Series ELO-231FRB — 11.2 K-factor
Upright and Pendent Sprinklers
Quick Response, Standard Coverage
ELO-231FRB Pendent Sprinkler with
General
Description
The 11.2 K-factor, Series ELO231FRB, Quick Response, Standard
Coverage,Upright and Pendent Sprinklers (Ref. Figure 1) are automati c
sprinklers of the frangible bulb type.
They are “quick response - spray
sprinklers” that produce a hemispherical water distributionpatternbelowthe
deflector.
The 11.2 K-factor, ELO-231FRB Upright and Pendent Sprinklers were
subjected to full scale, high-piled storage,fireteststoqualifytheiruseinlieu
of 5.6 or 8.0 K-factor standard spray
sprinklers for the protection of highpiled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, ELO-231FRB Sprinklers —
making their use highly advantageous
in high density applications, such as
the p rotection of high-piled storage.
For in-rack applications an upright intermediate level version of the Series
ELO-231FRB Sprinklers can be obtained by utilizing the Series ELO231FRB Upright Sprinkler with the
WSG-2Guard&Shield,andapendent
intermediate level version of the Series ELO-231FRB Sprinklers can be
obtained by utilizing the Series
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
tooperatein a firesituation or cause
it to operate prematurely.
theWS-2Shield.Ifthereis a possibility
of the pendent intermediate level version being exposed to mechanical
damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO231FRB Upright and Pendent Sprinklers described her ein must be installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
FireProtectionAssociation, in addition
to the standards of any other authorities having jurisdiction. Failure to do
so may impai r the perform ance of
these devices.
The owner is responsible for maintaining their fire protectionsystem and devices in proper operating condition.
The installing contractor or manufacturer should be contacted with any
questions.
Installation of Series ELO-231FRB
Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the
sprinkler’s Approvals and/or Listings.
Model/Sprinkler
Identification
Numbers
TY5131 - Upright 11.2K, 3/4"NPT
TY5231 - Pendent 11.2K, 3/4"NPT
TY5131 is a redesignation for C5131.
TY5231 is a redesignation for C5231,
G1870, and S2551.
Page 1 of 4 TFP344
MARCH, 2007
![](/html/a2/a244/a24473b832472113157472979043ff7c1d1c68146541c08b3efd9675e06e4eab/bg2.png)
Page2of4
SPRINKLER FINISH
TYPE TEMPERATURE BULB
LIQUID
155°F/68°C Red
UPRIGHT
(TY5131)
PENDENT
(TY5231)
NOTES:
1. Listed by Und erwriters Laboratories, Inc. (UL Listed).
2. Listed by Und erwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM App roved).
4. Approved by the City of New York under MEA 291-04-E.
200°F/93°C Green
286°F/141°C Blue
155°F/68°C
200°F/93°C
286°F/141°C
Red
Green
Blue
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231FRB UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
NATURAL
BRASS
1, 2, 3, 4
1, 2, 3, 4
TABLE A
TFP344
CHROME
PLATED
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Approved. (Refer to TableA for complete
approval information including corrosion resistant status. The approvals
apply to the service conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi
(161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly ..........
. . . . . Beryllium Nickel w/Teflon†
Bulb(3mmdia.)........Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
† Registered trademark of DuPont.
1/2
1/2
)
Design Criteria
ULandC-ULListing
Requirements
The 11.2 K- factor, Model ELO231FRB (TY5131 & TY5231) Sprinklers are to be installed in accordance
with NFPA 13 standard sprinkler position and area/density flow calculation
requirements for light, ordinary, or extra hazard occupancies, as well as
high piled storage occupancies (solid
piled, palletized,rackstorage,bin box,
and shelf storage including but not limitedtoClassI-IVand GroupAplastics)
with a minimum residual (flowing)
pressure of 7 psi (0,5 bar) for wet pipe
systems only.
FM Approval
Requirements
The 11.2 K- factor, Model ELO231FRB (TY5131 & TY5231) Sprinklers are to be installed in accordance
with the applicable “control mode density/area” guidelines provided by Factory Mutual for wet systems only. (FM
guidelines may differ from UL and CUL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Installation
The Series ELO-231FRB Sprinklers
must be installed in accordance with
the following instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or thereis a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
shouldbe present.The diameterof the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32
inch (2,4 mm ) for the 286°F/141°C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.lbs. (40,7 Nm) of torque
is to be used to install sprinklers with
3/4 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make-up for insufficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series ELO-231FRB Upright
and Pendent Sprinklers must be installed in accordance with the following instructions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thr ead sealant ap-