Series TY-FRL – 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Quick Response
General Description
TYCO Series TY-FRL 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are auto­matic sprinklers of the quick response solder type. They are standard spray sprinklers intended for use in fire sprin­kler systems designed in accordance with the standard installation rules recognized by the applicable listing or approval agency (e.g., UL Listing is based on NFPA requirements). Both the Pendent and Upright Sprinklers produce a hemispherical water distri­bution pattern below the deflector.
Intermediate level sprinklers are pri­marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele­vation sprinklers that could operate earlier during a fire. Intermediate level sprinklers are also used in other appli­cations such as beneath open gridded catwalks.
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
NOTICE
The Series TY-FRL Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Numbers (SINs)
TY312 3 ........... Upright 5.6K, 1/2 in. NPT
TY3221 ...........Pendent 5.6K, 1/2 in. NPT
TY4123 ........... Upright 8.0K, 3/4 in. NPT
TY4221 ...........Pendent 8.0K, 3 /4 in. NP T
TY3123 is a redesignation for Star SIN S1991 and Gem SIN G8986
TY3221 is a redesignation for Star SIN S1865 and Gem SIN G8972
TY4123 is a redesignation for Star SIN S1993 and Gem SIN G8153
TY4221 is a redesignation for Star SIN S1867 and Gem SIN G8172
Technical Data
Approvals
UL and C-UL Listed FM and NYC Approved
(Refer to Table A for complete approval information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficients
K=5.6 gpm/psi½ (80,6 lpm/bar½) K=8.0 gpm/psi½ (115, 2 l p m / b a r½)
Temperature Ratings
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . . . . . . . Nickel
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TEFLON
Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Page 1 of 4 AUGUST 2018 TFP355
Page 2
TFP355
FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT
* **
Pipe thread connections per
Temperature rating
Order Pendent Series TY-FRL Sprinkler and
(74,6 mm)
(71,4 mm)
* **
FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT
(69,9 mm)
(68,3 mm)
Page 2 of 4
Temperature rating is indicated on Deector or Shield
4-1/8" (104,8 mm) DIA.
2-3/4"
7/16" (11,1 mm) NOMINAL
MAKE-IN
Pipe thread connections per ISO 7-1 can be provided on special request
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH FLANGES
WRENCH
AREA
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
Order Pendent Series TY-FRL Sprinkler and Model S4 Shield Package separately for pendent assembly (Ref. Ordering Procedure)
4-1/8" (104,8 mm) DIA.
1/2" NPT
SECTION)
DEFLECTOR
**
*
SPEEDNUT
FIGURE 1
SERIES TY-FRL UPRIGHT (TY3123) & PENDENT (TY3221) INTERMEDIATE LEVEL SPRINKLERS
5.6K, QUICK RESPONSE, 1/2” NPT
is indicated on Deector or Shield
ISO 7-1 can be provided on special request
Model S4 Shield Package separately for pendent assembly (Ref. Ordering Procedure)
O-RING
2-11/16"
PENDENT
SERIES TY-FRL
4-1/8" (104,8 mm) DIA.
2-13/16"
1/2" (12,7 mm) NOMINAL
MAKE-IN
SERIES TY-FRL UPRIGHT (TY4123) & PENDENT (TY4221) INTERMEDIATE LEVEL SPRINKLERS
FACTORY
ASSEMBLED
UPRIGHT
SHIELD
WRENCH FLANGES
WRENCH
AREA
8.0K, QUICK RESPONSE, 3/4” NPT
Design Criteria
TYCO Series TY-FRL 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are intended for fire protection systems
designed in accordance with the stan­dard installation rules recognized by the applicable listing or approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM Approvals’ Loss Prevention Data Sheets).
4-1/8" (104,8 mm) DIA.
3/4" NPT
FIELD ASSEMBLED
*
MODEL S4 SHIELD
(SEE INSTALLATION
SECTION)
DEFLECTOR
FIGURE 2
**
*
Operation
The fusible link (heat collector) assem­bly is comprised of two halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, allowing the sprin­kler to operate.
