Tyco SW-20, SW-24 User Manual

Worldwide
Contacts
www.tyco-fire.com
Model SW-20 and SW-24 — 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)
General Description
The TYCO Model SW-20 and SW-24,
11.2 K-factor, Extended Coverage Ordi­nary Hazard (ECOH) Horizontal Side­wall Sprinklers, Standard Response are decorative glass bulb sprinklers designed for use in ordinary hazard occupancies per NFPA 13.
The SW-20 provides protection of cov­erage areas up to 16 ft x 20 ft (320 ft2), whereas the SW-24 provides protec­tion of coverage areas up to 16 ft x 24 ft (384 ft2), as compared to standard coverage horizontal sidewall sprinklers having a maximum coverage area of 10 ft x 10 ft (100 ft2) for ordi nary hazard occupancies.
Horizontal sidewall sprinklers are designed for installation along a wall or the side of a beam and are com­monly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable.
Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo­spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli­cable approval agencies, the testing is
not representative of all possible cor­rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit­ability of these corrosion resistant coatings for any given corrosive envi­ronment. The effects of ambient tem­perature, concentration of chemicals, and gas/chemical velocity, should be con sidered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Model SW-20 and SW-24 Sprin­klers described herein must be installed and maintained in compliance with this document and with the applicable stan­dards of the National Fire Protection Association, in addition to the stan­dards of any authorities having juris­diction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain­ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Sprinkler Identification Number (SIN)
TY5332 - SW-20 TY5337 - SW-24
TY5332 is a re-designation for C5332 TY5337 is a re-designation for C5337
SW-20
SW-24
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 11.2 GPM/psi½ (161,3 LPM/bar½)
Temperature Rating
SW-20: 155°F (68°C) & 200°F (93°C) SW-24: 200°F (93°C)
Finishes
Refer to Table B
Physical Characteristics:
Frame ............................Bronze
Button............................Bronze
Sealing Assembly . . . . . . . . . . . . . . . . Ber yllium
Nickel w/ TEFLON
Bulb .............................. Glass
Compression Screw . . . . . . . . . . . . . . . . . Brass
Deflector. . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Refer to Technical Data Sheet
IMPORTANT
TFP2300 for warnings pertaining to regulatory and health information.
Page 1 of 6 AUGUST 2018 TFP230
Technical Data
Approvals
UL and C-UL Listed
(Refer to the Design Criteria Section)
Polyester coated sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers
NYC under MEA 177-03-E
TFP230
**
*
(60,3 mm)
(19,1 mm)
Components:
6
3 4
1 2
5
**
(60,3 mm)
(19,1 mm)
Components:
5 6
2
1
4
3
WRENCH AS
WRENCH
Page 2 of 6
-
Frame
-
Button
-
Bulb
-
Compression Screw
-
Sealing Assembly
-
Deector
Temperature rating is
*
indicated on Deector.
**
Pipe thread connections per ISO 7-1 can be provided on special request.
5
6
TOP
RECESS
(END "B")
APPLY
SHOWN
*
3
1/2"
(12,7 mm)
4
CENTERLINE
OF SPRINKLER
WATERWAY
2 1
WRENCH
FLAT
FIGURE 3
W-TYPE 3 SPRINKLER
WRENCH
3/4" NPT
MAXIMUM
THROW
2"
(50,8 mm)
EXTENDED COVERAGE ORDINARY HAZARD
-
Frame
-
Button
-
Bulb
-
Compression Screw
-
Sealing Assembly
-
Deector
Temperature rating is
*
indicated on Deector.
**
Pipe thread connections per ISO 7-1 can be provided on special request.
