Twin City IM-4300 User Manual

Page 1
BCFS Belt Driven
Centrifugal Filtered Supply Fans
INSTALLATION, OPERATION & MAINTENANCE MANUAL
Models BCFS 140A through 240A
IM-4300
January 2006
Receiving, Inspection & Unpacking
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Before accepting delivery, carefully inspect each carton or crate for visible shipping damage. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage. Make notations of all damage on all copies of the bill of lading and have all copies countersigned by the delivering carrier. The carrier should also fill out a Carrier Inspection Report. The factory Traffic Department should then be contacted. File claim for damage with the carrier. Physical damage to the unit after acceptance is not the responsibility of Twin City Fan Companies, Ltd.
Unpack each carton or crate and verify that all required parts and proper quantities of each item have been received. Refer to drawings for part descriptions. Report shortages or missing items to your local representative to arrange for replacement parts.
Due to availability of carriers and truck space, it is not possible to guarantee that all items will be shipped together. Verification of shipments must be limited to only those items on the bill of lading.
The unit nameplate must be checked to make sure the voltage agrees with the power supply available.
Installation
CAUTION: Sheet metal parts, screws, clips and similar items inherently have sharp edges, and it is necessary that the installer and service personnel exercise caution.
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and with all applicable codes.
This equipment is to be installed by an experienced installation company and fully trained personnel.
The mechanical installation of the exhaust ventilator consists of making final connections between the unit, building services, and duct connections.
1. Before setting unit on curb (if damper is to be used), make sure that the damper is installed correctly and that it is operative. See diagram, page 6.
2. Position unit on roof curb so that the wiring can be run through one of the knockouts provided. Wiring to the unit may be run through knockouts provided in the curb cap or the side of the unit. Provide enough slack in the wiring to the unit to allow lifting, and removal for cleaning, and inspection.
3. Connect supply leads to the disconnect switch.
4. Check line voltage with the motor nameplate and the attached instruction cards.
5. Determine if wheel is free to rotate and has not been subject to misalignment in shipping or installation.
6. Apply power and check rotation of wheel with direc­tional label in motor compartment.
7. Lag bolt the unit to the roof curb using a minimum of four bolts, one at each corner. Replace unit top panel and fasten all latches securely.
©2006 Twin City Fan Companies, Ltd.
Page 2
Check, Test and Start Procedure
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equip­ment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
BEFORE STARTUP: Disconnect power to this unit before servicing the unit.
1. Check to verify that the wheel is free to rotate.
2. Verify that supply voltage on the line side of discon­nect agrees with voltage on unit identification plate and is within the utilization voltage range as indicated in Table 1.
3. On three-phase units check and calculate phase unbalance as follows:
% Voltage Unbalance = 100 x max. voltage deviation from avg. voltage ÷ avg. voltage
Example: Determine the percent voltage unbalance
given voltages of 220, 216 and 213.
How To Use The Formula: a. Avg. Voltage = 220 + 216 + 213 = 649 ÷ 3 = 216 b. Max. Voltage Deviation From Avg. Voltage =
220 – 216 = 4 c. % Voltage Unbalance = 100 x (4 ÷ 216) = 1.8% Voltage unbalance should not exceed 2%.
4. Apply power to unit and check rotation of wheel with
the directional arrow on the unit.
WARNING: The BCFS centrifugal wheels run in a coun­terclockwise direction when viewed opposite the air intake. If the wheel is run in the wrong direction, the motor will overload and burn out.
WARNING: Check three-phase units for rotation. For three-phase, rotation can be changed by interchanging any two of the three line leads. If unit is installed on temporary wiring, it should be rechecked when per­manently installed. Motor burn-out or tripped overload protection devices are usually the result of incorrect rotation.
WARNING: Motor overloading is usually the result of incorrect rotation, high voltage, or low voltage. The NEC states that motors used in devices such as filtered roof supply units must be protected by a separate overload device that is responsive to motor current or a thermal protector integral with the motor. Refer to Sections 430­22 of the NEC for additional information.
