Tyco HS2TCHPRO, HS2TCHPROBLK User manual

HS2TCHPRO/HS2TCHPROBLK Touchscreen User Manual
Uživatelská příručka dotykové obrazovky
HS2TCHPRO/HS2TCHPROBLK
HS2TCHPRO/HS2TCHPROBLK Touchscreen
Benutzerhandbuch
WARNING: This manual contains information on limitations regarding product use, function and information
on the limitation as to liability of the manufacturer. The entire manual should be carefully read.
UPOZORNĚNÍ: Tento návod obsahuje informace o omezení ve využívání výrobku a jeho funkci, a také informace o omezení odpovědnosti výrobce. Celý návod si pečlivě přečtěte.
WARNUNG: Dieses Handbuch enthält Informationen hinsichtlich der Einschränkungen bei der Verwendung des Produkts und der Funktionen und Informationen zu den Einschränkungen bezüglich der Haftung des Her-stellers. Lesen Sie das gesamte Handbuch aufmerksam durch.

Table of Contents

Table of Contents 2
Safety Notes 5
Important Safety Instructions 5
Regular Maintenance and Troubleshooting 5
Handling Precautions 5
Cleaning 5
Troubleshooting 5
Introduction 6
General System Operation 6
About Your Security System 6
Carbon Monoxide Detection (must be enabled by your Installer) 7
Fire Detection (must be enabled by your Installer) 7
Testing 7
Monitoring 7
Maintenance 7
Important Notice 7
Specifications and Features 8
Welcome Screen 8
Emergency Keys 9
Arming and Disarming the System 10
Stay Arm (Arming the Perimeter) 10
Silent Exi t Delay 10
Disarm 11
Away Arm 11
Exit Delay Time Restart 11
Alarm Cancel Window 11
Bell/Siren Sounds After Away Arming 12
Audible Exit Fault 12
Arming Error 12
Remote Arming and Di sarming 12
Using Your System 12
When Alarm Sounds 12
Intrusion (Burglary) Alarm Continuous Siren 12
If the Intrusion Alarm was Accidental 13
Fire Alarm Pulsed Siren 13
Wireless Carbon Monoxi de Alarm 13
Troubles 14
Alarm Memory 14
Sensor Reset 15
Outputs 15
Additional Functions 16
Photos 16
Quick Exit 16
Time & Date Programming 16
Keypad Mode 16
Door Chime (Chime enable/disable) 16
Zone Bypass 16
Zone Status Indicators 17
Bypassed Zones 17
Bypassing Zones with a HS2TCHPRO/HS2TCHPROBLK 17
Options Menu 17
Access Codes 18
Assign Proximity Tags 18
Delete Proximity Tags 18
User Code Attributes 19
Inherent Attributes (all codes except installer and maintenance) 19
Programmable Attributes 19
Bell Squawk Attribute 19
Partition Assignment 19
Erasing an Access Code 19
Installer Menu 19
User Functions 20
Time and Date 20
Auto-Arm Time 20
Enable DLS/Allow System Service 20
Event Buffer 20
System Test 20
Auto-Arm/Disarm Control 21
User Call-up 21
Engineer's Reset 21
Keypad Configuration 21
Chime Enabled/Disabled 22
Arming 22
Partition Status 22
Keypad Mode 23
Managing Partitions 23
Partitions 23
Single Partition Operation 23
Loaning a Keypad to Another Partition 23
Global Keypad Operation 24
Fire and CO Zone Types 25
Testing Your System 26
Testing Your Keypad Sounder and Siren 26
Testing Your Entire System 26
Walk Test Mode 26
Allowing Computer Access To Your System 26
Reference Sheets 27
System Information Enabled? 27
For Service 27
Central Station Information: 27
Installer Information: 27
Battery Installation / Service Date: 27
Access Codes (copy as needed) 28
Sensor / Zone Information (copy as needed) 29
Guidelines for Locating Smoke Detectors and CO Detectors 30
Smoke Detectors 30
Carbon Monoxide Detectors 31
Household Fire Safety Audit 32
Fire Escape Planning 32
License Agreement 33

Safety Notes

Safety Notes
This manual shall be used in conjuncti on with t he PowerSeries Pro User manual for the compatible alarm control panel: HS3032, HS3128, HS3248.
Always ensure you obtain the latest version of the User Guide. Updated versions of this User Guide are available by contacting your distributor.
Warning: Read and save these instructions! Follow all warnings and instructions specified within this document and/or on the equipment.

Important Safety Instructions

To reduce the risk of fire, electric shock and/or injury, observe the following:
l Do not spill any type of li quid on the equipment. l Do not attempt to service this product yourself. Opening or removing the cover may expose you to dan-
gerous voltage or other risk. Refer servicing to qualified service personnel. Never open the device your­self.
l Do not touch the equipment and its connected cables during an electrical storm; there may be a risk of
electric shock.
l Do not use the Alarm System to report a gas leak if the system is near a leak.

Regular Maintenance and Troubleshooting

Keep your HS2TCHPRO/HS2TCHPROBLK Touchscreen keypad in optimal condition by following all the instruc­tions that are included within this manual and/or marked on the product.

Handling Precautions

Do not apply excessive force to the display surface or the adjoining areas since this may cause the color tone to vary.

Cleaning

l If the display surface is contaminated, breathe on the surface and gently wipe it with a soft, dry cloth. If
still not completely clean, moisten cloth with isopropyl alcohol.
l Do not use abrasives, water, thinners, solvents or aerosol cleaners (spray polish), any aromatic solvents,
ketones etc. that may enter through holes in the HS2TCHPRO/HS2TCHPROBLK Touchscreen keypad and cause damage.

