SERIES 300V
115 and 230 VOLT AC
FUEL TRANSFER PUMP
Owner's Operation & Safety Manual
Models FR300V, FR301V, FR310V & FR311V
SAFETY INSTRUCTIONS
To ensure safe and effi cient operation, it is essential to read
and follow each of these warnings and precautions.
1. Improper use or installation of this product can cause serious
bodily injury or death.
2. Do NOT smoke near pump or use pump near an open fl ame
when pumping fl ammable fl uids. Fire could result.
3. A Fill-Rite fi lter should be used on pump outlet to ensure that no
foreign material is transferred to fuel tank.
4. Use gasoline and oil resistant thread sealant or sealant tape on
all threaded joints to protect against leakage.
5. Storage tank should be anchored to prevent tipping in both the
full and empty conditions.
6. To minimize static electricity buildup, only use static wire,
conductive hose when pumping fl ammable fl uids and keep
nozzle in contact with container being fi lled.
7. The pump motor is equipped with thermal overload protection. If
overheated, it will shut off without any damage to the windings.
Be sure to turn off the pump power if this occurs. When the
motor cools, it will restart without warning if power is on.
8. Take motors needing service to an authorized repair shop to
maintain “explosion proof” and “rain proof” integrity.
DANGER
Electrical wiring should be done by a licensed electrician in compliance
with local, state and national electric code NEC/ANSI/NFPA 70,
NFPA 30, NFPA 30A, as appropriate to the intended use of the pump.
Threaded rigid conduit, seal fi ttings and conductor seal should be used.
Pump should be properly grounded. Improper use or installation of this
product can cause serious bodily injury or death.
DIRECT MOUNTING TO UNDERGROUND TANK
1. Cut and thread both ends of a 2" pipe that will extend about 31"
above the ground when installed in tank fl ange.
2. Install this pipe in tank fl ange. Screw 2" standard pipe coupling
onto top of pipe.
3. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of
tank when screwed into tank adapter and tank adapter is
screwed into 2" coupling.
4. Screw this pipe into tank adapter, then screw tank adapter into
2" coupling.
5. Mount pump on tank adapter.
ISLAND INSTALLATION
1. Install tank and piping per illustration.
2. The threaded 1-1/4" suction pipe is to extend 32-1/2" above
island.
3. Remove coupler from pedestal pipe by loosening set screws.
4. Slip pedestal pipe/pump base assembly over suction pipe.
5. Loosen screws in pump base to allow pedestal pipe to slide
down exposing end of suction pipe.
6. Screw coupler onto suction pipe.
7. Slide pedestal pipe into coupler, tighten set screws. Tighten
screws in pump base.
8. Mount pump on coupler.
ELECTRICAL
Pump motor voltage is factory set at 115 VAC. See diagram to change
voltage setting.
1. Install pump. Read and understand all the electrical wiring
instructions before proceeding.
2. Remove pump's electrical junction box cover and straighten the
wires to make the stripped wire ends accessible outside of the
junction box.
WARNING: AUX. WIRE IS LIVE WIRE! The AUX. lead wire is
insulated and enclosed when shipped. Do not connect this wire
without fi rst verifying the 'ON' line voltage of the wire for
compatibility to the equipment to be installed. Maximum amperage
on wire is 1 ampere. The wire must be insulated and enclosed in
the junction box if not used.
3. Power to the unit should be supplied from a dedicated 30 amp
circuit breaker. No other equipment should be powered from this
breaker. Threaded rigid conduit, seal fi ttings and conductor seal
should be used. Provisions must be made to break both legs of
any AC circuit. Connect like colored pump wires to supply wires.
Ground wire must be connected.
4. Fold wires into junction box and replace cover making sure that
gasket is in place. Make sure screws are seated so there is no
space between the cover and the junction box.
WARNING
This product should not be used for fl uid transfer into aircraft. This
product is not suited for use with fl uids for human consumption or
fl uids containing water.
INSTALLATION
GENERAL
Pumps are furnished with a tank adapter for skid tank mounting;
pedestals are available for island installations. All tanks must be
properly vented. A pressure retaining vent/fi ll cap can be used to
reduce fuel loss due to evaporation but will reduce fl ow rate.