5. Electrical Input Check: Perform check of fan ampere
draw and verify that motor nameplate amps are not exceeded. Take account of the service factor range if motor is nameplated above a 1.0 service factor.
6. Fan RPM Check: Fan RPM should be checked and
verified with a tachometer. Refer to Table 2 for maxi­mum fan RPM values.
WARNING: Running fan at an RPM greater than the
maximum RPM value in Table 2 will overload the fan motor and lead to premature motor failure.
Table 1. Utilization Voltage Ranges
SYSTEM VOLTAGE/ UTILIZATION VOLTAGE UNIT NAMEPLATE MIN. MAX.
115/60/1 104 127 208-230/60/1 or 208-230/60/3 187 253 230/60/1 or 230/60/3 207 253 277/60/1 249 305 200/60/3 180 220 380/60/3 342 418 460/60/3 414 506 575/60/3 517 633 110/50/1 99 121 220/50/1 198 242 380-415/50/3 342 456 440/50/3 396 484
Table 2. Maximum Fan RPM
BCFS MAXIMUM MODEL
1/6 1100 1/4 1250
1/2 1590 3/4 1810
1.0 2000 1/6 730 1/4 840 1/3 930 180 1/2 1060 3/4 1220
1.0 1300
1.5 1530 1/3 580 1/2 660 3/4 760
1.5 960
2.0 1060
3.0 1180
5.0 1350
1/3 1380
140
1.0 840
240
MOTOR HP
FAN RPM
Maintenance
FILTERS: To gain access to filters, unlatch top panel
and slide top back approximately 2 inches. Lift filters out from top. Filters may be cleaned with soap and water or replaced. Filters should be cleaned regularly, as dirty filters will cause performance to be reduced. Frequency of cleaning depends upon the local environment and frequency of use of the fan.
1. The motors in these units are equipped with prelu­bricated ball bearings which are considered to be permanently lubricated.
2. Fan shaft pillow block bearings are equipped with grease gun fittings. These bearings are factory lubri­cated and, with normal operation, will need no lubri­cation for 3 to 6 months.
3. For pillow block bearings, use a low pressure grease gun with Alvania #2 or #3 grease or equivalent. Only a few strokes of the gun are required. Excess grease will be forced out through the bearing pressure relief holes. Use of a high pressure gun, however, is liable to blow the bearing seals.
2 Twin City IM-4300
Page 3
4. Belt tension is adjusted at the factory. It should be readjusted after a break-in period of 24 hours of actual operation.
5. To adjust belt tension, loosen the hex head screw in the tab of the motor plate. Snug belts by pulling on the motor until the belt is tight. Tension is correct if the belt can be twisted from
1
4 to 1⁄2 turn with mod-
erate pressure at a point midway between sheaves.
6. Belt condition and tension should be checked every 3 to 6 months depending on service. If belt tension is too tight, there is a possibility of overloading the motor as well as causing undue belt wear. If the belt tension is too slack, then the wheel will fall off in RPM, air delivery will decrease and the belts will wear quite rapidly.
7. If the air handled by the unit is dust or grease laden, a regular inspection and cleaning of the backdraft damper and the wheel will ensure smooth, efficient operation.
WARNING: Do not replace motor sheave with one larger in diameter. Do not replace fan sheave with one smaller in diameter. The sheave ratios are set so that the motor will not be overloaded within the range of the adjust­able sheave.
CHECK: Belt tension is adjusted at the factory, but it should be readjusted after a break-in period of approxi­mately 24 hours of actual operation.
Figure 2. Opening Location of Duct Adapter AccessoryFigure 1. Typical Installation
Apply foam tape to seal duct to unit to prevent leakage
Duct Adapter (Align this side with inlet side of curb)
L
W
Y
Duct
(Customer
Supplied)
Damper*
X
Figure 3. Location of Fan Outlet
Top View of Roof Curb Showing Duct Location
L
Curb
Sq.
