Series TY-FRL – 5.6 and 8.0 K-factor
Upright and Pendent Intermediate Level Sprinklers
Quick Response
General
Description
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers are automatic sprinklers of the quick response
solder type. They are standard spray
sprinklers intended for use in fire sprinkler systems designed in accordance
with the standard installation rules
recognized by the applicable listing
or approval agency (e.g., UL Listing is
based on NFPA requirements). Both
the Pendent and Upright Sprinklers
produce a hemispherical water distribution pattern below the deflector.
Intermediate level sprinklers are primarily designed for use in rack storage
sprinkler systems where their thermally
sensitive elements must be shielded
from the water spray of higher elevation sprinklers that could operate
earlier during a fire. Intermediate level
sprinklers are also used in other applications such as beneath open gridded
catwalks.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
NOTICE
The Series TY-FRL Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY312 3 ........... Upright 5.6K, 1/2 in. NPT
TY3221 ...........Pendent 5.6K, 1/2 in. NPT
TY4123 ........... Upright 8.0K, 3/4 in. NPT
TY4221 ...........Pendent 8.0K, 3 /4 in. NP T
TY3123 is a redesignation for Star SIN
S1991 and Gem SIN G8986
TY3221 is a redesignation for Star SIN
S1865 and Gem SIN G8972
TY4123 is a redesignation for Star SIN
S1993 and Gem SIN G8153
TY4221 is a redesignation for Star SIN
S1867 and Gem SIN G8172
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table A for complete approval
information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficients
K=5.6 gpm/psi½ (80,6 lpm/bar½)
K=8.0 gpm/psi½ (115, 2 l p m / b a r½)
Temperature rating
is indicated on
Deector or Shield
4-1/8" (104,8 mm) DIA.
2-3/4"
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
Pipe thread connections per
ISO 7-1 can be provided on
special request
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
WRENCH
AREA
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
Order Pendent Series TY-FRL Sprinkler and
Model S4 Shield Package separately for
pendent assembly (Ref. Ordering Procedure)
4-1/8" (104,8 mm) DIA.
1/2" NPT
SECTION)
DEFLECTOR
**
*
SPEEDNUT
FIGURE 1
SERIES TY-FRL UPRIGHT (TY3123) & PENDENT (TY3221) INTERMEDIATE LEVEL SPRINKLERS
5.6K, QUICK RESPONSE, 1/2” NPT
is indicated on
Deector or Shield
ISO 7-1 can be provided on
special request
Model S4 Shield Package separately for
pendent assembly (Ref. Ordering Procedure)
O-RING
2-11/16"
PENDENT
SERIES
TY-FRL
†
4-1/8" (104,8 mm) DIA.
2-13/16"
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
SERIES TY-FRL UPRIGHT (TY4123) & PENDENT (TY4221) INTERMEDIATE LEVEL SPRINKLERS
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH
FLANGES
WRENCH
AREA
8.0K, QUICK RESPONSE, 3/4” NPT
Design
Criteria
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers are
intended for fire protection systems
designed in accordance with the standard installation rules recognized
by the applicable listing or approval
agency (e.g., UL Listing is based on
the requirements of NFPA 13, and FM
Approval is based on the requirements
of FM Approvals’ Loss Prevention Data
Sheets).
4-1/8" (104,8 mm) DIA.
3/4" NPT
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
SECTION)
DEFLECTOR
FIGURE 2
**
*
Operation
The fusible link (heat collector) assembly is comprised of two halves that
are joined together by a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate, allowing the sprinkler to operate.
SPEEDNUT
O-RING
2-15/16"
PENDENT
SERIES
TY-FRL
†
Page 3
K-FACTOR
WRENCH
SPRINKLER
TYPE
TEMPERATURE
RATING
FRAME
COLOR CODE
SPRINKLER FINISH
NATURAL
BRASS
TFP355
Page 3 of 4
CHROME
PL ATED
5.6
1/2 in. NPT
8.0
3/4 in. NPT
Notes:
1. Liste d by Under writer s Labor atories , Inc. (UL) a s quick re sponse sprinkle rs
2. Listed by Und erwriters La borator ies, Inc. for use in Canada (C-UL) as quic k respon se sprinklers
3. A pproved by FM Global ( FM Approva ls) as quick response sprink lers
4. A pproved by the City of N ew York (NYC) unde r MEA 112-04-E
Upright ( TY3123)
&
Pendent (TY3221)
Upright ( TY4123)
&
Pendent (TY4221)
165° F ( 74°C)
Unpainted1, 2, 3, 4
TABL E A
5.6K & 8 .0K SERIES TY-FRL UPRIGHT & PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
LABORATORY LISTINGS AND APPROVALS
Installation
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers must
be installed in accordance with this
section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained with a torque
of 7 to 14 lb-ft (9,5 to 19,0 N·m).
