Tyco DV-5 User Manual

Page 1
DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System — Electric Actuation
General Description
The DV-5 Deluge Valve (described in Technical Data Sheet TFP1305) is a diaphragm style valve that depends upon water pressure in the Diaphragm Chamber to hold the Diaphragm closed against the water supply pressure. When the DV-5 Valve is set for service, the Diaphragm Chamber is pressurized through the trim connections from the inlet side of the system’s main con­trol valve, for example an O.S.&Y. gate valve or buttery valve (Ref. Figures 1 and 4).
Operation of an electrical device such as a heat sensitive thermostat, smoke detector, or electrical manual control station signals the Deluge Valve Re­leasing Panel to energize the Solenoid Valve. In turn, the energized Solenoid Valve opens to release water from the Diaphragm Chamber faster than it can be replenished through the 1/8 inch (3,2 mm) restriction provided by the Model ASV-1 Automatic Shut-Off Valve in the diaphragm supply connections (Item 5 - Fig. 3A and 5, also described in Technical Data Sheet TFP1384). This results in a rapid pressure drop in the Diaphragm Chamber and the force differential applied through the Dia­phragm that holds it in the set position is reduced below the valve trip point. The water supply pressure then forces the Diaphragm open permitting water to ow into the system piping, as well as through the Alarm Port to actuate the system alarms.
As water ows into the system, the pi­lot chamber of the Model ASV-1 Auto­matic Shut-Off Valve (Item 5 - Fig. 3A and 5) becomes pressurized and the ASV-1 automatically shuts off the di­aphragm chamber supply ow to the DV-5 Diaphragm Chamber. Shutting off the diaphragm chamber supply ow prevents the DV-5 Diaphragm Chamber from becoming re-pressurized, there­by preventing inadvertent closing of the DV-5 during a re (as may be the case should the Solenoid Valve become de­energized after its initial operation).
NOTICE
The DV-5 Deluge Valve with Electric Actuation Trim described herein must be installed and maintained in compli­ance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Worldwide
Contacts
www.tyco-fire.com
Page 1 of 14 OCTOBER 2014 TFP1320
Page 2
TFP1320
etc. (Fire Detection)
Page 2 of 14
13
6
5
11
14
7
8
3
9
1
15
2
4
-
1
DV-5 Deluge Valve
-
2
Main Control Valve (N.O.)
-
3
Diaphragm Chamber Supply Control Valve (N.O.)
-
4
Local Manual Control Station
-
5
Open Nozzles or Sprinklers
-
6
Heat Detectors, Smoke Detectors,
-
7
Water Supply Pressure Gauge
-
8
Diaphragm Chamber Pressure Gauge
-
9
System Drain Valve (N.C.)
-
10
Main Drain Valve (N.C.) (Shown at Rear of Valve)
-
11
Diaphragm Chamber Automatic Shut-Off Valve
FIGURE 1 (1 OF 2)
SYSTEM SCHEMATIC (FRONT VIEW)
ELECTRIC ACTUATION
-
12
Waterow Pressure Alarm Switch (Shown at Rear of Valve)
-
13
Water Motor Alarm (Optional)
-
14
Solenoid Valve
-
15
Deluge Valve Releasing Panel
Page 3
TFP1320
-
12
etc. (Fire Detection)
Waterow Pressure Alarm Switch
Page 3 of 14
6
5
15
14
12
13
11
9
3
10
1
2
-
1
DV-5 Deluge Valve
-
2
Main Control Valve (N.O.)
-
3
Diaphragm Chamber Supply Control Valve (N.O.)
-
4
Local Manual Control Station (Shown at Front of Valve)
-
5
Open Nozzles or Sprinklers
-
6
Heat Detectors, Smoke Detectors,
-
7
Water Supply Pressure Gauge (Shown at Front of Valve)
-
8
Diaphragm Chamber Pressure Gauge (Shown at Front of Valve)
-
9
System Drain Valve (N.C.)
-
10
Main Drain Valve (N.C.)
-
11
Diaphragm Chamber Automatic Shut-Off Valve
SYSTEM SCHEMATIC (REAR VIEW)
ELECTRIC ACTUATION
FIGURE 1 (2 OF 2)
-
13
Water Motor Alarm (Optional)
-
14
Solenoid Valve
-
15
Deluge Valve Releasing Panel
Page 4
TRIM SHOWN FULLY ASSEMBLED; COMPONENTS SUCH AS GAUGES
WATERFLOW
TFP1320
Page 4 of 14
PRESSURE
ALARM
SWITCH
DELUGE
SYSTEM
GROOVED
COUPLING
SHUT-OFF
FIGURE 2
DV-5 PRE-TRIMMED DELUGE VALVE
ELECTRIC ACTUATION
Technical Data
Approvals
UL and C-UL Listed FM Approved.
Valve Trim
The Vertical Electric Actuation Trim (Fig. 3A/3B) and Horizontal Electric Actuation Trim (Fig. 5) form a part of the laboratory listings and approvals for the DV-5 Valve and are necessary for its proper operation.
Each package of trim includes the fol­lowing items:
• Water Supply Pressure Gauge
• Diaphragm Chamber
Pressure Gauge
• Diaphragm Chamber Connections
• Manual Control Station
• Main Drain Valve
• System Drain Valve
• Alarm Test Valve
• Automatic Drain Valve
The following items are included in the Pre-trimmed Valve Assembly and can be ordered separately for the valve trim:
• Model BFV-N Buttery Valve
• Waterow Pressure Alarm Switch
(PS10-2)
• Figure 577 Grooved Coupling
To ease eld assembly of the trim ar­rangement, the vertical trim compo­nents are provided partially assembled as shown in Figure 3B.
DELUGE
ELECTRIC
ACTUATION
TRIM
NOTES:
1. SEE FIGURE 3, PER VALVE SIZE AS APPLICABLE, FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS AND COMPONENT PART NUMBERS.
2.
DV-5
VALVE
VALVE
AND SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT VALVE INSTALLATION.
The trim arrangement is provided with galvanized, black, or brass nipples and ttings. The galvanized and brass trim are intended for non-corrosive or cor­rosive conditions, whereas the black trim is principally intended for use with AFFF systems.
NOTE: When the system pressure is greater than 175 psi (12,1 bar), provision is to be made to replace the standard order 300 psi (20,7 bar) Water Pressure Gauges, shown in Figure 3A/3B and 5 with separately ordered 600 psi (41,4 bar) Water Pressure Gauges.
The Electric Actuation Trim is required for electric operation of the DV-5 Valve by a detection system consisting of electrical devices such as heat sen­sitive thermostats, smoke detectors, and/or electric manual pull stations. Information on the various types of separately ordered Solenoid Valves that may be used with this trim pack­age is given in Technical Data Sheet TFP2180. Nominal installation dimen­sions for the Vertical Electric Actuation Trim are shown in Figure 4.
NOTE: Approval by Factory Mutu­al is contingent on the use of an FM Approved 24VDC Solenoid Valve. FM only approves solenoid valves for use in non-hazardous locations.
Consult with the authority having ju­risdiction regarding installation cri­teria pertaining to electric actuation circuitry.
The Electric Actuation Trim is provided with a Model ASV-1 Automatic Shut-Off Valve (Item 5 - Fig. 3A and 5); conse­quently, the release circuit of the Re­leasing Panel need only provide the standard ten minutes of alarm condi-
tion intended to energize the Solenoid Valve to open. After the ten minute du­ration, at which point should the Sole­noid Valve become de-energized and close (especially while operating under battery back-up), the Automatic Shut­Off Valve will have already automatical­ly closed, thereby preventing the DV-5 Diaphragm Chamber from becoming re-pressurized, and preventing an in­advertent closing of the DV-5 during a re event.