Troubleshooting

Occasionally, you may have a problem with your system. If this happens, your Alarm Controller will display an error message. Refer to the provided list when you see an error message on the display. If additional help is required, contact your distributor for service.
Warning: This equipment, HS2TCHPRO/HS2TCHPROBLK Touchscreen keypad shall be installed and used within an environment that provides the poll ution degree max 2 and over-voltages category II non-hazardous loc­ations, indoor only. It is designed to be installed, serviced and/or repaired by service persons only [service person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and of measures to minimize the risks to that person or other persons]. There are no parts replaceable by the end-user within this equipment.
Warning: Never obstruct the access to the Alarm controller to which this equipment is connected. These safety instructions should not prevent you from contacting the distributor and/or the manufacturer to obtain any further clarification and/or answers to your concerns.
- 5 -

Introduction

Introduction
Figure 1- Controls and Indicators
The HS2TCHPRO/HS2TCHPROBLK Touchscreen is an interactive touch-sensitive color LCD that can be used on any PowerSeries Pro control panel. Due to the custom requirements of individual installations, some of the fea­tures described here may perform differentl y than described. Refer to your Install er's Instructions for the details of your specific installation and to the User Manual for general security system information.

General System Operation

Your security system is made up of a DSC control panel, one or more keypads and various sensors and detectors. The control panel will be mounted out of the way in a utility closet or in a basement. The metal cabinet contains the system electronics, fuses and standby battery.
Note: Only the i nstaller or service professional shall have access to the control panel.
All the keypads have an audible indicator and command entry keys. The keypad is used to send commands to the system and to display the current system status. The keypad(s) will be mounted in a convenient locati on inside the protected premises close t o the entry/exit door(s).
The security system has several zones of protection, each connected to one or more sensors (motion detectors, glassbreak detectors, door contacts, etc.). "Alarm Memory" on page14 for information on sensors in alarm for this Touchscreen keypad.

About Your Security System

Your DSC Security System has been designed to provide you with the greatest possible flexibility and con­venience. Read this manual carefully and have your install er instruct you on your system's operation and on which features have been impl emented in your system. All users of this system should be equally instructed in its use. Fill out the “System Information” page with all of your zone information and access codes and store this manual in a safe place for future reference.
Note: The PowerSeries security syst em includes specific false alarm reduction features and is classified in accord­ance with ANSI/SIA CP-01-2010 Control Panel Standard - Features for False Alarm Reduction. Please consult your installer for further information regarding the false alarm reduction features built into your system as all are not covered in this manual.
- 6 -
Introduction

Carbon Monoxide Detection (must be enabled by your Installer)

This equipment is capable of monitoring carbon monoxide detectors and providi ng a warning if carbon monoxide is detected. Please read the Family Escape Planning guidelines in this manual and instructions that are available with the carbon monoxide detector.

Fire Detection (must be enabled by your Installer)

This equipment is capable of monitoring fire detection devices such as smoke detectors and providing a warning if a fire condition is detected. Good fire detection depends on having adequate number of detectors placed in appropriate locations. This equipment should be installed in accordance with NFPA 72 (N.F.P.A., Batterymarch Park, Quincey MA 02269). Carefully review the Family Escape Planning guidelines in this manual.

Testing

To ensure that your system continues to function as intended, you must test it weekly. Please refer to the “Testing your System” section in this manual. If your system does not function properly, call your installing company for service.

Monitoring

This system is capable of transmitting alarms, troubles and emergency information to a central station. If you ini­tiate an alarm by mistake, immediately call the central station to prevent an unnecessary response.
Note: The monitoring function must be enabled by the installer before it becomes functional.
Note: There is a communicator delay of 30 seconds in this control panel. It can be removed, or it can be increased
up to 45 seconds, at the option of the end-user by consulting with the installer.
Note: For CP-01 systems, the monitoring function must be enabled by the inst aller before it becomes functional.

Maintenance

With normal use, the system requires minimum maintenance. Note the following points:
l Use the system test described in “Testing Your System” to check the battery condition. We recommend,
however that the standby batteries be replaced every 3 - 5 years.
l For other system devices such as smoke detectors, passive infrared, ultrasonic or microwave motion
detectors, or glassbreak detectors, consult the manufacturer's literature for testing and maintenance instructions.

Important Notice

A security system cannot prevent emergencies. It i s only int ended to alert you and, if included, your central sta­tion of an emergency situation. Security systems are very reliable but they may not work under all conditions, and they are not a substitute for prudent security practices or life and property insurance. Your security system should be installed and serviced by qualified security professionals who should instruct you on the level of protection that has been provided and on system operations.
- 7 -

Specifications and Features

Specifications and Features
Display 7" TFT (800 x 480) pixel) Color Touchscreen
Home button Home/Calibration/Reset
LED indicators 4 (Ready, Armed, Trouble, AC)
Dimensions (mounting) 8.5" x 5.1" x 0.8" [127.9 mm (L) x 195 mm (W) x 20.35 mm (D)]
Horizontal viewing angle 70°
Vertical viewing angle 70° (top), 50° (bottom)
Brightness 280 cd/m²
Operating environment
SD card slot Holds any standard Secure Digital (SD) card* (32 x 24 x 2.1 mm)
*If necessary, the SD card can be formatted to file system FAT16 or 32 using a PC. The maximum size SD card supported is 32GB.

