Tuthill TS06AS84, TS06AE93, TS06AE83, TS06AE71, TS06AE72 Installation, Operation & Parts Manual

...
Installation, Operation & Parts Manual
TS06A, LPG
Anodized Aluminum, Electronic Dispenser Meter
TS06AS86
with thermo well
Non-Compensated With Thermo Well
Assembly No., Single __ TS06AS83 __ TS06AS86
S/No.: __________________ The flow meter shipped under this general manual, has specifically:
ACCESSORIES REGISTER
Backpressure Valve None Strainer RAD register adaptor Vapor Eliminator EMR³ Register Differential Valve ELNC Register
TS06LPG 6/22/2012
INDEX
Safety Procedures 3 Installation & Operations 4-6 Torque & Wrench Chart 5 Meter Maintenance 7-10 Disassembly Flow Meter 9 Inlet Check Valve 10 Strainer 10 Vapor Eliminator 10 Differential Valve 10 Parts List: Meter & Strainer 13 Differential Valve 11 Inlet Check Valve 11 Vapor Eliminator 11 Troubleshooting 14 SCL (Pulser Assembly) 15-16 Meter calibration 16
S A F E T Y P R O C E D U R E S
This manual provides warnings and procedures that are intended to inform the owner/operator of the hazards present when using the Tuthill Transfer Systems, TUTHILL meters and other products. The reading of these warnings and the avoidance of such hazards is strictly in the hands of the owner/operator of the equipment. Neglect of that responsibility is not within the control of the manufacturer of the flow meter.
Read this manual as well as the literature provided in your owner’s manual. If you have any questions, consult with your full-service distributor or call the Service Department at Tuthill Transfer Systems, TUTHILL meters at 888-578-3258.
Please have the following information available when you make inquiries, order replacement parts, or schedule ser­vice. If a specific meter accessory is involved, please pro­vide the model and serial number of the accessory in ques­tion.
Meter Serial Number: ____________________________
Your Full Service Distributor:
Name: ________________________________
Telephone: _________________________________
IN THE EVENT OF A GAS LEAK
In the event of a large gas leak:
 Evacuate the area and notify the fire department or oth-
er appropriate authorities.
In the event of a small, contained gas leak:
 Isolate and stop the leak  Prevent accidental ignition  Prevent entrance of gas into other portions of the build-
ing. Be aware that LPG is heaver than air and will seek lower levels
 Evacuate all people from the danger zone  See that the gas is dispersed before resuming the busi-
ness and operations. If in doubt, notify your local au­thorities.
IN THE EVENT OF A GAS FIRE
In the event of large fires or fires that are spreading:
Evacuate the building and notify your local fire department. Stop the leakage only if you can safely reach the equipment.
The meters non-shock maximum operating pressure is indi­cated on the meter name plate. The meter should never be operated in excess of this pressure. Care should be taken to eliminate thermal and hydraulic shock conditions, so that they do not exceed the meters maximum working pressure.
In the event of small, contained fires that you can safely control:
Stop the leakage if you can safely reach the equipment. Then use the appropriate extinguisher: Class B fire extin­guisher, water, fog, etc. depending on the equipment. If in doubt, call your local fire department.
3
Installation & Operation
Installation:
Before Start-up of the Meter, make certain:
 The meter is properly mounted, secured and piped  All shipping plugs are removed and lines are clean of all
debris.
 All connections are tight and there are no leaks  All bleed and drain valves are closed  Do NOT smoke near the meter, or use the meter near
an open flame when metering flammable fluids. Fire or explosions could result.
 This meter is not intended for use with fluids for human
consumption.
*** Install the Meter and Accessories in Compli­ance with all applicable local, state and federal construction, electrical and safety codes. Addi­tionally, the LPG meter must be installed in ac­cordance with the requirements of ANSI-NFPA 58
Make sure that all necessary safety precautions have been taken including proper clothing, personal safety equipment and fire safety equipment if required.
Before shipment, protective thread caps were placed in the meter and accessories openings for protection. They should remain in place until your are ready to attach the piping.
The meter must always be securely bolted to a platform or supporting member, regardless of the mounting position. Never “hang” a meter on the connecting pipe.
Position the meter with service in mind. Provide ample work space. Removing covers can be difficult when work space is not available. Always supply a platform or support for the meter mounting.
Prior to meter installation, the entire piping system should be thoroughly flushed of all debris with a liquid that is compati­ble with the construction of the meter.
