Date: 10.07.2012 Page 4 of 28 user manual no. CRD 10617 FE
Safety instructions
1. Safety instructions
1.1 Scope of validity
This user manual applies exclusively to the following rotary encoders with PROFIsafe interface:
- CRDxx-xxxxRxxxxC2Z01
- CRDxx-xxxxRxxxxC2L01
1.2 Documentation
The following documents must be noted:
- The owner's system-specic operating instructions
- This user manual
- Data sheet number CRD 10534
- The pin assignment enclosed with the device
- Installation instruction TZY 10206 enclosed with the device
1.3 Proper use
TWK-ELEKTRONIK GmbH's rotary encoders and linear transducers are used to record rotary and linear positions,
and make their measured values available as an electric output signal. As part of a system, they must be connected
to the downstream electronics and must only be used for this purpose.
1.4 Commissioning
• The relevant device must only be set up and operated using this document and the documentation specied in point 1.2.
• Protect the device against mechanical damage during installation and operation.
• The device must only be commissioned and set up by a specialist electrician.
• Do not operate the device outside of the limit values which are specied in the data sheet.
• Check all electrical connections before commissioning the system.
Date: 10.07.2012 Page 5 of 28 user manual no. CRD 10617 FE
General
DP slaves
DP master (class 1)
PROFIBUS-DP
2 General
The PROFIBUS is a eld bus standard according to EN 50170. The technical and functional characteristics of the eld
bus system are dened in this standard. The protocol architecture is based on the OSI reference model, in accordance
with the international ISO 7498 standard. Layer 1 (Physical Layer) denes the transmission physics, layer 2 (Data Link
Layer) the bus access protocol, and layer 7 (Application Layer) the application functions. This document is based on
the Prol description for encoders which can be obtained from the PNO /1/. The Probus protocol chip SPC 3 from
Siemens is used as the interface module between the encoder electronics and the bus system.
For PROFIBUS-DP, data exchange between SPS/PC and the decentralised periphery (e.g. encoder) is carried out in
a predominantly cyclical manner. For parameterisation, diagnosis and alarm handling purposes, acyclical communi-
cation functions are also required for intelligent eld devices. In this case, reference must be made to the DIN 19245
Part 1 and 3 or to the EN 50170 standards.
In the case of PROFIBUS-DP, communication in the data back-up layer (layer 2) is carried out via the SRD (Send and
Request Data with Reply) and SDN (Send Data with no Acknowledge) functions.
Mono or multi-master systems may be implemented with PROFIBUS-DP. A maximum of 126 devices (master or
slaves) may be connected to one bus. The denition of the system conguration contains the number of stations,
the allocation of the station address to the I/O addresses, data consistency of the I/O data, format of the diagnosis
messages and the bus parameters which are used.
The parameters of the PROFIBUS subscribers are described in a GSD le (device data sheet). The specications
are executed in accordance with DIN 19245 Part 3 /4/.
Differentiation of the services, and an exact knowledge of these, are especially important for understanding the
PROFIBUS-DP philosophy. A distinction is made between the following in the manual:
Check_Conguration: Conguration of the encoder
Integration of the encoder into the network with various data formats,
or as a programmable or non-programmable slave, is possible.
(Example: F1: programmable (32 bit input/output data) multitour encoder
Data_Exchange: Position data of the encoder Cyclical enquiry regarding the encoder position. The position value is
depicted as a 16 bit or 32 bit value depending on the conguration.
Setting the preset value
Set_Parameter: Programming parameters
Denition of the operating mode of the encoder and denition of the values
for single turn resolution and total measuring range in units.
Slave_Diagnosis: Diagnosis of the slave subscriber (encoder)
Date: 10.07.2012 Page 6 of 28 user manual no. CRD 10617 FE
Installation instructions
Station 1Station 2
RxD/TxD-P (3)
DGND (5)
VP (6)
RxD/TxD-N (8)(8) RxD/TxD-N
(5) DGND
(3) RxD/TxD-P
(6) VP
Abschirmung
Schutz-
erdeerde
Schutz-
Verkabelung
Busabschluß
Datenleitung B
Datenleitung A
VP (6)
390
220
RxD/TxD-N (8)
390
DGND (5)
RxD/TxD-P (3)
3. Installation instructions for PROFIBUS-DP - RS 485
Basic characteristics of RS-485 transmission technology /2/:
Network topology: Linear bus, terminating resistors for bus termination
Stub lines are only permissible in the case of baudrates < 1.5 MBit/s
Lead: Sheathed, twisted pair cable
Number of stations: 32 stations in each segment without repeaters
Can be extended up to 126 with repeaters.