*
1/2" (12,7 mm)
NOMINAL
MAKE-IN
3/4"
2-3/8"
FIGURE 1
MODEL SW-20 (TY5332)
HORIZONTAL SIDEWALL SPRINKLER
11.2 K-FACTOR, 3/4 INCH NPT
TOP
WRENCH
CENTERLINE
9/16"
(14,3 mm)
OF SPRINKLER
WATERWAY
1
6
*
FLAT
6" (152,4 mm)
TO 12" (304,8 mm)
CEILING TO TOP
OF SPRINKLER
DEFLECTOR
DISTANCE
4/12
SLOPE
MAXIMUM
FIGURE 4
SPRINKLER PLACEMENT
UNDER SLOPED CEILINGS IN
LOADING DOCKS
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the
3/4" NPT
5
2
fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
2"
(50,8 mm)
3/4"
FIGURE 2
MODEL SW-24 (TY5337)
EXTENDED COVERAGE ORDINARY HAZARD
HORIZONTAL SIDEWALL SPRINKLER
11.2 K-FACTOR, 3/4 INCH NPT
3
4
1/2" (12,7 mm)
NOMINAL
MAKE-IN
2-3/8"
TFP230
Page 3 of 6
MODEL SW-20 ECOH HORIZONTAL SIDEWALL SPRINKLER (TY5332)
OH Group 1 (0.15 gpm/sq-ft)
Response
Rating
Coverage
(1)
Area
,
Ft x Ft (m x m)
Minimum
(2)
Flow
,
GPM (LPM)
Minimum
Pressure
PSI (BAR)
Deflector-To-Ceiling
(2)
,
Distance
In. (mm)
(3)
,
Sprinkler
Temperature
Rating, °F
Minimum
Spacing
Ft (m)
Standard 16 x 16 (4,9 x 4,9 38 (14 4) 11. 5 ( 0,7 9 ) 6 to 12 (150 to 300) 155, 200 8 (2,4)
Standard 16 x 18 (4,9 x 5,5) 43 (163) 14.7 (1,01) 6 to 12 (150 to 300) 155, 200 8 (2,4)
Standard 16 x 20 (4,9 x 6,1) 48 (182) 18.4 (1,27) 6 to 12 (150 to 300) 155, 200 8 (2,4)
MODEL SW-20 ECOH HORIZONTAL SIDEWALL SPRINKLER (TY5332)
OH Group 2 (0.20 gpm/sq.-ft.)
Response
Rating
Coverage
(1)
Area
,
Ft x Ft (m x m)
Minimum
(2)
Flow
,
GPM (LPM)
Minimum
Pressure
PSI (BAR)
Deflector-To-Ceiling
(2)
,
Distance
In. (mm)
(3)
,
Sprinkler
Temperature
Rating, °F
Minimum
Spacing
Ft (m)
Standard 16 x 16 (4,9 x 4,9 51 (193) 20.7 (1,43) 6 to 12 (150 to 300) 155, 200 8 (2,4)
Standard 16 x 18 (4,9 x 5,5) 58 (220) 26.8 (1,85) 6 to 12 (150 to 300) 155, 200 8 (2,4)
Standard 16 x 20 (4,9 x 6,1) 64 (242) 32.7 (2,25) 6 to 12 (150 to 300) 155, 200 8 (2,4)
MODEL SW-24 ECOH HORIZONTAL SIDEWALL SPRINKLER (T Y5337)
OH Group 1 (0.15 gpm/sq.-ft.)
Response
Rating
Coverage
(1)
Area
,
Ft x Ft (m x m)
Minimum
(2)
Flow
,
GPM (LPM)
Minimum
Pressure
PSI (BAR)
Deflector-To-Ceiling
(2)
,
Distance
In. (mm)
(3)
,
Sprinkler
Temperature
Rating, °F
Minimum
Spacing
Ft (m)
(4)
,
(4)
,
(4)
,
Standard 16 x 22 (4,9 x 6,7) 53 (200) 22.4 (1,54) 6 to 12 (150 to 300) 200 8 (2,4)
Standard 16 x 24 (4,9 x 7,3) 58 (220) 26.8 (1,85) 6 to 12 (150 to 300) 200 8 (2,4)
MODEL SW-24 ECOH HORIZONTAL SIDEWALL SPRINKLER (T Y5337)
OH Group 2 (0.20 gpm/sq.-ft.)
Response
Rating
Coverage
(1)
Area
,
Ft x Ft (m x m)
Minimum
(2)
Flow
,
GPM (LPM)
Minimum
Pressure
PSI (BAR)
Deflector-To-Ceiling
(2)
,
Distance
In. (mm)
(3)
,
Sprinkler
Temperature
Rating, °F
Minimum
Spacing
Ft (m)
(4)
Standard 16 x 22 (4,9 x 6,7) 71 (269) 40. 2 (2,77) 6 to 12 (150 to 300) 200 8 (2,4)
Standard 16 x 24 (4,9 x 7,3) 77 (291) 47,3 (3,26) 6 to 12 (150 to 300) 200 8 (2,4)
NOTES
1. Backwall (where sprinkler is located) by sidewall (length of throw).
2. Requireme nt is bas ed on mini mum ow in G PM from each sprin kler. The in dicted r esidu al pres sures are based on the nominal K-factor.