Welcome Screen

The date and time are displayed in the upper right corner of the screen. The system status (i.e., Ready, Armed, Exit Delay etc.) is displayed at the top of the screen.
Figure 2- Welcome Screen
0°C to +49°C (32°F to 120°F)
93% (max) relative humidity non-condensing
- 8 -

Emergency Keys

Emergency Keys
Figure 3- Emergency Screen
When the emergency key is pressed, a new screen is displayed with:
Fire Fire Assistance Required. Press and hold for 2 seconds to activate.
Medical Medical Assistance Required. Press and hold for 2 seconds to activate.
Panic Police Assistance Required. Press and hold for 2 seconds to activate.
Important: The Medical and Panic keys are ON by default. The Fire key will not function unless programmed by the Install er. Please ask your installer if the Fire, Medical and Panic keys are enabled.
Note: These events are recorded in the log.
- 9 -

Arming and Disarming the System

Arming and Disarming the System

Stay Arm (Arming the Perimeter)

Ask your alarm company if this function is available on your system.
Stay arming bypasses the interior protection (i.e., motion sensors) and arms the perimeter of t he system (i.e., doors and windows). Close all sensors (i.e., stop motion and close doors). The Ready ( ) indicator should be on. Press
the Stay Arm button and/or enter your Access Code and do not leave the premises (if your installer has pro-
grammed this button). During exit delay, the Armed ( ) and Ready ( )indicators turn on to visually i ndicate that the system is arming.
When the exit delay expires, the Ready LED turns off, the Armed LED remains on and the keypad stops sounding to indicate that the alarm system is armed.
Note: For SIA FAR listed panels, the Stay Arming exit delay will be twice as long as the Away Arming exit delay.

Silent Exit Delay

If the system is armed using the Stay Arm button or using t he "No Entry" Arming method ([*][9][access code], the audible progress annunciati on (keypad buzzer) is silenced and the exit time doubled for that exit period only (CP­01 versions only).
Note: For non CP-01 versions, Standard exit time is used.
When Stay Arm is selected from the Home screen:
l The display indicates “Exit Delay in Progress,” and the pre-programmed exit delay begins.
l The Armed LED Indicator turns on.
If Quick Arm is not enabled by the installer, then a numerical keypad is displayed (see following figure). Enter a valid access code to proceed.
Figure 4- Keypad
If Disarm is selected during the exit delay, a numeric keypad is displayed.
l Enter (tap) your access code.
l The arming sequence is aborted and the system returns to the Home screen.
l The Armed LED turns OFF.
At the end of the pre-programmed exit delay:
- 10 -
Arming and Disarming the System
l The Disarm screen is displayed.
l The Ready Indicator turns OFF.
l “Stay Armed-Bypass” is displayed in the Status Bar.
Note: This screen will go into stand-by mode after 15 minutes. Tap the screen to restore the display.

Disarm

If Disarm is selected:
l A numerical keypad is displayed.
l Enter your Access Code in the keypad.
l The system returns to the Home screen and the red Armed indicator turns OFF.
l The alarm status is momentarily displayed in t he status bar, then "Ready" is displayed.
l The green Ready indicator turns ON.
Note: If your code is invalid, the system will not disarm and a 2-second error tone will sound. If this happens, press # and try again.

Away Arm

When Away Arm is selected:
l Enter a valid access code to proceed.
l The Armed LED Indicator turns ON.
l "Exit Delay in Progress" is displayed in the Status Bar. The pre-programmed exit delay begins.
l The touchscreen "beeps" at a 1-second urgency interval during the exit delay. Then 3 beeps sound in the
last 10 seconds.
Note: If Quick Arm is not enabled by t he installer, a numerical keypad is displayed.
If Disarm is selected during the exit delay:
l A numeric keypad i s displayed. Tap your access code.
l The Arming sequence is aborted and the system returns to the Home screen.
l The Armed LED turns OFF.
At the end of the pre-programmed exit delay:
l The Disarm screen is displayed.
l The Ready Indicator turns OFF.
l "Away Armed" is displayed in the Status Bar.

Exit Delay Time Restart

The control panel provides an option where if an entry/exit zone is tripped, a second time prior to the end of the exit delay, the exit delay time restarts. The exit delay timer can only be restarted once.

Alarm Cancel Window

The control panel provides a period of time in which the user can cancel the alarm transmission. The minimum dur­ation of this time is five minutes. If the programmed alarm transmission delay has expired, canceling an alarm sends a message to the monitoring station. Upon a successful transmission of the cancelation message, the keypad will beep 6 times.
- 11 -
Arming and Disarming the System

Bell/Siren Sounds After Away Arming

Audible Exit Fault

In an attempt to reduce false alarms, the Audible Exit Fault is designed to notify you of an improper exit when arming t he system in the Away mode. In the event that you fail to exit the premises during the allotted exit delay period, or if you do not securely close the Exit/Entry door, the system wil l noti fy you that it was improperly armed in two ways: the keypad will emit one continuous beep and the bell or siren will sound.
Your installer will tell you if this feature has been enabled on your system. If this occurs:
1. Re-enter the premises.
2. Enter your access code to disarm the system. You must do this before the entry delay timer expires.
3. Follow the Away arming procedure again, making sure to close the entry/exit door properly.

Arming Error

An error tone will sound if the system is unable to arm. This will happen if the system is not ready to arm (i.e., sensors are open), or if an incorrect user code has been entered. If this happens, ensure all sensors are secure. Press [#] and try again, ensuring that a valid access code is entered. Please check with your install er to determine if arm­ing is inhibited by any other means.

