Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers
16.8 K-Factor
General Description
The TYCO Model ESFR-17 Upright Sprinklers are “Early Suppression, Fast Response Sprinklers” having a nominal K-Factor of 16.8 (Figure 1). They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily used for ceiling-only sprin­kler protection of (but not limited to) the following storage applications:
• Most encapsulated or non-encap­sulated common materials including cartoned, unexpanded plastics.
• Cartoned, expanded plastics.
• Some storage arrangements of rub­ber tires and roll paper.
For more specic criteria, refer to Table 1 in this data sheet as well as the applicable design standard.
The Model ESFR-17 Upright Sprin­klers provide the system designer with an upright option to the traditional pendent ESFR Sprinklers. With a K­Factor of 16.8, Model ESFR-17 Sprin­klers provide system designers with hydraulic and sprinkler placement options not presently available to traditional ESFR Sprinklers having a K-Factor of 14.0. In particular, the Model ESFR-17 Upright Sprinklers are
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cau­tions with respect to handling and installation of sprinkler sys­tems and components. Improp­er handling and installation can permanently damage a sprin­kler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
designed to operate at substantially lower-end head pressures compared to ESFR Sprinklers with 14.0 K-Fac­tors. This feature offers exibility when sizing system piping and positioning the system piping with respect to the ceiling.
Applications for the TYCO ESFR Sprinklers are expanding beyond cur­rently recognized installation stan­dards. For information on research re tests that may be acceptable to an Authority Having Jurisdiction, contact the Technical Services department.
NOTICE
The Model ESFR-17 Upright Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the ap­plicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction (for example, FM Global). Failure to do so may impair the perfor­mance of these devices.
Owners are responsible for maintain­ing their fire protection system and de­vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
In all cases, the appropriate NFPA or FM installation standard must be ref­erenced to ensure applicability and to obtain complete installation guide­lines. The general guidelines in this data sheet are not intended to provide complete installation criteria.
Model/Sprinkler Identification Number (SIN)
TY7126 - Upright K=16.8
Technical Data
Approvals
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi (241,9 LPM/bar
Temperature Ratings
165°F (74°C) 214°F (101°C)
Finish
Natural Brass
1/2
1/2
)
Page 1 of 4 MARCH, 2011 TFP316
TFP316
Page 2 of 4
Components:
-
Frame1
-
2 Deflector
-
Compression
3
Screw
-
Hook
4
-
5
Strut
-
Link Assembly
6
-
7
Button
-
Sealing
8
Assembly
-
Ejection Spring
9
-
Deflector Nut
10
10
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING
2
3
WRENCH
4
3-5/8"
5
6
8
(92,1 mm)
9
FLATS
1/2"
(12,7 mm) NOMINAL
MAKE-IN
THERMAL
SENSING
ELEMENT
1-5/8"
(41,3 mm)
7
1
MODEL ESFR-17 UPRIGHT, EARLY SUPPRESSION, FAST RESPONSE
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deector. . . . . . . . . . . . . . . . . . . . . Copper
Compression Screw. . . . . . . . . . .Stainless
Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . . . Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly. . . . . . . . . . . . Beryllium
Nickel w/ Teon*
Ejection Spring. . . . . . . . . . . . . . . . Inconel
Deector Nut . . . . . . . . . . . . . . . . . . Brass
Patents
U.S.A. Patent Numbers:
5,829,532 6,336,509
Additional Patents pending
Design
Criteria
The following general guidelines pro­vided for the TYCO Model ESFR-17 Upright Sprinklers may be used for quick reference.
NOTICE
The National Fire Protection Association (N FPA) and FM Glob a l (FM) p rovi de installation standards that must be used to properly design an automatic sprinkler sy s tem u tilizing Ea r l y S u p p r e s s ion, Fast Response (ESFR) Sprinklers. The guidelines provided by NFPA and FM may differ; consequently, the appropriate sta nd a r d mu s t be us ed fo r a giv e n installation.
* Registered trademark of Dupont
FIGURE 1
UPRIGHT SPRINKLER 16.8 K-FACTOR
In all cases, the appropriate NFPA or FM installation standard must be referenced to ensure app lic abilit y and to obtain complete installation guidelines, since the following general guidelines are not intended to provide complete installation criteria.
In addition to this data sheet, the fol­lowing data sheets describe other TYCO ESFR Sprinklers:
TFP312 — Model ESFR-25 (TY9226), K=25.2 Pendent Sprinkler
TFP315 — Model ESFR-17 (TY7226), K=16.8 Pendent Sprinkler
TFP318 — Model ESFR-1 (TY6226), K=14.0 Pendent Sprinkler
System Type
Wet pipe system
Roof Construction
Unobstructed or obstructed construc­tion; for example, smooth ceiling, bar joists, beam and girder, and so forth.
Where the depths of the solid struc­tural members (beams and stem, for example) exceed 12-inches (302 mm), install ESFR Sprinklers in each chan­nel formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run (16.7%)
Maximum Coverage Area
100 ft2 (9,3 m2)
In some cases, the installation stan­dards permit a greater coverage area.
3/4" NPT
Minimum Coverage Area
64 ft2 (5,8 m2) per NFPA 13/FM 2-0
Maximum Spacing
12 feet (3,7 m) for building heights up to 30 feet (9,1 m)
10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13 — Deflector-to-Ceiling Distance
3 to 12 inches (76 to 305 mm)
FM 2-0
Consult FM and/or FM Guidelines for allowable deector-to-ceiling dis­tances as well as thermal-sensing element-to-ceiling criteria.
Obstructions Below Upright ESFR Sprinklers, Including Branch Lines
Per the requirements of FM, obstruc­tions below upright ESFR Sprinklers can be ignored as follows:
• Open-web bar joists or trusses hav­ing chords no more than 4 inches (102 mm) wide.
• Bridging or wind bracing no more than 4 inches (102 mm) wide.
• Individual pipes and conduit 4 inches (102 mm) diameter or less 3-inch (DN80) pipe size or less will not re­quire sprigs).
• Individual groups of smaller pipe or conduit having a total width of 4 inches or less.