Model ESFR-17
Early Suppression, Fast Response Upright Sprinklers
16.8 K-Factor
General
Description
The TYCO Model ESFR-17 Upright
Sprinklers are “Early Suppression,
Fast Response Sprinklers” having a
nominal K-Factor of 16.8 (Figure 1).
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled storage.
Model ESFR-17 Sprinklers are
primarily used for ceiling-only sprinkler protection of (but not limited to)
the following storage applications:
• Most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics.
• Cartoned, expanded plastics.
• Some storage arrangements of rubber tires and roll paper.
For more specic criteria, refer to
Table 1 in this data sheet as well as
the applicable design standard.
The Model ESFR-17 Upright Sprinklers provide the system designer with
an upright option to the traditional
pendent ESFR Sprinklers. With a KFactor of 16.8, Model ESFR-17 Sprinklers provide system designers with
hydraulic and sprinkler placement
options not presently available to
traditional ESFR Sprinklers having
a K-Factor of 14.0. In particular, the
Model ESFR-17 Upright Sprinklers are
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions with respect to handling
and installation of sprinkler systems and components. Improper handling and installation can
permanently damage a sprinkler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
designed to operate at substantially
lower-end head pressures compared
to ESFR Sprinklers with 14.0 K-Factors. This feature offers exibility when
sizing system piping and positioning
the system piping with respect to the
ceiling.
Applications for the TYCO ESFR
Sprinklers are expanding beyond currently recognized installation standards. For information on research
re tests that may be acceptable to an
Authority Having Jurisdiction, contact
the Technical Services department.
NOTICE
The Model ESFR-17 Upright Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the applicable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction (for example, FM Global).
Failure to do so may impair the performance of these devices.
Owners are responsible for maintaining their fire protection system and devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
In all cases, the appropriate NFPA or
FM installation standard must be referenced to ensure applicability and
to obtain complete installation guidelines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Model/Sprinkler
Identification
Number (SIN)
TY7126 - Upright K=16.8
Technical
Data
Approvals
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT
ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi
(241,9 LPM/bar
Temperature Ratings
165°F (74°C)
214°F (101°C)
Finish
Natural Brass
1/2
1/2
)
Page 1 of 4 MARCH, 2011 TFP316
Page 2
TFP316
Page 2 of 4
Components:
-
Frame1
-
2 Deflector
-
Compression
3
Screw
-
Hook
4
-
5
Strut
-
Link Assembly
6
-
7
Button
-
Sealing
8
Assembly
-
Ejection Spring
9
-
Deflector Nut
10
10
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING
2
3
WRENCH
4
3-5/8"
5
6
8
(92,1 mm)
9
FLATS
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
THERMAL
SENSING
ELEMENT
1-5/8"
(41,3 mm)
7
1
MODEL ESFR-17 UPRIGHT, EARLY SUPPRESSION, FAST RESPONSE
The following general guidelines provided for the TYCO Model ESFR-17
Upright Sprinklers may be used for
quick reference.
NOTICE
The National Fire Protection Association
(N FPA) and FM Glob a l (FM) p rovi de
installation standards that must be used
to properly design an automatic sprinkler
sy s tem u tilizing Ea r l y S u p p r e s s ion,
Fast Response (ESFR) Sprinklers. The
guidelines provided by NFPA and FM
may differ; consequently, the appropriate
sta nd a r d mu s t be us ed fo r a giv e n
installation.
* Registered trademark of Dupont
FIGURE 1
UPRIGHT SPRINKLER 16.8 K-FACTOR
In all cases, the appropriate NFPA or FM
installation standard must be referenced
to ensure app lic abilit y and to obtain
complete installation guidelines, since
the following general guidelines are not
intended to provide complete installation
criteria.
In addition to this data sheet, the following data sheets describe other
TYCO ESFR Sprinklers:
• TFP312 — Model ESFR-25 (TY9226),
K=25.2 Pendent Sprinkler
• TFP315 — Model ESFR-17 (TY7226),
K=16.8 Pendent Sprinkler
• TFP318 — Model ESFR-1 (TY6226),
K=14.0 Pendent Sprinkler
System Type
Wet pipe system
Roof Construction
Unobstructed or obstructed construction; for example, smooth ceiling, bar
joists, beam and girder, and so forth.
Where the depths of the solid structural members (beams and stem, for
example) exceed 12-inches (302 mm),
install ESFR Sprinklers in each channel formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run
(16.7%)
Maximum Coverage Area
100 ft2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
3/4" NPT
Minimum Coverage Area
64 ft2 (5,8 m2) per NFPA 13/FM 2-0
Maximum Spacing
12 feet (3,7 m) for building heights
up to 30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13 — Deflector-to-Ceiling
Distance
3 to 12 inches (76 to 305 mm)
FM 2-0
Consult FM and/or FM Guidelines
for allowable deector-to-ceiling distances as well as thermal-sensing
element-to-ceiling criteria.
Obstructions Below Upright ESFR
Sprinklers, Including Branch Lines
Per the requirements of FM, obstructions below upright ESFR Sprinklers
can be ignored as follows:
• Open-web bar joists or trusses having chords no more than 4 inches
(102 mm) wide.
• Bridging or wind bracing no more
than 4 inches (102 mm) wide.
• Individual pipes and conduit 4 inches
(102 mm) diameter or less 3-inch
(DN80) pipe size or less will not require sprigs).
