Series ELO-231FRB — 11.2 K-factor
Upright and Pendent Sprinklers
Quick Response, Standard Coverage
ELO-231FRB Pendent Sprinkler with
General
Description
The 11.2 K-factor, Series ELO231FRB, Quick Response, Standard
Coverage,Upright and Pendent Sprinklers (Ref. Figure 1) are automati c
sprinklers of the frangible bulb type.
They are “quick response - spray
sprinklers” that produce a hemispherical water distributionpatternbelowthe
deflector.
The 11.2 K-factor, ELO-231FRB Upright and Pendent Sprinklers were
subjected to full scale, high-piled storage,fireteststoqualifytheiruseinlieu
of 5.6 or 8.0 K-factor standard spray
sprinklers for the protection of highpiled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, ELO-231FRB Sprinklers —
making their use highly advantageous
in high density applications, such as
the p rotection of high-piled storage.
For in-rack applications an upright intermediate level version of the Series
ELO-231FRB Sprinklers can be obtained by utilizing the Series ELO231FRB Upright Sprinkler with the
WSG-2Guard&Shield,andapendent
intermediate level version of the Series ELO-231FRB Sprinklers can be
obtainedbyutilizingthe Series
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
tooperatein a firesituation or cause
it to operate prematurely.
theWS-2Shield.Ifthereis a possibility
of the pendent intermediate level version being exposed to mechanical
damage, a G-2 Guard can be added.
WARNINGS
The 11.2 K-factor, Series ELO231FRB Upright and Pendent Sprinklers described her ein must be installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
FireProtectionAssociation, in addition
to the standards of any other authorities having jurisdiction. Failure to do
so may impai r the perform ance of
these devices.
The owner is responsible for maintaining their fire protectionsystem and devices in proper operating condition.
The installing contractor or manufacturer should be contacted with any
questions.
Installation of Series ELO-231FRB
Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the
sprinkler’s Approvals and/or Listings.
Model/Sprinkler
Identification
Numbers
TY5131 - Upright 11.2K, 3/4"NPT
TY5231 - Pendent 11.2K, 3/4"NPT
TY5131 is a redesignation for C5131.
TY5231 is a redesignation for C5231,
G1870, and S2551.
Page 1 of 4TFP344
MARCH, 2007
Page2of4
SPRINKLER FINISH
TYPETEMPERATUREBULB
LIQUID
155°F/68°CRed
UPRIGHT
(TY5131)
PENDENT
(TY5231)
NOTES:
1. Listed by Und erwriters Laboratories, Inc. (UL Listed).
2. Listed by Und erwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM App roved).
4. Approved by the City of New York under MEA 291-04-E.
200°F/93°CGreen
286°F/141°CBlue
155°F/68°C
200°F/93°C
286°F/141°C
Red
Green
Blue
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES ELO-231FRB UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
NATURAL
BRASS
1, 2, 3, 4
1, 2, 3, 4
TABLE A
TFP344
CHROME
PLATED
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Approved. (Refer to TableA for complete
approval information including corrosion resistant status. The approvals
apply to the service conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi
(161,4 LPM/bar
Temperature Ratings
RefertoTableA
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap . . . . . . . . . . . . . . Bronze
SealingAssembly ..........
. . . . . Beryllium Nickel w/Teflon†
Bulb(3mmdia.)........Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
† Registered trademark of DuPont.
1/2
1/2
)
Design Criteria
ULandC-ULListing
Requirements
The 11.2 K- factor, Model ELO231FRB (TY5131 & TY5231) Sprinklers are to be installed in accordance
with NFPA 13 standard sprinkler position and area/density flow calculation
requirements for light, ordinary, or extra hazard occupancies, as well as
high piled storage occupancies (solid
piled, palletized,rackstorage,bin box,
and shelf storage including but not limitedtoClassI-IVand GroupAplastics)
with a minimum residual (flowing)
pressure of 7 psi (0,5 bar) for wet pipe
systems only.