Fill-Rite fi lters are recommended when pumping fuels.
Pump has a built-in check valve with pressure relief to prevent fl uid
thermal expansion from causing unsafe system pressures. Do not use
additional check valves or foot valves unless they have a proper
pressure relief valve built into them. Additional check valves will
reduce fl ow rate.
Use a gasoline and oil resistant pipe sealant on all pipe threads to
protect against leaks.
SKID TANK MOUNTING
1. Cut a 1-1/4" pipe that will extend to at least 3" above bottom of
tank when screwed into tank adapter and tank adapter is
screwed into tank fl ange.
2. Screw pipe into tank adapter, then screw tank adapter into tank
fl ange.
3. Mount pump on tank adapter.
OPERATING INSTRUCTIONS
1. Reset meter to 0 (if applicable).
2. Remove nozzle from nozzle boot and move switch lever up. This
will turn the pump on.
3. Insert nozzle into container to be fi lled. To minimize static
electricity buildup, keep nozzle in contact with container.
4. Operate nozzle lever to dispense fl uid.
5. When desired amount of fl uid has been dispensed, release
nozzle lever, remove nozzle from container, move switch lever
to down position to turn off pump, replace nozzle in boot.
TROUBLESHOOTING
IF PUMP FAILS TO PRIME: Check suction line for leaks or
obstructions.
Check bypass valve for dirt. The bypass poppet should slide freely.
PUMP WILL NOT START: If motor hums but will not start, a probable
cause is a stuck rotor. Remove rotor cover; check rotor and vanes for
dirt. Also have an electrician check the electrical power to the pump.
LOW PUMPING CAPACITY: Strainer screen clogged; bypass valve
not seated properly; obstruction in suction lines. Make sure all 8
vanes slide easily in the rotor slots.

Pump won't prime 1. Suction line problem Check for leaks in suction line
2. Bypass valve open Remove and inspect valve; must move freely & be free of debris
3. Vanes sticking Check vanes and slots for nicks, burrs and wear
4. Gasket leakage Tighten covers and joints
5. Excessive rotor or vane wear Check rotor & vanes for excessive wear or damage
6. Outlet blocked Check pump outlet, hose, nozzle & filter for
blockage
7. Vapor Lock Reduce vertical and horizontal distance from pump to liquid;
Remove automatic nozzle
Pump hums but 1. Dirt in pump cavity Clean out pump cavity
will not operate 2. Motor failure Return to place of purchase
3. Broken key Remove all debris & replace key
Low capacity 1. Excessive dirt in screen Remove and clean screen
2. Suction line problem Check suction line for leaks or res
trictions; it may be too
small, too long or not airtight
3. Bypass valve sticking Remove and inspect valve; must move freely & be free of debris
4. Vanes sticking Check vanes and slots for wear
5. Excessive rotor or vane wear Check rotor & vanes for excessive wear or damage
6. Hose or nozzle damage Replace hose or nozzle
7. Plugged filter Replace filter
8. Low fluid level Fill tank
Pump runs
slowly 1. Incorrect voltage Check incoming line voltage while pump is running
2. Vanes sticking Check vanes and slots for nicks, burrs and wear
3. Wiring problem Check for loose connections
4. Motor problem Return to place of purchase
Motor stalls 1. Bypass valve sticking Remove and inspect valve; must move freely & be free of debris
2. Low voltage Check incoming line voltage while pump is running
3. Excessive rotor or vane wea
r Check rotor & vanes for excessive wear or damage
4. Debris in pump cavity Clean pump cavity
Motor overheats 1. Pumping high viscosity fluids These fluids can only be pumped for short periods of time
(less than 30 minutes duty cycle)
2. Clogged screen Remove and clean screen
3. Re stricted suction pipe Remove and clean pipe
4. Motor failure Return to place of pu
rchase
5. Pump rotor lock-up Clean and check pump rotor and vanes
Motor will not turn on 1. No power Check incoming power
2. Switch failure Return to place of purchase
3. Motor failure Return to place of purchase
4. Thermal protector failure Return to place of purchase
5. Incorrect/loose wiring Check wiring
Fluid leakage 1. Bad o-ring gasket Check all o-ring gaskets
2. Dirty shaft seal Clean seal & s
eal cavity
3. Bad shaft seal Replace seal
4. Incompatible fluid Refer wetted parts list to fluid manufacturer
5. Loose fasteners Tighten fasteners
TROUBLESHOOTING
SOLUTION
POSSIBLE CAUSE
PROBLEM

DESCRIPTION QTY.
