Tyco TY323, TY313, TY-FRB Series Quick Response

Page 1
Worldwide
Contacts
www.tyco-re.com
Worldwide
Contacts
www.tyco-fire.com
Series TY-FRB — 5.6 K-factor Upright and Pendent Intermediate Level Sprinklers Quick Response
General Description
The Series TY-FRB, 5.6 K-factor Up­right and Pendent Intermediate Level Sprinklers described in this data sheet are automatic sprinklers of the “quick response” 3 mm frangible bulb type. They are “standard spray” sprinklers intended for use in fire sprinkler sys­tems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA requirements). Both the Up­right and Pendent Sprinklers produce a hemispherical water distribution pat­tern below the deflector.
Intermediate Level Sprinklers are pri­marily designed for use in rack stor­age sprinkler systems where their thermally sensitive elements must be shielded from the water spray of high­er elevation sprinklers that could op­erate earlier during a fire. Intermediate Level Sprinklers are also used in oth­er applications such as beneath open gridded catwalks.
For additional Series TY-FRB Sprin­kler information, see Technical Data Sheet TFP172. For additional Guard and Shield information, see Technical Data Sheet TFP780.
NOTICE
The Series TY-FRB Sprinklers de­scribed herein must be installed and maintained in compliance with this document, as well as with the appli­cable standards of the National Fire
IMPO R TA N T
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condi­tion. The installing contractor or sprin­kler manufacturer should be contact­ed with any questions.
Sprinkler Identification Numbers
TY313 . . . . . . . . . . Upright 5.6K, 1/2” NPT
TY323 ..........Pendent 5.6K, 1/2” NPT
Technical Data
Approvals
UL and C-UL Listed FM Approved
(Refer to Table A for complete approv­al information.)
Maximum Working Pressure
175 psi (12,1 bar) 250 psi (17,2 bar)*
* The Maximum Working Pressure of 250 psi (17,2
bar) only applies to the listing by Underwriters Laboratory.
Discharge Coefficient
1/2
K=5.6 GPM/psi
Temperature Ratings
Refer to Table A
Finishes
TY-FRB Sprinkler . . . . . . . . . . . . . . . Brass
G1/S1 Guard with Shield .....Red or Zinc
G1 Guard .................Red or Zinc
S2 Shield ...................... Zinc
(80,6 LPM/bar
1/2
)
Physical Characteristics
Frame ....................... Bronze
Button................. Brass/Copper
Sealing Assembly....... Stainless Steel
w/TEFLON
Bulb ......................... Glass
Compression Screw. . . . . . . . . . . . Bronze
Deflector.....................Copper
G1 and G1/S1 Guard ...Painted or Plated
Steel
S2 Shield ................ Plated Steel
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Page 1 of 6 MA R CH 2013 TFP357
Page 2
TFP357
*
(73,0 mm)
NOMINAL MAKE-IN
3-1/2" DIA.
ordered seperately.
Pipe thread
*
(73,0 mm)
NOMINAL MAKE-IN
ordered seperately.
Pipe thread
FACTORY ASSEMBLED
4" DIA.
*
3-1/2" DIA.
ordered seperately.
Pipe thread
(50,8 mm)
Page 2 of 6
SHIELD
3"
(76,2 mm)
2-3/8"
(60,3 mm)
7/16" (11,1 mm)
SERIES TY-FRB UPRIGHT (TY313) INTERMEDIATE LEVEL SPRINKLER
7/16" (11,1 mm)
2-3/8"
(60,3 mm)
3"
(76,2 mm)
MODEL G1/S1
GUARD WITH
SHIELD
TY-FRB
TY-FRB
MODEL G1
GUARD
**
MODEL S2
SHIELD WITH
**
(101,6 mm)
2-7/8"
1/2" NPT
*
GUARD
BAR
GUARD
BASE PLATE
GUARD CLIP
ENGAGED
AGAINST GUARD
BASE PLATES
SPRINKLER
THREAD RELIEF
ENGAGED BY GUARD
BASE PLATES
FIGURE 1
WITH G1/S1 GUARD WITH SHIELD
O-RING
(88,9 mm)
2-7/8"
1/2" NPT
*
SPRINKLER
THREAD RELIEF
ENGAGED BY GUARD
BASE PLATES
GUARD CLIP
ENGAGED
AGAINST GUARD
BASE PLATES
GUARD
BASE PLATE
GUARD
BAR
connections per ISO 7-1 can be provided on special request.
Temperature
**
rating is indicated on Deector.
TY-FRB Sprinkler and G1/S1 Guard with Shield are
connections per ISO 7-1 can be provided on special request.
Temperature
**
rating is indicated on Deector.
TY-FRB Sprinkler, G1 Guard, and S2 Shield with O-Ring are
SERIES TY-FRB PENDENT (TY323 ) INTERMEDIATE LEVEL SPRINKLER
FIGURE 2
WITH S2 SHIELD AND G1 GUARD
7/16" (11,1 mm)
NOMINAL MAKE-IN
2"
SHIELD WITH
MODEL S2
O-RING
(88,9 mm)
1/2" NPT
*
SPRINKLER
WRENCH
FLATS
TY-FRB
**
**
connections per ISO 7-1 can be provided on special request.