Keep all external surfaces of the meter clean. Positive displacement meters are designed to operate full o f
liquid. The meter should be installed in a manner such that it remains full of liquid at all times.
Install the companion flanges. Tighten to a position that allows the meter to bolt to the companion flanges, free of pipe stress. The meter should always be supported by bolt­ing to a platform. Never use the connecting pipe as the means of support.
In critical installation, block valves and by-pass lines are recommended. This allows the meter to be ser­viced without interruption of flow in a critical process application.
Thermal and or over pressure relief valves are recom­mended and should be installed w henever it is possi­ble to block the meter between two valves. Thermal pressures many times the operating pressure are pos­sible with only a small rise in temperature.
It is recommended that a strainer be installed upstream of each meter to prevent damage from foreign matter such as weld slag, pipe scale, etc.
A means to calibrate and prove the meter should be provid­ed during installation. An easy means for diverting flow into a calibration vessel should be considered.
Hydraulic shock like thermal expansion can be harmful to the meter components. Consideration should be given to designing pumping and piping systems to eliminate hydraulic shock.
WIRING
 If the flow meter is part of a dispenser, please refer
to dispenser manufacturer wiring diagram.
 If the flow meter is used as a ‘stand-alone’ dispens-
ing meter, please refer to: Page for TS06A with ELNC register Page for TS06A with EMR register Page for TS06A used with other registers
Operation Requirements:
Upstream lines must be maintained full to prevent air from entering the meter. If the upstream or inlet lines are con­structed in a manner which allows reverse flow, foot or back check valves should be installed.
Underground tanks that are furnished with a submersible pump will eliminate many problems that occur with positive displacement pumps with suction pipes when the suction piping is incorrectly sized creating too large a lift.
4
Installation & Operation continued
Every meter should be calibrated under actual service and installation conditions. Follow your local Weights and Measures recommendations.
Provide a means of conveniently diverting liquid for calibra­tion purposes.
Give careful attention to your system’s pumping equipment and piping because of their influence on the liquid being measured as it enters the meter assembly. Systems should be made free of conditions that cause or introduce entrained air or vapor.
Follow the manufacturer’s recommendation fully when in­stalling pumps. Give particular attention to factors like: use of foot valves, pipe size to the inlet and conformance to net positive suction head (NPSH) conditions when suction pumping is required. Following the manufactures’ recom­mendations will minimize air and vapor elimination prob­lems.
Torque Chart
Start-Up:
Fill the system slowly to avoid operation on air or vapor. This can be accomplished in the following manner:
Throttle the meter inlet valve, and allow the meter and pip-
ing to fill slowly by gravity.
Crack open the outlet valve and start the pump, then slowly
open the inlet valve until the system is up to pressure. Open the outlet valve fully to establish full flow. Check the flow rate to assure the meter is operating within specified rates.
The meter is not designed to operate on air, but the design and materials of construction of the TUTHILL meter allows for operation on vapor for short periods of time without dam­age to the elliptical gears or other meter internals.
Note: Over- speed and hammer caused by the presence of vapor in the system can cause internal damage to the meter.
Pa rt # Discription Torque Wrench
FS2801 1/4" -20 x 1" Hex Bolt 12 ft-lbs 7/16" Box/Open E nd Wrench FS2800 1/4" -20 x 1" SHCS 12 ft-lbs 3/16" Allen Wrenc h FS2910 1/4" -20 x 5" Hex Bolt 12 ft-lbs 7/16" Box/Open E nd Wrench FS2911 1/4" -20 x 2 1/2" SHCS 12 ft-lbs 3/16" All en Wrench FS2914 1/4" -20 x 1 1/2" SHCS 12 ft-lbs 3/16" All en Wrench FS2919 1/4" -20 x 1 1/2" SHCS 3/16" Allen Wrenc h FS2959 1/2" -13 x 1 1/4" Hex Bolt 80 ft -lbs 3/ 4" Box / O pen E nd Wrenc h
5
Installation & Operation continued
Where the TS06A is used in a commercial or retail LPG dis­penser, the flow meter will be shown in dispenser manufac­turer wiring diagram.
When the TS06A-EDM is used as a free-standing dispenser meter, it can be used with many different electronic regis­ters, which can be either installed on the flow meter, or re­mote.
#5
#1
EL0300-5-?
#4
TS06A with SCL, to EMR³
#2 & #3
In wiring diagrams on these 2 pages, we show the flow me­ter used with registers available through Tuthill. it can of course also be used with many other registers.