3. T he centerline of the spri nkler wa terway i s locate d below the deector as show n in Figures 1 and 2.
4. M inimum s pacing i s for lateral dist ance be tween s prinklers lo cated al ong a sing le wall. O therw ise adjacent sp rinklers (i.e., s idewall s prink lers on a n adjace nt wall, on an opposite wall, or p enden t sprink lers) m ust be located outside of the maxi mum liste d protection ar ea of the ex tended c overage sidewal l sprink ler bei ng utiliz ed.
TABL E A
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
,
TFP230
Page 4 of 6
Design Criteria
The TYCO Model SW-20 and SW-24,
11.2 K-factor, Extended Coverage Ordi­nary Hazard (ECOH) Horizontal Side­wall Sprinklers are for use in ordinary hazard occupancies with non-combus­tible un obstructed construction and with a ceiling slope not exceeding 2 inches per foot (9.2°), using the design criteria provided in Table A, (as well as any additional requirements speci­fied in NFPA 13 for Extended Coverage Sidewall Spray Sprinklers).
A 36 in. (914 mm) clearance must be maintained between the top of the sprinkler deflector and any miscella­neous storage.
The SW-20 and SW-24 may be in stalled on sloped ceilings in loading docks with a maximum roof slope of 4 in. per foot (18.4°) as shown in Figure 4 and using the design criteria provided in Table A.
The SW-20 and SW-24 can be used only for exposed applications. The SW-20 and SW-24 cannot be recessed.
Installation
The TYCO Model SW-20 and SW-24,
11.2 K-factor, Extended Coverage Ordi­nary Hazard (ECOH) Horizontal Side­wall Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm).
A leak tight 1/2 in. NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Higher levels of torque can distort the sprinkler Inlet with con­sequent leakage or impairment of the sprinkler.
Do not attempt to compensate for insufficient adjustment in the Sprinkler by under- or over-tightening the Sprin­kler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to suit.
Step 1. Horizontal sidewall sprinklers are to be installed with their center­line perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the deflector is to face towards the ceiling.
Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 3 (End B) Sprinkler Wrench (Ref. Figure
3). With reference to Figures 1 and 2, the W-Type 3 Sprinkler Wrench is to be applied to the sprinkler wrench flats
Care and Maintenance
The TYCO Model SW-20 and SW-24,
11.2 K-factor, Extended Coverage Ordi­nary Hazard (ECOH) Horizontal Side­wall Sprinklers must be maintained and serviced in accordance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protec­tion system from the proper authorities and notify all personnel who may be affected by this action.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso­ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install­ing contractor or sprinkler manufac­turer regarding any questions.
Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor­dance with local requirements and/or national code.
Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin­kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa­tion Section).
Frequent visual inspections are rec­ommended to be initially performed for corrosion resistant coated sprin­klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of in specting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condi tion and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present.
P/N 51 – XXX – X – XXX
TFP230
Page 5 of 6
MODEL SIN
072 Model SW-20 TY5332
073 Model SW-24 TY5337
MODEL SW-20 AND SW-24 ECOH HORIZONTAL SIDEWALL SPRINKLERS
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name and Part Numbers (P/N).
Sprinkler Assemblies with NPT Thread Connections:
Specify: Model (specify) ECOH Hori­zontal Sidewall Sprinkler, SIN (specify), (specify) temperature rating, (specify) finish, P/N (specify from Table B)
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench, P/ N 5 6 - 89 5 -1- 0 01
SPRINKLER
FINISH
1 Natural Brass
Signal White (RAL9003)
4
9 Chrome Plated
TABL E B
WITH 3/4 INCH NPT CONNECTION
PART NUMBER SELECTION
Polyester
TEMPERATURE
155
200
(SW-20 or SW-24)
SPRINKLER
RATI NG
155° F ( 68°C)
(SW-20 Only)
200°F (93°C)
TFP230
Page 6 of 6