Tyco TY-B, TY3153, TY4153, TY3251, TY4251 Series Manual

Page 1
Worldwide
Contacts
www.tyco-fire.com
Series TY-B — 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response
General Description
The Series TY-B, 5.6 and 8.0 K-fac­tor Upright and Pendent Intermediate Level Sprinklers described in this data sheet are automatic sprinklers of the “standard response” 5 mm frangible bulb type. They are “standard spray” sprinklers intended for use in fire sprin­kler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA requirements). Both the Pendent and Upright Sprinklers produce a hemispherical water distri­bution pattern below the deflector.
Intermediate Level Sprinklers are pri­marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele­vation sprinklers that could operate earlier during a fire. Intermediate Level Sprinklers are also used in other appli­cations such as beneath open gridded catwalks.
Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is not representative of all possible cor-
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit­ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Series TY-B Sprinklers described herein must be installed and main­tained in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association, in addition to the stan­dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Sprinkler Identification Numbers
TY3153 . . . .Upright 5.6K, 1/2 in. NPT
TY3251 . . .Pendent 5.6K, 1/2 in. NPT TY415 3 . . . Upright 8.0K, 3/4 in. NPT TY4251 . . .Pendent 8.0K, 3/4 in. NPT
Technical Data
Approvals
UL and C-UL Listed FM and NYC Approved
(Refer to Table A for complete approval information including corrosion resis­tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 GPM/psi½ (80,6 LPM/bar½) K = 8.0 GPM/psi½ (115,2 LPM/bar½)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame ............................Bronze
Button...................... Brass/Copper
Sealing Assembly . . . . . . . . . . . . . . . . Ber yllium
Nickel w/TEFLON
Bulb .............................. Glass
Compression Screw . . . . . . . . . . . . . . . . Bronze
Deflector..........................Copper
Shield ........................Plated Steel
Page 1 of 6 AUGUST 2018 TFP351
Page 2
TF P351
* **
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)
(55,6 mm)
(FACTORY ASSEMBLED)
(60,3 mm)
Pipe thread connections per ISO 7-1 can be
Temperature rating is indicated on deector,
* **
Pipe thread connections per ISO 7-1 can be
Temperature rating is indicated on deector,
(FIELD ASSEMBLED - SEE INSTALLATION SECTION)(FACTORY ASSEMBLED)
(61,9 mm)
(58,7 mm)
Page 2 of 6
2-3/8"
shield, or adjacent to orice seat on frame.
3-1/2" (88,9 mm) DIA,
SHIELD SCREW
7/16" (11,1 mm) NOMINAL
MAKE-IN
UPRIGHT
SHIELD
WRENCH
FLATS
1/2"
**
NPT
*
provided on special request.
O-RING
WRENCH
FLATS
3-1/2" (88,9 mm) DIA,
PENDENTUPRIGHT
1/2" NPT
**
FIGURE 1
SERIES TY-B UPRIGHT (TY3153) AND PENDENT (T Y3251) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
5.6 K-FACTOR, 1/2 INCH NPT
shield, or adjacent to orice seat on frame.
provided on special request.
7/16" (11,1 mm)
NOMINAL MAKE-IN
2-3/16"
MODEL S2
SHIELD
3-1/2" (88,9 mm) DIA,
SHIELD SCREW
1/2"
2-7/16"
(12,7 mm) NOMINAL
MAKE-IN
3/4" NPT
SERIES TY-B UPRIGHT (TY4153) AND PENDENT (TY4253) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
8.0 K-FACTOR, 3/4 INCH NPT
O-RING
UPRIGHT
SHIELD
*
WRENCH
FLATS
**
FIGURE 2
WRENCH
FLATS
3-1/2" (88,9 mm) DIA,
PENDENTUPRIGHT
3/4" NPT
**
1/2" (12,7 mm)
NOMINAL MAKE-IN
2-5/16"
MODEL S2
SHIELD
Page 3
Page 3 of 6
SPRINKLER FINISH (SEE NOTE 5)
K TYPE TEMP. BULB LIQUID
135° F ( 57°C) Orange
155° F ( 68°C) Red
UPRIGHT
(T Y3153)
5.6
1/2 in.