Materials of Construction
NOTES: The galvanized or brass nip­ples and fittings for the Valve Trim provide corrosion resistance and are intended to extend the life of the instal­lation of the DV-5 Valve when exposed to internal and external corrosive con­ditions. Although these selections are intended to resist corrosion, it is rec­ommended that the end user or oth­er technical expert familiar with con­ditions at the proposed installation be consulted with respect to these selec­tions for a given corrosive condition.
Systems using a seawater or brackish water supply require special consid­erations in order to extend the life of the valve and trim. This type of system ideally should be configured with a pri­mary source of clean fresh water (e.g., a pressurized water tank) and that only upon system operation is the second­ary water supply (seawater or brack­ish water) allowed to enter the system. After the system operation, the sys­tem should be thoroughly flushed with clean fresh water. Following this rec­ommendation will increase the service life of the DV-5 Valve and Valve Trim.
Pressure Gauges. Bronze bourdon tube with brass socket.
Gauge Test Valve. Bronze body per ASTM B584.
Manual Control Station. Corrosion resistant copper alloys and glass lled PTFE seals. Thermoplastic enclosure.
Automatic Drain Valve. Brass body per ASTM B584, Type 440 stainless steel or brass per ASTM B134 Ball, and galvanized steel inlet.
Automatic Shut-Off Valve. Brass body, cover, and center seat per UNS C36000, Type 316 stainless steel spring, and Nylon fabric reinforced, natural rubber diaphragm per ASTM D2000.
Ball Valve. Corrosion resistant copper alloys and glass lled PTFE seals.
Spring Loaded Check Valve. Brass body and buna-n seal.
Page 5
TFP1320
Item 14.
2.
3.
4.
5.
1.
NOTES:
Page 5 of 14
NO.
DESCRIPTION P/N
1 2 3
Model MC-1 Manual Control Station 52-289-2-001
4
Model AD-1 Automatic Drain Valve 52-793-2-004 5 6
Item No. Not Used 7 8 9
10 31 11 12
Drip Funnel Connector
Drip Funnel Bracket
13
Drip Funnel
14 15 16
1/4" x 18" Tubing CH
1/2" Tubing Connector CH
17
1/2" x 12" Tubing CH
18
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
1/4" Plug CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
3/4" Plug CH
21
1/2" Union CH
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
QTY.
. .
2
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge
1
46-005-1-0021/4" Gauge Test Valve
1
. . . . . .
1
. . . . . . .
. . .
1
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
2
. . . . . . . . .
46-050-1-0041/2" Ball Valve
1
92-322-1-0021/2" Spring Loaded Check Valve
1
52-353-1-0051/2" Y-Strainer
1 2
46-049-1-0053/4" Swing Check Valve 1/4" x Close Nipple CH
2
46-048-1-0053/4" Angle Valve
1
92-211-1-005
1
92-211-1-003
1
92-343-1-007
1
92-032-1-0023/32" Vent Fitting 1 1 1 1 1 5
A1
16
27
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
29
20
35
43
33
24
29
(GREEN
TINT)
28
42
42
10
42
38
7
35
Electric Actuation Trim is comprised of Items 1-45
19 plus Items E2-E4. Item E1 ordered separately. Items A1-A3 included only in pre-trimmed valve assemblies as applicable; otherwise ordered separately.
31
31
23
All Fittings and Nipples are galvanized (Standard Order).
CH: Common Hardware. See Figure 2 of TFP1305 for
Valve Port identication. Route all Tubing to Drip Funnel,
NO. NO.
DESCRIPTION P/N DESCRIPTION P/N
22 23 24 45 25 26 27 28 29 30
32 33 34 35 36 37 38 39 40 41 42
. . . . . . . . . . . . . . . . . . . . . . . . . . .
3/4" Union CH 1/4" 90° Elbow CH 1/2" 90° Elbow CH 3/4" 90° Elbow CH 1/2" Tee CH 1/2" x 1/4" x 1/2" Tee CH 3/4" Tee CH 3/4" x 1/2" x 3/4" Tee 3/4" x 3/4" x 1/2" Tee CH
1/2" x Close Nipple CH 1/2" x 1-1/2" Nipple CH 1/2" x 2" Nipple CH 1/2" x 2-1/2" Nipple 1/2" x 5" Nipple CH 1/2" x 7" Nipple CH Select Nipple per Table CH Select Nipple per Table CH Select Nipple per Table CH 3/4" x Close Nipple CH 3/4" x 1-1/2" Nipple
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
30
15
42
42
22
42
42
42
28
11
44
1
21
2
36
39
27
2" (DN50)
GROOVE x GROOVE
DV-5 DELUGE VALVE
QTY. QTY.
2 1 8 1 3 3 2 2
CH
1
3
10
1 4
CH 2 1 1 1 1 1 8
CH
41
11
43
3/4" x 2" Nipple CH
44
3/4" x 4" Nipple CH Select Nipple per Table CH
E1
Solenoid Valve Ordered Separately Per Data Sheet TFP2180
E2
1/2" Tubing Connector CH
E3
1/2" x 24" Tubing CH
E4
1/2" x 1-1/2" Nipple CH
A1
Waterow Pressure Alarm Switch, Model PS10-2 25710
A2
Buttery Valve, Power Ball 300:
A3
Figure 577 Coupling:
Nipple
Number
38
45
35
24
4
33
E3
25
22
26
12
24
35
24
14
33
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
COMPONENTS INCLUDED ONLY IN
PRE-TRIMMED VALVE ASSEMBLIES:
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1/2" (DN40)
1/2" x 1-1/2"
3/4" x 1-1/2"45
E2
36
21
40
26
32
13
A3
A2
5
8
24
9
33
33
33
21
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
1/2" x 2"39 1/2" x 1-1/2" 1/2" x 5"40
SEPARATELY)
32
24
37
33
21
34
18
24
SHOWN
33
7
1 1 1
1 1 1 1
1
1 1
1 1
2" (DN50)
1/2" x 5-1/2" 3/4" x 2-1/2"
E1
(ORDERED
E4
21
26
33
3
17
Refer to Data Sheet
51024A1-1/2" (DN40) 51021A2" (DN50)
57715ACP1-1/2" (DN40) 57720ACP2" (DN50)
1/2" x 2"
33
1
27
32
24
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM
Y-Strainer. Bronze body per ASTM B584 and Type 304 stainless steel screen.
Swing Check Valve. Bronze body per ASTM B584 and buna-n seal.
Angle Valve. Bronze body per ASTM B584 and nitrile disc (TEFLON disc for 2 inch size valve).
3/32” Vent Fitting. Brass per ASTM B16.
Tubing Connector. Brass per ASTM B16.
Tubing. Type L copper per ASTM B88.
FIGURE 3A (1 OF 3)
Pipe Fittings. Galvanized mallea­ble iron per ANSI B16.3 or cast iron per ANSI B16.4; black malleable iron per ANSI B16.3 or cast iron per ANSI B16.4; or, bronze per ANSI B16.15.
Pipe Nipples. Schedule 40 galvanized steel per ASTM A53 or A135; Sched­ule 40 black steel per ASTM A53 or A135; or, Schedule 40 red brass pipe per ASTM B43.
