Tyco ELO-231FRB Series Manual

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series ELO-231FRB — 11.2 K-factor Upright and Pendent Sprinklers Quick Response, Standard Coverage
ELO-231FRB Pendent Sprinkler with
General Description
The 11.2 K-factor, Series ELO­231FRB, Quick Response, Standard Coverage,Upright and Pendent Sprin­klers (Ref. Figure 1) are automati c sprinklers of the frangible bulb type. They are “quick response - spray sprinklers” that produce a hemispheri­cal water distributionpatternbelowthe deflector.
The 11.2 K-factor, ELO-231FRB Up­right and Pendent Sprinklers were subjected to full scale, high-piled stor­age,fireteststoqualifytheiruseinlieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high­piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231FRB Sprinklers — making their use highly advantageous in high density applications, such as the p rotection of high-piled storage.
For in-rack applications an upright in­termediate level version of the Series ELO-231FRB Sprinklers can be ob­tained by utilizing the Series ELO­231FRB Upright Sprinkler with the WSG-2Guard&Shield,andapendent intermediate level version of the Se­ries ELO-231FRB Sprinklers can be obtained by utilizing the Series
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail tooperatein a firesituation or cause it to operate prematurely.
theWS-2Shield.Ifthereis a possibility of the pendent intermediate level ver­sion being exposed to mechanical damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO­231FRB Upright and Pendent Sprin­klers described her ein must be in­stalled and maintained in compliance with this document, as well as with the applicable standards of the National FireProtectionAssociation, in addition to the standards of any other authori­ties having jurisdiction. Failure to do
so may impai r the perform ance of these devices.
The owner is responsible for maintain­ing their fire protectionsystem and de­vices in proper operating condition. The installing contractor or manufac­turer should be contacted with any questions.
Installation of Series ELO-231FRB Pendent Sprinklers in recessed es­cutcheons will void all sprinkler war­ranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Model/Sprinkler Identification Numbers
TY5131 - Upright 11.2K, 3/4"NPT TY5231 - Pendent 11.2K, 3/4"NPT
TY5131 is a redesignation for C5131. TY5231 is a redesignation for C5231,
G1870, and S2551.
Page 1 of 4 TFP344
MARCH, 2007
Page2of4
SPRINKLER FINISH
TYPE TEMPERATURE BULB
LIQUID
155°F/68°C Red
UPRIGHT
(TY5131)
PENDENT
(TY5231)
NOTES:
1. Listed by Und erwriters Laboratories, Inc. (UL Listed).
2. Listed by Und erwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM App roved).
4. Approved by the City of New York under MEA 291-04-E.
200°F/93°C Green
286°F/141°C Blue
155°F/68°C 200°F/93°C
286°F/141°C
Red
Green
Blue
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231FRB UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
NATURAL
BRASS
1, 2, 3, 4
1, 2, 3, 4
TABLE A
TFP344
CHROME
PLATED
Technical Data
Approvals
UL and C-UL Listed. FM and NYC Ap­proved. (Refer to TableA for complete approval information including corro­sion resistant status. The approvals apply to the service conditions indi­cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi (161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly ..........
. . . . . Beryllium Nickel w/Teflon†
Bulb(3mmdia.)........Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
† Registered trademark of DuPont.
1/2
1/2
)
Design Criteria
ULandC-ULListing Requirements
The 11.2 K- factor, Model ELO­231FRB (TY5131 & TY5231) Sprin­klers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calculation requirements for light, ordinary, or ex­tra hazard occupancies, as well as high piled storage occupancies (solid piled, palletized,rackstorage,bin box, and shelf storage including but not lim­itedtoClassI-IVand GroupAplastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet pipe systems only.
FM Approval Requirements
The 11.2 K- factor, Model ELO­231FRB (TY5131 & TY5231) Sprin­klers are to be installed in accordance with the applicable “control mode den­sity/area” guidelines provided by Fac­tory Mutual for wet systems only. (FM guidelines may differ from UL and C­UL Listing criteria.)
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Installation
The Series ELO-231FRB Sprinklers must be installed in accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the bulb is cracked or thereis a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble shouldbe present.The diameterof the air bubble is approximately 1/16 inch (1,6 mm) for the 155°F/68°C to 3/32 inch (2,4 mm ) for the 286°F/141°C temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi­mum of 30 ft.lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi­cient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.
The Series ELO-231FRB Upright and Pendent Sprinklers must be in­stalled in accordance with the follow­ing instructions.
Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position.
Step 2. With pipe thr ead sealant ap-