#6
EMR³ ground
1. The SCL is model specific, and in some cases also application specific. Do NOT transfer to another flow
meter without consulting with Tuthill.
2. Use 4 conductor shielded cable.
3. Terminate shields at receiving instrument (register).
4. Move W1 shunt (jumper) to match operating voltage:
5. S1 must be in Q position.
6. Output signal has an internal pull-up resistor (1000 ) on each channel.
7. If the receiving instrument (register) is more than 200’ (60 m) cable distance from the flow meter, an amplifier is required on the pulse signal. If this option was not ordered, please consult with Tuthill prior to start-up.
Both pins covered: 5VDC Regulated
= EL0300-5-1
1 pin exposed: 5.5 - 12 VDC
= EL0300-5-3
6
Installation & Operation continued
TS06A with SCL & ER9044 (ELNC-1141) register, AC powered through EL2057
ELPS-2057 AC power supply & barrier
EL0300-5 SCL inside flow meter front cover
1. This drawing does not guarantee compliance for intrinsically safe apparatus. Refer to CD1000, CD1001 and State & National electrical codes.
2. Terminate shields only at J1-4.
3. Cable lengths are limited by entity parameters.
7
Installation & Operation continued
TS06A with SCL & ER-9044-2 (ELNC-1141E) register, with Backlight Display & 10:1 Pulse, AC powered through EL2057
1. This drawing does not guarantee compliance for intrinsically safe apparatus. Refer to CD1000, CD1001 and­State & National electrical codes.
2. Cable lengths are limited by entity parameters.
3. ELPS output option: Install U1, R3, TB6.
8
Installation & Operation continued
Theory of Operation;
The TUTHILL meters LPG metering system combines an oval gear positive displacement meter, differential valve, strainer and vapor eliminator in one assembly. The differen­tial valve incorporates a piston type construction with the piston moving away from its seat when at least 15 PSI pres­sure (above product vapor pressure) is maintained at the meter outlet. The soft seat valve assures measurement accuracy by requiring pump operation for delivery, by requir­ing adequate back pressure to prevent product vaporization during measurement and by requiring blockage of flow whe n the vapor eliminator release valve is open. The strainer prevents foreign particulate from entering and damaging the meter. The meters close tolerance machine construction and no metal to metal contact provides accurate liquid measurement.
Installation, Flow Meter:
Install the meter assembly in a dispenser cabinet, or a truck deck to a secure base using the bolt holes on the “feet” of the strainer assembly base. Make inlet and outlet connec­tions at the flanged surfaces on the strainer and differential valve, respectively. Leave a minimum of 12 inches be-
tween he strainer flange and any obstacle for servicing the strainer.
Installation, Vent Line:
The vent line from the meter’s vapor vent to the vapor spac e on the supply tank should a minimum of 1/4” inside diameter tube or pipe. A shutoff valve must be installed in the vapor vent line to allow removal of the strainer or service on the meter. The vapor release vent line must be returned to the vapor space of the supply tank and normally should not be made common with the other vapor return lines or pump by-
pass lines. When properly installed, this line must permit free flow in
either direction. If the vent line is closed the meter will not function, as the differential valve will not open. These in­structions must be followed to maintain proper function of the differential valve.
Support:
Prevent pipe strain or stress from occurring when making connections to meter or accessories and during repairs. Pipe strain and stress occurs when the pipes are not sup­ported or are not aligned correctly to the meter. The weight of the pipes must always be supported independent of the meter. This meter and accessories can easily be removed without affecting the pipes or the pipe alignment. Never leave any of the pipes hinging.
Storage:
If the meter is used for seasonal work, at the end of each season the meter should be removed from the system and thoroughly flushed with a compatible liquid. This includes removing the drain on the front and rear covers. Then flush the product from the front and rear covers. If flushing with water is preferred, extra care should be taken to drain the meter completely and to dry all internal parts. Immediate refilling with a compatible liquid (or oil misting) is essential to prevent corrosion as well as ice damage to parts from mois­ture that was overlooked after flushing and drying.
9
Flow Meter Maintenance
Danger!! Danger!! Danger!!
Relieve all internal pressure before servicing.
Line pressure must be 0.0 PSI
Serious injury or death from fire or explosion could result from maintenance of an
improperly de-pressurized and evacuated system.
Preparing for Service:
 Close the belly valve of the supply tank.  Close the valve on the vapor return line.  Close the manual valve in the supply line on eh inlet
side of the meter. If no manual valve exists on the inlet side, consult the dispenser manufacturer on installer for procedures to depressurize the system.