Remote Arming and Disarming

The system can be armed and/ or disarmed using the remote wireless key or proximity tag. When arming the sys­tem by using the Arm button on the wireless key, the system will acknowledge the command by sounding a single bell squawk (if bell squawk is enabled). When disarming using the Disarm button on the wireless key, the system will acknowledge the command by sounding two bell squawks (if bell squawk is enabled) that can be heard from the exterior of the premises.
To arm the system with a proximity tag:
l Present your proximity tag to a keypad equipped with a proximity sensor anytime the system Ready
indicator is on.
l If configured by your installer, enter your access code.
To disarm the system with a proximity tag:
l Present your proximity tag to a keypad equipped with a proximity sensor anytime the system is armed.
(Armed indicator is on) and if configured as required, enter your access code.
l If you walk through the entry door the keypad will beep. Present your Proximity tag within ____
seconds t o avoid an alarm condition.

Using Your System

This section provides additional information about how to use your alarm system.

When Alarm Sounds

The system can generate 3 different alarm sounds:
l Temporal/pulsed siren = Fire Alarm
l 4 beeps, 5-second pause, 4 beeps = Carbon Monoxide Alarm
l Continuous siren = Intrusion (Burglary Alarm)
Note: The priority of signals is fire alarm, carbon monoxide alarm and medical alarm, then burglary alarm.
Note: Medical alarm is silent. It only results in an alarm transmission to the monitoring station.

Intrusion (Burglary) Alarm Continuous Siren

If you are unsure of the source of the alarm, approach with caution! If the alarm was accidental, enter your Access Code to silence the alarm. Call your central station to avoid a dispatch.
- 12 -
Arming and Disarming the System
If the Intrusion Alarm was Accidental
1. Enter your Access Code to silence the alarm. If the code is entered within 30s (or the programmed value of the alarm transmission delay) the transmission of the alarm to the monitoring station will be canceled.
2. Call your central station to avoid a dispatch.

Fire Alarm Pulsed Siren

Follow your emergency evacuation plan immediately!
If the fire alarm was accidental (e.g., burned toast, bathroom steam, etc.), enter your Access Code to silence the alarm. Call your cent ral station to avoid a dispatch. To reset the detectors, see the Sensor Reset section.

Wireless Carbon Monoxide Alarm

Activation of your CO alarm indicates the presence of carbon monoxide (CO), which can be fatal. During an alarm, the red LED on the CO detector flashes rapidly and the buzzer sounds with a repeating cadence of: 4 quick beeps, 5-second pause, 4 quick beeps. Also, during an alarm, the siren connected to the control panel produces a repeat­ing cadence of 4 quick beeps, 5-second pause, 4 quick beeps. The keypad will also provide audible and visual indication of the CO alarm.
If an Alarm Sounds:
1. Operate silence button.
2. Call emergency services or your fire department.
3. Immediately move outdoors or to an open door/window.
Warning: Carefully review your Carbon Monoxide Installation/User Guide to determine the necessary actions required to ensure your safety and ensure that the equipment is operating correctly. Incorporate the steps outlined in the guide into your evacuation plan.
- 13 -

Troubles

Troubles
When a trouble condition is detected, the Trouble (!) or System indicator will turn on, and the keypad will
beep every 10 seconds. Press the (!) key to silence the beeps. Press (!) to view the trouble condition. The
Trouble (!) or System indicator will flash. The corresponding trouble will light up.
Troubles Comments Action
Service Required (Press for more details)
AC Loss
Phone Trouble The system has detected that the telephone line is disconnected.
Communication
Failure
Zone Fault
Zone Tamper
Wireless Low Battery
Loss of Clock
Limit Exceeded
Low Battery General System Supervision
Bell Circuit RF Jam Detected
General System Trouble Panel Low Battery
General System Tamper Panel AC Loss
If the building and/or neighborhood has lost electrical power, the system will continue to operate on battery for several hours.
The system attempted to communicate with the monitoring station, but failed. This may be due to Telephone Line Fault.
The system is experiencing difficulties with one or more sensors on the system. Press to display the zone.
The system has detected a tamper condition with one or more sensors on the sys­tem. Press to display the zone.
The system has detected a low battery condition with one or more mod­ules/sensors on the system. Press to display the zone, keypad, wireless key(s) and RF Delinquency low battery conditions. Press again to see zone troubles.
If complete power was lost (AC and Battery), the time and date will need to be reprogrammed.
[01] Interactive zone: The number of zones configured in the panel is not sup­ported by ADC firmware (e.g.:>220)
[02] Interactive partition: The number of partitions configured is not supported by ADC firmware (e.g.:>8)
Call for
service
Call for
service
Call for
service
Call for
service
Call for
service
Call for
service
Call for
service
Reprogram
Time &
Date

Alarm Memory

When an alarm occurs, the Alarm indicator flashes.
To view which sensor(s) generated the alarm, press Alarms.
The sensor number where the alarm occurred will be displayed (e.g., zone 3). Use the [<][>] scroll keys to view the sensors in alarm memory. Press Back or Home to exit. To clear the memory, arm and disarm the system. If an alarm sounded while armed, the keypad will automatically go to alarm memory when you disarm the system. In this instance, you should approach with caution, as the intruder may still be within the building/premises.
- 14 -
Troubles
Figure 5- Alarms in Memory

Sensor Reset

Certain sensors, after having detected an alarm condition, require a reset to exit the alarm condition (e.g., glass break sensors, smoke detectors, etc.). Ask your alarm company if this function is required on your system.
To reset the detectors, press the Reset (Command Output 2 if the installer did not program a label) button on t he Outputs screen. If a sensor fails to reset, it may still be detecting an alarm condition. If the sensor reset is suc­cessful, the alarm is canceled. If unsuccessful, the alarm will reactivate or continue.