FM Approval
Requirements
The 11.2 K- factor, Model ELO231FRB (TY5131 & TY5231) Sprinklers are to be installed in accordance
with the applicable “control mode density/area” guidelines provided by Factory Mutual for wet systems only. (FM
guidelines may differ from UL and CUL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Installation
The Series ELO-231FRB Sprinklers
must be installed in accordance with
the following instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or thereis a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
shouldbe present.The diameterof the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32
inch (2,4 mm ) for the 286°F/141°C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maximum of 30 ft.lbs. (40,7 Nm) of torque
is to be used to install sprinklers with
3/4 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make-up for insufficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series ELO-231FRB Uprightand Pendent Sprinklers must be installed in accordance with the following instructions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thr ead sealant ap-
TFP344
**
Temperature rating is indicated on deflector.
*
Pipe thread connections per ISO 7/1 can be
provided on special request.
2-13/16"
(71,4 mm)
TYP.
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
TY5131
UPRIGHT - 3/4" NPT (TY5131) AND PENDENT - 3/4" NPT (TY5231) SPRINKLERS
THREAD
RELIEF
WRENCH
FLATS
3/4"
NPT
**
ESCUTCHEON
SEATING
SURFACE
2-1/16"
(52,4 mm)
PENDENT
TY5231
FIGURE 1
11.2 K-FACTOR SERIES ELO-231FRB
1
2
3
4
5
6
CROSS
SECTION
Page 3 of 4
Components:
-
1
Frame
-
2
Seal
Assembly
-
3
Cap
-
Bulb
4
-
5
Compression
Screw
-
Deflector
6
*
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
3 Sprinkler Wrench (Ref. Figure 2).
Withreference to Figure 1, theW-Type
3 Sprinkler Wrench is to be applied to
the w rench flats.
Care and
Maintenance
Series ELO-231FRB Sprinklers must
be maintained and serviced in accordance with the following instructions:
NOTES
Before closing a fire protection system
control valve for maintenance work on
the fire protection system that it controls, permission to shut down the affected fire protection system must be
obtained from the proper authorities
and all personnel who may beaffected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be be
painted, plated, coated or otherwise
altered after leaving the factory. Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers— before, during,
and after installation. Sprinklers damaged by dropping, striking, wrench
twist/slippage, or the like, must be replaced.Also, replaceanysprinkler that
has a cracked bulb or that has lost
liquid from its bulb (ref. Installation
Section Note).
The owner is responsible for the inspection, testing, and maintenance of
"FITTINGSIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
(END "A")
FIGURE 2
W-TYPE 3 SPRINKLER
WRENCH
their fire protection system and devices in compl ianc e with this document, as well as with the applicable
standards of the National Fire Protection Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
code.
Page4of4
TFP344
Limited
Warranty
Products manufacturedby Tyco Fire &
Building P roducts (TFBP) are warranted solely to the original Buyer for
ten (10) years against defects inmaterial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or components manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeen subject to misuse,improper
installation, corrosion, or which have
not been installed, maintained, modified or repaired in accordance with applicable Standards of theNational Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall beeither
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizesany person to assume forit,
any other obligation in connection with
the sale of products or parts of products.TFBPshall not be responsible for
sprinkler system design errorsor inaccurate or incomplete information supplied b y B uyer or Buyer’s representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,special or consequentialdamages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, express or implied, including warranties
ofmerchantability andfitnessfor aparticular purpose.
This limited warranty sets forth the exclusive remedy for claims based on
failure of or defect in products, materials or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
P/N 5 0 — XXX — X — XXX
SPRINKLER
TYPENATURAL BRASS1
5009
502PENDENT
UPRIGHT
3/4" NPT
(TY5131)
3/4" NPT
(TY5231)
PRODUCT SYMBOL NUMBER SELECTION
11.2 K-FACTOR SERIES ELO-231FRB
QUICK RESPONSE UPRIGHT AND PENDENT SPRINKLERS
CHROME PLATED
TABLE B
Ordering
Procedure
A Product Symbol Number (P/N) is not
specified when ordering sprinklers
with thread connections per ISO 7/1.
Contact your local distributor for availability.
Sprinkler Assemblies
with NPT Thread Connection:
Specify: (specify SIN), 11.2 K-factor,
(specify temperature rating), Series
ELO-231FRB Quick Response (specify Pendent or Upright) Sprinkler with
(specify finish), P/N (specify from Ta-