PART NO.
22 300F7744 Inlet Gasket Buna (-224) 3
NO.
ITM.
DESCRIPTION QTY.
300F7801 Automatic Nozzle
TH14 Pedestal Kit
F4010PM Particulate Filter
700ACCF7017 Filter Head
23 300H0757 Pump Housing (Models FR310V & FR311V) 1
24 700H1168 Anti-Siphon Plug 1
25a 700F0651 2” x 1 1/4” Tank Adapter 1
25b 300H1164 2” x 1 1/4” BSPT Tank Adapter Opt.
26 1200F6576 Gasket for Anti-Siphon Device 1
27 300G9432 Washer 1/4” Split lock 1
28 300G9273 10-32NC-2B x 1.50 SHCS 1
29 700H0676 O-Ring for fl ange 1
31 300H0133 Meter Flange 1
32 300G9129 O-Ring (2-146) 1
33 304F7904 1/4-20 1/2 HWHMS 4
34 300F7761 Switch Lever 1
35 300G8967 Junction Box 1
36 300G8971 Junction Box Cover 1
37 901MK300V 901 Meter (Models FR301V & FR311V) 1
38 300F7773 1” x 12’ Hose 1
39 800F4400 1” Street Elbow 1
40 300F7745 3/8-16 x 2 HHCS 2
41 300F7765 Nozzle Cover 1
42 700F3125 1” Manual Nozzle 1
43 300F7759 Nozzle Retainer 1
30a 300H0129 1” Outlet Flange 1
30b 300H1243 1” BSPT Outlet Flange 1
44 700F2950 5/16 Lock Nut 2
45a 100G8800 1/4-20 x 3/4 HWHTHS (FR301V & FR311V) 8
45b 900H0409 1/4-20 x 3/4 HWG Swageform 8
Repair Kit (Includes items 3, 4, 5, 6, 8, 9, 12, 13, 18 & 22)
NO.
P ART
300G7375 Motor - 1/2 HP 115/230 VAC, 50/60 Hz (Models FR300V, FR310V) UL/CSA 1
300G7638 Motor - 3/4 HP 115/230 VAC, 50 Hz (Model FR310VE, FR311VE) AUS 1
300G8368 Motor - 0.55KW 230 VAC, 50/60 Hz (Models FR310VE, FR311VE) ATEX, 1
NO.
ITM.
1 300G7376 Motor - 3/4 HP 115/230 VAC, 50/60 Hz (Models FR310V, FR311V) UL/CSA 1
2 LP50G9973 3/8-16 x 1” SHCS 2
3 300F7787 Rotor Insert 1
4 300KTH0034 Seal Assembly Kit (Includes Items 11 & 15) 1
5 300F7743 O-Ring Gasket Buna (-236) 1
6 700G7063 Rotor Cover 1
300KTG9180 BIODIESEL and E85 Kit (Includes items 2, 5, 11, 15, 4, 13, 14, 17, 21 & 22) ACCESSORIES
7 300G7296 3/8-16 x 3/4 HHCS 4
8 300G8379 Rotor 1
9 300H0723 Vanes 8
11 700F2688 Retaining Ring (Included w/Item 4) 1
10 300F7746 3/8-16 x 3 HHCS 2
12 300F7723 Bypass Valve Assembly 1
13 800F4380 O-Ring Buna (2-131) 1
14 300F7731 Bypass Cap 1
15 30F4660 Seal Washer (Included w/Item 4) 1
16 700F2810 5/16-18 x 7/8 HHCS 8
17 300F7739 Check Valve Cover 1
18 300F7742 O-Ring Gasket Buna (-231) 1
19 300F7735 Check Valve Assembly 1
20 300G8621 Lower Housing 1
20 300H1241 Lower Housing BSPT Opt.
