Twin City ES-110 User Manual

MPQN/MPQS Modular Plenum Fans
INSTALLATION, OPERATION & MAINTENANCE MANUAL
ES-110
February 2012
Contents
Introduction .........................................................................1
Shipping and Receiving .....................................................1
Handling .............................................................................. 1
Short Term Storage ...........................................................1
Long Term Storage............................................................1
Foundations and Supporting Structures .......................... 2
Fan Installation ...................................................................3
Assembly of Fans and Sealing/Isolation Strips ..............3
Fan Operation – Safety .....................................................3
Operation Checklist ............................................................ 4
Maintenance of Fans ......................................................... 4
General Motor Maintenance ......................................... 4
Wheel and Shaft Maintenance ..................................... 5
Structural Maintenance ................................................. 5
Troubleshooting Guidelines................................................ 5
Troubleshooting Performance Problems
Air Capacity Problems ..................................................5
Noise Problems .............................................................5
Vibration Problems ........................................................ 5
Motor Problems ............................................................. 5
Limitation of Warranties and Claims ............................... 6
Introduction
The purpose of this manual is to provide instructions that complement good general practices when install­ing or operating fans manufactured by Twin City Fan & Blower. It is the responsibility of the purchaser to pro­vide qualified personnel experienced in the installation, operation, and maintenance of air moving equipment. Instructions given in the body of this manual are gen­eral in nature and apply to a variety of models manu­factured by Twin City Fan & Blower. Most units can be installed and maintained with the instructions given. Special applications may require additional information. These instructions are supplied in the form of attached appendices. Use the instructions in the appendix if the direc­tions in this manual differ from instructions in the appendix. As always, follow good safety practices when install­ing, maintaining and operating your air moving equip­ment. A variety of safety devices are available. It is the user’s responsibility to determine adequate safety measures and to obtain the required safety equipment.
Handling
Handling of all air moving equipment should be con­ducted by trained personnel and be consistent with safe handling practices. Verify the lift capacity and operat­ing condition of handling equipment. Maintain handling equipment to avoid serious personal injury. Units shipped completely assembled may be lifted with slings and spreader bars. Use well-padded chains, cables or nylon straps. On most units, lifting lugs are provided for attaching chains (see Figure 1). Lift the fan in a fash­ion that protects the fan and fan coating from damage. Never lift a fan by the inlet or discharge flange, shafting or drives, wheel or impeller, motor or motor base, or in any other manner that may bend or distort parts. Partial or disassembled units require special handling. All parts should be handled in a fashion which pro­tects the coatings and parts from damage. Components should be handled such that forces are not concentrated and bending or distortion cannot occur.
Figure 1. Lifting Lug Locations
SWIVEL EYE HOOK (By Customer)
A
DETAIL A
NOTE: When lifting, the straps/chains should be at a minimum angle of 45
Housing should be lifted using straps and spreaders. Do not distort housing or side plates when lifting.
o
Shipping and Receiving
All Twin City Fan & Blower products are carefully con­structed and inspected before shipment to insure the highest standards of quality and performance. Compare all components with the bill of lading or packing list to verify that the proper unit was received. Check each unit for any damage that may have occurred in transit. Any damage should be reported immediately to the carrier and the necessary damage report filed.
©2012 Twin City Fan Companies, Ltd.
Short Term Storage
If fan installation is to be delayed, store the unit in a protected area. Protect the fan and motor bearings from moisture and vibration (or shock loading).
Long Term Storage
Prior to Storage – Motor bearings are to be greased at
the time of going into extended storage per the motor manufacturer’s specifications.
Storage Procedure – Fans should be stored indoors whenever possible where control over temperature, shock and dust is reasonably maintained. If units are to be stored outside in the elements, they should be cov­ered with a water-resistant material. Stored equipment should be stored on a clean, dry floor or blocked up off the ground on blocks to prevent unit from setting in any water or directly on the ground. If shock or vibration will be present during storage, the unit may need to be placed on some type of vibration dampening material to aid in preventing brinelling of the bearing surfaces.
Periodic Check – On a monthly interval, the equipment should be checked to ensure that it has remained in an acceptable stored condition. The fan wheel should be rotated several times by hand while adding enough grease to replenish the bearing surfaces with fresh grease and to maintain a full bearing cavity. Grease used must be compatible with that already supplied in the motor and fan bearings. The fan impeller should be left at approximately 180 degrees from that of the previous month to prevent the shaft and impeller from taking a set in one position. Storage records should be maintained which indicate the above requirements have been followed. Consult the motor manufacturer for proper storage, space heater connection and lubrication if the unit was supplied with one.
Start-Up – When the unit is removed from storage, all bearing grease should be purged and replenished with fresh grease as per the lubrication decal. The motor should be measured to verify that the resistance is still at a satisfactory level compared to the value recorded prior to storage.
Foundations and Supporting Structures
Floor mounted fans should be installed on a flat, level surface with sufficient structure support. Support shall be suitable for static and dynamic loads and foundation frequencies be separated at least 20% from the rota­tional speed/speed ranges. If the fans are mounted on a sub-structure, an inertia base with spring isolator system should be considered. Fans mounted to or within a structure should be placed as close as possible to a rigid member such as a wall or column. The structure must be designed for rotating equipment; static design for strength is not sufficient to insure proper operation. Supports for suspended fans must be cross-braced to prevent side sway. Structural resonance should be at least 20% from fan operating speed. Any ducting and/or dampers with sleeves should have independent support; do not use the fan for support. Isolating the fan from ductwork with flex connections eliminates transmission of vibration.
