Tyco TY-FRB Series, TY-FRB 5.6, TY-FRB 8.0, TY3631, TY4631 Quick Response

Series TY-FRB – 5.6 and 8.0 K-factor Conventional (Old Style) Sprinklers Quick Response
Worldwide
Contacts
www.tyco-fire.com
General Description
The TYCO Series TY-FRB, 5.6 and
8.0 K-factor, Conventional Sprinklers described in this technical data sheet are Quick Response, Standard Cover­age, decorative 3 mm glass bulb type spray sprinklers. These sprinklers are intended to be installed either pendent or upright and, in either position, produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and approximately 50% of the discharge directed downwards.
Conventional sprinklers are generally used with Ordinary and Extra High Hazard Class Systems, as defined by the automatic sprinkler system instal­lation rules of the country and author­ity having jurisdiction. The National Fire Protection Association (NFPA) permits the use of “Old Style Sprinklers” where special construction features require a unique water distribution, for the pro­tection of fur vaults, or to replace similar sprinklers that had been installed prior to 1955.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli­cable Approval agencies, the testing is not representative of all possible cor­rosive atmospheres. Consequently,
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and installation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The TYCO Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the NFPA, in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Numbers (SINs)
TY3631 – 5.6K, 1/2” NPT TY4631 – 8.0K, 3/4” NPT
Technical Data
Approvals
UL and C-UL Listed LPCB Approved VdS Approved NYC Approved
(Refer to Table A for complete approval information.)
Sprinklers with Polyester Finish are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi K=8.0 gpm/psi
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . .Brass/Copper
Sealing Assembly ..Beryllium Nickel w /TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
1/2
(80,6 lpm/bar
1/2
(11 5,2 l p m / b a r
1/2
1/2
)
)
Page 1 of 4 JANUARY 2017 TFP666
TFP666
* **
*
PENDENT
PENDENT
SHOWN UPRIGHT
SHOWN UPRIGHT
Pipe thread connections per
Temperature rating is
(55,6 mm)
Components:
(END "A" USED FOR
3/4" NPT MODELS)
Page 2 of 4
2-3/16"
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Design Criteria
The TYCO Series TY-FRB Conventional Sprinklers are intended for fire protec­tion systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements). The Series TY-FRB Conventional Sprinklers are only for non-recessed applications.
indicated on Deector or adjacent to orice seat on Frame.
ESCUTCHEON
PLATE SEATING
SURFACE
1-1/2"
(38,1 mm)
-
1
Frame
-
2
Button
-
3
Sealing Assembly
SURFACE
1-1/2"
(38,1 mm)
3/4"
NPT
SHOWN
4 5
****
1/2" NPT
SHOWN
ISO 7-1 can be provided on special request.
7/16" (11,1 mm)
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
6
5
4
2
3
1
ESCUTCHEON
PLATE SEATING
*
2-1/4"
(57,2 mm)
FIGURE 1
SERIES TY-FRB 5.6 K-FACTOR (TY36 31) AND 8.0 K-FACTOR (TY4631)
QUICK RESPONSE CONVENTIONAL SPRINKLERS
Installation
The Series TY-FRB Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). A maximum of 21 ft.-lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. A leak-tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.-lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.-lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Step 1. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 2). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the Wrench Flats.
(END "B" USED FOR
-
Bulb
-
Compression Screw
-
Deector6
1/2" (12,7 mm)
WRENCH RECESS
*
NOMINAL
MAKE-IN
WRENCH
FLATS
CROSS SECTION
WRENCH RECESS
1/2" NPT MODELS)
FIGURE 2 W-T Y PE 6
SPRINKLER WRENCH
6
5
4
2
3
1