Outputs

Your installer may have programmed these keys to perform various functions (reset smoke detector after an alarm, open your garage door, etc.) To activate these functions, press Output and then press the appropriate option. For additional information, refer to the section: Sensor reset.
Figure 6- Outputs
- 15 -

Additional Functions

Additional Functions

Photos

You can create a slideshow of photos to View on the keypad. Photos are added using an SD card (32x24x2.1 mm. Not suppli ed).
The photos must be .jpg format and can be up to 1280 x 720 in size. For best results, use 800 x 480 resolution. Use photo editing software to adjust the size of your photos.
To start the slideshow, set the screen saver to photo mode. The slideshow plays automatically until the timeout is reached or the screen is touched again.
To add photos:
1. Press Options, User Functions, Keypad Config, Picture Frame, Select Photos. Thumbnail i mages of the photos on your SD card are displayed.
2. Touch an image to add it to the slideshow. Touch it a second time to remove it.
Use the Transition Time slider to program the amount of time each photo is on screen, from 5 seconds to 1 minute.
Use the Photo Frame Timeout slider to control how long your slideshow plays for, from 1 minute to 2 hours. Select Never to keep the slideshow runni ng until the screen is touched.
Note: Maximum of 255 photos are supported.

Quick Exit

If the system is armed and you need to exi t, use the quick exit function to avoid disarming and rearming the sys­tem. To activate this function, tap the Quick Exit icon. You have 2 minutes to leave the premises through your exit door. When the door i s closed again the remaining exit time is canceled.

Time & Date Programming

Tap on Options. Select User Functions [Master Code] and then select Time & Date. Tap on t he section you would like to change and use the up/down arrows to change time/date. Once done, press Save.

Keypad Mode

This option allows the HS2TCHPRO/HS2TCHPROBLK Touchscreen to function as a traditional DSC keypad.

Door Chime (Chime enable/disable)

The keypad indicates the current state of the door chime function (Enabled or Disabled). To choose the opposite function, tap the 'Chime' icon. Three beeps indicate that the chime is ON (Enabled). One long beep indicates that chime is OFF (Disabled).
Note: The door chime feature should be used i n Disarmed mode only.

Zone Bypass

This screen allows you to view the status of the zones on the system.
- 16 -

Options Menu

Figure 7- Zone Cl osed

Zone Status Indicators

Ready Zone is closed
Open The zone is open and needs to be closed

Bypassed Zones

Use the zone bypass feature when a zone is open but the system needs to be armed. Bypassed zones will not cause an alarm when opened. Bypassing zones reduces the level of security. If you are bypassing a zone because it is not functioning, call a service t echnician immediately so that the problem can be resolved and your system returned to proper working order.
Ensure that no zones are unintentionall y bypassed when arming your system. Zone bypassing can only be per­formed while the system is disarmed. Bypassed zones are automatically canceled each time the system is disarmed and must be bypassed again, if required, before the next arming.
Note: 24-hour zones can only be unbypassed manually.
Note: For security reasons, your installer has programmed the system to prevent certain zones from being
bypassed. (e.g., smoke detectors).

Bypassing Zones with a HS2TCHPRO/HS2TCHPROBLK

When in the Zone Status page, scroll up/down through the desired zones, and tap on the bypass icon to bypass the zone. To unbypass a zone, tap t he unbypass icon.
Note: For UL listed installations, zones can only be bypassed manually.
Options Menu
Access the following functions by pressing Options on the right side of the home page. See the online HS2TCHPRO/HS2TCHPROBLK User Manual for more information.
l Access Codes
l Installer Menu
l User Functions
l Chime Enabled/Disabled
l Partition Status
l Keypad Mode
- 17 -
Options Menu
Figure 8- Options

Access Codes

When Access Codes is selected from the Options menu, the keypad prompts for a Master Code. When a valid Master Code is entered, a numeric keypad is displayed with arrows to scroll through the list of users. Press the Select button to enter the user options.
Set Access Code: adds/edits the 4-digit or 6-digit code Set Partitions: assigns the user to partitions User Options: enables/disables different options for the user Delete User: deletes the user from the system
The access codes have programmable attributes which allow zone bypassing, or one-time use activation.
Master Code (Access Code 01): The master code, if programmed, can only be changed by the installer. Supervisor Codes: These codes can be used to program additional codes which have equal or lesser attributes.
Once programmed, the supervisor codes receive the master code’s attributes. These attributes are changeable. Any user code can be made a supervisor code by enabling User Code Attribute 1 (see the following for details).
Duress Codes: Duress codes are standard user codes that transmit the Duress Reporting Code when entered to
perform any function on the system. Any user code can be made a duress code by enabling User Code Attribute 2 (see the following for details).
Note: Duress codes are not valid when entering User Programming, Master Functions or Installer’s sections.
Note: Access codes cannot be programmed as a duplicate or as a “Code +/- 1”.

Assign Proximity Tags

Depending on how your keypad is programmed, proximity tags can be used to either arm/disarm the system or to perform a programmed function (e.g. unlock a cabinet or storeroom door). Present the tag to the tag reader.
1. Press [*][5]Master/Supervisor Code].
2. Enter a 4-digit or 6-digit user code.
3. Press 2.
4. Pass the enrolled tag near the tag reader.