 Slowly open the valve/nozzle on the end of the supply
line
 After product is bled off, close the valve/nozzle at the
end of the supply line.
 Open the bleed valve provided by your installer to re-
lieve the system pressure. Product will drain from the meter system.
 As product is bleeding from the bleed valve, slowly reo-
pen and close the valve/nozzle on the discharge line. Repeat this step until the product stops draining from the bleed valve and discharge line valve/nozzle.
 Leave the discharge line valve/nozzle open whil e work-
ing on the system.
General Service:
 Do not scratch or mar any of the precision machined
surfaces by prying or sanding parts.
 Torque specifications. All fasteners such as screws and
bolts should be torqued to proper specifications. See the “Torque Chart” in this manual.
 Stone the machined surfaces when reassembling the
meter to assure the machined surfaces are free of burrs and scratches.
 Removing flange seals: When removing the flange
assembly, always carefully remove the O-ring seal. Make sure that the flange surface is clean. Discard and replace the old O-ring seals if it is nicked or scratched in any way. It is undamaged, it can be re-used.
 Examine all fasteners: make sure fasteners are not
bent, rusted, or have pulled or burred threads. The threads should all appear evenly placed. If the bolts are bent, check the housing and cover for flatness. Use a straight edge to determine flatness. Use a stone to remove any burrs on the flat surfaces for the housing.
 Look for gaps: When disassembling a meter, use a
feeler gauge to check for gaps between the post and gear plates and housing. If you do find gaps, check the plates for flatness with a straight edge. Gaps can be caused by shock problems that must be resolved. Con­tact your full service distributor, or the Service Depart­ment at TUTHILL meters for assistance if this occurs.
 Check the O-Rings: O-rings should be smooth.
Cracked or worn O-rings should be replaced. However, a more serious problem of shock my have occurred if the O-rings are nibbled or extruded. Shock problems must be verified and resolved. Contact your full service distributor, or the Service Department at TUTHILL me­ters for assistance if this occurs.
 Check the post and gear plates: Check the plates for
flatness. Use a straight edge. Warped plates can be caused by hydraulic shock problems that must be re­solved. Contact your full service distributor, or the Ser­vice Department at TUTHILL meters for assistance if this occurs.
 Weights & Measures: Check with the regulatory agenc y
that governs Weights and Measures in your area. Re­moving a seal wire may require Weight & Measures recalibration.
 Repair pulled threads with threaded insert fasteners.
These can be used in many instances. Contact your full
-service distributor for advice if this occurs.
 Coating threads: When removing and replacing bolts
and screws in a meter, always coat the threads with anti
-seize.
10
Flow Meter Maintenance
11
Flow Meter Maintenance
Danger!! Danger!! Danger!!
Relieve all internal pressure before servicing.
Line pressure must be 0.0 PSI
Serious injury or death form fire or explosion could result from maintenance of an
Meter Disassembly:
 If your meter is equipped with an electronic register,
remove the register and register housing assembly.
 Disconnect the outlet flange (30) and the vapor tube
connecting the differential valve and the vapor return line.
 Remove the four bolts (26) and (27) and the dust cover
(25).
 Disconnect the outlet wiring from the electronic pulser
assembly (SCL) terminal TB1 (See SCL service manu­al)
Note: If the SCL does not require service, and there is no damage to the meter cover (22), it is possible to re­place the meter using the existing meter cover. In this case it is not necessary to disconnect the outlet wiring.
 Remove the four bolts (23) and the SCL housing (22).
 Install a new oval gear set (17) if necessary. Gears
should be perpendicular to each other. The gears will not rotate a complete revolution if not installed properly. Once installed, the gears should rotate freely with out binds or rubs. Check the clearance between the gears and the body. There should be a minimum of .003 inch between gears (17) and the meter cover (22). If there is any binds or rubs between the gears and the meter body, it is recommended that the meter be replaced.
 Reinstall the meter cover (22).  Reinstall the differential valve.  It is recommended that all O-rings and seals be re-
placed during service, but a good inspection is critical if seals are reused.
 Calibrate the meter and return to service.
 Inspect the internal parts for wear. Gear may be re-
placed at this point if all other components are good.
 Remove the bolts ( ) and remove the differential valve.  Remove the four bolts (20) and the meter assembly
(body (19) and post plate (14).
