Tyco TY-B, TY3153, TY4153, TY3251, TY4251 Series Manual

Worldwide
Contacts
www.tyco-fire.com
Series TY-B — 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response
General Description
The Series TY-B, 5.6 and 8.0 K-fac­tor Upright and Pendent Intermediate Level Sprinklers described in this data sheet are automatic sprinklers of the “standard response” 5 mm frangible bulb type. They are “standard spray” sprinklers intended for use in fire sprin­kler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA requirements). Both the Pendent and Upright Sprinklers produce a hemispherical water distri­bution pattern below the deflector.
Intermediate Level Sprinklers are pri­marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele­vation sprinklers that could operate earlier during a fire. Intermediate Level Sprinklers are also used in other appli­cations such as beneath open gridded catwalks.
Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is not representative of all possible cor-
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Series TY-B Sprinklers described herein must be installed and main­tained in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association, in addition to the stan­dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Sprinkler Identification Numbers
TY3153 . . . .Upright 5.6K, 1/2 in. NPT
TY3251 . . .Pendent 5.6K, 1/2 in. NPT TY415 3 . . . Upright 8.0K, 3/4 in. NPT TY4251 . . .Pendent 8.0K, 3/4 in. NPT
Technical Data
Approvals
UL and C-UL Listed FM and NYC Approved
(Refer to Table A for complete approval information including corrosion resis­tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 GPM/psi½ (80,6 LPM/bar½) K = 8.0 GPM/psi½ (115,2 LPM/bar½)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame ............................Bronze
Button...................... Brass/Copper
Sealing Assembly . . . . . . . . . . . . . . . . Ber yllium
Nickel w/TEFLON
Bulb .............................. Glass
Compression Screw . . . . . . . . . . . . . . . . Bronze
Deflector..........................Copper
Shield ........................Plated Steel
Page 1 of 6 AUGUST 2018 TFP351
TF P351
* **
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)
(55,6 mm)
(FACTORY ASSEMBLED)
(60,3 mm)
Pipe thread connections per ISO 7-1 can be
Temperature rating is indicated on deector,
* **
Pipe thread connections per ISO 7-1 can be
Temperature rating is indicated on deector,
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)(FACTORY ASSEMBLED)
(61,9 mm)
(58,7 mm)
Page 2 of 6
2-3/8"
shield, or adjacent to orice seat on frame.
3-1/2" (88,9 mm) DIA,
SHIELD SCREW
7/16" (11,1 mm) NOMINAL
MAKE-IN
UPRIGHT
SHIELD
WRENCH
FLATS
1/2"
**
NPT
*
provided on special request.
O-RING
WRENCH
FLATS
3-1/2" (88,9 mm) DIA,
PENDENTUPRIGHT
1/2" NPT
**
FIGURE 1
SERIES TY-B UPRIGHT (TY3153) AND PENDENT (T Y3251) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
5.6 K-FACTOR, 1/2 INCH NPT
shield, or adjacent to orice seat on frame.
provided on special request.
7/16" (11,1 mm)
NOMINAL MAKE-IN
2-3/16"
MODEL S2
SHIELD
3-1/2" (88,9 mm) DIA,
SHIELD SCREW
1/2"
2-7/16"
(12,7 mm) NOMINAL
MAKE-IN
3/4" NPT
SERIES TY-B UPRIGHT (TY4153) AND PENDENT (TY4253) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
8.0 K-FACTOR, 3/4 INCH NPT
O-RING
UPRIGHT
SHIELD
*
WRENCH
FLATS
**
FIGURE 2
WRENCH
FLATS
3-1/2" (88,9 mm) DIA,
PENDENTUPRIGHT
3/4" NPT
**
1/2" (12,7 mm)
NOMINAL MAKE-IN
2-5/16"
MODEL S2
SHIELD