Delete Proximity Tags

To delete a proximity tag:
1. Select Options, Access Codes [enter Master code].
2. Select a user to delete.
- 18 -
Options Menu
3. Select Prox Tag Prog then delete.

User Code Attributes

1. The default attributes of a new code will be the attributes of the code used to enter User Programming whether it is a new code or an existing code being programmed.
2. System Master Code 01 has partition access for all partitions, as well as attributes 3-4 ON by default.
Note: These attributes are not changeable.

Inherent Attributes (all codes except installer and maintenance)

Arm/Disarm: Any access code with partition access enabled wi ll be valid for arming and disarming that par-
tition.
Command Outputs ([*][7][1], [*][7][2], [*][7][3], and [*][7][4]): If these outputs require access code
entry, any Access Code with partit ion access will be valid for performing the command output functions on that partition.

Programmable Attributes

1. Supervisor Code 5. For Future Use
2. Duress Code 6. For Future Use
3. Zone Bypassing Enabled 7. Bell Squawk upon Arming/Disarming
4. Remote Access 8. One Time Use Code

Bell Squawk Attribute

This attribute is used to determine whether an access code should generate an arming/disarming Bell Squawk upon entry of the code for Away arming. The wireless keys with access codes associated with them may generate Arm­ing/Disarming Bell squawks. If desired, this option may be used with codes that are manually entered. Please con­tact your installer to have this programmed.
Note: The Master Code cannot use the Bell Squawk attribute, but is required to enable it for other codes.
Note: This feature cannot prevent the Arming/Disarming squawks from being generated if an access code assigned
to a wireless key is manually entered at a keypad.
Note: This feature is used to annunciate fire trouble signals and also trouble conditions for medical applications.

Partition Assignment

1. This section is used to assign users to available partitions. To assign partitions:
2. Select Options > Access Codes.
3. Enter the master code.
4. Select a user.
5. Select Partition Attributes.
6. Select the partition(s) to assign to the user.
Notes on Access Codes and Programming
l The master code’s attributes cannot be changed. l When a new code is programmed in User Programming it will be checked against all other codes in the
system. If a duplicate code is found, an error tone is given and the code i s returned to what it was before it was changed. This applies to both 4 and 6-digit codes.

Erasing an Access Code

To erase a code, select the code and choose Delete User. The system will delete the code immediately and the user will be returned to select another code.

Installer Menu

These functions are for the installer’s use only.
- 19 -
Options Menu

User Functions

First disarm the system then enter Options, User Functions, then Master Code. This command is used to gain access to the fol lowing list of master functions of the system:

Time and Date

Enter desired time and date.

Auto-Arm Time

The system can be programmed to arm at a programmed time each day, per partition. Upon entry of this section, enter the desired Auto-Arm time for each day of the week.
At the selected Auto-Arm time, the keypad buzzers will sound for a programmed amount of time (programmable by the installer only) to warn that an auto-arm is in progress. The bell can also be programmed to squawk once every 10 seconds during this warning period. When the warning period is complete, the system will arm with no exit delay and in Away mode.
Auto-Arming can be canceled or postponed by entering a vali d access code only during the programmed warning period. Auto-Arming will be attempted at the same time the next day. When the Auto-Arming process is canceled or postponed, the Auto-arm Cancelation Reporting Code will be transmitted (if programmed).
If arming is inhibited by one of the following, the Auto-Arm Cancelation transmission will be communicated:
l AC / DC Inhibit Arm
l Latching System Tampers
l Zone Expander Supervisory Fault
Note: For UL/ULC listed installations, the auto-arm feature shall be canceled when there are zones in an off-nor­mal condition.

Enable DLS/Allow System Service

If enabled, the installer will be able to access Installer Programming via remote (DLS). The DLS window will remain open for 6 hrs, during which time the inst aller will be able to enter DLS an unlimited number of times. After the 6-hr window has expired, Installer’s Programming will be unavailable again until the window is re­opened.

Event Buffer

l Displays the date, time and the full description of the event
l The Log is organized from the most recent event (Top) to past events (Down)
l The Left arrow scrolls forward in time
l The Right arrow scrolls back in time
l The Back returns you to the Home screen
l This screen will time out to the Home screen after 30 seconds of inactivity

System Test

The system’s bell output, keypad lights and communicator are tested. This test will also measure the panel’s standby battery.
Important:
l To ensure that your system continues to function as intended, you must test your system weekly.
l For UL HOME HEALTH CARE listed appli cations, the system shall also be tested weekly without AC
power. To remove AC from the control unit, remove the screw from the restraining tab of the plug in adapter and remove the adapter from the AC outlet. After completing the test of the unit using only the battery backup source, reconnect the plug in adapter and attach the screw through the restraining tab, so that the adapter is securely attached to the outlet.
l Should your system fail to function properly, contact your installation company immediately.
- 20 -
Options Menu
l All smoke detectors must be tested by your smoke detector installer once a year to ensure proper oper-
ation.

Auto-Arm/Disarm Control

Pressing Auto-Arm while in the User Function menu will enable (three beeps) or disable (one long beep) the Auto-Arm and Auto-Disarm feature, by partition. Wi th thi s feature enabled, the panel will automatically arm in Away mode (Stay/Away zones active) or disarm at the same time each day. The Auto-Arm time is programmed with the Auto-Arm time button. Auto-Disarm must be programmed by the syst em installer.