NPT
PENDENT
(T Y3251)
UPRIGHT
(TY415 3)
8.0
3/4 in.
NPT
PENDENT
(TY42 51)
NOTES:
1. UL Listed.
2. C-UL Listed.
3. FM Approved.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
*150°F (66°C) Maximum Ceiling Temperature. ** With Zinc Plated Shield. N/A: Not Available
175°F ( 79°C ) Ye llow
200°F (93°C) Green
28 6°F (141° C) Blue
360°F (182°C) Mauve
135° F ( 57°C) Orange
155° F ( 68°C) Red
175°F ( 79°C ) Ye llow
200°F (93°C) Green
28 6°F (141° C) Blue 1*, 2*, 3*, 4*
360°F (182°C) Mauve N/A
135° F ( 57°C) Orange
155° F ( 68°C) Red
175°F ( 79°C ) Ye llow
200°F (93°C) Green
28 6°F (141° C) Blue
360°F (182°C) Mauve
135° F ( 57°C) Orange
155° F ( 68°C) Red
175°F ( 79°C ) Ye llow
200°F (93°C) Green
28 6°F (141° C) Blue 1*, 2*, 3*, 4*
360°F (182°C) Mauve N/A
NATURAL
BRASS**
1, 2, 3, 4 1, 2, 3, 4 N/A
1, 2, 3, 4 1**, 2* *, 3**, 4**
1, 2, 3, 4 1, 2, 3, 4 N/A
1, 2, 3, 4 1**, 2* *, 3**, 4**
LEAD
COATE D
WAX
COATE D**
TABL E A
LABORATORY LISTINGS AND APPROVALS
WAX OVER
LEAD
COATE D**
1, 2, 3, 4
1, 2, 3, 4
TF P351
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Design Criteria
The Series TY-B Pendent and Upright Intermediate Level Sprinklers are intended for fire protection systems designed in accordance with the stan­dard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets).
Page 4
TF P351
(END "A" USED FOR
3/4" NPT MODELS)
Page 4 of 6
Installation
The Series TY-B, Upright and Pendent Intermediate Level Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 360°F (182°C) tempera­ture ratings.
A leak tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 b-ft (9,5 to 19,0 N·m). A leak tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N·m). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Upright Sprinklers
The Series TY-B Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions.
Step 1. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (refer to Figure 3), except that an 8 in. or 10 in. adjust­able Crescent wrench is to be used for wax coated sprinklers. With reference to Figure 1 or 2, the W-Type 6 Sprin­kler Wrench or the Crescent wrench, as applicable, is to be applied to the wrench flats.
Pendent Sprinklers
The Series TY-B Intermediate Level Pendent Sprinklers must be installed in accordance with the following instructions.
Step A. Thread the S2 Shield onto the sprinkler threads with the stamped markings toward the deflector and just to the end of the threads. The final assembly step is easier to accom­plish if the Shield is not disengaged by continuing to turn the Shield past the threads.
Step B. Roll the O-Ring over the sprin­kler threads until it seats against the Shield.
Step C. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step D. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (refer to Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats.
Step E. Rotate the S2 Shield clock­wise (looking up) so that it slightly com­presses the O-Ring between the Shield and sprinkler fitting.
Wax Coated Sprinklers
When installing wax coated sprinklers with the adjustable Crescent wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environ­ment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench tightening the sprinkler, the jaws of the wrench are to be adjusted to just contact the sprinkler wrenching flanges. After wrench tightening the sprinkler, loosen the wrench jaws before removing the wrench.
After installation, the sprinkler wrench flats and frame arms must be inspected and the wax coating retouched (repaired) whenever the coating has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gently applying a heated 1/8 in. diam­eter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed.
NOTES
Only retouching of the wax coating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precau­tions need to be taken, when handling the heated rod, in order to prevent the installer from being burned.
If attempts to retouch the wax coating with complete coverage are unsuc­cessful, additional wax can be ordered
WRENCH RECESS
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
FIGURE 3
W-TYPE 6 SPRINKLER
WRENCH
in the form of a wax stick (the end of which is color coded). Only the correct color coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previously described, touch the rod to the area requiring additional wax with the rod angled downward, and then touch the wax stick to the rod approximately one­half inch away from the area requiring retouching. The wax will melt and run down onto the sprinkler.