1. Sufficient structure must be provided to support weight of fan assembly.
2. Sufficient restraint must be provided to resist the pressure force against the fans. Typically fans are assembled in an application in a modular fashion with multiple fans working in parallel. The cumulative thrust force must be restrained to prevent the fan assemblies from leaning or tipping forward. The force acting on the fan assemblies is calculated as shown below.
Thrust force (lb
27.68
H x W x N x P
f) =
s
Where P
s = Maximum operating static pressure (in. w.g.)
W = Width of each individual fan (in.) H = Height of each individual fan (in.) N = Quantity of fans in system
27.68 = conversion factor for in. w.g. to PSI
Example Parallel fan system employing nine (9) – Size 182 fans
in a 3 x 3 configuration. (3 fans high x 3 fans wide)
System pressure is 5 inches of water column. Outside dimension of fan housing = approx. 32 in. by
32 in.
Thrust force (lb
27.68
Thrust force (lb
27.68
Note: The thrust force is distributed evenly across the front surface of the parallel fan system.
H x W x N x P
f) =
32 x 32 x 9 x 5
f) =
s
= 1665 (lbf)
3. Recommend attachments to the sides and top of the parallel fan system incorporating some form of spring support, i.e. rubber snubbers/isolators or springs. Such devices should be attached to prevent significant point loading on an individual fan. They should be located on the side of the parallel fan system at the top cor­ner and along the top every 2 fans or less.
a. When the fans are rigidly mounted to the base, an
assumption can be made that half of the thrust load will be supported at the base, and the sup­ports added at the top of the fan need to carry a minimum of one half of the thrust load.
b. When the fans are supported on an isolation base
or isolators, it will be necessary to add thrust restraints around the periphery of the fan assembly to support the entire thrust load. Flex connec­tions are required when using isolators or isolation base.
c. Attachments to the fan can be made utilizing the
factory mounting holes. Recommend that the gage of the materials be checked for tear out strength in thrust applications. If necessary utilize multiple mounting hole locations to distribute the load.
2
Twin City Engineering Supplement ES-110
Figure 2.
RUBBER GASKET
NOTE 5
RUBBER GASKET
OUTER SHELL
RUBBER GASKET
NOTES
D
B
A
RUBBER GASKET
RUBBER GASKET
C
NOTES:
1. On the horizontal between fans, one strip of gasket material is needed on inlet side & two on drive end on 222 & above, 200 and below get one strip on each end.
2. Gaskets need to connect in all corners to ensure proper sealing.
3. Rubber gasket is to be placed directly next to the mounting holes on the inlet and drive side.
4. Rubber gasket is 1/2 in. x 2 in. x cut-to-fit.
5. Rubber gasket is to be held in place be double-stick foam tape during assembly.
Fan Installation – Factory Assembled Units
Follow proper handling instructions given earlier.
1. Move the fan to the final mounting position.
2. Remove skid, crates, and packing materials carefully.
3. If supplied, place vibration pads or isolation base on mounting bolts. Line up holes in fan base with bolts.
4. Place fan on mounting structure. Carefully level unit using shims as required at all mounting hole loca­tions. Bolt down the unit.
Assembly of Fans and Sealing/Isolation Strips
1. Fans must be securely bolted to a base either directly through the factory mounting holes or with a properly designed clip. Final bolting of layer of fans to the support structure or base should be done after the individual fans are bolted together as a row.
2. During installation rubber strips need to be installed between each fan. Use double-sided foam tape to hold strips in place during installation. Two (2) to three (3) pieces of tape can be used as needed for this purpose (each end and middle of rubber strip). Location of these strips is documented in Figure 2.
3. The first fan on the bottom row will have the 2 verti­cal strips placed next to the mounting holes. Note: Strips should be cut to ensure an airtight seal between fans.
4. The bolts to be snugged up on vertical sections for the first row. Once all strips are in place, the bolts shall be tightened to torque values in table. See Table 1.
Table 1. Torque Values MPQN/MPQS Fasteners
Size
3/8 – 16 UNC
Net Type
Nylock 16 – 17
Torque Values
(ft lbs)
DETAIL A
DETAIL C
FRAME
PERF. PLATE
OUTER SHELL
MOUNTING HOLE
OUTER SHELL
RUBBER GASKET
RUBBER GASKET
OUTLET ONLY
222 & ABOVE
FRAME
RUBBER GASKET
RUBBER GASKET
DETAIL B
DETAIL D
RUBBER GASKET
OUTER SHELL
MOUNTING HOLE
RUBBER GASKET
RUBBER GASKET
5. The bolts holding the fan to the supporting structure can now be torqued.
6. Rubber strips are then placed on the top of the fan to support the fan above it according to the pattern shown. Note: On larger fan assemblies 2 strips are used in the back to support the weight of the motor.
7. The second row and succeeding rows can be installed using the same assembly steps as the first row.
8. Rubber strips are not normally needed on the outside or top of the parralel fan system.
9. Sealing around the perimeter should be accomplished using a flexible material.
Fan Operation - Safety
For general safety practices for air moving equipment, see AMCA Bulletin 410. Twin City Fan & Blower has many safety accesso­ries available. These safety devices include (but are not limited to) inlet and discharge screens. The use, abuse, or non-use of safety devices is the responsibility of the purchaser. Facility-related safety conditions include fan acces­sibility and location. How easily can non-service person­nel access the unit? Is the fan in a hazardous duty environment? Was the unit ordered for this duty? Other concerns must also be addressed. All fans should be powered through switches which are easily accessible to service personnel from the fan. Every switch should have the ability to be “locked-off” by the service person and the key to be retained by this person to prevent acci­dental power of the fan while service is in process.
3
Twin City Engineering Supplement ES-110
Loading...
+ 5 hidden pages