User Call-up

This option gives your service provider temporary access to the alarm control panel for remote servicing.

Engineer's Reset

If an alarm has occurred on your system, the system will not allow you to rearm (Ready light is OFF). You will need to contact your installer. They will check and reset the system for you. This may involve a visit to check your system. After the reset is performed, your system will function properly again.

Keypad Configuration

Figure 9- Keypad Configuration
Display Options: sets the brightness and screen timeout of the Touchscreen, as well as screen saver options. Buzzer Control: sets the buzzer volume of the Touchscreen. Note: For SIA CP-01, the buzzer volume shall not
be placed at the minimum setting.
Note: For UL/ULC installations, the buzzer level shall not be changed from the default level.
Picture Frame: selects the pictures that will be displayed on the slideshow. Calibration: calibrates the Touchscreen. Clock Mode: displays the digital clock. Clean Mode: allows the user to touch (i.e., clean) the screen without enabling or disabling any functions. The
screen will remain in this mode for 30 seconds, then return to the Keypad Configuration screen.
- 21 -
Options Menu
Figure 10- Clean Mode
Home Page: can be configured in one of two different views, Classic (square buttons) and Contemporary
(rondel).

Chime Enabled/Disabled

Door Chime: To turn the door chime function On/Off, tap t he Chime icon. 3 beeps indicate that the chime is
ON. 1 long beep i ndicates the Chime is OFF.

Arming

Stay Arm: arms the system in Stay mode Away Arm: arms the system in Away mode Night Arm: To fully arm the syst em when it has been armed in Stay Mode, press Night Arm button. All interior
zones will now be armed except for devices programmed as Night Zones. Night zones are only armed in Away mode. Thi s permits limited movement within the premises when the system is fully armed. Ensure that your installer has provided you with a list identifying zones programmed as night 18 zones. When the interior zones have been activated (i.e., Night Arm), you must enter your access code to disarm the system to gain access to interior areas that have not been programmed as night zones.
Quick Exit: refer to the section: Quick Exit Global Away Arm: arms all partitions to which the User Code is assigned, in Away mode. Global Stay Arm: arms all partitions to which the User Code is assigned, in Stay mode. No Entry Arm: arms the system with no entry.

Partition Status

To view the partition status, press Options, User Functions, then Partition Status. The keypad shows basic status for up to 8 partitions, depending on the configuration of your system. Each partition is identified along with its current status.
- 22 -

Managing Partitions

Figure 11- Partition Status

Keypad Mode

This option allows the HS2TCHPRO/HS2TCHPROBLK Touchscreen to function as a traditional DSC keypad.
Managing Partitions
A partition is a limited area of the premises which operates i ndependently from the other areas. Partitioning a sys­tem can be beneficial if the property has outbuildings that need to be secured independently of a main area or if the home has a separate apartment. Each partition can have it s own keypad, or a keypad can have access to all par­titions. User access to partitions is controlled via access code. A master code can access the entire system and par­titions, while a user code is limited to assigned partitions.

Partitions

Keypads can be configured to control an individual partition or all partitions.
Note: Access to this feature must be configured by your installer.

Single Partition Operation

Single partition keypads provide access to alarm functionality for an assigned partition.
Single partition keypads behave as follows:
l Displays the armed set state of the partition. l Displays open zones, if assigned to the partition the keypad is on. l Displays bypassed zones and allows zone bypassing or creating bypass groups of zones assigned to the
keypad partition.
l Displays system troubl es (system low battery, system component faults/tampers). l Displays alarms in memory that occurred on the partition. l Allows the door chime to be Enabled/disabled. l System test (sounds bells/PGMs assigned to the partition). l Label programming (zone, partition and user labels for the partition). l Command output controls (outputs assigned to the partition, or global outputs such as smoke detector
reset).
l Temperatures.

Loaning a Keypad to Another Partition

The HS2TCHPRO/HS2TCHPROBLK Touchscreen Keypad can be loaned to operate on other partiti ons. When a keypad is loaned to another partition, it will behave on the loaned partition as if it was originally assigned there. An access code must be entered before loaning a keypad to another partition. An access code is also required to perform any function on that partition.
- 23 -
Managing Partitions
To loan a keypad to another partition:
1. Select Options > Partition Status.
2. Enter your access code.
3. Select the partition to loan the keypad to. If the keypad is inactive for more than 30 seconds, it will return to its original partition.

Global Keypad Operation

Once a valid access code is entered, a global keypad will display the status of any partitions that the user has per­mission to view. From this overview, you can loan the global keypad to a partition, arm all partitions or disarm all partitions. The status of each partition will be identified by a partition status icon. For an explanation of par­tition status icons, see the table below. The global arm and global disarm buttons will arm or disarm all displayed partitions.
To Loan a Global Keypad to Another Partition:
1. Select Partition Status.
2. Select the partition to loan the keypad to.
Figure 12- Global Keypad Mode
Partition
Status Icon
Description
GREEN BACKGROUND Partition is ready to be armed
Partition is in exit delay
GRAY BACKGROUND Partition is not ready to be armed
Partition is in alarm
Partition is in entry delay
Partition is armed
- 24 -
Managing Partitions

Fire and CO Zone Types

l If a Fire zone generates an alarm only the partition the fire zone is assigned to will go into alarm. Other
partitions retain their current state.
l If the [F] key on a global keypad is used to generate an alarm all enabled partitions will go into alarm. l One or more fire keypads may be located on any partition. l On alarm, the fire auto-scroll display appears on all partition keypads and on all global keypads. Fire
alarm silence and fire system reset may be done directly on any partition keypad. To silence a fire or CO alarm from a global keypad requires that the global keypad be loaned to one of the partitions.
- 25 -

Testing Your System

Testing Your System
Note: If you are going to perform a System Test, call your Monitoring Station to inform them when you begin and also when you end the test.

