Tyco TY3133, TY-FRB Series, TY4133, TY4231, TY3231 User Manual

Page 1
Worldwide
Contacts
www.tyco-fire.com
Series TY-FRB – 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Quick Response
General Description
TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are auto­matic sprinklers of the quick response 3 mm frangible bulb type. They are standard spray sprinklers intended for use in fire sprinkler systems designed in accordance with the standard instal­lation rules recognized by the appli­cable listing or approval agency (e.g., UL Listing is based on NFPA require­ments). Both the pendent and upright sprinklers produce a hemispherical water distribution pattern below the deflector.
Intermediate level sprinklers are pri­marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele­vation sprinklers that could operate earlier during a fire. Intermediate level sprinklers are also used in other appli­cations such as beneath open gridded catwalks.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is not representative of all possible cor-
rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Numbers (SINs)
TY3133 – Upright, 5.6K, 1/2 in. NPT TY3231 – Pendent, 5.6K, 1/2 in. NPT TY4133 – Upright, 8.0K, 3/4 in. NPT TY4231 – Pendent, 8.0K, 3/4 in. NPT
Refer to Technical Data Sheet TFP2300 for warnings per taining to regulatory and health information.
IMPORTANT
Page 1 of 6 AUGUST 2018 TFP356
Page 2
TFP356
* **
FIELD ASSEMBLED PENDENTFACTORY ASSEMBLED UPRIGHT
(55,6 mm)
(60,3 mm)
* **
FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT
(61,9 mm)
(58,7 mm)
Page 2 of 6
Temperature rating is indicated on Deector, Shield or adjacent to orice seat on frame
3-1/2" (88,9 mm) DIA.
7/16"
2-3/8"
(11,1 mm) NOMINAL
MAKE-IN
Pipe thread connections per ISO 7-1 can be provided on special request
FACTORY
ASSEMBLED
UPRIGHT SHIELD
WITH SCREW
WRENCH
FLATS
*
FIELD ASSEMBLED
MODEL S2 SHIELD
(SEE INSTALLATION
Order Pendent Series TY-FRB Sprinkler and Model S2 Shield Package separately for pendent assembly (Ref. Ordering Procedure)
3-1/2" (88,9 mm) DIA.
1/2" NPT
SECTION)
DEFLECTOR
**
*
O-RING
PENDENT
SERIES TY-FRB
FIGURE 1
SERIES TY-FRB UPRIGHT (TY3133) & PENDENT (TY3231) INTERMEDIATE LEVEL SPRINKLERS
5.6K, QUICK RESPONSE, 1/2 INCH NPT
Temperature rating is indicated on Deector, Shield or adjacent to orice seat on frame
3-1/2" (88,9 mm) DIA.
Pipe thread connections per ISO 7-1 can be provided on special request
Order Pendent Series TY-FRB Sprinkler and Model S2 Shield Package separately for pendent assembly (Ref. Ordering Procedure)
3-1/2" (88,9 mm) DIA.
2-3/16"
FACTORY
ASSEMBLED
UPRIGHT SHIELD
WITH SCREW
WRENCH
FLATS
2-7/16"
1/2" (12,7 mm) NOMINAL
MAKE-IN
SERIES TY-FRB UPRIGHT (TY4133) & PENDENT (TY4231) INTERMEDIATE LEVEL SPRINKLERS
8.0K, QUICK RESPONSE, 3/4 INCH NPT
Maximum Working Pressure
Technical Data
Approvals
UL and C-UL Listed FM and NYC Approved
(Refer to Table A for complete approval information, including corrosion-resistant status.)
175 psi (12,1 bar)
Discharge Coefficients
K=5.6 GPM/psi½ (80,6 LPM/bar½) K=8.0 GPM/psi½ (115,2 LPM/bar½)
Temperature Ratings
Refer to Table A
Finishes
Sprinklers: Refer to Table A
*
FIELD ASSEMBLED
MODEL S2 SHIELD
(SEE INSTALLATION
FIGURE 2
3/4" NPT
SECTION)
DEFLECTOR
**
O-RING
2-5/16"
PENDENT
SERIES TY-FRB
*
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly ..Ber yllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Shield . . . . . . . . . . . . . . . . . . . . . . . .Plated Steel
Page 3
TFP356
Page 3 of 6
K-FACTOR
5.6
1/2 in. NPT
SPRINKLER
TYPE
UPRIGHT
(TY3133)
UPRIGHT
(TY3231)
PENDENT
( T Y413 3 )
TEMPERATURE
RATING
135 °F (57 °C) Orange
155 °F (68 °C) Red
175 °F (79 °C) Yel l ow
200 °F (93 °C) Green
286 °F (141 °C) Blue
135 °F (57 °C) Orange
155 °F (68 °C) Red
175 °F (79 °C) Yel l ow
200 °F (93 °C) Green
286 °F (141 °C) Blue
135 °F (57 °C) Orange
155 °F (68 °C) Red
175 °F (79 °C) Yel l ow
200 °F (93 °C) Green
BULB
LIQUID COLOR
SPRINKLER FINISH
NATURAL
BRASS*
1, 2, 3, 4
LEAD
COATE D**
1, 2, 3, 4
N/A
1, 2, 3, 4
8.0
3/4 in. NPT
PENDENT
(TY4231)
Notes:
1. UL Liste d as quick re sponse s prinklers
2. C-UL Liste d as quick re sponse s prinklers
3. F M Approved as quick re sponse sprinkle rs
4. A pproved by t he City of N ew York (NYC) under MEA 354- 01-E * With zin c plated shield ** Whe re Lead Coated sprinklers a re noted to be U L and C-UL Listed, th e sprinkl ers are Listed as co rrosio n-resistant spr inkler s;
where Lead Coated sprinkl ers are no ted to be FM App roved, the s prinkle rs are Ap proved as corrosio n-resi stant sprinkler s.
