Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Email: techserv@tycofp.com
Model ESFR-17
Early Suppression, Fast Response Upright Sprinklers
16.8 K-Factor
General
Description
The TYCO Model ESFR-17 Upright
Sprinklers are “Early Suppression,
Fast Response Sprinklers” having a
nominal K-Factor of 16.8 (Figure 1).
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled storage.
Model ESFR-17 Sprinklers are
primarily used for ceiling-only sprinkler protection of (but not limited to)
the following storage applications:
• Most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics.
• Cartoned, expanded plastics.
• Some storage arrangements of rubber tires and roll paper.
For more specic criteria, refer to
Table 1 in this data sheet as well as
the applicable design standard.
The Model ESFR-17 Upright Sprinklers provide the system designer with
an upright option to the traditional
pendent ESFR Sprinklers. With a KFactor of 16.8, Model ESFR-17 Sprinklers provide system designers with
hydraulic and sprinkler placement
options not presently available to
traditional ESFR Sprinklers having
a K-Factor of 14.0. In particular, the
Model ESFR-17 Upright Sprinklers are
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions with respect to handling
and installation of sprinkler systems and components. Improper handling and installation can
permanently damage a sprinkler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
designed to operate at substantially
lower-end head pressures compared
to ESFR Sprinklers with 14.0 K-Factors. This feature offers exibility when
sizing system piping and positioning
the system piping with respect to the
ceiling.
Applications for the TYCO ESFR
Sprinklers are expanding beyond currently recognized installation standards. For information on research
re tests that may be acceptable to an
Authority Having Jurisdiction, contact
the Technical Services department.
NOTICE
The Model ESFR-17 Upright Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the applicable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction (for example, FM Global).
Failure to do so may impair the performance of these devices.
Owners are responsible for maintaining their fire protection system and devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
In all cases, the appropriate NFPA or
FM installation standard must be referenced to ensure applicability and
to obtain complete installation guidelines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Model/Sprinkler
Identification
Number (SIN)
TY7126 - Upright K=16.8
Technical
Data
Approvals
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT
ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi
(241,9 LPM/bar
Temperature Ratings
165°F (74°C)
214°F (101°C)
Finish
Natural Brass
1/2
1/2
)
Page 1 of 4 MARCH, 2011 TFP316
TFP316
Page 2 of 4
Components:
-
Frame1
-
2 Deflector
-
Compression
3
Screw
-
Hook
4
-
5
Strut
-
Link Assembly
6
-
7
Button
-
Sealing
8
Assembly
-
Ejection Spring
9
-
Deflector Nut
10
10
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING
2
3
WRENCH
4
3-5/8"
5
6
8
(92,1 mm)
9
FLATS
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
THERMAL
SENSING
ELEMENT
1-5/8"
(41,3 mm)
7
1
MODEL ESFR-17 UPRIGHT, EARLY SUPPRESSION, FAST RESPONSE
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deector. . . . . . . . . . . . . . . . . . . . . Copper
Compression Screw. . . . . . . . . . .Stainless
Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . . . Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly. . . . . . . . . . . . Beryllium
Nickel w/ Teon*
Ejection Spring. . . . . . . . . . . . . . . . Inconel
Deector Nut . . . . . . . . . . . . . . . . . . Brass
Patents
U.S.A. Patent Numbers:
5,829,532
6,336,509
Additional Patents pending
Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-17
Upright Sprinklers may be used for
quick reference.
NOTICE
The National Fire Protection Association
(N FPA) and FM Glob a l (FM) p rovi de
installation standards that must be used
to properly design an automatic sprinkler
sy s tem u tilizing Ea r l y S u p p r e s s ion,
Fast Response (ESFR) Sprinklers. The
guidelines provided by NFPA and FM
may differ; consequently, the appropriate
sta nd a r d mu s t be us ed fo r a giv e n
installation.
* Registered trademark of Dupont
FIGURE 1
UPRIGHT SPRINKLER 16.8 K-FACTOR
In all cases, the appropriate NFPA or FM
installation standard must be referenced
to ensure app lic abilit y and to obtain
complete installation guidelines, since
the following general guidelines are not
intended to provide complete installation
criteria.
In addition to this data sheet, the following data sheets describe other
TYCO ESFR Sprinklers:
• TFP312 — Model ESFR-25 (TY9226),
K=25.2 Pendent Sprinkler
• TFP315 — Model ESFR-17 (TY7226),
K=16.8 Pendent Sprinkler
• TFP318 — Model ESFR-1 (TY6226),
K=14.0 Pendent Sprinkler
System Type
Wet pipe system
Roof Construction
Unobstructed or obstructed construction; for example, smooth ceiling, bar
joists, beam and girder, and so forth.
Where the depths of the solid structural members (beams and stem, for
example) exceed 12-inches (302 mm),
install ESFR Sprinklers in each channel formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run
(16.7%)
Maximum Coverage Area
100 ft2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
3/4" NPT
Minimum Coverage Area
64 ft2 (5,8 m2) per NFPA 13/FM 2-0
Maximum Spacing
12 feet (3,7 m) for building heights
up to 30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13 — Deflector-to-Ceiling
Distance
3 to 12 inches (76 to 305 mm)
FM 2-0
Consult FM and/or FM Guidelines
for allowable deector-to-ceiling distances as well as thermal-sensing
element-to-ceiling criteria.
Obstructions Below Upright ESFR
Sprinklers, Including Branch Lines
Per the requirements of FM, obstructions below upright ESFR Sprinklers
can be ignored as follows:
• Open-web bar joists or trusses having chords no more than 4 inches
(102 mm) wide.
• Bridging or wind bracing no more
than 4 inches (102 mm) wide.
• Individual pipes and conduit 4 inches
(102 mm) diameter or less 3-inch
(DN80) pipe size or less will not require sprigs).
• Individual groups of smaller pipe
or conduit having a total width of 4
inches or less.