![](/html/03/03aa/03aad0fde373dee51917f11dee8b5c10c62e4e146b3203ab4f2bf76cb512ca5c/bg1.png)
Worldwide
Contacts
Type EA-1 PROTECTOSPRAY
Directional Spray Nozzles, Automatic,
Medium Velocity
www.tyco-fire.com
General
Description
The TYCO Type EA-1 PROTECTOSPRAY Directional Spray Nozzles are
automatic (frangible bulb) directional
spray nozzles designed for use in water
spray fixed systems for fire protection
applications. They are external deflector-type nozzles that discharge a uniformly filled cone of medium velocity
water droplets.
The Type EA-1 PROTECTOSPRAY
Directional Spray Nozzles are effective
in covering exposed vertical, horizontal,
curved, and irregular shaped surfaces
in a cooling spray to prevent excessive
absorption of heat from an external
fire and possible structural damage or
spread of fire to the protected equipment. However, use of an automatic
nozzle requires consideration of the
response time of the thermal element.
The Type EA-1 PROTECTOSPRAY
Directional Spray Nozzles are also
especially effective for area coverage and are sometimes used in lieu of
standard sprinklers where directional
spray is considered more appropriate. In some applications, depending
on water design density requirements,
the Type EA-1 Nozzles are also used for
fire control or extinguishment.
The Type EA-1 PROTECTOSPRAY
Directional Spray Nozzles are available
in three orifice sizes and a wide variety
of spray angles (included angle of discharge), as well as temperature ratings
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
to provide versatility in system design.
It is recommended that the end user be
consulted with respect to the suitability of the materials of construction and
finish for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and
gas/chemical velocity should be considered, at a minimum, along with the
corrosive nature to which the sprinklers
may be exposed.
The Type EA-1 PROTECTOSPRAY
Directional Spray Nozzle is a re-designation for the Gem Type EA-1.
NOTICE
The Type EA-1 PROTECTOSPRAY
Directional Spray Nozzles described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association, in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The design of individual water spray
fixed systems can vary considerably,
depending on the characteristics and
nature of the hazard, the basic purpose
of the spraying system, the configuration of the hazard, and wind/draft conditions. Because of these variations,
as well as the wide range of available
nozzle spray characteristics, the design
of water spray fixed systems for fire
protection must only be performed by
experienced designers who thoroughly
understand the limitations as well as
capabilities of such systems.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
(Also refer to Figure 2, Note 2)
Discharge Coefficient
Refer to Table A
Spray Angles
Refer to Table B
Temperature Rating
Refer to Table C
Finish and Material
Refer to Table D
Thread Connection
1/2 in. NPT
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Bushing (K=1.4 & K= 2.8) . . . . . . . . . . . . . . Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Bulb (11 mm dia.) . . . . . . . . . . . . . . . . . . . .Glass
Bulb Seats . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Spacer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Spring Plates . . . . . . . . . . . . . . . . . . . . . . Inconel
Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the nozzle to activate and water to flow.
Page 1 of 6 AUGUST 2018 TFP800
![](/html/03/03aa/03aad0fde373dee51917f11dee8b5c10c62e4e146b3203ab4f2bf76cb512ca5c/bg2.png)
TFP800
Page 2 of 6
-
Frame1
-
2 Deector
-
Upper Bulb Seat
3
-
4
Lower Bulb Seat
SIZE
STAMPED ON
WRENCHING
AREA FOR
1/4" & 3/8"
ORIFICE
1/2"
-
5
Pin
-
6 Button
-
7 Spacer
-
8 Spring Plates
1-3/4"
(44,5 mm)
7/16" (11,1 mm)
FIGURE 1
TYPE EA-1 PROTECTOSPRAY NOZZLE
NOMINAL DIMENSIONS
ORIFICE
SIZE
Inches
1/4 0.220 (5,59) 1.4 20,2
3/8 0.312 (7,92) 2.8 40,3
1/2 0.435 (11,05) 5.6 80,6
MINIMUM
DIAMETER
Inches (mm)
TABL E A
SELECTION OF ORIFICE SIZES
65° 95° 80° 110 ° 125° 140 ° 160° 180°
TABL E B
SELECTION OF SPR AY ANGLES
Design
Criteria
Nozzle Placement
Where direct impingement of water
spray onto all of the protected surface
is required by the authority having jurisdiction, the nozzles are to be spaced
and directed so that their spray patterns will completely cover the planeof-protection with the minimum
required average density. However, it
is recommended that indoor nozzle
spacing be 12 ft (3,7 m) or less and that
outdoor nozzle spacing be 10 ft (3,0 m)
or less. Where rundown or slippage is
planned, for example, exposure protec-
-
9
Lower Bulb
Gasket
-
Gasket10
-
11 Bulb
3"
(76,2 mm)
3-7/16"
(87,3 mm)
K-FACTO R
GPM/psi
tion of vessels per NFPA 15, the above
½
-
12 Bushing
orice only)
SPRAY ANGLE
MARKING
11
10
12
LPM/bar
½
2
5
3
9
4
7
8
6
1
recommended indoor and outdoor
spacings also apply.
When used for protecting the surfaces
of a vessel, for example, the nozzles
are positioned normal to and approximately 2 ft (0,6 m) from the surface.
This approach, in conjunction with
a properly selected spray angle, will
tend to make more effective use of the
spray as well as help minimize the disturbance effects of wind/draft conditions on the water spray patterns.
Spray Patterns
The Design Spray Profiles for the nozzle
spray angles of 65 to 180 degrees are
shown in Figure 2 and apply to discharge pressures of 20 to 60 psi (1,4
TEMPERATURE
RATI NG
135° F (57 °C) Unpainted Orange
175°F ( 7 9 °C) White Yell o w
250°F (121°C) Blue Blue
325°F (163°C ) Red Mauve
400°F (204°C) Green Black
500°F (260°C) Orange Black
FRAME
COLOR
CODE
BULB
CODE
COLOR
LIQUID
TABL E C
SELECTION OF
TE M P E R AT U R E RATING S
FINISH &
MAT E RIAL
Natural Finish
Bronze
Chrome Plated
Bronze
Lead Coated
Bronze
Corrosion-Resistant
Wax-Coated Bronze
TEMPERATURE
RATI NGS
All Ratings
135° F (57 °C)
175°F ( 7 9 °C)
250°F (121°C)
325°F (163°C )
135° F (57 °C)
175°F ( 7 9 °C)
TABL E D
SELECTION OF
FINISH AND MATERIALS
to 4,1 bar). Discharge pressures in
excess of 60 psi (4,1 bar) will result in a
decrease in coverage area because the
spray patterns tend to draw inwards
at higher pressures. Refer inquiries
on higher discharge pressures to the
Technical Services Department.
The maximum axial distances between
the nozzle tip and plane-of-protection,
for exposure protection, are given in
Table E and F. When the axial distance
from the nozzle tip to the plane-ofprotection is 2 ft (0,6 m) or less, the
Design Spray Profile is the same as
the nominal spray angles of 65 to 140
degrees.
Heat Sensitivity
Because the Type EA-1 PROTECTOSPRAY Directional Spray Nozzles
are automatic nozzles, they must be
located with consideration of their
ability to detect abnormal temperature increases due to fire. Therefore,
it is recommended that NFPA 13 be
reviewed with respect to the rules
that define the permitted distance
below ceilings and the spacing limitations for standard coverage automatic
sprinklers as a function of occupancy
hazard.