Page 6
TFP1320
Item 15.
2.
3.
4.
5.
1.
NOTES:
Page 6 of 14
DESCRIPTION P/N
NO.
1 19 2
Model MC-1 Manual Control Station 52-289-2-001
3
Model AD-1 Automatic Drain Valve 52-793-2-004
4 5
Item No. Not Used
6 7 8
9 10 11 12
Drip Funnel Connector
13
Drip Funnel Bracket
14
Drip Funnel
15 16
1/4" x 18" Tubing CH
17
1/2" Tubing Connector CH
18
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
QTY.
2
. .
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge
1
46-005-1-0021/4" Gauge Test Valve
1
. . . . . .
1
. . . . . . .
1 1
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
. . . . . . . . . . . . . . . . . . . . . . .
2
A1
46-050-1-0041/2" Ball Valve
1
92-322-1-0021/2" Spring Loaded Check Valve
1
52-353-1-0051/2" Y-Strainer
1
46-049-1-0053/4" Swing Check Valve
1
46-048-1-0053/4" Angle Valve
1
46-048-1-0071-1/4" Angle Valve
1
92-211-1-005
1
92-211-1-003
1
92-343-1-007
1
92-032-1-0023/32" Vent Fitting 1 1
17
. . . . . . . . .
28
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
30
21
36
45
35
25
30
(GREEN
29
44
10
44
35
7
12
Electric Actuation Trim is
40
comprised of Items 1-48 plus Items E2-E4. Item E1 ordered separately. Items
20
A1-A3 included only in pre-trimmed valve assemblies as applicable; otherwise ordered separately.
All Fittings and Nipples are galvanized (Standard Order).
33
24
CH: Common Hardware. See Figure 2 of TFP1305 for
Valve Port identication. Route all Tubing to Drip Funnel,
DESCRIPTION P/N DESCRIPTION P/N
NO. NO.
1/2" x 12" Tubing CH 1/4" Plug CH
20 21
3/4" Plug CH 1/2" Union CH
22
3/4" Union CH
23
1/4" 90° Elbow CH
24
1/2" 90° Elbow CH
25
3/4" 90° Elbow CH
26
1/2" Tee CH
27
1/2" x 1/4" x 1/2" Tee
28
3/4" Tee CH
29 30
3/4" x 1/2" x 3/4" Tee 3/4" x 3/4" x 1/2" Tee CH
31 32
1-1/4" x 3/4" x 1-1/4" Tee CH 1/4" x Close Nipple CH
33
1/2" x Close Nipple CH
34
1/2" x 1-1/2" Nipple CH
35
1/2" x 2-1/2" Nipple
36
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
31
16
TINT)
44
36
QTY. QTY.
1 1 1 5 2 1 8 1 3 3
CH 1 2
CH 1 1 2 2
13
2
CH
43
11
46
25
26
37
1/2" x 3-1/2" Nipple CH 1/2" x 4" Nipple CH
38 39
1/2" x 4-1/2" Nipple CH 1/2" x 5" Nipple CH
40
1/2" x 5-1/2" Nipple CH
41
1/2" x 7" Nipple CH
42 43
3/4" x Close Nipple CH 3/4" x 1-1/2" Nipple
44
3/4" x 2" Nipple CH
45
3/4" x 4-1/2" Nipple CH
46
1-1/4" x 2" Nipple CH
47
1-1/4" x 4" Nipple
48
E1
Solenoid Valve Ordered Separately Per Data Sheet TFP2180 1/2" Tubing Connector CH
E2
1/2" x 24" Tubing CH
E3
1/2" x 1-1/2" Nipple CH
E4
A1
Waterow Pressure Alarm Switch, Model PS10-2 25710
A2
Model BFV-N Buttery Valve, 3" (DN80) 59300F030N
A3
Figure 577 Coupling, 3" (DN80) 57730ACP
35
E3
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
COMPONENTS INCLUDED ONLY IN
PRE-TRIMMED VALVE ASSEMBLIES:
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
E2
4
23
44
44
23
43
27
43
38
13
15
32
47
48
1
22
2
39
35
28
33
3" (DN80)
A2
A3
25
35
22
41
22
35
42
25
25
25
27
35
14
5
35
34
42
35
8
9
35
22
37
19
25
GROOVE x GROOVE
DV-5 DELUGE VALVE
SHOWN
35
7
1 1 1 1
2 3 5 1 1 1 1
1 1 1 1
1 1
. . .
1
. . . . . . . . . .
E1
(ORDERED
SEPARATELY)
E4
22
27
35
3
18
CH
CH
Refer to Data Sheet
35
34
25
1
28
3 INCH (DN80) DV-5 DELUGE VALVE
FIGURE 3A (2 OF 3)
EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM
Page 7
TFP1320
Item 15.
2.
3.
4.
5.
1.
NOTES:
28
Page 7 of 14
. . . . . .
. . . . . . .
. . . . . . . . .
. . .
A1
QTY.
2 1 1 1 1
2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 2 1 8 1 3 3 2
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge 46-005-1-0021/4" Gauge Test Valve
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
46-050-1-0041/2" Ball Valve 92-322-1-0021/2" Spring Loaded Check Valve 52-353-1-0051/2" Y-Strainer 46-049-1-0053/4" Swing Check Valve 46-048-1-0061" Angle Valve 46-048-1-0092" Angle Valve 92-211-1-005 92-211-1-003 92-343-1-007 92-032-1-0023/32" Vent Fitting
CH CH
17
DESCRIPTION P/N
NO.
1 2 3
Model MC-1 Manual Control Station 52-289-2-001
4
Model AD-1 Automatic Drain Valve 52-793-2-004
5
Item No. Not Used
6 35 7 8
9 10 11 12 13
Drip Funnel Connector
14
Drip Funnel Bracket
15
Drip Funnel 16 17
Select Tubing per Table CH 18
1/2" Tubing Connector CH 19
1/2" x 24" Tubing CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
1/4" Plug CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
3/4" Plug CH 22
1/2" Union CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
1" Union CH 24
1/4" 90° Elbow CH 25
1/2" 90° Elbow CH 26
1" 90° Elbow CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
1/2" Tee CH 28
1/2" x 1/4" x 1/2" Tee
3/4" x 1/2" x 3/4" Tee
29
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
28
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
29
21
36
45
35
25
29
16
(GREEN
TINT)
44
10
46
41
7
Electric Actuation Trim is comprised of Items 1-52 plus Items E2-E4. Item E1 ordered separately. Items A1-A3 included only in
40
20
pre-trimmed valve assemblies as applicable; otherwise ordered separately.
All Fittings and Nipples are galvanized (Standard Order).
CH: Common Hardware.
33
24
See Figure 2 of TFP1305 for Valve Port identication.
Route all Tubing to Drip Funnel,
NO.
