Tyco ELO-231B, TY5251, TY5851, TY5151 Series Manual

Worldwide
Contacts
Series ELO-231B – 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
www.tyco-fire.com
General Description
TYCO Series ELO-231B 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprinklers of the frangible bulb type. They are standard response, spray sprinklers that produce a hemi­spherical water distribution pattern below the deflector.
The 11.2 K-factor, ELO-231B Sprinklers were subjected to full-scale, high-piled storage fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231B Sprinklers, making their use highly advantageous in high density applications, such as the pro­tection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copper alloy components used in Series ELO-231B Sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although wax, lead, and polyester coated sprin­klers have passed the standard corro­sion tests of the applicable approval agencies, the testing is not repre­sentative of all possible corrosive atmospheres. Consequently, it is rec­ommended that the end-user be con­sulted with respect to the suitability of these corrosion resistant coatings
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/ chemical velocity, should be consid­ered, as a minimum, along with the cor­rosive nature of the chemical to which the sprinklers will be exposed.
An upright intermediate level version of the Series ELO-231B Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231B Upright Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231B Sprinklers can be obtained by utilizing the Series ELO-231B Pendent Sprinkler with the WS-2 Shield. If there is a pos­sibility of the pendent intermediate level version being exposed to mechanical damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231B Upright and Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Installation of Series ELO-231B Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Sprinkler Identification Numbers (SINs)
Refer to Table A for sprinkler identifica­tion numbers.
Page 1 of 6 AUGUST 2018 TFP342
TFP342
TY5851
TY5251
SECTION
TY5151
(71,4 mm)
1/2" (12,7 mm)
Compression
Components:
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2" NPT
SERIES ELO-231B 11.2K UPRIGHT 3/4 INCH NPT (TY5151), UPRIGHT 1/2 INCH NPT (TY5851), AND
PENDENT 3/4 INCH NPT (TY5251) SPRINKLERS, STANDARD RESPONSE
Technical Data
Approvals
UL and C-UL Listed FM Approved NYC Approved
Refer to Table C for specific details on laboratory and approvals, including corrosion-resistant status. The approv­als apply to the service conditions indi­cated in the Design Criteria section.)
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb (5 mm dia.) . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Additional Technical Data
Refer to Table A for additional techni­cal data.
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4"
NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar)
Temperature Rating °F (°C)
Thread Size 3/4 in. NPT or 1/2 in. NPT
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Note:
1. Refer to Table C for laboratory listings and approvals.
1
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
TECHNICAL DATA
Design Criteria
UL and C-UL Listing Requirements
TYCO Series ELO-231B 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers are to be installed in accordance with NFPA 13 standard sprinkler position and area/ density flow calculation requirements for light, ordinary, or extra hazard occu­pancies, as well as high-piled storage occupancies (solid-piled, palletized, rack storage, bin box, and shelf storage including but not limited to Class I-IV
1
3/4"
1
NPT
2
3
4
5
6
CROSS
TY5151 - Upright 3/4 in. NPT TY5251 -Pendent 3/4 in. NPT TY5851 - Upright 1/2 in. NPT
TY5151 is a re-de signation for Ce ntral SIN C5151. TY5251 is a re-desi gnation for Cent ral, Gem , and Star SINs C5251, G1871, and S2531, respecti vely. TY5851 is a re-designati on for Central SIN C5851.
11. 2 G P M /psi½ (161,4 LPM/bar½)
155 ºF (68 ºC)1
200 ºF (93 ºC)
286 ºF (141 ºC)
2
3 4 5
6
TABL E A
and Group A plastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems. Refer to Table B for additional information.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231B Sprinklers are to be installed in accor­dance with the applicable control mode density/area guidelines provided by FM Global.
Note: FM Approval guidelines may differ from UL and C-UL Listing criteria.
-
Frame
-
Seal Assembly
-
Cap
-
Bulb
­Screw
-
Deector
Temperature
*
rating is indicated on deector.
*
TFP342
Page 3 of 6
Storage Type
Sprinkler Type Standard Coverage Storage
Response Type SR SR
System Type Wet, Dry Wet, Dry
Temperature Rating °F (°C)
1
Open Frame (that is, no solid shelves) Single, Double, Multiple-
Row, or Portable Racj Storage of Class I-IV and Group A or B
Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or B
Plastics
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Rolled Paper Storage (Refer to the standard.) Refer to NFPA 13 Refer to FM 8-21
NFPA FM Global
155 ºF (68 ºC)1
200 ºF (93 ºC)
286 ºF (141 ºC)
155 ºF (68 ºC)1
200 ºF (93 ºC)
286 ºF (141 ºC)
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Flammable Liquid Storage (Refer to the standard.) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage (Refer to the standard.) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks (Control mode only,
refer to the standard.)
Note:
1. Refer to Table C f or laboratory listing s and app rovals. N/A - Not App licable
Refer to NFPA 13 N/A
TABL E B
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
SPRINKLER
TYPE
TEMPERATURE
RATI NG
BULB
LIQUID
155° F ( 68°C) Red
UPRIGHT
(TY5151 & T Y5851)
200°F (93°C) Green
28 6°F (141° C) Blue 3 3
155° F ( 68°C) Red
PENDENT
(T Y5251)
200°F (93°C) Green
28 6°F (141° C) Blue 3 3
Notes:
1. Listed by Under writer s Labo ratori es, Inc. ( UL)
2. Listed by Unde rwri ters Laboratories, I nc. for us e in Canada (C-UL)
3. A pprove d by FM Globa l (FM Approvals)
4. A pprove d by the Cit y of New York (NYC) un der ME A 291-04-E a. Liste d/Appr oved for a ma ximum c eiling te mpera ture of 150°F ( 66°C).
