Tyco ESFR-17 User Manual

Page 1
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Email: techserv@tycofp.com
Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers
16.8 K-Factor
General Description
The TYCO Model ESFR-17 Upright Sprinklers are “Early Suppression, Fast Response Sprinklers” having a nominal K-Factor of 16.8 (Figure 1). They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily used for ceiling-only sprin­kler protection of (but not limited to) the following storage applications:
• Most encapsulated or non-encap­sulated common materials including cartoned, unexpanded plastics.
• Cartoned, expanded plastics.
• Some storage arrangements of rub­ber tires and roll paper.
For more specic criteria, refer to Table 1 in this data sheet as well as the applicable design standard.
The Model ESFR-17 Upright Sprin­klers provide the system designer with an upright option to the traditional pendent ESFR Sprinklers. With a K­Factor of 16.8, Model ESFR-17 Sprin­klers provide system designers with hydraulic and sprinkler placement options not presently available to traditional ESFR Sprinklers having a K-Factor of 14.0. In particular, the Model ESFR-17 Upright Sprinklers are
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cau­tions with respect to handling and installation of sprinkler sys­tems and components. Improp­er handling and installation can permanently damage a sprin­kler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
designed to operate at substantially lower-end head pressures compared to ESFR Sprinklers with 14.0 K-Fac­tors. This feature offers exibility when sizing system piping and positioning the system piping with respect to the ceiling.
Applications for the TYCO ESFR Sprinklers are expanding beyond cur­rently recognized installation stan­dards. For information on research re tests that may be acceptable to an Authority Having Jurisdiction, contact the Technical Services department.
NOTICE
The Model ESFR-17 Upright Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the ap­plicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction (for example, FM Global). Failure to do so may impair the perfor­mance of these devices.
Owners are responsible for maintain­ing their fire protection system and de­vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
In all cases, the appropriate NFPA or FM installation standard must be ref­erenced to ensure applicability and to obtain complete installation guide­lines. The general guidelines in this data sheet are not intended to provide complete installation criteria.
Model/Sprinkler Identification Number (SIN)
TY7126 - Upright K=16.8
Technical Data
Approvals
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi (241,9 LPM/bar
Temperature Ratings
165°F (74°C) 214°F (101°C)
Finish
Natural Brass
1/2
1/2
)
Page 1 of 4 MARCH, 2011 TFP316
Page 2
TFP316
Page 2 of 4
Components:
-
Frame1
-
2 Deflector
-
Compression
3
Screw
-
Hook
4
-
5
Strut
-
Link Assembly
6
-
7
Button
-
Sealing
8
Assembly
-
Ejection Spring
9
-
Deflector Nut
10
10
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING
2
3
WRENCH
4
3-5/8"
5
6
8
(92,1 mm)
9
FLATS
1/2"
(12,7 mm) NOMINAL
MAKE-IN
THERMAL
SENSING
ELEMENT
1-5/8"
(41,3 mm)
7
1
MODEL ESFR-17 UPRIGHT, EARLY SUPPRESSION, FAST RESPONSE
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deector. . . . . . . . . . . . . . . . . . . . . Copper
Compression Screw. . . . . . . . . . .Stainless
Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . . . Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly. . . . . . . . . . . . Beryllium
Nickel w/ Teon*
Ejection Spring. . . . . . . . . . . . . . . . Inconel
Deector Nut . . . . . . . . . . . . . . . . . . Brass
Patents
U.S.A. Patent Numbers:
5,829,532 6,336,509
Additional Patents pending
Design
Criteria
The following general guidelines pro­vided for the TYCO Model ESFR-17 Upright Sprinklers may be used for quick reference.
NOTICE
The National Fire Protection Association (N FPA) and FM Glob a l (FM) p rovi de installation standards that must be used to properly design an automatic sprinkler sy s tem u tilizing Ea r l y S u p p r e s s ion, Fast Response (ESFR) Sprinklers. The guidelines provided by NFPA and FM may differ; consequently, the appropriate sta nd a r d mu s t be us ed fo r a giv e n installation.
* Registered trademark of Dupont
FIGURE 1
UPRIGHT SPRINKLER 16.8 K-FACTOR
In all cases, the appropriate NFPA or FM installation standard must be referenced to ensure app lic abilit y and to obtain complete installation guidelines, since the following general guidelines are not intended to provide complete installation criteria.
In addition to this data sheet, the fol­lowing data sheets describe other TYCO ESFR Sprinklers:
TFP312 — Model ESFR-25 (TY9226), K=25.2 Pendent Sprinkler
TFP315 — Model ESFR-17 (TY7226), K=16.8 Pendent Sprinkler
TFP318 — Model ESFR-1 (TY6226), K=14.0 Pendent Sprinkler
System Type
Wet pipe system
Roof Construction
Unobstructed or obstructed construc­tion; for example, smooth ceiling, bar joists, beam and girder, and so forth.
Where the depths of the solid struc­tural members (beams and stem, for example) exceed 12-inches (302 mm), install ESFR Sprinklers in each chan­nel formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run (16.7%)
Maximum Coverage Area
100 ft2 (9,3 m2)
In some cases, the installation stan­dards permit a greater coverage area.
3/4" NPT
Minimum Coverage Area
64 ft2 (5,8 m2) per NFPA 13/FM 2-0
Maximum Spacing
12 feet (3,7 m) for building heights up to 30 feet (9,1 m)
10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13 — Deflector-to-Ceiling Distance
3 to 12 inches (76 to 305 mm)
FM 2-0
Consult FM and/or FM Guidelines for allowable deector-to-ceiling dis­tances as well as thermal-sensing element-to-ceiling criteria.