 Clean all surfaces using a brush or fine (200 grit) emery
cloth.
 Inspect and repair the inlet check valve if you have this
option.
 Inspect the meter body for damage. Use 200 grit pap er
to remove small scratches and blemishes, if the dam­age is more than superficial, replace the body.
 Inspect the post and post plate. Replace if there is any
wear.
 Inspect the O-ring seals, and replace any damaged or
brittle seals.
 Reinstall the meter in reverse order.
12
Flow Meter Maintenance
Inlet Check Valve Service: (Optional component)
 Disconnect the outlet piping from the meter assembly at
the differential valve outlet flange.
 Remove the meter as detailed in the METER DISAS-
SEMBLY section.
 Remove the back check valve assembly (11).  Manually open and close the valve to assure proper
operations.
 Inspect for dirt of salt build-up and clean if necessary.
 Inspect the slide valve. Remove and build–up of salts or
dirt which may cause the valve to stick. The valve should slide freely without any signs of sticking. There should be no scratches or burrs on the valve assembly. Replace if there are signs of damage.
 Inspect all seals, and replace if damaged or brittle.  Re-assemble the meter in the opposite direction making
sure all bolts are torqued to the proper specifications.
 Inspect the seals for wear or damage. Replace worn or
brittle seals.
 Reassemble the valve and install in the strainer hous-
ing. This valve is optional and will not retrofit into strain­er housing not originally supplied with the valve.
 Reassemble the system making sure bolts are torqued
to the proper specifications
Strainer Service: (See page 8)
 Remove the four bolts (37) from the rear cover and re-
move the cover (7).
 Inspect the seal (12) and replace if damaged or brittle  Remove the strainer (10). Clean the strainer with low
pressure air, blowing out all loose sediment. Wash the strainer with solvent.
 Inspect the strainer for holes or other damage and re-
place if necessary.
 Re-assemble making sure the bolts are torqued to the
proper specifications.
Vapor Eliminator Service: (See pages 8 & 11)
 Disconnect the vapor return line flange and the differen-
tial valve tubing.
Differential Valve Service (see page 11):
 Remove the outlet piping flange.  Remove the connecting tube between the differential
valve and the vapor eliminator.
 Remove the Screws (1) securing the cover (2) from the
valve body (4).
 Remove the differential valve piston assembly (8) and
spring (7).
 Inspect the valve body and cover for damage. Clean all
surfaces of dirt or deposits using a fine (200 grit) emery cloth if necessary. If damage is more than superficial, replace the valve.
 Inspect all seals and replace any brittle or damaged
seals. It is recommended that all seals be replaced during service.
 Replace the U-Cup seals (8a). Note proper positi on of
the seals. Use a small amount of Teflon lubricant to help install the seals.
 Replace the square cut seal (8b). Use thread sealer
(Locktite Blue) when installing the fastener (7e).
 Re-assemble the valve in the opposite manner.
 Remove the five bolts (3) from the vapor eliminator
housing.
 Remove the cover (4) from the vapor eliminator hous-
ing.
 Remove the float and valve assembly (34) from the
cover for inspection.
 Inspect the float for damage or leakage. A crack will
allow the float to fill with liquid and sink thus prevent the valve form closing. A collapsed float is an indication of over pressure or hammer and these operation condi­tions must be corrected before reusing the meter.