DESCRIPTION P/N
1" x 1" x 1/2" Tee CH
30
1" x 3/4" x 1" Tee
31
2" x 1" x 2" Tee CH
32 33
1/4" x Close Nipple CH 1/2" x Close Nipple CH
34
1/2" x 1-1/2" Nipple CH 1/2" x 2-1/2" Nipple
36 37
Select Nipple per Table 1/2" x 5" Nipple CH
38 39
1/2" x 6" Nipple CH
40
1/2" x 7" Nipple CH Select Nipple per Table CH
41 42
Select Nipple per Table CH
43
Select Nipple per Table CH
44
3/4" x 1-1/2" Nipple
45
3/4" x 2" Nipple CH
46
Select Nipple per Table CH
47
1" x Close Nipple CH
48
1" x 3" Nipple CH
49
Select Nipple per Table CH
50
2" x 3" Nipple CH
51
2" x 5" Nipple CH
52
Select Nipple per Table CH
E1
Solenoid Valve Ordered Separately Per Data Sheet TFP2180
E2
1/2" Tubing Connector CH
E3
1/2" x 24" Tubing CH
E4
1/2" x 1-1/2" Nipple CH
. . . . . . . . . . . . . . . . . . . . .. .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
30
47
23
31
23
47
47
48
32
50
51
12
1
22
2
38
35
28
33
4" (DN100)
GROOVE x GROOVE
DV-5 DELUGE VALVE
SHOWN
QTY.
1 1
CH 1 2 2
10
3
CH 1
CH 2 1 2 1 1 1 1
CH 1 1 5 1 1 1 1 1
Refer to 1
Data Sheet 1 1 1
47
11
NO.
A1
A2
A3
49
36
26
47
25
37
27
36
25
13
15
9
25
A3
A2
35
COMPONENTS INCLUDED ONLY IN
PRE-TRIMMED VALVE ASSEMBLIES:
DESCRIPTION P/N
Waterow Pressure Alarm Switch, Model PS10-2 25710 Model BFV-N Buttery Valve:
Figure 577 Coupling:
Tube
No.
17
Nipple
No.
41
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Select Appropriate Tube Size
per DV-5 Deluge Valve Size
4" 6"
(DN100)
1/4" x 24"
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
4" 6"
(DN100)
1/2" x 3"37 1/2" x 3" 1/2" x 5"
1/2" x 2-1/2"
1/2" x 2"42 1/2" x 6-1/2"43 3/4" x 2-1/2"46
1" x 6"49 1" x 9"
1/2" x 7"52 1/2" x 7" 1/2" x 9"
E3
E2
4
39
22
42
43
25
25
(DN150)
1/4" x 24"
(DN150)
1/2" x 5-1/2"
1/2" x 3" 1/2" x 7-1/2" 3/4" x 3-1/2"
(ORDERED
SEPARATELY)
E4
27
QTY.
1
1 1 1
1 1 1
E1
22
27
35
14
5
35
34
35
52
35
8
22
38
25
3
19
18
35
59300F040N4" (DN100) 59300F060N6" (DN150) 59300F080N8" (DN200)
57740ACP4" (DN100) 57760ACP6" (DN150) 57780ACP8" (DN200)
8"
(DN200)
1/4" x 32"
8"
(DN200)
1/2" x 8-1/2" 1/2" x 3-1/2"
1/2" x 9"
3/4" x 4-1/2"
1" x 12"
35
25
1
34
22
35
7
4, 6, AND 8 INCH (DN100, DN150 AND DN200) DV-5 DELUGE VALVES
FIGURE 3A (3 OF 3)
EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM
Page 8
TFP1320
WATER SUPPLY
DIAPHRAGM
Page 8 of 14
WATERFLOW
PRESSURE ALARM
SWITCH, ORDERED
SEPARATELY
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
NIPPLE
Nipple
Number
Main Drain
1
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM TEST VALVE (NORMALLY
CLOSED)
SYSTEM
WATER
SUPPLY
PRESSURE
GAUGE
1
Size
MAIN
1-1/2" (DN40)
1/2" x Close 1/2" x Close2
1/2" x 5"3 3/4" x 1-1/2"4 3/4" x 1-1/2"5 3/4" x 2-1/2" 1/2" x 1-1/2"6 1/2" x 1-1/2" 1/2" x 3" 1/2" x 3"1/2" x 1-1/2" 1/2" x 5"
1/2" x 7"7 1/2" x 7" 1/2" x 7" 1/2" x 7"1/2" x 7" 1/2" x 9"
3/4" NPT 3/4" NPT 2" NPT 2" NPT1-1/4" NPT
1/4" x 18"Tube 1 1/4" x 18" 1/4" x 24" 1/4" x 24"1/4" x 18" 1/4" x 32"
NIPPLE
1-1/4 INCH NPT
Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
VENT FITTING (GREEN TINT)
B
4
NIPPLE
6
DRIP
FUNNEL
CONNECTION
TO DRAIN
A
C
2" (DN50)
1/2" x 2"
1/2" x Close 1/2" x 5-1/2" 3/4" x 1-1/2"
TUBE 1
DRAIN VALVE
(NORMALLY
AUTOMATIC
DRAIN VALVE
MAIN DRAIN
CONNECTION
(SIZED PER
TABLE)
3" (DN80) 1/2" x 1-1/2" 1/2" x 1-1/2"
1/2" x 7" 3/4" x 1-1/2" 3/4" x 4-1/2"
SYSTEM
CLOSED)
NIPPLE
DIAPHRAGM
CHAMBER SUPPLY
CONTROL VALVE
(NORMALLY
5
4" (DN100)
1/2" x 2-1/2"
1/2" x 2" 1/2" x 6-1/2" 3/4" x 2-1/2"
1" x 6" 1" x 9"
NOTES:
Install subassemblies in alphabetical order.1.
2.
See Figure 2 of TFP1305 for Valve Port identication.
Route all Tubing to Drip Funnel.3. When DV-5 trips, Automatic Shut-Off Valve
4. shuts off diaphragm chamber supply.
5. Nipples 1-7 and Tube 1 vary in length relative to DV-5 size. Select per table. All other nipples and tubing packed unassembled shall be installed per appropriate trim exploded view, Figure 3A Part 1, 2, or 3.