• Individual groups of smaller pipe
or conduit having a total width of 4
inches or less.
Page 3
TFP316
Page 3 of 4
Storage TypeNFPAFM
Open Frame (that is, no solid shelves)
Single, Double, Multiple-Row, or Portable Rack Storage
of Class I-IV and Group A or B Plastics
Refer to NFPA 13, Chapters 16 and 17.Refer to FM 2-0 and 8-9.
Solid Pile or Palletized Storage of Class I-IV
and Group A or B Plastics
Idle Pallet StorageRefer to NFPA 13, Chapter 12.Refer to FM 2-0, 8-9, and 8-24.
Rubber Tire StorageRefer to NFPA 13, Chapter 18.Refer to FM 2-0 and 8-9.
Rolled Paper Storage (Refer to the standard.)Refer to Chapter 13, Chapter 19.Refer to FM 8-21.
Flammable Liquid Storage (Refer to the standard.) N/AN/A
Aerosol Storage (Refer to the standard.)N/AN/A
Automotive Components in Portable Racks
(Control mode only; refer to the standard.)
N/A = Non-Applicable
Refer to NFPA 13, Chapters 14 and 15.Refer to FM 2-0 and 8-9.
N/AN/A
TABLE 1
MODEL ESFR-17 UPRIGHT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Operation
The fusible link assembly is comprised
of two link halves that are joined together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
owing water.
Installation
The TYCO Model ESFR-17 Upright
Sprinklers must be installed in accordance with the following instructions.
NOTICE
Avoid damage to the fusible Link Assembly during installation by using
the Frame arms only to handle the
sprinkler (that is, do not apply pressure to the fusible Link Assembly)
and by using the appropriate sprinkler
wrench. Failure to do so can lead to an
unstable link assembly and premature
activation of the sprinkler. Damaged
sprinklers must be replaced.
Obtain a leak-tight 3/4 inch NPT sprinkler joint by applying a minimum-tomaximum torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). Higher levels of
torque can distort the sprinkler inlet
with consequent leakage or impairment of the sprinkler.
1. Install the Model ESFR-17 Upright
Sprinkler in the Upright position
(Figure 2).
2. With pipe-thread sealant applied,
hand-tighten the sprinkler into the
sprinkler tting. Do not apply pressure to the Link Assembly, and
handle the Model ESFR-17 Sprinkler only by the Frame arms.
3. Wrench-tighten the Model ESFR-17
Sprinkler using only the W-Type 21
Sprinkler Wrench (Figure 2) and by
fully engaging (seating) the wrench
on the sprinkler wrench ats (Figure 1).
4. After installation, inspect the Link
Assembly of each Model ESFR-17
Sprinkler for damage. In particular, verify that the Link Assembly
and Hook are positioned as illus-
WRENCH
RECESS
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE 2
W-TYPE 21
SPRINKLER WRENCH
trated in Figure 1, and that the Link
Assembly is not bent, creased, or
forced out of normal position in any
way. Replace damaged sprinklers.
Page 4
TFP316
Page 4 of 4
Care and
Maintenance
The TYCO Model ESFR-17 Sprinklers
must be maintained and serviced
in accordance with the following
instructions.
NOTICE
Before closing a fire protection system
mai n contr o l v a lve fo r m a inte n a n c e
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection systems
from the proper authorities and notify all
personnel who may be affected by this
action.
Exercise care to avoid damage before,
during, and after installation. Never
paint, plate, coat, or otherwise alter
automatic sprinklers after they leave
the factory.
Replace sprinklers that:
• were modied or over-heated.
• were damaged by dropping, striking, wrench twisting, wrench slippage, or the like.
• are leaking or exhibiting visible
signs of corrosion.
Responsibility lies with the owner for
the inspection, testing, and maintenance of their re protection system
and devices in compliance with this
document, as well as with the applicable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any authorities having jurisdiction.
Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualied
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco
Fire Suppression & Building Products (TFSBP) are war ranted solely to
the original Buyer for ten (10) years
against defects in mate rial and workmanship when paid for and properly
installed and maintained under normal use and service. This warranty
will expire ten (10) years from date of
shipment by TFSBP. No warranty is
given for products or com ponents
manufactured by companies not afliated by ownership with TFSBP or for
products and components which have
been subject to misuse, improper installation, corrosion, or which have
not been installed, maintained, modied or repaired in accordance with
ap plicable Standards of the National
Fire Protection Association, and/or
the standards of any other Authorities
Having Jurisdiction. Materials found
by TFSBP to be defective shall be either repaired or replaced, at TFSBP’s
sole option. TFSBP neither assumes,
nor authorizes any person to assume
for it, any other obligation in connection with the sale of products or parts
of prod ucts. TFSBP shall not be responsible for sprinkler system design
errors or inac curate or incomplete information sup plied by Buyer or Buyer’s repre sentatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental, indirect, special or consequential
dam ages, including but not limited to
labor charges, regardless of whether
TFSBP was informed about the possibility of such damages, and in no
event shall TFSBP’s liability exceed an
amount equal to the sales price.
The foregoing warranty is made in
lieu of any and all other warranties,
express or implied, including warranties of merchantability and tness for
a particular purpose.
This limited warranty sets forth the exclusive remedy for claims based on
failure of or defect in products, materials or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name. Refer to
the Price List for a complete listing of
Part Numbers (P/Ns).