13
Flow Meter Maintenance
3/4” Back Check Valve Assembly
Air Eliminator Assembly
(Optional)
Item # Qty Description Part #
1 Complete Backcheck Valve Assy. VP3075
1 1 Piston, 3/4" Backcheck Valve MP4001 2 1 Spring MS8031 3 1 "O" Ring SL3114-UL 4 1 Body, 3/4" Backcheck Valve MP3075-1 5 1 Poppet, 3/4" Backcheck Valve MP3076 6 1 10-32 x .375 SHCS FS9651 7 1 "O" Ring SL218
Item # Qty Discription Part #
1 A/E Assembly AE8201
1 1 Outlet Port , 3/ 4" A/E Ass em bl y MP 4060 2 1 Val ve Sleeve, 3/ 4" A / E A ss em bly MP 5200 3 1 3/32 Roll P i n MS 9260 4 1 Float Connec tor MP 1582 5 1 1/16 Cotter Pin FS9213 6 1 Float MS9100
Differential Valve Assembly
Item # Qty Description Part # 1 Complete valve assembly DV6100
1 6 Bolt, 1/4"-20 x 1" ALSTPL SHCS FS2801 2 1 Cover, 2/4" Differential Valve CP6101 3 1 "O" Ring, UL Buna SL3224 4 1 Valve Body, 3/4" Differential Valve MP6100 5 1 "O" Ring, UL Buna SL3132 6 1 Spring, 3/4" Differential Valve MS8035
7 1 Repair Kit, Piston, 3/4" Differential Valve RK4000 7a 2 U-Cup Seal, UL Viton SL1212-U 7b 1 "O" Ring, Sq. Cut, UL Buna SL3212-SQ 7c 1 Seal Retainer ST6102 7d 1 Piston, Brass, 3/4" Differential Valve MP4000
14
Exploded View
15
Parts List
R
R
R
R
R
R
R
R
R
R
R
Item # Descript ion QTY
1 Relief Valve
2.a Fl ange 1" FNPT ( ALUM) Flange 1" FBSP ( ALUM)
3 1/4-20 x 5" Hex B olt 4 C ov er, Vapor Eliminator 5 H ousing, Vapor Eliminator 6 O-Ring, B una 7 Strainer Flange, Blind 8 Thermowell
in S83, S 84, E83, E93, E71- 73 in S86, S88, E 86 & E96
9Strainer Housing 10 Strainer Bas ket 11 O-Ring, Buna 12 O-Ring, Buna, Square Cut
2 & 13 I ncluded in f lange kit s:
3/4" NPT 3/4" BSP 1" NP T
1" BS P 14 Post Plate Assembly 15 Dowel P ins 16 includ ed in #14 nss nss 17 Gear S et 18 O- Ring, Buna 19 Meter Body 20 1/4" - 20 x 3. 2 5 S HC S 21 Dowel P ins 22 Cover, Chamber
22b SCL Assembly, 5V regulated ***
SCL Assembly, 6-12 V *** 23 1/4" - 20 x 1. 2 5 S HC S 24 Gask et , Du st Cover 25 Dust Co ver 26 1/4" - 20 x 0. 5 S HC S 27 1/4" - 20 x 0.3 75 S HC S w/ h ole 28 Differential Valve
Differential Valve Hose Assy. 29 O- Ring, Buna 31 1/4" - 20 x 1"- Hex B olt
33
Cover Blind
34
Vapor Eliminator Float Assy
35
1/4" Lock Wash ers
37
1/2" - 13 x 1.25" Hex Bolt
Strainer Basket M agnet
38 39
Magnet Ho l d er
1 1 1 6 1 1 2 1
00 1 1 1 2 2
1 or or or
1
2
1
2
1
4
2
1
1 or
4
1
1
2
2
1
1
2
4
1
1 10
9
1
1
SINGLE
MS8400 MP2568 MP2569 FS2910 MP2561 MP2565 SL3156 MP2562
MP2564-1 MP2560 SA8010-200 SL3123 SL3324-SQ
FK2075UA FK2075UB FK2100UA FK2100UB CP25952 MS2119-8
GS550CC SL3151 MB2551 FS2911 MS2001 MP2574 EL0300-5-1-3 EL0300-5-3-3 FS1803 SL7000 ST1301 FS9812 FS9810 DV6100 MS5075 SL3127 FS2801 MP2573 MP2573 AE8201 AE8201 FS9302 FS9302
MP5008 MP5008 MS7017 MS7017
QTY
1 1 1 6 1 1 1 0
1 1 1 1 1
1 or or or
2
4
2
4
2
4
4
2
2 or
8
2
2
4
4
2
2
4
8
*** Not al l S CL s oft ware is the s am e. Output ty pe and frequency m ay vary . Please have m et er m odel and S /N avail able for y our s pecific produc t.
= Rec om m ended S pare P art s
R
TWIN
MS8400 MP2568 MP2569 FS2910 MP2561 MP2565 SL3156 MP2562
MP2564-1 MP2560 SA8010-200 SL3123 SL3324-SQ
FK2075-1UA FK2075-1UB FK2100-1UA FK2100-1UB CP25952 MS2119-8
GS550CC SL3151 MB2551 FS2911 MS2001 MP2574 EL0300-5-1-3 EL0300-5-3-3 FS1803 SL7000 ST1301 FS9812 FS9810 DV6100 MS5075 SL3127 FS2801
16
Trouble Shooting
Problem
Leakage from seal cover.
Product flows through meter but the regis­ter does not operate
Breaking teeth on gears.