4" (DN100)
FLANGE x FLANGE
DV-5 DELUGE
VALVE SHOWN
OPEN)
1/2 INCH NPT
CONNECTION FROM
6" (DN150)
1/2" x 5-1/2"
1/2" x 3" 1/2" x 7-1/2" 3/4" x 3-1/2"
D
SHUT-OFF VALVE
8" (DN200) 1/2" x 8-1/2" 1/2" x 3-1/2"
1/2" x 9"
3/4" x 4-1/2"
1" x 12"
2" NPT
1/2 INCH CONDUIT
CONNECTION FOR
"ELECTRIC DETECTION"
ORDERED SEPARATELY
NIPPLE
7
AUTOMATIC
(NORMALLY
OPEN)
SOLENOID VALVE,
(NORMALLY CLOSED)
NIPPLE
2
NIPPLE
3
CHAMBER
PRESSURE
GAUGE
MANUAL
CONTROL
STATION
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
FIGURE 3B
OPERATIONAL COMPONENTS OF VERTICAL ELECTRIC ACTUATION TRIM
EXPLODED ARRANGEMENT OF SEMI-PREASSEMBLED TRIM
Page 9
Nominal Installation Dimensions in Inches and (mm)
Valve
LEFT VIEW FRONT VIEW
Size
1-1/2"
DN40
2"
DN50
3"
DN80
4"
DN100
6"
DN150
8"
DN200
A
7.00
(177,8)
7.13
(181,0)
7.81
(198,4)
10.00
(254,0)
11.38
(289,0)
12.00
(304,8)
B
8.88
(225,4)
9.13
(231,8)
10.44
(265,1)
11.75
(298,5)
14.31
(363,5)
16.00
(406,4)
C
13.19
(335,0)
13.19
(335,0)
13.19
(335,0)
14.31
(363,5)
15.31
(388,9)
16.25
(412,8)
D
10.50
(266,7)
10.50
(266,7)
10.50
(266,7)
10.50
(266,7)
10.50
(266,7)
10.50
(266,7)
E
15.25
(387,4)
15.56
(395,3)
19.13
(485,8)
22.13
(562,0)
23.31
(592,1)
25.50
(647,7)
MINIMUM CLEARANCE
*
F
1.25
(31,8)
0.94
(23,8)
1.63
(41,3)
1.75
(44,5)
3.50
(88,9)
1.75
(44,5)
(147,6)
(152,4)
(170,0)
(217,5)
(252,4)
10.75
(273,1)
G
5.81
6.00
6.69
8.56
9.94
H
1.81
(46,0)
2.00
(50,8)
2.69
(68,3)
4.44
(112,7)
5.81
(147,6)
6.50
(165,1)
J
3.00
(76,2)
3.00
(76,2)
4.25
(108,0)
6.25
(158,8)
6.25
(158,8)
6.25
(158,8)
K
7.00
(177,8)
7.00
(177,8)
7.00
(177,8)
7.13
(181,0)
7.13
(181,0)
7.13
(181,0)
L
3.88
(98,4)
3.00
(76,2)
0.88
(22,2)
0.63
(15,9)
1.81
(46,0)
7.38
(187,3)
Page 9 of 14
M
8.00
(204,0)
8.63
(220,0)
12.75
(324,0)
15.75
(400,0)
18.13
(460,4)
22.50
(570,0)
TFP1320
N
4.02
(102,1)
4.09
(103,9)
3.85
(98,0)
4.56
(116,0)
5.86
(149,0)
5.26
(134,0)
* * *
F
H K
G
B
N
J
DCA
L
FIGURE 4
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DELUGE VALVES
VERTICAL ELECTRIC ACTUATION / NOMINAL INSTALLATION DIMENSIONS
*
E
M
Page 10
TFP1320
SEPARATELY)
Page 10 of 14
NO. NO.
DESCRIPTION P/N DESCRIPTION P/N
10 11 12
Drip Funnel Connector
13
Drip Funnel Bracket
14
Drip Funnel 15 24 16
1/4" x 18" Tubing CH 17
1/2" Tubing Connector CH 18
1/2" x 12" Tubing CH
33
5
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
24
E4
40
26
32
33
21
24
37
32
26
33
35
21
. . . . . .
. . . . . . .
. . . . . . . . .
33
QTY.
. .
2
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge
1
46-005-1-0021/4" Gauge Test Valve 1 1
. . .
1
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
2
46-050-1-0041/2" Ball Valve 1
92-322-1-0021/2" Spring Loaded Check Valve 1
52-353-1-0051/2" Y-Strainer
33
NO.
DESCRIPTION P/N
1 19 2 3
Model MC-1 Manual Control Station 52-289-2-001
4
Model AD-1 Automatic Drain Valve 52-793-2-004 5 6
Item No. Not Used 7 8 9
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
33
1
19
7
2
GROOVE x GROOVE
DV-5 DELUGE VALVE
31
31
39
23
21
27
35
21
2" (DN50)
SHOWN
36
7
24
9
8
34
24
QTY. QTY.
1
46-049-1-0053/4" Swing Check Valve
2
46-048-1-0053/4" Angle Valve
1
92-211-1-005
1
92-211-1-003
1
92-343-1-007
1
92-032-1-0023/32" Vent Fitting 1 1 1
E2
E3
E1
(ORDERED
SEPARATELY)
33
1
21
33
27
3
36
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
20
A1
(ORDERED
38
24
32
33
24
43
27
29
42
35
44
10
15
(GREEN
TINT)
22
42
42
18
42
26
28
35
30
16
29
24
17
4
14
12
42
11
42
22
42
28
41
45
25
11
13
42
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1/4" Plug CH
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
3/4" Plug CH 21 22 23
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
E1
E2 E3 E4
A1
. . . . . . . . . . . . . . . . . . . . . . . . . . .
1/2" Union CH
. . . . . . . . . . . . . . . . . . . . . . . . . . .
3/4" Union CH
1/4" 90° Elbow CH
1/2" 90° Elbow CH
3/4" 90° Elbow CH
1/2" Tee CH
1/2" x 1/4" x 1/2" Tee CH
3/4" Tee CH
3/4" x 1/2" x 3/4" Tee
3/4" x 3/4" x 1/2" Tee CH
1/4" x Close Nipple CH
1/2" x Close Nipple CH
1/2" x 1-1/2" Nipple CH
1/2" x 2" Nipple CH
1/2" x 2-1/2" Nipple
1/2" x 5" Nipple CH
1/2" x 7" Nipple CH
Select Nipple per Table CH
Select Nipple per Table CH
Select Nipple per Table CH
3/4" x Close Nipple CH
3/4" x 1-1/2" Nipple
3/4" x 2" Nipple CH
3/4" x 4" Nipple CH
Select Nipple per Table CH
Solenoid Valve Ordered Separately
Per Data Sheet TFP2180
1/2" Tubing Connector CH
1/2" x 24" Tubing CH
1/2" x 1-1/2" Nipple CH
Waterow Pressure Alarm Switch,
Model PS10-2 25710
Nipple
Number
38
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
COMPONENTS ORDERED SEPARATELY:
. . . . . . . . . . . . . . . . . . . . . . . .
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
1-1/2" (DN40)
1/2" x 1-1/2"
1/2" x 2"39 1/2" x 1-1/2" 1/2" x 5"40
3/4" x 1-1/2"45
1 1 5 2 1 8 1 3 3 2 2
CH 1 2 3
10
1 4
CH 2 1 1 1 1 1 8
CH 1 1 1
Refer to 1
Data Sheet 1 1 1
1
2" (DN50)
1/2" x 2"
1/2" x 5-1/2" 3/4" x 2-1/2"
NOTES:
Electric Actuation Trim is comprised of
1. Items 1-45 plus Items E2-E4. Items A1 and E1 ordered separately.
All Fittings and Nipples are galvanized
2. (Standard Order).
CH: Common Hardware.
3. See Figure 2 of TFP1305 for Valve Port
4. identication.
Route all Tubing to Drip Funnel, Item 14.
5.
6. Horizontal Arrangement uses only 7 out of 8 of Item 24, and 9 out of 10 of Item 33. Discard unused material.
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DELUGE VALVES
EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM
Installation
General Instructions
Proper operation of the DV-5 Deluge Valves depends upon their trim being installed in accordance with the in­structions given in this Technical Data Sheet. Failure to follow the appropri­ate trim diagram may prevent the DV-5 Valve from functioning properly, as well as void listings, approvals, and the manufacturer’s warranties.
The DV-5 Valve must be installed in a readily visible and accessible location.
The DV-5 Valve, associated trim, and wet pilot lines must be maintained at a minimum temperature of 40°F (4°C).
FIGURE 5 (1 OF 3)
Heat tracing of the DV-5 Valve or its associated trim is not permitted. Heat tracing can result in the formation of hardened mineral deposits that are ca­pable of preventing proper operation.
The DV-5 Deluge Valve is to be in­stalled in accordance with the follow­ing criteria:
Step 1. All nipples, ttings, and de­vices must be clean and free of scale and burrs before installation. Use pipe thread sealant sparingly on male pipe threads only.
Step 2. The DV-5 Valve must be trimmed in accordance with Figure 3A/3B or 5.
Step 3. Care must be taken to ensure that check valves, strainers, globe valves, etc. are installed with the ow arrows in the proper direction.