Temperature rating is indicated on Deector.
TY-FRB Sprinkler and S2 Shield with O-Ring are
FIGURE 3
SERIES TY-FRB PENDENT (TY323 ) INTERMEDIATE LEVEL SPRINKLER
WITH S2 SHIELD
Page 3
TFP357
WITH SPRINKLER PROPERLY INSTALLED,
CAREFULLY SPREAD BASE PLATES APART AND FIT
PLATES UNTIL SNUG
PLATES
INSTALLATION
CLIP FULLY
TOWARD BASE PLATES UNTIL FULLY ENGAGED
Page 3 of 6
K TYPE TE M P.
5.6 1/2” NPT
NOTES :
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
GUARD ONTO SPRINKLER ENGAGING SPRINKLER
THREAD RELIEF BY BASE PLATES
BASE
PLATES
CLIP
ADJACENT
BAR
MODEL
G1 GUARD
SWIVEL CLIPS OVER ADJACENT
BARS AND SLIDE TOWARD BASE
SERIES TY-FRB
PENDENT
SPRINKLER
BULB
LIQUID
135° F (57 °C ) Orange
UPRIGHT
(T Y313 )
with Guard/
Shield
(G1/S1)
PENDENT
(TY323)
with Guard/
Shield
(G1/S2) or
Shield only
(S2)
155° F (68° C) Red
175°F ( 7 9 °C) Yel l ow
200°F (93°C) Green
28 6°F (141°C ) Blue
135° F (57 °C ) Orange
155° F (68° C) Red
175°F ( 7 9 °C) Yel l ow
200°F (93°C) Green
28 6°F (141°C ) Blue
TABL E A
LABORATORY LISTINGS AND APPROVALS
MODEL
G1/S1 GUARD
WITH SHIELD
SERIES TY-FRB
MODEL
S2 SHIELD
FIRST
CLIP FULLY
ENGAGED
BAR
SLOT
INSTALLATION TOOL
(SHIPPED WITH
GUARDS)
UPRIGHT
SPRINKLER
FIRST
CLIP FULLY
ENGAGED
WITH INSTALLATION TOOL APPLIED OVER
ADJACENT BARS, PRESS SECOND CLIP
SPRINKLER FINISH
NATURAL BRASS
1, 2, 3
INSTALLATION
TOOL
CLIP
SECOND
ENGAGED
BASE
TOOL
CLIP
A PLIER MAY BE
USED
INSTALLATION PROCEDURES FOR MODEL G1 GUARD AND S2 SHIELD (PENDENT SPRINKLER )
FIGURE 4
AND MODEL G1/S1 GUARD WITH SHIELD (UPRIGHT SPRINKLER)
Page 4
TFP357
WRENCH RECESS
Page 4 of 6
Design Criteria
The Series TY-FRB, 5.6 K-factor Up­right and Pendent Intermediate Level Sprinklers are intended for fire pro­tection systems designed in accor­dance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Pre­vention Data Sheets).
Installation
The Series TY-FRB, 5.6 K-factor Up­right and Pendent Intermediate Level Sprinklers must be installed in accor­dance with this section:
General Instruction
Do not install any bulb type sprin­kler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diam­eter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Upright Sprinklers
The Series TY-FRB Intermediate Lev­el Upright Sprinklers must be installed in accordance with the following instructions.
Step 1. With pipe thread sealant ap­plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 5). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats.
Step 3. Mount the Model G1/S1 Guard with Shield on the sprinkler. With the Clips loose, spread the two halves of the Sprinkler Guard enough to pass by the sprinkler deflector from the side.
Step 4. Spread the two halves of the Sprinkler Base Plates enough to pass over the sprinkler Thread Relief portion of the sprinkler. (Refer to Figure 1.)
Step 5. With the Sprinkler Guard po­sitioned on the Thread Relief portion of the sprinkler, engage the Bars with Clips from opposing Guard Halves, then slide the Clips up until they are seated against the Base Plates, com­pleting the installation as shown in Figure 1 and 4.
NOTE: To help assist with the sliding of the Clips, use the Guard Installation Tool as shown in Figure 4. Additional­ly, pliers can be used to facilitate the final seating of the Clips.
NOTICE
The Clips must seat against the Base Plates to be fully seated in order to complete the installation. The Model G1/S1 Guard with Shield may be lo­cated in any position relative to the sprinkler frame arms.
Pendent Sprinklers
The Series TY-FRB Intermediate Lev­el Pendent Sprinklers must be in­stalled in accordance with the follow­ing instructions.
Step A. Thread the S2 Shield on to the sprinkler threads with the stamped markings toward the deflector and just to the end of the threads. The fi­nal assembly step is easier to accom­plish if the Shield is not disengaged by continuing to turn the Shield past the threads.
