Series TY-L — 5.6 and 8.0 K-factor
Upright and Pendent Intermediate Level Sprinklers
Standard Response
General
Description
The Series TY-L, 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers described in this
data sheet are automatic sprinklers
of the “standard response” solder
type. They are “standard spray” sprinklers intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA requirements). Both
the Pen dent and Upright Sprinklers
produce a hemispherical water distribution pattern below the deflector.
Intermediate Level Sprinklers are primarily designed for use in rack storage
sprinkler systems where their thermally
sensitive elements must be shielded
from the water spray of higher elevation sprinklers that could operate
earlier during a fire. Intermediate Level
Sprinklers are also used in other applications such as beneath open gridded
catwalks.
NOTICE
The Series TY-L Sprinklers described
herein must be installed and maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association, in addition to the standards of any other authorities hav ing
jurisdiction. Failure to do so may impair
the performance of these devices.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY3113 – Upright 5.6K, 1/2”NPT
TY3211 – Pendent 5.6K, 1/2”NPT
TY4113 – Upright 8.0K, 3/4”NPT
TY4211 – Pendent 8.0K, 3 /4”NPT
TY3113 is a redesignation for S1809
and G3253
TY3211 is a redesignation for S1801
and G3112
TY4113 is a redesignation for S1822
and G3153
TY4211 is a redesignation for S1811
and G3102
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
(Refer to Table A for complete approval
information including corrosion resistant
status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 gpm/psi½ (80,6 lpm/bar½)
K = 8.0 gpm/psi½ (11 5, 2 l p m /ba r½)
Temperature Ratings
Refer to Table A
Finishes
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Button . . . . . . . . . . . Bronze w/ TEFLON
Ejection Spring . . . . . . . . . . . . . . Stainless Steel
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Hook ..................... Bronze/MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Fusible Element . . . . . . . . . . . . .Solder, Copper,
Stainless Steel
Page 1 of 4 AUGUST 2018 TFP350
TFP350
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)(FACTORY ASSEMBLED)
3" (76,2 mm) DIA,
(FACTORY ASSEMBLED)
3" (76,2 mm) DIA,
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)
Page 2 of 4
1/2" NPT
2-11/16"
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
UPRIGHT PENDENT
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
WRENCH
AREA
MODEL S5
PENDENT
SHIELD
WITH
O-RINGS
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT ( TY3113) AND PENDENT (TY3211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT
3/4" NPT
2-3/4"
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
MODEL S5
PENDENT
SHIELD
WITH
O-RINGS
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
2-5/8"
2-11/16"
WRENCH
AREA
UPRIGHT PENDENT
FIGURE 2
STANDARD RESPONSE SERIES TY-L UPRIGHT ( TY4113) AND PENDENT (TY4211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT
SPRINKLER FINISH
K = 5.6 UPRIGHT TY3113
K = 5.6 PENDENT TY3211
TEM P.
RATI NG
16 5°F (74° C ) UNPAINTED
280° F (138°C) BLUE
NOTES
1. Listed by Under write rs Lab orator y, Inc. (UL).
2. Listed by Unde rwriters L abora tory, Inc. for use in Ca nada (C-UL)
3. A pprove d by Factor y Mutual Research Corporation.
FRAME COLOR
CODE
NATURAL BRASS NATURAL BRASS
K = 8.0 UPRIGHT TY4113
K = 8.0 PENDENT TY4211
1, 2, 3212°F (100°C) WHITE
TABL E A