Testing Your Keypad Sounder and Siren

The System Test performs a two-second check of the keypad sounder and bell or siren, in addition to testing the keypad status lights and the panel backup battery.
1. Press Options, User Functions [Master Code], then System Test. The following will occur:
- The system activates all keypad sounders and bells or sirens for 2 seconds. All keypad lights turn ON.
- The Ready, Armed, and Trouble LEDs will flash for the duration of the test.
2. To exit the function menu, press [#].

Testing Your Entire System

All smoke detectors in this installation must be tested by your smoke detector inst aller or dealer once a year to ensure they are functioning correctly. It is the user’s responsibility to test the system weekly (excluding smoke detectors). Ensure you follow all the steps in the “Testing Your Keypad Sounder and Siren” section.
Note: Should the system fail to function properly, call your installation company for service immediately.
1. Prior to testing, ensure that the system is disarmed and the Ready light is on.
2. Close all zones to return the system to the Ready state.
3. Perform a Syst em Test by following the steps in the “Testing Your Keypad Sounder and Siren” section.
4. To test the zones, activate each detector in turn (e.g., open each door/window or walk in motion detector areas).
On an HS2TCHPRO/HS2TCHPROBLK keypad, the following message will be displayed when each zone
(detector) is activated: “Ready to Force,” “Not Ready”. Use the zone status but ton t o view which zones are open. The message wi ll disappear when the zones are closed.
Note: Some features described above will not be functional unless enabled by your installer. Ask your installer which features are functional on your system.

Walk Test Mode

The installer can initiate a Walk Test mode for the system. While in Walk Test mode, the Ready, Armed, and Trouble LEDs will flash to indi cate that Walk Test i s active. When the system automatically terminates the Walk Test mode, it will annunciate wi th an audible warning (5 beeps every 10 seconds), beginni ng five minutes prior to the termination of the test.

Allowing Computer Access To Your System

From time to time, your installer may need to send information to or retrieve information from your security sys­tem. Your installer will do this by having a computer call your system over the telephone line. You may need to prepare your system to receive this ‘downloading’ call. To do t his, press Options, User Functions [Master Code], then System Serv/DLS from the Touchscreen. This allows downloading for a limited period of time. During this time, the system will answer incoming downloading calls. For more information on this feature, please ask your installer.
- 26 -

Reference Sheets

Reference Sheets
Fill out the following information for future reference and store this guide in a safe place.

System Information Enabled?

[F] FIRE [+] Medical [P] PANIC
The Exit Delay Time is ___ seconds
The Entry Delay Time is ___ seconds

For Service

Central Station Information:

Account #: ________________ Telephone #: ________________

Installer Information:

Company #: ________________ Telephone #: ________________

Battery Installation / Service Date:

__________________________
__________________________
__________________________
If you suspect a false alarm signal has been sent to the central monitoring station, call the station to avoid an unnecessary response.
- 27 -

Access Codes (copy as needed)

HS3032/HS3128/HS3248 MASTER CODE [01]: ______________________
User Access Code User Access Code User
01 35 69 02 36 70 03 37 71 04 38 72 05 39 73 06 40 74 07 41 75 08 42 76 09 43 77 10 44 78 11 45 79 12 46 80 13 47 81 14 48 82 15 49 83 16 50 84 17 51 85 18 52 86 19 53 87 20 54 88 21 55 89 22 56 90 23 57 91 24 58 92 25 59 93 26 60 94 27 61 95 28 62 96 29 63 97 30 64 98 31 65 99 32 66 100 33 67 34 68
Reference Sheets
- 28 -
Reference Sheets

Sensor / Zone Information (copy as needed)

Zone Protected Area Sensor Type
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
- 29 -

Guidelines for Locating Smoke Detectors and CO Detectors

Guidelines for Locating Smoke Detectors and CO Detectors
The following information is for general guidance only and it is recommended that local fire codes and reg­ulations be consulted when locating and installing smoke and CO alarms.

Smoke Detectors

Research has shown that all hostile fires in homes generate smoke to a greater or lesser extent. Experiments with typical fires in homes indicate that detectable quantities of smoke precede detectable levels of heat in most cases. For these reasons, smoke alarms should be installed outside of each sleeping area and on each storey of the home. The following information is for general guidance only and it is recommended that local fire codes and reg­ulations be consulted when locating and installing smoke alarms. It is recommended that additional smoke alarms beyond those required for minimum prot ection be installed. Additional areas that should be protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace and util ity rooms; and any hallways not protected by the required units. On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists, uninsulated ceil­ings, etc. Consul t National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other appropriate national standards for installation recommendations.
l Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these loc-
ations may prevent the unit from detecting smoke.
l Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around
the detector may prevent smoke from entering the unit.
l Do not locate detectors in areas of high humidity.
l Do not locate detectors in areas where the temperature rises above 38°C (100°F) or falls below 5°C
(41oF).
Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72, the National Fire Alarm Code: 29.5.1.1.
Where requi red by other governing l aws, codes, or standards for a specific type of occupancy, approved single­and multiple-station smoke alarms shall be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a sleeping room, with the distance measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
- 30 -
Loading...
+ 74 hidden pages