Tyco TY-L, TY3113, TY4113, TY3211, TY4211 Series Manual

Page 1
Worldwide
Contacts
www.tyco-fire.com
Series TY-L — 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response
General Description
The Series TY-L, 5.6 and 8.0 K-fac­tor Upright and Pendent Intermedi­ate Level Sprinklers described in this data sheet are automatic sprinklers of the “standard response” solder type. They are “standard spray” sprin­klers intended for use in fire sprinkler systems designed in accordance with the standard installation rules rec­ognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA requirements). Both the Pen dent and Upright Sprinklers produce a hemispherical water distri­bution pattern below the deflector.
Intermediate Level Sprinklers are pri­marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele­vation sprinklers that could operate earlier during a fire. Intermediate Level Sprinklers are also used in other appli­cations such as beneath open gridded catwalks.
NOTICE
The Series TY-L Sprinklers described herein must be installed and main­tained in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association, in addition to the stan­dards of any other authorities hav ing jurisdiction. Failure to do so may impair the performance of these devices.
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Number (SIN)
TY3113 – Upright 5.6K, 1/2”NPT TY3211 – Pendent 5.6K, 1/2”NPT TY4113 – Upright 8.0K, 3/4”NPT TY4211 – Pendent 8.0K, 3 /4”NPT
TY3113 is a redesignation for S1809 and G3253
TY3211 is a redesignation for S1801 and G3112
TY4113 is a redesignation for S1822 and G3153
TY4211 is a redesignation for S1811 and G3102
Technical Data
Approvals
UL and C-UL Listed FM Approved (Refer to Table A for complete approval information including corrosion resistant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 gpm/psi½ (80,6 lpm/bar½) K = 8.0 gpm/psi½ (11 5, 2 l p m /ba r½)
Temperature Ratings
Refer to Table A
Finishes
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Button . . . . . . . . . . . Bronze w/ TEFLON
Ejection Spring . . . . . . . . . . . . . . Stainless Steel
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Hook ..................... Bronze/MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Fusible Element . . . . . . . . . . . . .Solder, Copper,
Stainless Steel
Page 1 of 4 AUGUST 2018 TFP350
Page 2
TFP350
(68,3 mm)
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)(FACTORY ASSEMBLED)
3" (76,2 mm) DIA,
(66,7 mm)
(FACTORY ASSEMBLED)
3" (76,2 mm) DIA,
(69,9 mm)
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)
(68,3 mm)
Page 2 of 4
1/2" NPT
2-11/16"
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
UPRIGHT PENDENT
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH FLANGES
WRENCH
AREA
MODEL S5
PENDENT
SHIELD
WITH
O-RINGS
7/16" (11,1 mm) NOMINAL
MAKE-IN
FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT ( TY3113) AND PENDENT (TY3211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT
3/4" NPT
2-3/4"
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH FLANGES
MODEL S5
PENDENT
SHIELD
WITH
O-RINGS
1/2" (12,7 mm) NOMINAL
MAKE-IN
2-5/8"
2-11/16"
WRENCH
AREA
UPRIGHT PENDENT
FIGURE 2
STANDARD RESPONSE SERIES TY-L UPRIGHT ( TY4113) AND PENDENT (TY4211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT
SPRINKLER FINISH
K = 5.6 UPRIGHT TY3113
K = 5.6 PENDENT TY3211
TEM P.
RATI NG
16 5°F (74° C ) UNPAINTED
280° F (138°C) BLUE
NOTES
1. Listed by Under write rs Lab orator y, Inc. (UL).
2. Listed by Unde rwriters L abora tory, Inc. for use in Ca nada (C-UL)
3. A pprove d by Factor y Mutual Research Corporation.
FRAME COLOR
CODE
NATURAL BRASS NATURAL BRASS
K = 8.0 UPRIGHT TY4113
K = 8.0 PENDENT TY4211
1, 2, 3212°F (100°C) WHITE
TABL E A
LABORATORY LISTINGS AND APPROVALS
Page 3
TFP350
WRENCH
Page 3 of 4
Operation
A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached, the alloy melts, the balls are forced toward each other releasing the tension mech­anism, allowing the sprinkler to operate.