Step 4. Drain tubing to the Drip Funnel must be installed with smooth bends that will not restrict ow.
Step 5. The main drain and Drip Funnel drain may be interconnected provided a check valve is located at least 12 inches (300 mm) below the Drip Funnel.
Step 6. Suitable provision must be made for disposal of drain water. Drain­age water must be directed such that it will not cause accidental damage to property or danger to persons.
Step 7. Connect the Diaphragm Cham ber Supply Control Valve to the inlet side of the system’s Main Control Valve in order to facilitate setting of the DV-5 Valve (Ref. Figure 4).
Step 8. Unused pressure alarm switch connections must be plugged.
-
Page 11
. . . . . .
SEPARATELY)
Discard unused material.
. . . . . . .
QTY.
. .
2 1 1 1
. . .
1
NO.
DESCRIPTION P/N
1 2 3
Model MC-1 Manual Control Station 52-289-2-001
4
Model AD-1 Automatic Drain Valve 52-793-2-004
5
. . . . . . . . . . . . . . . . .
35
25
22
35
1
20
33
24
28
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
7
2
33
3" (DN80)
GROOVE x GROOVE
DV-5 DELUGE VALVE
SHOWN
35
22
40
25
45
21
39
7
35
35
30
28
30
36
A1
(ORDERED
48
12
47
NO. NO.
DESCRIPTION P/N DESCRIPTION P/N
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge Item No. Not Used 46-005-1-0021/4" Gauge Test Valve
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
35
6 7 8 9
10
25
35
9
8
34
5
37
25
22
35
27
35
38
23
44
10
44
44
16
(GREEN
TINT)
44
29
17
44
23
32
43
46
26
43
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . .
E4
42
25
35
42
27
35
35
22
41
25
19
27
36
31
13
43
11
Page 11 of 14
QTY. QTY.
2
46-050-1-0041/2" Ball Valve
1
92-322-1-0021/2" Spring Loaded Check Valve
1
52-353-1-0051/2" Y-Strainer
1
46-049-1-0053/4" Swing Check Valve
E2
E1
(ORDERED
SEPARATELY)
1
22
28
34
25
18
4
15
11 12 13
Drip Funnel Connector
14
Drip Funnel Bracket
15
Drip Funnel 16 17
1/4" x 18" Tubing CH 18
1/2" Tubing Connector CH 19
1/2" x 12" Tubing CH 20
1/4" Plug CH 21
E3
3
3/4" Plug CH
1/2" Union CH
22 23
3/4" Union CH
1/4" 90° Elbow CH
24 25
1/2" 90° Elbow CH
3/4" 90° Elbow CH
26
1/2" Tee CH
27 28
1/2" x 1/4" x 1/2" Tee
3/4" Tee CH
29 30
3/4" x 1/2" x 3/4" Tee 31
3/4" x 3/4" x 1/2" Tee CH 32
1-1/4" x 3/4" x 1-1/4" Tee CH 33
1/4" x Close Nipple CH 34
1/2" x Close Nipple CH 35
1/2" x 1-1/2" Nipple CH
1/2" x 2-1/2" Nipple
36
1/2" x 3-1/2" Nipple CH
37
1/2" x 4" Nipple CH
38
1/2" x 4-1/2" Nipple CH
39
1/2" x 5" Nipple CH
40
1/2" x 5-1/2" Nipple CH
41
1/2" x 7" Nipple CH
42
3/4" x Close Nipple CH
43
3/4" x 1-1/2" Nipple
44
3/4" x 2" Nipple CH
45
3/4" x 4-1/2" Nipple CH
46
1-1/4" x 2" Nipple CH
47
1-1/4" x 4" Nipple
48
E1
Solenoid Valve Ordered Separately
Per Data Sheet TFP2180
E2
1/2" Tubing Connector CH
E3
1/2" x 24" Tubing CH
E4
1/2" x 1-1/2" Nipple CH
Waterow Pressure Alarm Switch,
A1
Model PS10-2 25710
NOTES:
Electric Actuation Trim is comprised of
1. Items 1-48 plus Items E2-E4. Items A1 and E1 ordered separately.
All Fittings and Nipples are galvanized
2. (Standard Order).
CH: Common Hardware.
3. See Figure 2 of TFP1305 for Valve Port
4. identication.
14
Route all Tubing to Drip Funnel, Item 15.
5.
6. Horizontal Arrangement uses only 7 out of 8 of Item 25, and 12 out of 13 of Item 35.
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
COMPONENTS ORDERED SEPARATELY:
. . . . . . . . . . . . . . . . . . . . . . . .
13
TFP1320
1
46-048-1-0053/4" Angle Valve
1
46-048-1-0071-1/4" Angle Valve 92-211-1-005
1 1
92-211-1-003
1
92-343-1-007
1
92-032-1-0023/32" Vent Fitting 1 1 1 1 1 5 2 1 8 1 3
CH
3 1
CH
2 1 1 2 2
CH
2 1 1 1 1 1 2 3
CH
5 1 1 1
CH
1
Refer to 1
Data Sheet 1 1 1
1
3 INCH (DN80) DV-5 DELUGE VALVE
FIGURE 5 (2 OF 3)
EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM
Step 9. Conduit and electrical connec­tions are to be made in accordance with the requirements of the authority having jurisdiction and/or the National Electric Code.
Step 10. Before a system hydrostatic test is performed in accordance with NFPA 13 system acceptance test re­quirements, the DV-5 Diaphragm Chamber is to be depressurized, the Automatic Drain Valve (Item 4, Fig. 3A and 5) is to be temporarily replaced with a 1/2 inch NPT plug, the 3/32 inch Vent Fitting (Item 16 - Fig. 3A and 5) is to be temporarily replaced with a 1/4 inch NPT plug, and the Diaphragm Cover Bolts must be uniformly and se­curely tightened using a cross-draw sequence. After tightening, double­check to make certain that all of the Diaphragm Cover Bolts are securely tightened.
Page 12
TFP1320
SEPARATELY)
Page 12 of 14
DESCRIPTION P/N
NO.
1 2 3
Model MC-1 Manual Control Station 52-289-2-001
4 18
Model AD-1 Automatic Drain Valve 52-793-2-004 1/2" Tubing Connector CH
5
Item No. Not Used
6 7 8
9 10 11 12
Drip Funnel Connector
13 14
Drip Funnel Bracket
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
QTY.
2
92-343-1-005300 psi/ 2000 kPa Water Pressure Gauge
. .
1
46-005-1-0021/4" Gauge Test Valve
1
. . . . . .
1 1
. . . . . . . . . . . . . . . . . . . . . . . .
1
92-343-1-021Model ASV-1 Automatic Shut-Off Valve
. . .
2
46-050-1-0041/2" Ball Valve
1
. . . . . . . . .
35
92-322-1-0021/2" Spring Loaded Check Valve
1
52-353-1-0051/2" Y-Strainer
1
46-049-1-0053/4" Swing Check Valve
1
46-048-1-0061" Angle Valve
1
46-048-1-0092" Angle Valve
1
92-211-1-005
1
92-211-1-003
35
25
22
9
35
1
20
33
2
33
24
28
40
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
21
7
4" (DN100)
GROOVE x GROOVE
DV-5 DELUGE VALVE
SHOWN
35
22
38
7
41
35
25
45
25
29
46
28
29
51
A1
(ORDERED
36
50
12
32
DESCRIPTION P/N
NO.
