Worldwide
Contacts
Series ELO-231B – 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
www.tyco-fire.com
General
Description
TYCO Series ELO-231B 11.2K Standard
Response, Standard Coverage Upright
and Pendent Sprinklers (Ref. Figure 1)
are automatic sprinklers of the frangible
bulb type. They are standard response,
spray sprinklers that produce a hemispherical water distribution pattern
below the deflector.
The 11.2 K-factor, ELO-231B Sprinklers
were subjected to full-scale, high-piled
storage fire tests to qualify their use
in lieu of 5.6 or 8.0 K-factor standard
spray sprinklers for the protection of
high-piled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, ELO-231B Sprinklers, making
their use highly advantageous in high
density applications, such as the protection of high-piled storage.
Wax or lead coatings can be used
to extend the life of the copper alloy
components used in Series ELO-231B
Sprinklers beyond that which would
otherwise be obtained when exposed
to corrosive atmospheres. Although
wax, lead, and polyester coated sprinklers have passed the standard corrosion tests of the applicable approval
agencies, the testing is not representative of all possible corrosive
atmospheres. Consequently, it is recommended that the end-user be consulted with respect to the suitability
of these corrosion resistant coatings
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and gas/
chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which
the sprinklers will be exposed.
An upright intermediate level version
of the Series ELO-231B Sprinklers for
in-rack applications can be obtained by
utilizing the Series ELO-231B Upright
Sprinkler with the WSG-2 Guard &
Shield, and a pendent intermediate
level version of the Series ELO-231B
Sprinklers can be obtained by utilizing
the Series ELO-231B Pendent Sprinkler
with the WS-2 Shield. If there is a possibility of the pendent intermediate level
version being exposed to mechanical
damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231B
Upright and Pendent Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Installation of Series ELO-231B Pendent
Sprinklers in recessed escutcheons will
void all sprinkler warranties, as well as
possibly void the sprinkler’s Approvals
and/or Listings.
Sprinkler
Identification
Numbers (SINs)
Refer to Table A for sprinkler identification numbers.
Page 1 of 6 AUGUST 2018 TFP342
TFP342
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2"
NPT
SERIES ELO-231B 11.2K UPRIGHT 3/4 INCH NPT (TY5151), UPRIGHT 1/2 INCH NPT (TY5851), AND
PENDENT 3/4 INCH NPT (TY5251) SPRINKLERS, STANDARD RESPONSE
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
NYC Approved
Refer to Table C for specific details on
laboratory and approvals, including
corrosion-resistant status. The approvals apply to the service conditions indicated in the Design Criteria section.)
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb (5 mm dia.) . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Additional Technical Data
Refer to Table A for additional technical data.
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4"
NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar)
Temperature Rating °F (°C)
Thread Size 3/4 in. NPT or 1/2 in. NPT
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Note:
1. Refer to Table C for laboratory listings and approvals.
1
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
TECHNICAL DATA
Design
Criteria
UL and C-UL
Listing Requirements
TYCO Series ELO-231B 11.2K Standard
Response, Standard Coverage Upright
and Pendent Sprinklers are to be
installed in accordance with NFPA 13
standard sprinkler position and area/
density flow calculation requirements
for light, ordinary, or extra hazard occupancies, as well as high-piled storage
occupancies (solid-piled, palletized,
rack storage, bin box, and shelf storage
including but not limited to Class I-IV
1
3/4"
1
NPT
2
3
4
5
6
CROSS
TY5151 - Upright 3/4 in. NPT
TY5251 -Pendent 3/4 in. NPT
TY5851 - Upright 1/2 in. NPT
TY5151 is a re-de signation for Ce ntral SIN C5151.
TY5251 is a re-desi gnation for Cent ral, Gem , and
Star SINs C5251, G1871, and S2531, respecti vely.
TY5851 is a re-designati on for Central SIN C5851.
11. 2 G P M /psi½ (161,4 LPM/bar½)
155 ºF (68 ºC)1
200 ºF (93 ºC)
286 ºF (141 ºC)
2
3
4
5
6
TABL E A
and Group A plastics) with a minimum
residual (flowing) pressure of 7 psi (0,5
bar) for wet or dry pipe systems. Refer
to Table B for additional information.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231B
Sprinklers are to be installed in accordance with the applicable control mode
density/area guidelines provided by FM
Global.
Note: FM Approval guidelines may
differ from UL and C-UL Listing criteria.
-
Frame
-
Seal
Assembly
-
Cap
-
Bulb
Screw
-
Deector
Temperature
*
rating is
indicated on
deector.
*