Fan Outlet
Y
Roof Curb
Nailer
Duct Flange
By Customer
Strip
Position duct adapter as shown and secure to nailer strip
with nails in holes provided in duct adapter.
*For a standard gravity (spring return) damper, recess the damper a minimum of 2" inside the duct in order to clear the fan outlet. For an optional motorized damper, the damper must be recessed 12" to allow for clearance between the actuator and fan outlet.
MODEL DIMENSION (IN.) BCFS W L X Y
140A 8 180A 10 240A 13
X
MODEL DIMENSION (IN.) CURB SUPPLY BCFS W L X Y SQ. DAMPER
140A 8 19 2
W
180A 10 22 2 240A 13
DIMENSIONS ARE NOT TO BE USED FOR CONSTRUCTION.
1
2 191⁄2 2
1
2 221⁄2 1
11
16 291⁄2 1
1
2 71⁄4 30 x 30 8 x 19
1
3
16 29 2 113⁄4 47 x 47 13 x 29
8 91⁄4 36 x 36 10 x 22
1
4 7
7
8 9
3
4 111⁄2
Inlet Side of Fan (Provide a min. of 15" between inlet side and nearest obstruction)
3 Twin City IM-4300
Page 4
Motor Installation
To prevent damage during shipment, the motor of this unit has been installed at the factory, tested, then removed and shipped separately. Please follow the instructions below to reinstall the motor.
1. Fasten the motor plate to the bearing plate by insert­ing the hinge pin in the holes and then putting a hitch pin in the hole of the hinge pin.
See Figure 4.
2. Install the belts on the sheaves, apply tension and tighten the bolt at the top of the motor plate or the nut on the jacking bolt to maintain tension. The ideal
Figure 4. Motor Plate Assembly Figure 5. Sheave Alignment
HINGE PIN
TENSION HOLD BOLT
HITCH PIN
belt tension is to be enough so that the belt does not slip under peak load. Do not over-tighten the belt as it will severely reduce the life of the bearings.
3. Check the sheave alignment as shown in Figure 5 below and align sheaves with a straightedge if nec­essary. Be sure the belt tension is rechecked if the sheave alignment is changed.
Note: The belt tension will need to be rechecked after the fan has been operating for a few days. There is an initial break-in period for the belts in which they may stretch.
Limitation of Warranties and Claims
Seller warrants to the original purchaser that the goods sold hereunder shall be free from defects in workman­ship and material under normal use and service (except in those cases where the materials are supplied by the buyer) for a period of one year from the date of original installation or eighteen (18) months from the date of ship­ment, whichever occurs first. The liability of seller under this warranty is limited to replacing, repairing, or issuing credit (at cost, F.O.B. factory and at seller’s discretion) for any part or parts which are returned by buyer during such period provided that:
a. seller is notified in writing within ten (10) days follow-
ing discovery of such defects by buyer, or within ten (10) days after such defects should reasonably have been discovered, whichever is less;
b. the defective unit is returned to seller, transportation
charges prepaid by buyer.
c. payment in full has been received by seller for said
products; and
d. seller’s examination of such unit shall disclose to its
satisfaction that such defects have not been caused by misuse, neglect, improper installation, repair, alteration, act of God, or accident.
No warranty made hereunder shall extend to any seller product whose serial number is altered, effaced or removed. Seller makes no warranty, express or implied, with respect to motors, switches, controls, or other components of seller’s product, where such components are warranted separately by their respective manufactur­ers. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. In no event shall seller be liable to buyer for indirect, incidental collateral, or consequential damages of any kind. (BUYER’S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY (60) DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE IN CONNECTION WITH ANY CONTRACT FORMED HEREUNDER. BUYER AGREES THAT SUCH FAILURE TO PAY SHALL CONSTITUTE A VOLUNTARY WAIVER OF ANY AND ALL SUCH WARRANTIES ARISING PURSUANT TO SUCH CONTACT.)
Twin ciTy fan & blower | www.Tcf.com
5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601
1MPP11/09
Loading...