15 16 17
19 20 21 22 23 24 25 26 27 28
. . . . . . . . . . . . . . . . . . . . . . . . . .
Drip Funnel
Select Tubing per Table CH
1/2" x 24" Tubing CH 1/4" Plug CH 3/4" Plug CH 1/2" Union CH 1" Union CH 1/4" 90° Elbow CH 1/2" 90° Elbow CH 1" 90° Elbow CH 1/2" Tee CH 1/2" x 1/4" x 1/2" Tee CH
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
25
35
8
5
34
43
38
27
35
22
52
35
39
36
25
23
48
10
44
47
31
16
(GREEN
TINT)
17
30
47
23
47
47
49
26
E4
25
27
42
22
27
37
47
QTY.
1
92-343-1-007
1
92-032-1-0023/32" Vent Fitting
1
1 1 1 5 2 1 8 1 3 3
(ORDERED
SEPARATELY)
35
22
35
18
19
4
13
11
E2
E1
14
(DN150)
1/4" x 24"
(DN150)
1/2" x 5-1/2"
1/2" x 3" 1/2" x 7-1/2" 3/4" x 3-1/2"
QTY.
10
2 1 1 1 2 2
3 1 2 1 2 1 1 1 1 1 1 5 1 1 1 1 1
1 1 1 1
1
CH
CH
CH CH
CH
Refer to Data Sheet
8"
(DN200)
1/4" x 32"
8"
(DN200)
1/2" x 8-1/2" 1/2" x 3-1/2"
1/2" x 9"
3/4" x 4-1/2"
1" x 12"
DESCRIPTION P/N
NO.
3/4" x 1/2" x 3/4" Tee
29
1" x 1" x 1/2" Tee CH
30
1" x 3/4" x 1" Tee
31
2" x 1" x 2" Tee CH
32
1/4" x Close Nipple CH
33
1/2" x Close Nipple CH
34
1/2" x 1-1/2" Nipple CH
35
1/2" x 2-1/2" Nipple
36
Select Nipple per Table
37
1/2" x 5" Nipple CH
38
1/2" x 6" Nipple CH
39
1/2" x 7" Nipple CH
40
Select Nipple per Table CH
41
Select Nipple per Table CH
42
Select Nipple per Table CH
43
3/4" x 1-1/2" Nipple
44
3/4" x 2" Nipple CH
45
Select Nipple per Table CH
46
1" x Close Nipple CH
47
E3
1
1" x 3" Nipple CH
48
Select Nipple per Table CH
49
2" x 3" Nipple CH
50
2" x 5" Nipple CH
51
Select Nipple per Table CH
52
Solenoid Valve Ordered Separately
E1
Per Data Sheet TFP2180 1/2" Tubing Connector CH
E2
1/2" x 24" Tubing CH
E3
1/2" x 1-1/2" Nipple CH
E4
COMPONENTS ORDERED SEPARATELY:
Waterow Pressure Alarm Switch,
A1
Model PS10-2 25710
28
Tube
No.
3
34
25
17
Nipple
No.
41
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
Select Appropriate Tube Size
per DV-5 Deluge Valve Size
4" 6"
(DN100)
1/4" x 24"
Select Appropriate Nipple Sizes
per DV-5 Deluge Valve Size
4" 6"
(DN100)
1/2" x 3"37 1/2" x 3" 1/2" x 5"
1/2" x 2-1/2"
1/2" x 2"42 1/2" x 6-1/2"43 3/4" x 2-1/2"46
1" x 6"49 1" x 9"
1/2" x 7"52 1/2" x 7" 1/2" x 9"
NOTES:
Electric Actuation Trim is comprised of
1.
15
Items 1-52 plus Items E2-E4. Items A1 and E1 ordered separately.
All Fittings and Nipples are galvanized
2. (Standard Order).
CH: Common Hardware.
3. See Figure 2 of TFP1305 for Valve Port
4. identication.
Route all Tubing to Drip Funnel, Item 15.
5.
6. Horizontal Arrangement uses only 7 out of 8 of Item 25, and 2 out of 3 of Item 36. Discard unused material.
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DELUGE VALVES
FIGURE 5 (3 OF 3)
EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM
Page 13
TFP1320
Page 13 of 14
Valve Setting Procedure
Steps 1 through 11 are to be performed when initially setting the DV-5 Deluge Valve; after an operational test of the re protection system; or, after system operation due to a re.
NOTE: When the system is using ei­ther a seawater or brackish water sup­ply, it is recommended that the system be thoroughly flushed with clean fresh water. Following this recommendation will increase the service life of the DV-5 Valve and Trim.
Step 1. Close the Main Control Valve. Step 2. Close the Diaphragm Chamber
Supply Control Valve. Step 3. Open the Main Drain Valve,
System Drain Valve, and all auxiliary drains in the system. Close the System Drain Valve and auxiliary drain valves after water ceases to discharge. Leave the Main Drain Valve open.
Step 4. Depress the plunger of the Au­tomatic Drain Valve to verify that it is open and that the DV-5 Valve is com­pletely drained.
Step 5. Clean the Strainer in the Dia­phragm Chamber Supply connection by removing the clean-out plug and strainer basket. The Strainer may be ushed out by momentarily opening the Diaphragm Chamber Supply Con­trol Valve.
Step 6. Reset the actuation system.
Manual Actuation — Push the operat­ing lever up; however, do not close the hinged cover at this time.
Electric Actuation — Reset the electric detection system in accordance with the manufacturer’s instructions to de­energize the solenoid valve.
Step 7. Open the Diaphragm Chamber Supply Control Valve and allow time for full pressure to build up in the Dia­phragm Chamber.
Step 8. Operate (open) the Manu­al Control Station to vent trapped air from the Diaphragm Chamber. If nec­essary, rst open the hinged cover, and then fully pull down on the operating lever. Slowly close the operating lever, by pushing it up, after aerated water ceases to discharge from the Manual Control Station drain tubing. Close the hinged cover and insert a new break rod in the small hole through the top of the enclosing box.
Step 9. Inspect the drain connections from the Manual Control Station and Solenoid Valve. Any leaks must be cor­rected before proceeding to the next step.
Step 10. Verify the ability for the DV-5 Diaphragm to hold pressure as follows:
With the diaphragm chamber pressur­ized per Step 8, temporarily close the Diaphragm Chamber Supply Control Valve, and then monitor the Diaphragm Chamber Pressure Gauge for a drop in pressure.
If a drop in pressure is noted, the DV-5 Diaphragm is to be replaced and/or any leaks must be corrected before pro­ceeding to the next step.
If the Diaphragm Chamber Pressure Gauge indicates no drop in pressure, re-open the Diaphragm Chamber Sup­ply Control Valve and proceed to the next step.
Ste p 11. Slowly open the Main Con­trol Valve. Close the Main Drain Valve as soon as water discharges from the drain connection. Observe the Auto­matic Drain Valve for leaks. If there are leaks, determine/correct the cause of the leakage problem. If there are no leaks, the DV-5 Valve is ready to be placed in service and the Main Control Valve must then be fully opened.
NOTE: When the Main Control Valve is opened, the pressure on the Dia­phragm Chamber may increase. This increase in pressure is normal, and if the pressure is greater than 250 psi (17,2 bar), the pressure is to be relieved by partially and temporarily opening the Manual Control Station; however, do not allow the pressure as indicated on the Diaphragm Chamber Pressure Gauge to drop below the supply pres­sure shown on the Water Supply Pres­sure Gauge, since this action may re­sult in tripping of the DV-5 Valve.