SPEEDNUT
O-RING
2-15/16"
PENDENT
SERIES TY-FRL
Page 3
K-FACTOR
WRENCH
SPRINKLER
TYPE
TEMPERATURE
RATING
FRAME
COLOR CODE
SPRINKLER FINISH
NATURAL
BRASS
TFP355
Page 3 of 4
CHROME
PL ATED
5.6
1/2 in. NPT
8.0
3/4 in. NPT
Notes:
1. Liste d by Under writer s Labor atories , Inc. (UL) a s quick re sponse sprinkle rs
2. Listed by Und erwriters La borator ies, Inc. for use in Canada (C-UL) as quic k respon se sprinklers
3. A pproved by FM Global ( FM Approva ls) as quick response sprink lers
4. A pproved by the City of N ew York (NYC) unde r MEA 112-04-E
Upright ( TY3123)
&
Pendent (TY3221)
Upright ( TY4123)
&
Pendent (TY4221)
165° F ( 74°C)
Unpainted 1, 2, 3, 4
TABL E A
5.6K & 8 .0K SERIES TY-FRL UPRIGHT & PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE LABORATORY LISTINGS AND APPROVALS
Installation
TYCO Series TY-FRL 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be installed in accordance with this section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). A maximum of 21 lb-ft (28,5 N·m) of torque may be used to install sprin­klers with 1/2 in. NPT connections. A leak-tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N·m). A maximum of 30 lb-ft (40,7 N·m) of torque is to be used to install sprinklers with 3/4 in. NPT connections. Higher levels of torque may distort the sprin­kler inlet and cause leakage or impair­ment of the sprinkler.
Upright Sprinklers
The Series TY-FRL Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions:
Step 1. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure
3). With reference to Figure 1 or 2, the W-Type 9 Sprinkler Wrench is to be applied to the wrenching area.
Pendent Sprinklers
The Series TY-FRL Intermediate Level Pendent Sprinklers must be installed in accordance with the following instructions:
Step 1. Install the speed nut over the sprinkler threads until it seats against
the sprinkler wrenching area flange as shown in Figure 1 or 2, as applicable.
Step 2. Install the Model S4 Shield over the sprinkler threads, and then roll the O-ring over the sprinkler threads until it is seated firmly against the shield.
Step 3. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting.
Step 4. Tighten the sprinkler into the sprinkler fitting using only the W-Type 9 Sprinkler Wrench (Ref. Figure
3). The wrench is to be applied to the sprinkler wrenching area shown in Figure 1 or 2, as applicable.
When installed correctly, the O-ring will be slightly compressed and the shield will be held firmly in place.
Care and Maintenance
TYCO Series TY-FRL 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but
RECESS
FIGURE 3 W-T Y PE 9
SPRINKLER WRENCH
if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin­kler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installa­tion Section).
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan­dards of any other authorities having jurisdiction. Contact the installing con­tractor or sprinkler manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
have not operated, should be replaced
Page 4
TFP355
Page 4 of 4
P/N 58 — XXX — X — XXX
986 5.6K UPRIGHT (1/2 in. NPT) TY3123
153 8.0K UPRIGHT (3/4 in. NPT) T Y4123
SERIES TY-FRL UPRIGHT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
P/N 58 — XXX — X — XXX
982 5.6K PENDENT (1/2 in. NPT ) TY3221
172 8.0K PENDENT (3/4 in. NPT ) T Y4221
SERIES TY-FRL PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE
(MODEL S4 PENDENT SHIELD, SPEED-NUT AND O-RING MUST BE SEPARATELY ORDERED)
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
1
9
SPRINKLER
FINISH
NAT URAL
BRASS
CHROME
PL AT ED
SIN
TABL E B
PART NUMBER SELECTION
1
9
SPRINKLER
FINISH
NAT URAL
BRASS
CHROME
PL AT ED
SIN
TABL E C
PART NUMBER SELECTION
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name, including description and part number (P/N).
Upright Sprinkler Assemblies with NPT Thread Connections (with Shield)
Specify: Series TY-FRL Upright Inter­mediate Level Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Table B)
Pendent Sprinkler Assemblies with NPT Thread Connections (Shield ordered separately)
Specify: Series TY-FRL Pendent Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Tabl e C)
TEMPERATURE
RATING
165 16 5° F ( 74°C )
TEMPERATURE
RATING
165 16 5° F ( 74°C )
Model S4 Sprinkler Shield
Includes S4 Shield, one O-Ring and one Speednut.
Specify: Model S4 Sprinkler Shield, (specify) finish, (specify) Thread Size, P/N (specify):
Plain Brass
1/2 in. NPT . . . . . . . . . . . . . . . . . . . 5 6-9 52-1-00 1
3/4 in. NPT . . . . . . . . . . . . . . . . . . . 56-152-1-0 01
Chrome Plated
1/2 in. NPT . . . . . . . . . . . . . . . . . . .56-951-9-001
3/4 in. NPT . . . . . . . . . . . . . . . . . . . 56-152- 9 -00 1
Sprinkler Wrench
Specify: W-Type 9 Sprinkler Wrench, P/N 56-000-1-8499
1400 Pennbro ok Park way, Lan sdale, PA 19446 | Telephon e +1-215-362-0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; MONEL and IN CONEL are registe red trademarks o f Special Metals C orporation; TEFLON is a regi stered tradema rk of DuPont