Tyco ESFR-1 General Description Manual

Model ESFR-1
14.0 K-Factor Pendent Sprinkler Early Suppression, Fast Response
General Description
TYCO Model ESFR-1 Pendent Sprin­klers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 14.0. They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
Model ESFR-1 Sprinklers are primarily designed for protection of the following storage arrangements:
• most encapsulated or non-encap­sulated common materials including cartoned, unexpanded plastics
• some storage arrangements of rubber tires, roll paper, flammable liquids
For more specific criteria, refer to Table A as well as the applicable design standard.
Applications for the TYCO ESFR Sprin­klers are expanding beyond currently recognized installation standards. For information on research fire tests (with flammable liquids and aerosols, for example) that may be acceptable to an authority having jurisdiction, contact the Tyco Fire Protection Products (TFPP) Technical Services.
IMP ORTA NT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and installation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
NOTICE
The Model ESFR-1 Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the perfor­mance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
In all cases, the appropriate NFPA, FM Global installation standard, or other applicable standard, must be referenced to ensure applicability and to obtain complete installation guide­lines. The general guidelines in this data sheet are not intended to provide complete installation criteria.
Sprinkler Identification Number (SIN)
TY6 226
TY6226 is a re-designation for Central SIN C6226, Gem SIN G8440, and Star SIN S8000.
Technical Data
Approvals
UL and C-UL Listed FM Approved VdS A pproved NYC Approved under MEA 356-01-E LPCB Approved (Cert. Nos. 094b and 007l)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT
Discharge Coefficient
K=14.0 gpm/psi
Temperature Ratings
165°F (74°C) and 212°F (100°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Sealing Assembly . Beryllium Nickel w/ TEFLON
1/2
(201,6 lp m/b ar
1/2
)
Page 1 of 4 MARCH 2015 TFP318
TFP318
Components:
(47,6 mm)
THERMAL
Page 2 of 4
1
7
-
Frame
1
-
Deector
2
-
Compression
3
Screw
-
4
Hook
-
5
Strut
-
Link Assembly
6
-
Button
7
-
Sealing
8
Assembly
-
Ejection Spring
9
8
9
6
5
4
3
2
MODEL ESFR-1 PENDENT SPRINKLER, 14.0K
Design Criteria
The following general guidelines pro­vided for the TYCO ESFR-1 Sprinklers can be used for quick reference.
NOTICE
The National Fire Protection Associa­tion (NFPA) and FM Global (FM Approv­als) provide installation standards that must be used to properly design an automatic sprinkler system utilizing Early Suppression, Fast Response (ESFR) Sprinklers. The guidelines pro­vided by NFPA and FM may differ; con­sequently, the appropriate standard must be used for a given installation.
In all cases, the appropriate NFPA or FM installation standard must be ref­erenced to assure applicability and to obtain complete installation guidelines, since the following general guidelines are not intended to provide complete installation criteria.
In addition to this technical data sheet, the following data sheets describe other TYCO ESFR Sprinklers:
TFP312 Model ESFR-25 (TY9226) K=25.2 Pendent Sprinkler
TFP315
Model ESFR-17 (TY7226) K=16.8 Pendent Sprinkler
TFP316
Model ESFR-17 (TY7126) K=16.8 Upright Sprinkler
1/2"
(12,7 mm) NOMINAL
MAKE-IN
3-9/16"
(90,5 mm)
WRENCH
FLATS
FIGURE 1
EARLY SUPPRESSION, FAST RESPONSE
System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed construc­tion (e.g., smooth ceiling, bar joists, beam and girder, and so forth)
Where the depths of solid struc­tural members (beams and stem, for example) exceed 12 inches (302 mm), install ESFR Sprinklers in each channel formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run (16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation stan­dards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per NFPA 13 / FM Global 2-0
Maximum Spacing
12 feet (3,7 m) for building heights up to 30 feet (9,1 m)
10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage Sprinklers.
3/4" NPT
1-1/2"
(38,1 mm)
SENSING
ELEMENT
TEMPERATURE
1-7/8"
RATING
Operation
The fusible link assembly is com­prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and flowing water.
Loading...
+ 2 hidden pages