After setting a re protection system, notify the proper authorities and advise those responsible for monitoring pro­prietary and/or central station alarms.
Care and Maintenance
The following procedures and inspec­tions must be performed as indicated, in addition to any specic requirements of the NFPA, and any impairment must be immediately corrected.
Before closing a re protection system Main Control Valve for maintenance work on the re protection system that it controls, permission to shut down the affected re protection systems must rst be obtained from the proper au­thorities and all personnel who may be affected by this action must be notied. Reset the DV-5 Deluge Valve in accor­dance with the Valve Setting Procedure section.
The owner is responsible for the in­spection, testing, and maintenance of their re protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa­tion (e.g., NFPA 25), in addition to the standards of any authority having juris­diction. Contact the installing contrac­tor or product manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualied Inspec­tion Service in accordance with local requirements and/or national codes.
NOTICE
Some of the procedures outlined in this section will result in operation of the associated alarms. Consequently, notification must first be given to the owner and the fire department, central station, or other signal station to which the alarms are connected.
When the system is using either a sea­water or brackish water supply, inter­nal and external inspection of the DV-5 Valve and Trim is essential. Parts show­ing any signs of corrosion must be re­placed to ensure the integrity of the system.
Annual Operation Test Procedure
Proper operation of the DV-5 Valve (i.e., opening of the DV-5 Valve as during a re condition) must be veried at least once a year as follows:
Step 1. If water must be prevented from owing beyond the riser, perform the following steps:
• Close the Main Control Valve.
• Open the Main Drain Valve.
•
Open the Main Control Valve one turn beyond the position at which water just begins to ow from the Main Drain Valve.
• Close the Main Drain Valve. Step 2. Test the Deluge Valve Releas-
ing Panel in accordance with the man­ufacturer’s instructions to energize the solenoid valve.
NOTE: Be prepared to quickly perform Steps 3, 4, and 5, if water must be pre­vented from flowing beyond the riser.
Step 3. Verify that the DV-5 Valve has tripped, as indicated by the ow of wa­ter into the system.
Step 4. Close the system’s Main Con­trol Valve.
Step 5. Close the Diaphragm Chamber Supply Control Valve.
Step 6. Reset the DV-5 Deluge Valve in accordance with the Valve Setting Procedure.
Page 14
TFP1320
Page 14 of 14
Quarterly Waterflow Alarm Test Procedure
Testing of the system waterow alarms must be performed quarterly. To test the waterow alarm, open the Alarm Test Valve, which will allow a ow of water to the Pressure Alarm Switch and/or Water Motor Alarm. Upon sat­isfactory completion of the test, close the Alarm Test Valve.
Limited Warranty
For warranty terms and conditions, visit www.tyco-re.com.
Ordering Procedure
NOTE: Part Numbers for factory pre­trimmed DV-5 Valves are provided in the Price Book.
DV-5 Semi-Preassembled Vertical Electric Actuation Trim
Specify: (specify size and nish — gal­vanized is standard) Semi-Preassem­bled Vertical Electric Actuation Trim for DV-5 Deluge Valves, P/N (specify):
1-1/2 & 2 Inch Galvanized ... P/N 52-477-2-309
1-1/2 & 2 Inch Black........ P/N 52-47 7-1- 30 9
1-1/2 & 2 Inch Brass........ P/N 52-477-3-309
3 Inch Galvanized ..........P/N 52- 477-2-106
3 Inch Black ...............P/N 52-477-1-10 6
3 Inch Brass .............. P/N 52-47 7-3-106
4, 6 & 8 Inch Galvanized .... P/N 52-477-2-3 03
4, 6 & 8 Inch Black ......... P/N 52-477-1-303
4, 6 & 8 Inch Brass .........P/N 52-477-3-303
DV-5 Unassembled Electric Actuation Trim for Vertical or Horizontal Installation
Specify: (specify size and nish — gal­vanized is standard) Unassembled Electric Actuation Trim for Vertical or Horizontal Installation of DV-5 Deluge Valves, P/N (specify):
1-1/2 & 2 Inch Galvanized ... P/N 52-477-2-209
1-1/2 & 2 Inch Black.........P/N 52-477-1-209
1-1/2 & 2 Inch Brass........ P/N 52-477-3-209
3 Inch Galvanized ......... P/N 52-477-2-206
3 Inch Black ...............P/N 52-477-1-206
3 Inch Brass .............. P/N 52-477-3-206
4, 6 & 8 Inch Galvanized .... P/N 52-477-2-203
4, 6 & 8 Inch Black ..........P/N 52-477-1-203
4, 6 & 8 Inch Brass ......... P/N 52-477-3-203
Pre-trimmed DV-5 Assembly Electric Actuation Trim with Butterfly Valve
Specify: (size), G x G End Connection, Pre-trimmed DV-5 Assembly with But­tery Valve, P/N (specify):
1-1/2 Inch G x G ...........P/N 52- 913 - 0-1AP
2 Inch G x G ..............P/N 5 2- 92 3-0 -1A P
3 Inch G X G ..............P/N 52- 9 33 - 0-1AP
4 Inch G x G ..............P/N 52 -9 43- 0 -1AP
6 Inch G x G ..............P/N 52 -9 63- 0 -1AP
8 Inch G x G ..............P/N 52-983-0-1AP
Pre-trimmed DV-5 Assembly Electric Actuation Trim without Butterfly Valve
Specify: (specify size), (specify) End Connection, Pre-trimmed DV-5 As­sembly without Buttery Valve, P/N (specify):
1-1/2 Inch T x T ...........P/N 52-913-3-1AP
2 Inch T x T...............P/N 52-923-3-1AP
3 Inch F x F............... P/ N 52-93 3-1 -1AP
3 Inch F x G ..............P/N 52-933 -2-1AP
4 Inch F x F............... P/ N 52-94 3-1 -1AP
4 Inch F x G ..............P/N 52-943 -2-1AP
6 Inch F x F............... P/ N 52-96 3-1 -1AP
6 Inch F x G ..............P/N 52- 963 -2-1AP
8 Inch F x F............... P/ N 52-98 3-1 -1AP
8 Inch F x G ..............P/N 52-983 -2-1AP
Accessories
Refer to the Technical Data Sheets for the following, as applicable, for details and additional accessories:
600 PSI Water
Pressure Gauge . . . . . . .....P/N 92-343-1-004
Solenoid Valve for
Electric Actuation..............See TFP2180
Model PS10-2 Potter Electric Waterow Pressure
Alarm Switch . . . . . . . . . ...........P/N 25710
Model WMA-1 Water
Motor Alarm . . . . . . . . . ....P/N 52-6 30-1-0 01
Replacement Trim Parts
Specify: (description) for use with DV-5 Deluge Valve, P/N (see Figure 3A or 5).
Accessories
Refer to the Technical Data Sheets for the following, as applicable, for details and additional accessories:
600 PSI Water
Pressure Gauge ...........P/N 92-343-1-004
Model PS10-2 Potter Electric Waterow Pressure
Alarm Switch ...................P/N 25710
Model WMA-1 Water
Motor Alarm .............P/N 52 -6 3 0-1-0 01P
Model MC-1 Manual Control Stations with Galvanized Connections for Remote Wet Pilot
Actuation ................P/N 52-289-2-001
Replacement Trim Parts
Specify: (description) for use with DV-5 Deluge Valve, P/N (see Figure 3A or 5)
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Loading...