21a 900F8076 1” Meter Fitting 1
21b 900F8074 1” BSPT Meter Fitting Opt.
300KTG9180
5

ANTI-SIPHON
The pumps are shipped with a threaded vacuum breaker installed.
Fill-Rite recommends that the vacuum breaker be tubed back to the
tank. The vacuum breaker is used to break a siphon should an open
nozzle or a leaking hose be below the fl uid level in the tank with the
pump turned off.
ANTI-SIPHON TUBING INSTALLATION
The following illustration shows methods of installing tubing for the
vacuum breaker that terminates in the vapor space at the top of the
tank. The tubing must terminate in the vapor space; if the tubing
terminates below the liquid level of the tank, the vacuum breaker will
not prevent siphoning. It is also very important that there are no liquid
traps in the tubing. The tubing must have a continuous slope from the
pump down to the tank. If the pump is installed below the top of the
tank, the tubing may slope both ways from a single high point above
the tank. Alternately, tubing can be piped to any available opening on
top of tank it the tank adapter is not used. Use reducer bushings as
required.
Fill-Rite recommends using the vacuum breaker tank adapter with a 1/4 npt
opening in the side of the hex portion that terminates in the vapor space of
the tank. Install tank adapter per instructions found in this manual. Make
liquid tight connection from the adapter to the vacuum breaker using a
minimum of 1/4 metal tubing compatible with the liquid being pumped. If a
vacuum breaker tank adapter is used and the 1/4 npt opening is not used for
the tubing, plug the opening liquid tight.
6

Tel 260 747-7524 Fax 260 747-3159
Fort Way ne, Indiana USA 46809
8825 Aviation Drive
www.tuthill.com
PRODUCT WARRANTY
Tuthill Transfer Systems (“Manufacturer”) warrants to each consumer
buyer of its Fill-Rite products (the “Buyer”), from the date of invoice or
sales receipt, that goods of its manufacture (“Goods”) will be free from
defects of material and workmanship. Duration of this warranty is as
follows:
• Heavy Duty Products - Two years
• Standard Duty Products – One year
• Economy Duty Products – One year
• Cabinet pumps, Parts, and Accessories - One year
Manufacturer’s sole obligation under the foregoing warranties will
be limited to either, at Manufacturers’ option, replacing or repairing
defective Goods (subject to limitations hereinafter provided) or
refunding the purchase price for such Goods theretofore paid by
the Buyer, and Buyer’s exclusive remedy for breach of any such
warranties will be enforcement of such obligations of Manufacturer.
If Manufacturer so requests the return of the Goods, the Goods will
be redelivered to Manufacturer in accordance with Manufacturer’s
instructions F.O.B. Factory. The remedies contained herein shall
constitute the sole recourse of the Buyer against Manufacturer for
breach of warranty. IN NO EVENT SHALL MANUFACTURER’S
LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF THE
MANUFACTURE, SALE, DELIVERY, OR USE OF THE GOODS
EXCEED THE PURCHASE PRICE OF THE GOODS. The foregoing
warranties will not extend to Goods subjected to misuse, neglect,
accident or improper installation or maintenance, or which have
been altered or repaired by anyone other than Manufacturer or its
authorized representative. THE FOREGOING WARRANTIES
ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES OF
MERCHANTABILITY, FITNESS FOR PURPOSE OF ANY OTHER
TYPE, WHETHER EXPRESS OR IMPLIED. No person may vary the
foregoing warranties and remedies except in writing signed by a duly
authorized offi cer of Manufacturer. Warranties or remedies that differ
from the foregoing shall not otherwise be binding on Manufacturer. The
Buyer’s acceptance of delivery of the Goods constitutes acceptance of
the foregoing warranties and remedies, and all conditions and limitations
thereof.
8