Design Criteria
The Series TY-L Pendent and Upright Intermediate Level Sprinklers are intended for fire protection systems designed in accordance with the stan­dard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM Global’s Loss Prevention Data Sheets).
Installation
The Series TY-L Sprinklers must be installed in accordance with this section.
NOTE: A leak-tight 1/2 in. NPT sprin­kler joint should be obtained by apply­ing a minimum-to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). A leak tight 3/4 in. NPT sprinkler joint should be obtained by applying a minimum­to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N·m). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Upright Sprinklers
The Series TY-L Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions.
Step 1. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1 or 2, the W-Type 9 Sprinkler Wrench is to be applied to the wrenching area.
Pendent Sprinklers
The Series TY-L Intermediate Level Pendent Sprinklers must be installed in accordance with the following in structions.
Step 1. Roll one of the two required O-Rings over the sprinkler threads until it seats against the sprinkler wrenching area flange as shown in Figure 1 or 2, as applicable.
Step 2. Install the Shield over the sprin­kler threads, and then roll the second O-Ring over the sprinkler threads until it is seated firmly against the Shield.
Step 3. With pipe thread sealant ap plied, hand tighten the sprinkler into the sprinkler fitting.
Step 4. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure 3). The wrench is to be applied to the sprinkler wrenching area shown in Figure 1 or 2, as applicable.
When installed correctly, the O-Rings will be slightly compressed and the Shield will be held firmly in place.
RECESS
FIGURE 3
W-TYPE 9 SPRINKLER
WRENCH
Care and Maintenance
The Series TY-L Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modi­fied or over-heated sprinklers must be replaced.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso­ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install­ing contractor or product manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
Page 4
TFP350
Page 4 of 4
P/N 53 — XXX — X — XXX
SIN
253 5.6K UPRIGHT (1/2 in. NPT) T Y311 3
153 8.0K UPRIGHT (3/4 in. NPT) T Y4113
PART NUMBER SELECTION
SERIES TY-L UPRIGHT INTERMEDIATE LEVEL SPRINKLERS
(UPRIGHT SHIELD INCLUDED WITH SPRINKLER)
P/N 51 — XXX — X — XXX
SIN
112 5.6K PENDENT (1/2 in. NPT) T Y3211
102 8.0K PENDENT (3/4 in. NPT) T Y42 11
PART NUMBER SELECTION
SERIES TY-L PENDENT SPRINKLERS
(MODEL S5 PENDENT SHIELD & O-RING MUST BE SEPARATELY ORDERED)
1 NATURAL BRASS
TABL E B
1 NATURAL BRASS
TABL E C
SPRINKLER
SPRINKLER
TEMPERATURE
RATI NG
165 16 5°F (74° C )
212 212°F (100°C)
280 280° F (138°C)
TEMPERATURE
RATI NG
165 16 5°F (74° C )
212 212°F (100°C)
280 280° F (138°C)
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product name and Part Number (P/N).
Upright Sprinkler Assemblies with Shield and NPT Thread Connections
Specify: (Specify Model/SIN), Stan­dard Response, (specify K-factor), (specify temperature rating), Series TY-L Upright Intermediate Level Sprin­klers with natural brass finish, P/N (specify from Table B)
Pendent Sprinkler Assemblies with (Shield Ordered Separately) and NPT Thread Connections
Specify: (Specify Model/SIN), Stan­dard Response, (specify K-factor), (specify temperature rating), Series TY-L Pendent Sprinkler with natural brass finish, P/N (specify from Table C)
Model S5 Pendent Shield Package
Specify: S5 Pendent Shield Package (one shield / two O-Rings) for use with (specify 1/2 in. NPT or 3/4 in. NPT) Series TY-L Pendent Sprinklers, P/N (specify)
1/2 in. NPT ...................56-015-6-802
3/4 in. NPT ...................56-015-6-803
Sprinkler Wrench
Specify: W-Type 9 Sprinkler Wrench, P/N 56-000-1-849
1400 Pennbr ook Par kway, L ansd ale, PA 19446 | Tele phon e +1-215-36 2-07 00
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; MONEL is a reg istered tradema rk of Special Met als Corporatio n; TEFLON is a regi stered tradema rk of DuPont
Loading...