when exposed to corr osiv e atmospheres. Although wax, lead, and polyester coated sprin­klers have passed the standard corro­sion tests of the applicable approval agencies, the testing is not repre-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail tooperateinafiresituationor cause it to operate prematurely.
mospheres.Consequently,itisrecom­mendedthattheenduserbe consulted with respect to the suitability of these corrosion resistant coatings for any given corrosive environment. The ef­fects of ambient temperature, concen­tration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive na­ture of the chemicalto which the sprin­klers will be exposed.
An upright intermediate level version of the Series ELO-231B Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231B Up­right Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231B Sprinklers can be obtained by utiliz­ing the Series ELO-231B Pendent SprinklerwiththeWS-2Shield.Ifthere is a possibility of the pendent interme­diate level version being exposed to mechanical damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO-231B Upright and P endent Sprinklers de­scribed herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association, in addition to the standardsof any other authorities hav­ing jurisdiction. Failure to do so may
impair the performance of these de­vices.
The owner is responsible for maintain­ing their fire protection system and de­vices in proper operating condition. The installing contractor or manufac­turer should be contacted with any questions.
Installation of Series ELO-231B Pen­dent Sprinklers in recessed escutch­eons will void all spr inkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Page 1 of 6 TFP342
MARCH, 2007
Page2of6
TYPE TEMPERATURE BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
SPRINKLER FINISH
LEAD
COATED
WAX
COATED
TFP342
WAX
OVER LEAD
UPRIGHT
(TY5151
&
TY5851)
PENDENT
(TY5251
NOTES:
1. Listed by U nderwriters Laboratories, Inc. (UL Listed).
2. Listed by U nderwriters Laboratories, Inc. for use in Canada ( C-UL Listed).
3. Approved by Fa ctory Mutual Research C orporation (FM Approved).
4. Approved by t he City of New York under MEA 291-04-E. (a). FM Approved for a maximum ceiling temperature of 150°F/66°C.
155°F/68°C Red 200°F/93°C Green
286°F/141°C Blue
155°F/68°C 200°F/93°C
286°F/141°C
Red
Green
Blue
1, 2, 3, 4
1, 2, 3, 4
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
Model/Sprinkler Identification Numbers
TY5151 - Upright 11.2K, 3/4"NPT TY5251 - Pendent 11.2K, 3/4"NPT TY5851 - Upright 11.2K, 1/2"NPT
TY5151 is a redesignation for C5151. TY5251 is a redesignation for C5251,
G1871, and S2531. TY5851 is a redesignation for C5851.
Technical Data
Approvals
UL and C-UL Listed. FM and NYC Ap­proved. (Refer to Table A for complete approval information including corro­sion resistant status. The approvals apply to the service conditions indi­cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi (161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
RefertoTableA
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly...........
. . . . . . Beryllium Nickel w/Teflon†
Bulb(5mmdia.) ....... Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . . Bronze
1/2
1/2
)
3
3 3
3
3 3
Design Criteria
ULandC-ULListing Requirements
The 11.2 K-factor, Model ELO-231B (TY5151, TY5251 & TY5851) Sprin­klers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calculation requirements for light, ordinary, or ex­tra hazard occupancies, as well as high piled storage occupancies (solid piled, palletized,rack storage, bin box, and shelf storage including but not lim­itedtoClass I-IV and Group A plastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231B (TY5151, TY5251 & TY5851) Sprin­klers are to be installed in accordance with the applicable “control mode den­sity/area” guidelines provided by Fac­tory Mutual. (FM guidelines may differ from UL and C-UL Listing criteria.)
(a)
(a)
† Registered trademark of DuPont.
Loading...
+ 4 hidden pages