Step B. Roll the O-Ring over the sprinkler threads until it seats against the Shield.
Step C. With pipe thread sealant ap­plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step D. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 5). With reference to Figure 2 or 3, the W­Type 6 Sprinkler Wrench is to be ap­plied to the wrench flats.
Step E. Rotate the S2 Shield clock­wise (looking up) so that it slightly compresses the O-Ring between the Shield and sprinkler fitting.
Note: Installation of the S2 Shield only is completed at this point (Ref. Figure
3). If installing a G1 Guard, proceed to the next step.
Step F. Mount the Model G1 Guard on the sprinkler. With the Clips loose, spread the two halves of the Sprinkler Guard enough to pass by the sprinkler deflector from the side.
Step G. Spread the two halves of the Sprinkler Base Plates enough to pass over the sprinkler Thread Relief portion of the sprinkler. (Refer to Figure 2.)
Step H. With the Sprinkler Guard po­sitioned on the Thread Relief portion of the sprinkler, engage the Bars with Clips from opposing Guard Halves, then slide the Clips up until they are seated against the Base Plates, com­pleting the installation as shown in Figure 2 and 4.
NOTE: To help assist with the sliding of the Clips, use the Guard Installation Tool as shown in Figure 4. Additional­ly, pliers can be used to facilitate the final seating of the Clips.
NOTICE
The Clips must seat against the Base Plates to be fully seated in order to complete the installation. The Model G1 Guard may be located in any po­sition relative to the sprinkler frame arms.
(USE ONLY
END "A")
FIGURE 5
W-TYPE 6 SPRINKLER
WRENCH
Page 5
TFP357
Page 5 of 6
P/N 77 – XXX – X – XXX
TEMPERATURE
RATI NG
370 5.6K UPRIGHT2 (1/2 ˝ N PT )
SIN
1
TY 313
1 NATURAL BRASS
SPRINKLER
FINISH
135 135°F (57°C )
155 155°F (68°C)
371 5.6K PENDENT3 (1/2 ˝ N PT )
1. Use suffix “I” for ISO 7-1 connection, for example, 77-370-1-175-I
2. Upright G1/S1 Guard with Shield Assembly must be ordered se pa rate ly.
3. Model S2 Pendent Shield with O -Ring, and Optional Model G1 Guard must be ordered separately.
1
TY323
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Care and Maintenance
The Series TY-FRB, 5.6 K-factor Up­right and Pendent Intermediate Lev­el Sprinklers must be maintained and serviced in accordance with this section:
Before closing a fire protection sys­tem main control valve for mainte­nance work on the fire protection sys­tem that it controls, permission to shut down the affected fire protection sys­tem must be obtained from the prop-
vices in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association (e.g., NFPA 25), in ad­dition to the standards of any other authorities having jurisdiction. The in­stalling contractor or sprinkler manu­facturer should be contacted relative to any questions.
It is recommended that automatic sprinkler systems be inspected, test­ed, and maintained by a qualified In­spection Service in accordance with local requirements and/or national code.
er authorities and all personnel who may be affected by this action must
Ordering
be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid dam­age to the sprinklers -before, during, and after installation. Sprinklers dam­aged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa­tion Section).
The owner is responsible for the in­spection, testing, and maintenance of their fire protection system and de-
Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name and Part Numbers (P/N).
Series TY-FRB Intermediate Sprin­klers are comprised of separately or­dered components: Sprinkler, Guard, and/or Shield.
Upright Sprinkler Assemblies with NPT Thread Connections
Specify: Series TY-FRB Upright Inter­mediate Level Sprinkler, K=5.6, (spec­ify SIN), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Table B)
Pendent Sprinkler Assemblies with NPT Thread Connections
Specify: Series TY-FRB Pendent Sprinkler, K=5.6, (specify SIN), Quick Response, (specify) temperature rat­ing, (specify) finish, P/N (specify from Table B) .
TABL E B
175 175°F ( 79 ° C)
200 200°F (93°C)
286 286° F (141°C)
Model G1/S1 Guard with Shield
Specify: Model G1/S1 Sprinkler Guard with Shield, (specify) finish, P/N (specify).
Red Painted .........P/N 56-938-1-066
Zinc Chromate . . . . . . . P/N 56-938-9-066
Model G1 Sprinkler Guard
Specify: Model G1 Sprinkler Guard, (specify) finish, P/N (specify).
Red Painted .........P/ N 56 - 938-1- 0 01
Zinc Chromate . . . . . . . P/N 56-938-9-001
Model S2 Pendent Shield with O-Ring
Specify: Model S2 Pendent Shield with O-Ring, 1/2” NPT, Series TY­FRB Pendent Sprinklers, P/N 56- 070-9-332.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387.
Additional* Guard Installation Tools
Specify: Guard Installation Tool for Model G1 Sprinkler Guards, P/N 56-000-8-597.
* The Guard Installation Tool is included with
orders in original carton quantities.
Page 6
TFP357 Page 6 of 6
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Copyright © 2013 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Loading...