Obstructions Below Upright ESFR Sprinklers, Including Branch Lines
Per the requirements of FM, obstruc­tions below upright ESFR Sprinklers can be ignored as follows:
• Open-web bar joists or trusses hav­ing chords no more than 4 inches (102 mm) wide.
• Bridging or wind bracing no more than 4 inches (102 mm) wide.
• Individual pipes and conduit 4 inches (102 mm) diameter or less 3-inch (DN80) pipe size or less will not re­quire sprigs).
• Individual groups of smaller pipe or conduit having a total width of 4 inches or less.
Page 3
TFP316
Page 3 of 4
Storage Type NFPA FM
Open Frame (that is, no solid shelves) Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics
Refer to NFPA 13, Chapters 16 and 17. Refer to FM 2-0 and 8-9.
Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics
Idle Pallet Storage Refer to NFPA 13, Chapter 12. Refer to FM 2-0, 8-9, and 8-24.
Rubber Tire Storage Refer to NFPA 13, Chapter 18. Refer to FM 2-0 and 8-9.
Rolled Paper Storage (Refer to the standard.) Refer to Chapter 13, Chapter 19. Refer to FM 8-21.
Flammable Liquid Storage (Refer to the standard.) N/A N/A
Aerosol Storage (Refer to the standard.) N/A N/A
Automotive Components in Portable Racks (Control mode only; refer to the standard.)
N/A = Non-Applicable
Refer to NFPA 13, Chapters 14 and 15. Refer to FM 2-0 and 8-9.
N/A N/A
TABLE 1
MODEL ESFR-17 UPRIGHT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Operation
The fusible link assembly is comprised of two link halves that are joined to­gether by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and owing water.
Installation
The TYCO Model ESFR-17 Upright Sprinklers must be installed in accor­dance with the following instructions.
NOTICE
Avoid damage to the fusible Link As­sembly during installation by using the Frame arms only to handle the sprinkler (that is, do not apply pres­sure to the fusible Link Assembly) and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.
Obtain a leak-tight 3/4 inch NPT sprin­kler joint by applying a minimum-to­maximum torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impair­ment of the sprinkler.
1. Install the Model ESFR-17 Upright
Sprinkler in the Upright position (Figure 2).
2. With pipe-thread sealant applied,
hand-tighten the sprinkler into the sprinkler tting. Do not apply pres­sure to the Link Assembly, and handle the Model ESFR-17 Sprin­kler only by the Frame arms.
3. Wrench-tighten the Model ESFR-17
Sprinkler using only the W-Type 21 Sprinkler Wrench (Figure 2) and by fully engaging (seating) the wrench on the sprinkler wrench ats (Fig­ure 1).
4. After installation, inspect the Link
Assembly of each Model ESFR-17 Sprinkler for damage. In particu­lar, verify that the Link Assembly and Hook are positioned as illus-
WRENCH
RECESS
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE 2
W-TYPE 21
SPRINKLER WRENCH
trated in Figure 1, and that the Link Assembly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.
Page 4
TFP316
Page 4 of 4
Care and Maintenance
The TYCO Model ESFR-17 Sprinklers must be maintained and serviced in accordance with the following instructions.
NOTICE
Before closing a fire protection system mai n contr o l v a lve fo r m a inte n a n c e work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action.
Exercise care to avoid damage before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory.
Replace sprinklers that:
• were modied or over-heated.
• were damaged by dropping, strik­ing, wrench twisting, wrench slip­page, or the like.
• are leaking or exhibiting visible signs of corrosion.
Responsibility lies with the owner for the inspection, testing, and mainte­nance of their re protection system and devices in compliance with this document, as well as with the appli­cable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions.
Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualied Inspection Service in accordance with local requirements and/or national codes.
Limited Warranty
Products manufactured by Tyco Fire Suppression & Building Prod­ucts (TFSBP) are war ranted solely to the original Buyer for ten (10) years against defects in mate rial and work­manship when paid for and properly installed and maintained under nor­mal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or com ponents manufactured by companies not afli­ated by ownership with TFSBP or for products and components which have been subject to misuse, improper in­stallation, corrosion, or which have not been installed, maintained, modi­ed or repaired in accordance with ap plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFSBP to be defective shall be ei­ther repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connec­tion with the sale of products or parts of prod ucts. TFSBP shall not be re­sponsible for sprinkler system design errors or inac curate or incomplete in­formation sup plied by Buyer or Buy­er’s repre sentatives.
In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for inciden­tal, indirect, special or consequential dam ages, including but not limited to labor charges, regardless of whether TFSBP was informed about the pos­sibility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price.
The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warran­ties of merchantability and tness for a particular purpose.
This limited warranty sets forth the ex­clusive remedy for claims based on failure of or defect in products, materi­als or components, whether the claim is made in contract, tort, strict liability or any other legal theory.
This warranty will apply to the full ex­tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indi­cate the full product name. Refer to the Price List for a complete listing of Part Numbers (P/Ns).
Sprinkler Assemblies
Specify: (temperature rating), natural brass, TY7126 Upright Sprinkler, P/N (below).
165°F (74°C) . . . . . . . . . . . . . . .P/N 58-447-1-165
214°F (101°C) . . . . . . . . . . . . . .P/N 58-447-1-214
Special-Order Sprinkler Assemblies with ISO 7/1 Thread Connections
Specify: (temperature rating), natu­ral brass, TY7126 Upright Sprinkler with ISO 7/1 thread connection, P/N (below).
165°F (74°C) . . . . . . . . . . . . . . P/N 58-448-1-165
214°F (101°C) . . . . . . . . . . . . . P/N 58-448-1-214
Sprinkler Wrench
Specify: W-Type 21 Sprinkler Wrench, P/N 56-001-0-686.
Copyright © 2007-2011 Tyco Fire Suppression & Building Products. All rights reserved.