Tyco ELO-231FRB Series Manual

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series ELO-231FRB — 11.2 K-factor Upright and Pendent Sprinklers Quick Response, Standard Coverage
ELO-231FRB Pendent Sprinkler with
General Description
The 11.2 K-factor, Series ELO­231FRB, Quick Response, Standard Coverage,Upright and Pendent Sprin­klers (Ref. Figure 1) are automati c sprinklers of the frangible bulb type. They are “quick response - spray sprinklers” that produce a hemispheri­cal water distributionpatternbelowthe deflector.
The 11.2 K-factor, ELO-231FRB Up­right and Pendent Sprinklers were subjected to full scale, high-piled stor­age,fireteststoqualifytheiruseinlieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high­piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231FRB Sprinklers — making their use highly advantageous in high density applications, such as the p rotection of high-piled storage.
For in-rack applications an upright in­termediate level version of the Series ELO-231FRB Sprinklers can be ob­tained by utilizing the Series ELO­231FRB Upright Sprinkler with the WSG-2Guard&Shield,andapendent intermediate level version of the Se­ries ELO-231FRB Sprinklers can be obtained by utilizing the Series
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail tooperatein a firesituation or cause it to operate prematurely.
theWS-2Shield.Ifthereis a possibility of the pendent intermediate level ver­sion being exposed to mechanical damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO­231FRB Upright and Pendent Sprin­klers described her ein must be in­stalled and maintained in compliance with this document, as well as with the applicable standards of the National FireProtectionAssociation, in addition to the standards of any other authori­ties having jurisdiction. Failure to do
so may impai r the perform ance of these devices.
The owner is responsible for maintain­ing their fire protectionsystem and de­vices in proper operating condition. The installing contractor or manufac­turer should be contacted with any questions.
Installation of Series ELO-231FRB Pendent Sprinklers in recessed es­cutcheons will void all sprinkler war­ranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Model/Sprinkler Identification Numbers
TY5131 - Upright 11.2K, 3/4"NPT TY5231 - Pendent 11.2K, 3/4"NPT
TY5131 is a redesignation for C5131. TY5231 is a redesignation for C5231,
G1870, and S2551.
Page 1 of 4 TFP344
MARCH, 2007
Page2of4
SPRINKLER FINISH
TYPE TEMPERATURE BULB
LIQUID
155°F/68°C Red
UPRIGHT
(TY5131)
PENDENT
(TY5231)
NOTES:
1. Listed by Und erwriters Laboratories, Inc. (UL Listed).
2. Listed by Und erwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM App roved).
4. Approved by the City of New York under MEA 291-04-E.
200°F/93°C Green
286°F/141°C Blue
155°F/68°C 200°F/93°C
286°F/141°C
Red
Green
Blue
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231FRB UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
NATURAL
BRASS
1, 2, 3, 4
1, 2, 3, 4
TABLE A
TFP344
CHROME
PLATED
Technical Data
Approvals
UL and C-UL Listed. FM and NYC Ap­proved. (Refer to TableA for complete approval information including corro­sion resistant status. The approvals apply to the service conditions indi­cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi (161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly ..........
. . . . . Beryllium Nickel w/Teflon†
Bulb(3mmdia.)........Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
† Registered trademark of DuPont.
1/2
1/2
)
Design Criteria
ULandC-ULListing Requirements
The 11.2 K- factor, Model ELO­231FRB (TY5131 & TY5231) Sprin­klers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calculation requirements for light, ordinary, or ex­tra hazard occupancies, as well as high piled storage occupancies (solid piled, palletized,rackstorage,bin box, and shelf storage including but not lim­itedtoClassI-IVand GroupAplastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet pipe systems only.
FM Approval Requirements
The 11.2 K- factor, Model ELO­231FRB (TY5131 & TY5231) Sprin­klers are to be installed in accordance with the applicable “control mode den­sity/area” guidelines provided by Fac­tory Mutual for wet systems only. (FM guidelines may differ from UL and C­UL Listing criteria.)
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Installation
The Series ELO-231FRB Sprinklers must be installed in accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the bulb is cracked or thereis a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble shouldbe present.The diameterof the air bubble is approximately 1/16 inch (1,6 mm) for the 155°F/68°C to 3/32 inch (2,4 mm ) for the 286°F/141°C temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi­mum of 30 ft.lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi­cient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.