NATURAL
BRASS
1, 2, 3, 4
1, 2, 3, 4
CHROME
PL ATED
SPRINKLER FINISH
LEAD
COATE D
WAX
COATE D
TABL E C
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
WAX-OVER-LEAD
COATE D
3
a
3
a
TFP342
"FITTING SIDE"
WRENCH
(END "A")
Page 4 of 6
TOWARDS SPRINKLER
FITTING
RECESS
FIGURE 2 W-T Y P E 3
SPRINKLER WRENCH
Installation
TYCO Series ELO-231B 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers must be installed in accordance with this section.
A leak-tight 3/4 in. NPT sprinkler joint should be obtained by applying a min­imum-to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 Nm). A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum-to­maximum torque of 7 to 14 lb-ft (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler inlet with con­sequent leakage or impairment of the sprinkler.
Notes: Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approxi­mately 1/16 in. (1,6 mm) for the 155°F (68°C) to 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings.
Do not attempt to make up for insuf­ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.
The Series ELO-231B Upright and Pendent Sprinklers must be installed in accordance with the following instructions.
Note: Pendent sprinklers are to be installed in the pendent position; upright sprinklers are to be installed in the upright position.
Step 1. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 3 Sprinkler Wrench (Ref. Figure 2), except
that an 8 in. or 10 in. adjustable wrench is to be used for wax-coated sprinklers. With reference to Figure 1, the W-Type 3 Sprinkler Wrench or the adjustable wrench, as applicable, is to be applied to the wrench flats.
When installing wax-coated sprinklers with the adjustable wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench-tightening the sprinkler, the jaws of the wrench are to be adjusted to just contact the sprin­kler wrench flats. After wrench-tight­ening the sprinkler, loosen the wrench jaws before removing the wrench.
After installation, the sprinkler wrench flats and frame arms must be inspected and the wax coating retouched (repaired) whenever the coating has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gently applying a heated 1/8 in. diam­eter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed.
Notes: Only retouching of the wax coating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precau­tions need to be taken, when handling the heated rod, in order to prevent the installer from being burned.
If attempts to retouch the wax coating with complete coverage are unsuc­cessful, additional wax can be ordered in the form of a wax stick (the end of which is color-coded). Only the correct color-coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previ­ously described, touch the rod to the area requiring additional wax with the rod angled downward, and then touch the wax stick to the rod approximately 1/2 in. away from the area requiring retouching. The wax will melt and run down onto the sprinkler.
Care and Maintenance
TYCO Series ELO-231B 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers must be main­tained and serviced in accordance with this section.
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or other­wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin­kler that has a cracked bulb or that has lost liquid from its bulb. For additional information, refer to Installation section.
Frequent visual inspections are rec­ommended to be initially performed for corrosion resistant sprinklers, after the installation has been completed, to verify the long term potential integrity of the sprinkler coatings. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associ­ation, such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the install­ing contractor or product manufacturer with any questions.
P/N 50 — XXX — X — XXX
TFP342
Page 5 of 6
501 11.2K UPRIGHT (1/2 in. NPT) TY5851
510 11.2K UPRIGHT (3/4 in. NPT) TY5151
512 11.2K PENDENT (3/4 in. NPT) TY5251
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
SIN
1
6
7
8
9
TABL E D
PART NUMBER SELECTION
SPRINKLER
FINISH
NAT U R AL
BRASS
WAX
CO ATED
LEAD
CO ATED
WAX- OVER- LE AD
CO ATED
CHROME
PL AT ED
Ordering Procedure
Sprinkler Assemblies with NPT Thread Connection
Specify: Series ELO-231B 11.2K Stan­dard Response (specify Pendent or Upright) Sprinkler, SIN (specify), (specify temperature rating), with (specify) finish, P/N (specify from Table D)
Sprinkler Wrench
Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1- 0 0 1
TEMPERATURE
RATI NG
155 155° F ( 68°C)
200 200°F (93°C)
286 28 6°F (141° C)
Wax Sticks
(for retouching wrench-damaged wax coating)
Specify: (specify Color) color-coded Wax Stick for retouching (specify tem­perature rating) temperature rated Series ELO-231B Sprinklers, P/N (specify):
Red for 155°F (68°C) ...........56- 0 6 5-1-155
Blue for 20 0°F (93°C)
and 286°F (141°C) .............5 6 -06 5 -1- 28 6
Notes: Each wax stick is suitable for retouching up to twenty-five sprinklers.
The wax used for 286°F (141°C) sprin­klers is the same as for 200°F (93°C) sprinklers, and, therefore, the 286°F (141°C) sprinkler is limited to the same maximum ceiling temperature as the 200°F (93°C)sprinkler, such as 150°F (66°C).
TFP342
Page 6 of 6
1400 Pennbrook Par kway, Lansdale, PA 194 46 | Telep hone +1-215- 362-0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on; TEFLON is a regi stered tradema rk of DuPont
Loading...