Page 5
TF P351
Page 5 of 6
Care and Maintenance
The Series TY-B, Upright and Pendent Intermediate Level Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb (refer to Installation Section).
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan­dards of any other authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be con­tacted relative to any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national code.
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name and Part Numbers (P/N).
Upright Sprinkler Assemblies with Shield and NPT Thread Connections
Specify: Series TY-B (specify SIN), (specify K-factor), Upright Intermedi­ate Level Sprinkler Standard Response, (specify) temperature rating, with (specify finish or coating), P/N (specify from Table B)
Pendent Sprinkler Assemblies with (Shield Ordered Separately) and NPT Thread Connections
Specify: Series TY-B (Specify SIN), (specify K-factor), Pendent Sprinkler Standard Response, (specify) tem­perature rating, with (specify finish or coating), P/N (specify from Table C)
Model S2 Pendent Shield & O-Ring
Specify: S2 Pendent Shield & O-Ring for use with (specify 1/2” NPT or 3/4” NPT) Series TY-B Pendent Sprinklers, P/N (specify)
1/2 in. NPT S2 Pendent
Shield & O-Ring . . . . . . P/N 56 -070 - 9-3 32
3/4 in. NPT S2 Pendent
Shield & O-Ring . . . . . . P/N 56 - 070 - 9-3 42
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Wax Sticks (for retouching wrench damaged wax coating)
Specify: (Specify color) color coded Wax Stick for retouching (specify) temperature rating temperature rated Series TY-B Sprinklers, P/N (specify)
Black for 135°F (57°C) ..P/N 5 6 - 0 6 5 -1-13 5 Red for 155°F (68°C) ...P/ N 56-065-1-155 Yellow for 175°F (79°C). .P/N 56- 065-1-175 Blue for 200°F (93°C)
and 286°F (141°C)..... P/N 56-065-1-286
NOTES
Each wax stick is suitable for retouch­ing up to twenty-five sprinklers.
The wax used for 286°F (141°C) sprin­klers is the same as for 200°F (93°C) sprinklers, and, therefore, the 286°F (141°C) sprinkler is limited to the same maximum ceiling temperature as the 200°F (93°C) sprinkler (i.e., 150°F (66°C).
Page 6
TF P351
Page 6 of 6
P/N 57 – XXX – X – XXX
TF P351
Page 6 of 6
SIN
533 5.6K UPRIGHT (1/2 in. NPT) TY315 3
543 8.0K UPRIGHT (3/ in.˝ NPT) T Y4153
1 NATURAL BRASS
7 LEAD COATED
TABL E B
SERIES TY-B UPRIGHT INTERMEDIATE LEVEL SPRINKLERS
PART NUMBER SELECTION
(Upright Shield Included With Sprinkler)
P/N 57 – XXX – X – XXX
SIN
SPRINKLER
SPRINKLER
TEMPERATURE
RATI NG
135 135° F (57° C)
155 155°F (6 8° C)
175 175°F ( 79° C)
200 200°F (93°C)
286 28 6° F ( 141°C )
360 360°F (182°C)
TEMPERATURE
RATI NG
571 5.6K PENDENT (1/2 in. NPT ) TY3 251
591 8.0K PENDENT (3/4 in. NPT ) TY42 51
SERIES TY-B PENDENT SPRINKLERS
(Model S2 Pendent Shield & O-Ring Must Be Separately Ordered)
1 NATURAL BRASS
6
7 LEAD COATED
8
WA X C OATE D
286°F (141°C) MAXIMUM
WAX OVER LE AD
286°F (141°C) MAXIMUM
TABL E C
PART NUMBER SELECTION
135 135° F (57° C)
155 155°F (6 8° C)
175 175°F ( 79° C)
200 200°F (93°C)
286 28 6° F ( 141°C )
360 360°F (182°C)
1400 Pennbrook Par kway, Lansdale, PA 194 46 | Telep hone +1-215- 362- 0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; TEFLON is a regi stered tradema rk of DuPont
Loading...