No flow or low flow through the meter
Probable Cause and Solution
 Seal has been damaged due to shock  Cover bolts have not bee tightened sufficiently  Replace seal and /or re-torque bolts
 Pulser is not functioning properly  Meter gears are jammed and not turning  Replace the pulser, inspect internal meter parts
 Starting or stopping flow too rapidly.  Normal wear after long service  Replace gears  Correct system operation  Check pump by-pass setting.
 Faulty non-functioning pump  Differential vale not open or not functioning. Replace valve  Meter “frozen” due to build up of salts or frozen material. Clean meter
internals and inspect for damage
 Vapor vent line valve shut or obstruction in vapor vent line. Open valve
or remove obstruction
 Strainer dirty and plugged. Clean Strainer  U-Cups on differential valve leaking. Replace U-Cups
Meter operates too slowly:
Product flows through the meter but regis­ter does not record properly:
 Differential valve internal mechanism faulty. Valve does not open full y.  Meter gears or rotors partially “salted”, enough to slow the rotating
gears. To correct, clean gears.
 Strainer partially plugged. Clean strainer basket.  Pump not functioning properly. Repair pump
 Pulse output board faulty, or not calibrated for electronic register.  Vapor release valve sticking.  Differential valve leaking.  Repair or replace as necessary.
17
SCL & Pulser Assembly
SCL (Scaler/Calibrator/Linearizer)
Description: Tuthill SCL is a small electronic device de­signed to provide the function of a pulse Scaler, an electron­ic Calibrator and Linearizer. This electronics package replaces a mechanical gear plate and mechanical calibrator while at the same time providing the ability to improve the accuracy of a metering device during low flow operation, thus improving the overall meter accuracy, and extending the flow range of the metering device. The SCL may be used in conjunction with other Tuthill electronics to solve many of your electronic interface requirements.
Specifications:
 Input Voltage : 5Vdc and 6 to12 Vdc  Input Current : 25ma @ 5Vdc  Operating Temperature: -40
o
C to +85°C
(U/L T4 upper limit is +40C)
 Input signal : Hall Effect sensors, single or
dual, or single ended input
from 5Vdc logic
 Input Frequency : 2000 Hz (max)
Output:
 Quadrature Pulse  Output Voltage : Proportional to
power supply voltage
 Duty Cycle : Symmetrical Quadrature
with 50/50 D.C.
 Output Frequency : (Input Frequency) X (ECF)
Scaled to application
 Linearizer : 32 points maximum  Calibrator Range : +/- 3.0%  Output pulse on-time : Fixed by firmware
OPERATION:
The SCL may be used to perform a number of functions depending upon the users application. The following is a brief description of several of the SCL functions.
SCALER MODE:
When operating in the Scaler mode only, the SCL app lies a single error correction factor (ECF) to the incoming pulse signal. If a single correction factor is applied to the entire range of meter frequency inputs then the output frequency is proportional to the input frequency times the ECF (SCL Pulses out = SCL Pulses in times ECF). If the ECF is 1.0 (no scaling factor) the output frequency is equal to the inp ut frequency.
As an example, use this feature when the customer’s elec­tronics requires a precise frequency or pulse resolution in­put. If the customer’s electronics required 100 pulses per liter, then 100 PPL becomes the base pulse resolution based on which all input pulses are scaled. If, as an exam­ple, the meter is providing 108 pulses per liter, then an ECF of 0.925 (100/108) would be programmed into the SCL, and the output pulse frequency would be equivalent to the se­lected base resolution of 100 PPL.
LINEARIZER MODE:
If a metering device is not producing an output within the limits of accuracy required for an application, the SCL may be used as a linearizer. A linearizer is a device, which rec­ognizes the output frequency of the metering device, and applies a correction factor (ECF), chosen for that frequency to improve the accuracy of the metering device.
The number of ECF points chosen for a specific application depends upon the accuracy of the metering device. In weights and measure applications, there is an ECF applied at each flow rate point where the meter accuracy varies by
0.25% from the previous flow rate point. The ECF data is stored electronically in the SLC at the facto-
ry . The electronic chip storing this data is permanently at­tached to the printed circuit board. The ECF chip is marked with a code, that is used to reference the exact set of ECF data, that is supplied in your SCL device.
CALIBRATOR MODE:
The SCL is equipped with two rotary switches S3 and S4, and a two position switch S2. The three switches allow the
SCL to adjust the pulse output up or down by 3%. This allows the operator, or W&M authorities to calibrate the
meter without having to alter scale factors in customer elec­tronics. This feature is designed to replace mechanical cali­brators used in the field for years to adjust the meter output to accurately match the volume in a proving vessel.