A maximum of 21 lb-ft (28,5 N·m) of
torque may be used to install sprinklers with 1/2 in. NPT connections.
A leak-tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 to 20 lb-ft (13,4 to 26,8 N·m). A
maximum of 30 lb-ft (40,7 N·m) of
torque is to be used to install sprinklers
with 3/4 in. NPT connections. Higher
levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Upright Sprinklers
The Series TY-FRL Intermediate Level
Upright Sprinklers must be installed
in accordance with the following
instructions:
Step 1. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into
the sprinkler fitting using only the
W-Type 9 Sprinkler Wrench (Ref. Figure
3). With reference to Figure 1 or 2, the
W-Type 9 Sprinkler Wrench is to be
applied to the wrenching area.
Pendent Sprinklers
The Series TY-FRL Intermediate Level
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Step 1. Install the speed nut over the
sprinkler threads until it seats against
the sprinkler wrenching area flange as
shown in Figure 1 or 2, as applicable.
Step 2. Install the Model S4 Shield over
the sprinkler threads, and then roll the
O-ring over the sprinkler threads until it
is seated firmly against the shield.
Step 3. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting.
Step 4. Tighten the sprinkler into
the sprinkler fitting using only the
W-Type 9 Sprinkler Wrench (Ref. Figure
3). The wrench is to be applied to the
sprinkler wrenching area shown in
Figure 1 or 2, as applicable.
When installed correctly, the O-ring will
be slightly compressed and the shield
will be held firmly in place.
Care and
Maintenance
TYCO Series TY-FRL 5.6K and 8.0K
Quick Response Upright and Pendent
Intermediate Level Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
control valve for maintenance work on
the fire protection system that it controls, permission to shut down the
affected fire protection system must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
RECESS
FIGURE 3
W-T Y PE 9
SPRINKLER WRENCH
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation Section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(e.g., NFPA 25), in addition to the standards of any other authorities having
jurisdiction. Contact the installing contractor or sprinkler manufacturer with
any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
have not operated, should be replaced
Page 4
TFP355
Page 4 of 4
P/N 58 — XXX — X — XXX
9865.6K UPRIGHT (1/2 in. NPT)TY3123
1538.0K UPRIGHT (3/4 in. NPT)T Y4123
SERIES TY-FRL UPRIGHT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
P/N 58 — XXX — X — XXX
9825.6K PENDENT (1/2 in. NPT )TY3221
1728.0K PENDENT (3/4 in. NPT )T Y4221
SERIES TY-FRL PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
(MODEL S4 PENDENT SHIELD, SPEED-NUT AND O-RING MUST BE SEPARATELY ORDERED)
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
1
9
SPRINKLER
FINISH
NAT URAL
BRASS
CHROME
PL AT ED
SIN
TABL E B
PART NUMBER SELECTION
1
9
SPRINKLER
FINISH
NAT URAL
BRASS
CHROME
PL AT ED
SIN
TABL E C
PART NUMBER SELECTION
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name, including
description and part number (P/N).
Upright Sprinkler Assemblies with
NPT Thread Connections
(with Shield)
Specify: Series TY-FRL Upright Intermediate Level Sprinkler, (specify
K-factor), Quick Response, (specify)
temperature rating, (specify) finish, P/N
(specify from Table B)
Pendent Sprinkler Assemblies with
NPT Thread Connections
(Shield ordered separately)
Specify: Series TY-FRL Pendent
Sprinkler, (specify K-factor), Quick
Response, (specify) temperature
rating, (specify) finish, P/N (specify from
Tabl e C)
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on;
MONEL and IN CONEL are registe red trademarks o f Special Metals C orporation;
TEFLON is a regi stered tradema rk of DuPont