Plug-type connector: Variants implemented in the case of the CRD model series:
Connecting cap, Round plug RS 25, 12-pin
DESINA (LWL and Cu-version)
(pin assignment according to /1/)
Wiring and bus termination for PROFIBUS-DP /2/, (Note: 9-pin Sub-D plug)
Transmission length depending on transmission speed for cable type A
Baud rate (kBit/s)9,619,293,75187,55001.50012.000
Transmission length in (m)1200120012001000400200100
Cable type A specications: Characteristic impedance: 135...165 Ohm
Capacitance per unit length coating: < 30 pF/m
Loop resistance: 110 Ohm /km
Core diameter: 0.64 mm
Core cross-section: > 0.34 mm²
Shield
Connection
Data line B
Data line A
Terminating
resistance of the bus
also see: Installation guideline for PROFIBUS -FMS/DP (PNO No. 2.111/2)
Implementation guide DIN 19245 Part 3 (PNO No. 2.001/2)
Date: 10.07.2012 Page 7 of 28 user manual no. CRD 10617 FE
Installation instructions
OFF
ON
1234
5
678910
DIP-Schalter
2 : 1
3.1 Connection of encoder with RS plug
The-pin assignment for the 12-pin RS plug (Note: Numeration of the-pins in clockwise direction (view facing contact
side of the bushing), encoder: Bushing) conforms to the prole denition for encoders /1/. The terminating resistors
must be implemented in the counterplug or in the subsequent electronics. For this connection type attention should
be paid to the length of the branch lines in the bus system and the total bus length.
When delivered, each encoder with RS plug has the default address 123. Via the DP master, it is possible to change
the address of a DP slave. The slave address which is to be newly assigned must lie within the range 1-126 (DDLM_
Set_Slave_Add).
3.2 Connection of encoder with connecting cap
Terminal 1
Anschlußklemme 1
Sub-D - Connector
Sub D Stecker
15 poles / sockets
15 polig/Buchse
DIP-Switch
DIP-Schalter
BAA’ B’
+ UB -
ON
OFF
Terminal 2
Anschlußklemme 2
(PROFIBUS)
(PROFIBUS)
The connecting cap for triple connection technology is a T-coupler, which is installed in the PROFIBUS.
It is equipped with three PG connections, which are subdivided as follows:
PG 7: Voltage supply for the encoder (24 VDC +/-)
PG 9: Bus in (Receive/transmit data A,B)
PG 9: Bus out (Receive/transmit data A’,B’)
The encoder is connected via the 15-pin SUB-D plug. In the event of an error, the encoder can be replaced without
time-consuming installation. The connecting cap is disconnected from the encoder by undoing 2 fastening screws
(Note: O-ring seal)
Setting the station/subscriber address is carried out via the DIP switches in the connecting cap.The address range lies
between 1 and 126 (Default address: 123). The address cannot be changed via the DDLM_Set_Slave_Add service.
(Note: GSD le in accordance with encoder version).
Setting the terminating resistors is carried out via the 10-fold DIP switch (9,10) in the connecting cap, which ay be
Date: 10.07.2012 Page 8 of 28 user manual no. CRD 10617 FE
Installation
PG9PG9PG7
SRD
LED-Statusanzeigen
UB
Befestigungs-schrauben M4
C Err
Status LED (connecting cap)
VSSRDCErr
Status LED
Incorrect congurationxxx
Impermissible parameterxxx
Code error
(see diagnosis bytes 62 - 63)
xx
Screw M4
Class 1 Gerätekonguration i.O.xx
Class 2 Gerätekonguration i.O.xxx
VS - power supply, Err - error, C - class, SRD - data trafc
Conguration
4. Conguration function (DDLM_Chk_Cfg)
The absolute encoders with PROFIBUS-DP are classied as follows:
Encoder with Class 1 functionality
Class 1 devices are characterised by the fact that only the position value (16 bit or 32 bit) of the encoder is transmitted
via the bus. No parameterisation of encoder parameters is carried out. In this case, a distinction is made between
the D0 and D1 congurations. The D0 conguration contains the data format: 1 word input data, consistency and D1
contains 2 word input data, consistency.
Encoder with Class 2 functionality
Class 2 devices are characterised by the fact that they can be parameterised via the bus. In this case, a distinction
is made between the F0 and F1 congurations. The F0 conguration has the data format 1 word input data, 1 word
output data, consistency and F1 contains 2 word input data, 2 word output data, consistency .
Possible conguratons of the encoder:
Conguration function (DDLM_Chk_Cfg)
SelectionClassData
Class 2 32
Bit In/ Out
Class 2 16
Bit In/ Out
Class 1 32
Bit In
Class 1 16
Bit In
2
2
1
1
32 Bit In/
Output data
16 Bit In/
Output data
32 Bit Input
data
16 Bit Input
data
Identier
byte
F1
F0
D1
D0
Assignment Octet-
No. and MSB/LSB
Octet 1/Bit 7: MSB
Octet 4/Bit 0: LSB
Octet 1/Bit 7: MSB
Octet 2/Bit 0: LSB
Octet 1/Bit 7: MSB
Octet 4/Bit 0: LSB
Octet 1/Bit 7: MSB
Octet 2/Bit 0: LSB
Date: 10.07.2012 Page 9 of 28 user manual no. CRD 10617 FE
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.