N/A – Not App licable
286 °F (141 °C) Blue
135 °F (57 °C) Orange
155 °F (68 °C) Red
175 °F (79 °C) Yel l ow
200 °F (93 °C) Green
286 °F (141 °C) Blue
N/A
TABL E A
5.6K & 8 .0K SERIES TY-FRB UPRIGHT & PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE LABORATORY LISTINGS AND APPROVALS
Design Criteria
TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are intended for fire protection systems
designed in accordance with the stan­dard installation rules recognized by the applicable listing or approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM Approvals’ Loss Prevention Data Sheets).
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Page 4
TFP356
(END "A" USED FOR
3/4" NPT MODELS)
Page 4 of 6
WRENCH RECESS
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
FIGURE 3 W-T Y PE 6
SPRINKLER WRENCH
Installation
TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be installed in accordance with this section.
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286°F (141°C) tempera­ture ratings.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 Nm). A leak-tight 3/4 in. NPT sprinkler joint should be obtained by applying a minimum-to­maximum torque of 10 to 20 lb-ft (13,4 to 26,8 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Upright Sprinklers
The Series TY-FRB Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions:
Step 1. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats.
Pendent Sprinklers
The Series TY-FRB Intermediate Level Pendent Sprinklers must be installed in accordance with the following instructions:
Step 1. Thread the Model S2 Shield onto the sprinkler threads with the stamped markings toward the deflector and just to the end of the threads. The final assembly step is easier to accom­plish if the shield is not disengaged by continuing to turn the shield past the threads.
Step 2. Roll the O-ring over the sprin­kler threads until it seats against the shield.
Step 3. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 4. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats.
Step 5. Rotate the Model S2 Shield clockwise (looking up) so that it slightly compresses the O-ring between the shield and sprinkler fitting.
Care and Maintenance
TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal­lation section for additional information.
Frequent visual inspections are rec­ommended to be initially performed for corrosion resistant coated sprin­klers, after the installation has been completed, to verify the integrity of the corrosion-resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan­dards of any other authorities having jurisdiction. Contact the installing con­tractor or sprinkler manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
Page 5
P/N 57 — XXX — X — XXX
TFP356
Page 5 of 6
1
7
SPRINKLER
FINISH
NAT URAL
BRASS
LEAD
CO ATE D
SIN
333 5.6K UPRIGHT (1/2 in. NPT) TY3133
343 8.0K UPRIGHT (3/4 in. NPT) T Y4133
TABL E B
SERIES TY-FRB UPRIGHT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
PART NUMBER SELECTION
P/N 57 — XXX — X — XXX
1
7
SPRINKLER
FINISH
NAT URAL
BRASS
LEAD
CO ATE D
SIN
371 5.6K PENDENT (1/2 in. NPT ) TY3231
391 8.0K PENDENT (3/4 in. NPT) TY4231
TEMPERATURE
RATING
135 13 °F (57°C)
155 155° F (68°C)
175 17 5° F (7 9°C )
200 200°F (93°C)
286 28 6° F (141°C)
TEMPERATURE
RATING
135 135°F (57°C)
155 155° F (68°C)
SERIES TY-FRB PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
(MODEL S2 PENDENT SHIELD MUST BE SEPARATELY ORDERED)
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name, including description and part number (P/N).
TABL E C
PART NUMBER SELECTION
Upright Sprinkler Assemblies with NPT Thread Connections (with Shield)
Specify: Series TY-FRB Upright Inter­mediate Level Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Table B)
Pendent Sprinkler Assemblies with NPT Thread Connections (Shield ordered separately)
Specify: Series TY-FRB Pendent Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Tabl e C)
175 17 5° F (7 9°C )
200 200°F (93°C)
286 28 6° F (141°C)
Model S2 Sprinkler Shield
Includes S2 Shield and one O-Ring.
Specify: Model S2 Sprinkler Shield, (specify) Thread Size, P/N (specify):
1/2 in. NPT . . . . . . . . . . . . . . . . . . 56- 070-9 -332
3/4 in. NPT . . . . . . . . . . . . . . . . . . 56- 070-9 -342
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Page 6
TFP356
Page 6 of 6
1400 Pennbro ok Park way, Lans dale, PA 19446 | Telephone +1-215- 362- 0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; TEFLON is a regi stered tradema rk of DuPont
Loading...