Tyco EA-1 PROTECTOSPRAY General Description Manual

Worldwide
Contacts
Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity
www.tyco-fire.com
General Description
The TYCO Type EA-1 PROTECTO­SPRAY Directional Spray Nozzles are automatic (frangible bulb) directional spray nozzles designed for use in water spray fixed systems for fire protection applications. They are external deflec­tor-type nozzles that discharge a uni­formly filled cone of medium velocity water droplets.
The Type EA-1 PROTECTOSPRAY Directional Spray Nozzles are effective in covering exposed vertical, horizontal, curved, and irregular shaped surfaces in a cooling spray to prevent excessive absorption of heat from an external fire and possible structural damage or spread of fire to the protected equip­ment. However, use of an automatic nozzle requires consideration of the response time of the thermal element.
The Type EA-1 PROTECTOSPRAY Directional Spray Nozzles are also especially effective for area cover­age and are sometimes used in lieu of standard sprinklers where directional spray is considered more appropri­ate. In some applications, depending on water design density requirements, the Type EA-1 Nozzles are also used for fire control or extinguishment.
The Type EA-1 PROTECTOSPRAY Directional Spray Nozzles are available in three orifice sizes and a wide variety of spray angles (included angle of dis­charge), as well as temperature ratings
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
to provide versatility in system design.
It is recommended that the end user be consulted with respect to the suitabil­ity of the materials of construction and finish for any given corrosive environ­ment. The effects of ambient tempera­ture, concentration of chemicals, and gas/chemical velocity should be con­sidered, at a minimum, along with the corrosive nature to which the sprinklers may be exposed.
The Type EA-1 PROTECTOSPRAY Directional Spray Nozzle is a re-desig­nation for the Gem Type EA-1.
NOTICE
The Type EA-1 PROTECTOSPRAY Directional Spray Nozzles described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa­tion, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The design of individual water spray fixed systems can vary considerably, depending on the characteristics and nature of the hazard, the basic purpose of the spraying system, the configura­tion of the hazard, and wind/draft con­ditions. Because of these variations, as well as the wide range of available nozzle spray characteristics, the design of water spray fixed systems for fire protection must only be performed by experienced designers who thoroughly understand the limitations as well as capabilities of such systems.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Technical Data
Approvals
UL and C-UL Listed FM Approved
Maximum Working Pressure
175 psi (12,1 bar) (Also refer to Figure 2, Note 2)
Discharge Coefficient
Refer to Table A
Spray Angles
Refer to Table B
Temperature Rating
Refer to Table C
Finish and Material
Refer to Table D
Thread Connection
1/2 in. NPT
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Bushing (K=1.4 & K= 2.8) . . . . . . . . . . . . . . Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Bulb (11 mm dia.) . . . . . . . . . . . . . . . . . . . .Glass
Bulb Seats . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Spacer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Spring Plates . . . . . . . . . . . . . . . . . . . . . . Inconel
Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the nozzle to acti­vate and water to flow.
Page 1 of 6 AUGUST 2018 TFP800
TFP800
Components:
NOMINAL MAKE-IN
(1/4" & 3/8"
NPT
Page 2 of 6
-
Frame1
-
2 Deector
-
Upper Bulb Seat
3
-
4
Lower Bulb Seat
SIZE
STAMPED ON
WRENCHING
AREA FOR
1/4" & 3/8"
ORIFICE
1/2"
-
5
Pin
-
6 Button
-
7 Spacer
-
8 Spring Plates
1-3/4"
(44,5 mm)
7/16" (11,1 mm)
FIGURE 1
TYPE EA-1 PROTECTOSPRAY NOZZLE
NOMINAL DIMENSIONS
ORIFICE
SIZE
Inches
1/4 0.220 (5,59) 1.4 20,2
3/8 0.312 (7,92) 2.8 40,3
1/2 0.435 (11,05) 5.6 80,6
MINIMUM
DIAMETER
Inches (mm)
TABL E A
SELECTION OF ORIFICE SIZES
65° 95° 80° 110 ° 125° 140 ° 160° 180°
TABL E B
SELECTION OF SPR AY ANGLES
Design Criteria
Nozzle Placement
Where direct impingement of water spray onto all of the protected surface is required by the authority having juris­diction, the nozzles are to be spaced and directed so that their spray pat­terns will completely cover the plane­of-protection with the minimum required average density. However, it is recommended that indoor nozzle spacing be 12 ft (3,7 m) or less and that outdoor nozzle spacing be 10 ft (3,0 m) or less. Where rundown or slippage is planned, for example, exposure protec-
-
9
Lower Bulb Gasket
-
Gasket10
-
11 Bulb
3"
(76,2 mm)
3-7/16"
(87,3 mm)
K-FACTO R
GPM/psi
tion of vessels per NFPA 15, the above
½
-
12 Bushing
orice only)
SPRAY ANGLE
MARKING
11
10
12
LPM/bar
½
2
5
3
9
4
7
8
6
1
recommended indoor and outdoor spacings also apply.
When used for protecting the surfaces of a vessel, for example, the nozzles are positioned normal to and approx­imately 2 ft (0,6 m) from the surface. This approach, in conjunction with a properly selected spray angle, will tend to make more effective use of the spray as well as help minimize the dis­turbance effects of wind/draft condi­tions on the water spray patterns.
Spray Patterns
The Design Spray Profiles for the nozzle spray angles of 65 to 180 degrees are shown in Figure 2 and apply to dis­charge pressures of 20 to 60 psi (1,4
TEMPERATURE
RATI NG
135° F (57 °C) Unpainted Orange
175°F ( 7 9 °C) White Yell o w
250°F (121°C) Blue Blue
325°F (163°C ) Red Mauve
400°F (204°C) Green Black
500°F (260°C) Orange Black
FRAME COLOR
CODE
BULB
CODE COLOR LIQUID
TABL E C
SELECTION OF
TE M P E R AT U R E RATING S
FINISH &
MAT E RIAL
Natural Finish
Bronze
Chrome Plated
Bronze
Lead Coated
Bronze
Corrosion-Resistant Wax-Coated Bronze
TEMPERATURE
RATI NGS
All Ratings
135° F (57 °C)
175°F ( 7 9 °C) 250°F (121°C) 325°F (163°C )
135° F (57 °C)
175°F ( 7 9 °C)
TABL E D
SELECTION OF
FINISH AND MATERIALS
to 4,1 bar). Discharge pressures in excess of 60 psi (4,1 bar) will result in a decrease in coverage area because the spray patterns tend to draw inwards at higher pressures. Refer inquiries on higher discharge pressures to the Technical Services Department.
The maximum axial distances between the nozzle tip and plane-of-protection, for exposure protection, are given in Table E and F. When the axial distance from the nozzle tip to the plane-of­protection is 2 ft (0,6 m) or less, the Design Spray Profile is the same as the nominal spray angles of 65 to 140 degrees.
Heat Sensitivity
Because the Type EA-1 PROTEC­TOSPRAY Directional Spray Nozzles are automatic nozzles, they must be located with consideration of their ability to detect abnormal tempera­ture increases due to fire. Therefore, it is recommended that NFPA 13 be reviewed with respect to the rules that define the permitted distance below ceilings and the spacing limita­tions for standard coverage automatic sprinklers as a function of occupancy hazard.
Loading...
+ 4 hidden pages