The Series ELO-231FRB Upright and Pendent Sprinklers must be in­stalled in accordance with the follow­ing instructions.
Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position.
Step 2. With pipe thr ead sealant ap-
TFP344
**
Temperature rating is indicated on deflector.
*
Pipe thread connections per ISO 7/1 can be provided on special request.
2-13/16"
(71,4 mm)
TYP.
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
TY5131
UPRIGHT - 3/4" NPT (TY5131) AND PENDENT - 3/4" NPT (TY5231) SPRINKLERS
THREAD
RELIEF
WRENCH
FLATS
3/4"
NPT
**
ESCUTCHEON
SEATING
SURFACE
2-1/16"
(52,4 mm)
PENDENT
TY5231
FIGURE 1
11.2 K-FACTOR SERIES ELO-231FRB
1
2
3
4
5
6
CROSS
SECTION
Page 3 of 4
Components:
-
1
Frame
-
2
Seal Assembly
-
3
Cap
-
Bulb
4
-
5
Compression Screw
-
Deflector
6
*
plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 3 Sprinkler Wrench (Ref. Figure 2). Withreference to Figure 1, theW-Type 3 Sprinkler Wrench is to be applied to the w rench flats.
Care and Maintenance
Series ELO-231FRB Sprinklers must be maintained and serviced in accord­ance with the following instructions:
NOTES
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the af­fected fire protection system must be obtained from the proper authorities and all personnel who may beaffected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be be painted, plated, coated or otherwise altered after leaving the factory. Modi­fied sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid dam­age to the sprinklers— before, during, and after installation. Sprinklers dam­aged by dropping, striking, wrench twist/slippage, or the like, must be re­placed.Also, replaceanysprinkler that has a cracked bulb or that has lost liquid from its bulb (ref. Installation Section Note).
The owner is responsible for the in­spection, testing, and maintenance of
"FITTINGSIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
(END "A")
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
their fire protection system and de­vices in compl ianc e with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in­stalling contractor or sprinkler manu­facturer should be contacted relative to any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code.
Page4of4
TFP344
Limited Warranty
Products manufacturedby Tyco Fire & Building P roducts (TFBP) are war­ranted solely to the original Buyer for ten (10) years against defects inmate­rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com­ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeen subject to misuse,improper installation, corrosion, or which have not been installed, maintained, modi­fied or repaired in accordance with ap­plicable Standards of theNational Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall beeither repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizesany person to assume forit, any other obligation in connection with the sale of products or parts of prod­ucts.TFBPshall not be responsible for sprinkler system design errorsor inac­curate or incomplete information sup­plied b y B uyer or Buyer’s repre­sentatives.
In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,special or consequentialdam­ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price.
Theforegoingwarrantyismadeinlieu of any and all other warranties, ex­press or implied, including warranties ofmerchantability andfitnessfor apar­ticular purpose.
This limited warranty sets forth the ex­clusive remedy for claims based on failure of or defect in products, materi­als or components, whether the claim is made in contract, tort, strict liability or any other legal theory.
P/N 5 0 — XXX — X — XXX
SPRINKLER
TYPE NATURAL BRASS1
500 9
502 PENDENT
UPRIGHT
3/4" NPT (TY5131)
3/4" NPT (TY5231)
PRODUCT SYMBOL NUMBER SELECTION
11.2 K-FACTOR SERIES ELO-231FRB
QUICK RESPONSE UPRIGHT AND PENDENT SPRINKLERS
CHROME PLATED
TABLE B
Ordering Procedure
A Product Symbol Number (P/N) is not specified when ordering sprinklers with thread connections per ISO 7/1.
Contact your local distributor for avail­ability.
Sprinkler Assemblies with NPT Thread Connection:
Specify: (specify SIN), 11.2 K-factor, (specify temperature rating), Series ELO-231FRB Quick Response (spec­ify Pendent or Upright) Sprinkler with (specify finish), P/N (specify from Ta-
ble B). Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001.
286
TEMPERATURE
RATING
155°F/68°C155 200°F/93°C200
286°F/141°C
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446