Twin City IM-4220 User Manual

Forward Curved Inline Duct Blowers
INSTALLATION, OPERATION & MAINTENANCE MANUAL
August 2014
IM-4220
Model DBS – 080 through 200 Model DBT – 080 through 200
Receiving, Inspection, & Unpacking
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Before accept­ing delivery, carefully inspect each carton or crate for visible shipping damage. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage. Make notations of all damage on all copies of the bill of lading and have all copies countersigned by the delivering carrier. The car­rier should also fill out a Carrier Inspection Report. The factory Traffic Department should then be contacted. File claim for damage with the carrier. Physical damage to the unit after acceptance is not the responsibility of Twin City Fan Companies, Ltd.
Unpack each carton or crate and verify that all required parts and proper quantities of each item have been received. Refer to drawings for part descriptions. Report shortages or missing items to your local representative to arrange for replacement parts.
Due to availability of carriers and truck space, it is not possible to guarantee that all items will be shipped together. Verification of shipments must be limited to only those items on the bill of lading.
The unit nameplate must be checked to make sure the voltage agrees with the power supply available.
©2014 Twin City Fan Companies, Ltd.
General Installation
CAUTION: Sheet metal parts, screws, clips and similar items inherently have sharp edges, and it is necessary that the installer and service personnel exercise cau­tion.
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and with all applicable codes.
Electrical Connection
This equipment is to be installed by an experienced installation company and fully trained personnel.
The mechanical installation of the inline centrifugal fan consists of making final connections between the unit, building services, and duct connections.
1. Connect supply wiring to the disconnect switch (non-fused standard). Check the wiring diagrams on the motor for connections.
2. The motor is factory set at the voltage marked on the fan nameplate. Check the line voltage with the nameplate voltage and wiring diagrams.
3. The main power wiring should be sized for the ampacity shown on the dataplate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.
CAUTION: Use copper conductors only.
CAUTION: Protect wiring from sharp edges. Leave
some slack in the line to prevent damage.
4. Disconnect switches are not fused. The power leads must be protected at the point of distribution in accordance with the fan dataplate.
Check, Test & Start Procedure
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equipment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
BEFORE START-UP: Disconnect power to this unit before servicing the unit.
1. Check to verify that the wheel is free to rotate.
2. Verify that supply voltage on the line side of discon-
nect agrees with voltage on fan data plate and is within the 10% utilization voltage.
3. Apply power to unit and check rotation of wheel with
the directional arrow on the unit. See Figure 1.
WARNING: Rotation is critical. If allowed to operate
in the wrong direction, the motor will overload and burn out.
WARNING: Check units for rotation. For three-phase,
rotation can be changed by interchanging any two of the three line leads. If unit is checked on temporary
5. On fans without a thermal protector integral to the motor (refer to unit or motor dataplate to determine if protector is present) a separate overload device is required. Refer to Sections 430-32 of the N.E.C. for sizing.
6. All units must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI/NFPA 70). A ground lug is provided as standard in the unit terminal box. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. DO NOT use the ground lug for connecting a neutral conductor.
7. Supply voltage to the inline fan should not vary by more than 10% of the value indicated on the unit dataplate. Phase unbalance must not exceed 2%.
WARNING: Failure of motor due to operation on
improper line voltage or with excessive phase unbal­ance constitutes product abuse and may cause severe damage to the unit’s electrical components.
wiring, it should be rechecked when permanently installed. Motor burn-out or tripped overload protec­tion devices are usually the result of wrong rotation.
4. Electrical Input Check: Perform check of fan ampere
draw and verify that motor nameplate amps are not exceeded. Take into account the service factor range if motor is nameplated above a 1.0 service factor.
5. Fan RPM should be checked and verified with a
tachometer.
NOTE: The fan was balanced at the factory to be
within stringent vibration levels before shipment. However, there are several things that may cause vibration, such as rough handling in shipment and installation, weak foundations and alignments.
Figure 1. Fan Wheel Rotation
Rotation
Rotation
2 Twin City IM-4220
V-Belts
V-belts on these belt driven fans are oil, heat, and static resistant type and oversized for continuous duty. With proper installation and maintenance, years of operating efficiency can be added to the lifespan of the V-belt drive.
The condition of V-belts and the amount of belt ten­sion should be checked prior to start-up (see Figure
2). When it becomes necessary to adjust belt tension, do not over-tension as bearing damage will occur. Recommended belt tension should permit
1
64" deflection per inch of span of the belt at the center of the belt span. To find this point, measure halfway between the pulley centerlines as shown in Figure 3. Extreme care must be exercised when adjusting V-belts as not to mis­align the pulleys. Any misalignment will cause a sharp
1. Where tensioning rods are not provided, adjustment is more easily obtained by loosening and adjusting one side of the motor bracket at a time.
2. Always loosen tension adjustment enough to place belts on sheaves without running belts over the edge of either sheave. A new belt may be seriously dam­aged internally by careless handling (see Figure 6).
WARNING: When removing or installing belts, never force belts over pulleys without loosening motor first to relieve belt tension.
3. Fan speed can be increased by closing the adjust­able motor pulley or decreased by opening it. Always check the load on the motor when increasing the fan speed.
reduction in belt life and will also produce squeaky, annoying noises (see Figure 4). On units equipped with 2 groove pulleys, adjustments must be made so that there is equal tension on all belts (see Figure 5).
Figure 2. Eliminate Slack Figure 3. Belt Deflection
Belt Span
Slack belts wear excessively, cause slippage and deliver less power. For longest belt life, always provide proper tension
Figure 4. Mounting Belts Figure 5. Sheaves
CORRECT
INCORRECT
Mount belts straight. Shafts must be parallel
Figure 6. Belts
and sheaves in alignment to prevent unnec­essary belt wear.
Deflection
Deflection = 64
Belt Span
Two-groove variable pitch sheaves must be opened the same number of turns on both sides; otherwise, slip­page occurs, wearing belts rapidly,
Do not force belt. Forcing the belt will break the cords and cause belt failure.
Twin City IM-4220 3
Loading...
+ 5 hidden pages