The calibrator feature may be used if the SCL in being used as a scaler only, or as a scaler/linearizer.
SWITCHES:
S1 : Allows the choice of either a single channel input,
or a two channel quadrature input.
S2 : Is used in conjunction with S3 and S4.
If in the minus (-) position, an increase in the S3 and S4 switch settings will decrease the pulse output. A decrease in pulse output will increase the volume in a prover vessel. If in the plus (+) position, an in­crease in the S3 and S4 will increase the pulse out­put. An increase in pulse output will decrease the volume in the prover vessel.
S3/S4 Adjust the SCL pulse output up or down +/-3.0%.
S3 and S4 will allow for 00-99 settings. Each incre­ment changed in this setting, changes the SCL pulse output by approximately 0.03%
18
Flow Meter Calibration
Y
METER CALIBRATION:

Flow meter re-calibration should be on a volume equal to 1 minute of flow at maximum flow rate.
 All tests should be performed 3 times under identi-
cal conditions to confirm repeatability.
 Maintain a permanent file fo r each flow meter, and
record % change each time the meter is re­calibrated.
When the change is significantly higher than that found in previous re-calibrations, it is time to re­build the flow meter (replace the two oval gears).
METER CALIBRATION:
The calibrator allows you to adjust the outpu t of the SCL up or down, like a mechanical calibrator, +/- 3% in increments of 0.03%.
 After calibrating a known volume (X) into an accurate
prover (or through a master meter with adequate resolu­tion), compare with register reading (Y) and calculate correction:
To reduce the volume in a prover vessel (can), place
switch S2 in the plus(+) position.
X-
X
x 100
= % correction
 Adjust the S3 and S4 to the position required for the
necessary volume reduction in the prover can. Switch S3 and S4 represent readings of 00 to 99, and each increment will adjust the output approximately 0.03%.
Example:
Using a 20 gallon (75.7 liter) can, the can reads 113.5 ml high. The meter error is (113.5/75700) = 0.0015 or .15%. To adjust the meter output, place S2 in the positive position, and set S3 and S4 to read 05. This is approximately a 0.15% adjustment.
Activate the Reset push button switch to enter the new program settings. Retest the flow meter.
 To increase the volume in the prover vessel. Place
switch S2 in the negative (-) position, and set switches S3 and S4 to the proper settings to adjust the output. Activate the Reset push button switch to enter the new data.
NOTE: If S2 is in the plus (+) position, and S3 and S4
are at 15 as an example, then moving the posi tion of S3 and S4 to 00 will provide a (0.03 x 15) =.45% increase in the prover volume. To obtain a greater increase in the prover volume, S2 must be placed in the minus (-) position and S3 and S4 rotated to the proper position to obtain the desired change in pulse resolution. The opposite is true if S2 is already in the minus (-) position at the beginning of calibration.
 Finally:
 Re-seal the flow meter.  Enter date and % correction on the permanent flow
meter record.
As long as degree of change is moderate, the flow meter is in good condition.
If there is a sudden significant jump in correction required, the rotors are likely about worn out. Rotor replacement should be considered now, rather than letting further wear cause rotors to start rubbing on flow meter housing.
METER CALBRATION: INCREASED PRECISION.
The standard method for calculating the single point adjust­ment is to obtain the error as a percentage of the desired test volume. In the previous examples, an excess volume in the prover vessel of 113.5 ml became 0.15% and the adjust­ment was 05 on S3 and S4.
However, the 0.15% correctly needs to be applied to the nominal ECF for the particular meter profile in order to more precisely calculate the adjustment for S3 and S4. The nomi­nal ECF is the particular profile base divided by the natural meter pulse resolution.
As an example, a meter type which is scaled to 100 ppl and has 410 ppg pulse resolution, has a nominal ECF of
378.5/410 = 0.9232. 0.15% of 9232 is 13.84. When divided by 3, the switch setting is 04.6. In this example, 4.6 is rounded up to 05. This is the same result as before be­cause the ECF is close to unity (1.0000). If the ECF was
0.4200, then the switch setting would be 02. There are applications where the nominal ECF is not near
unity. In those cases, the nominal ECF needs to be known and used for the calculation. If the standard calculation is used, the adjustment would be excessive and the meter technician would have to estimate the reduction in his set­tings and perform an additional test run.
19
NOTES
20
Loading...